This document specifies requirements and recommendations concerning the physical security of data centres based on the criteria and classifications for “availability”, “security” and “energy efficiency enablement” within ISO/IEC 22237-1. This document provides designations for the data centre spaces defined in ISO/IEC 22237-1. This document specifies requirements and recommendations for such data centre spaces, and the systems employed within those spaces, in relation to protection against: a) unauthorized access addressing organizational and technological solutions; b) intrusion; c) internal fire events igniting within data centre spaces; d) internal environmental events (other than fire) within the data centre spaces which would affect the defined level of protection; e) external environmental events outside the data centre spaces which would affect the defined level of protection. NOTE Constructional requirements and recommendations are provided by reference to ISO/IEC 22237-2. Safety and electromagnetic compatibility (EMC) requirements are outside the scope of this document and are covered by other standards and regulations. However, information given in this document can be of assistance in meeting these standards and regulations. Conformance of data centres to the present document is covered in Clause 4.

  • Standard
    34 pages
    English language
    sale 15% off

This document gives calculation methods, guidance and requirements for the design, installation, acceptance testing, routine testing and maintenance for pressure differential systems (PDS).
PDSs are designed to hold back smoke at a leaky physical barrier in a building, such as a door (either open or closed) or other similarly restricted openings and to keep tenable conditions in escape and access routes depending on the application.
It covers systems intended to protect means of escape e.g. staircases, corridors, lobbies, as well as systems intended to provide a protected firefighting space (bridgehead) for the fire services.
It provides details on the critical features and relevant procedures for the installation.
It describes the commissioning procedures and acceptance testing criteria required to confirm that the calculated design is achieved in the building.
This document gives rules, requirements and procedures to design PDS for buildings up to 60 m.
For buildings taller than 60 m the same requirements are given (e.g. Table 1), but additional methods of calculation and verification are necessary. Requirements for such methods and verification are given in Annex D, but the methods fall outside the scope of this document [e.g. Additional mathematical analysis and/or Computational Fluid Dynamics (CFD)].
Routine testing and maintenance requirements are also defined in this document.
In the absence of national requirements and under expected ambient and outside conditions, the requirements in Table 1 are fulfilled by the PDS.

  • Standard
    118 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document provides guidance and rules to notified bodies (for fire dampers) allowing them to produce/validate an extended field of application report for fire dampers. This document identifies the parameters that affect the fire resistance of dampers. It also identifies the factors that need to be considered when deciding whether, or by how much, the parameter can be extended when contemplating the fire resistance performance of an untested, or untestable variation in the construction.
This document explains the principles behind how a conclusion on the influence of specific parameters/constructional details relating to the relevant criteria (E, I, S) can be achieved.
This document does not cover dampers used for smoke control.
It is the intention that the application of this document makes it possible to identify which specifications to test to maximize the field of application. Some information on test programmes is given for guidance purposes.

  • Standard
    45 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document provides guidance and rules to notified bodies (for fire dampers) allowing them to produce/validate an extended field of application report for fire dampers based on testing undertaken in accordance with EN 1366 2. This document identifies the parameters that affect the fire resistance of fire dampers. It also identifies the factors that need to be considered when deciding whether, or by how much, the parameter can be extended when contemplating the fire resistance performance of an untested, or untestable variation in the construction.
This document explains the principles behind how a conclusion on the influence of specific parameters/constructional details relating to the relevant criteria (E, I, S) can be achieved.
This document does not cover dampers used for smoke control or non-mechanical fire barriers.
It is the intention that the application of this document makes it possible to identify which specifications to test to maximize the field of application. Some information on test programmes is given for guidance purposes.

  • Standard
    45 pages
    English language
    sale 10% off
    e-Library read for
    1 day

(1) This technical specification gives minimum design, installation and commissioning requirements for powered smoke and heat control systems for enclosed car parks using horizontal flow powered ventilation, with or without sprinkler protection, on one or more levels, for cars and light commercial vehicles (max 3,5 t), to reach the design objectives outlined in this technical specification.
see design objectives in CEN TC191 SC1 doc. N721, 5.1 (1):
For any fire location, the system shall keep at least one access route sufficiently clear of smoke for fire-fighters from the exterior or from a protected access route (e.g. stairwell) to a distance of 15 m from the front of the fire. Criteria should be verified when the conditions within the car park have reached a steady-state regime.
NOTE: The limit of 15 m is necessary to reach the fire with the jet from the hose nozzle.
(2) This technical specification is applicable for fires of cars powered by petrol or diesel or other fuels which will have a fire performance similar to vehicles powered by petrol or by electricity. It is not applicable for other fires within the car park (e.g. storage).
NOTE: It is assumed that cars powered by fuels other than petrol or diesel will have a fire performance similar to vehicles powered by petrol or diesel.
(3) This technical specification only covers traditional car parks that are with cars parked alongside each other with common access roadways/lanes for cars to be driven in and out. It does not cover other forms of car parking systems, such as stacking systems. Smoke and heat control systems for vehicles more than 3,5 t (lorry parks, coach parks, etc.) are not covered by this technical specification.
(4) This technical specification does not cover requirements for day‐to‐day ventilation.
(5) Any other risks than fire from cars are not covered by this technical specification.

  • Technical specification
    51 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document gives minimum design, installation and commissioning requirements for powered smoke and heat control systems for enclosed car parks using horizontal flow powered ventilation, with or without sprinkler protection, on one or more levels, for cars and light commercial vehicles (max 3,5 t), to reach the design objectives outlined in this document .
This document is applicable for car parks with vehicles powered by petrol, diesel, electricity, CNG or LPG.
NOTE 1   For the purpose of this document for smoke ventilation systems, it is assumed that cars powered by electricity, CNG (compressed natural gas) or LPG (liquefied petroleum gas) will have similar HRR to vehicles powered by petrol or diesel.
NOTE 2   Cars powered by hydrogen are not covered by this document.
This document only covers traditional car parks that are with cars parked alongside each other, with common car access lanes. It does not cover other forms of car parking systems, such as stacking systems.
This document does not cover requirements for day‐to‐day ventilation.
Any other risks than fire from cars are not covered by this document.

  • Technical specification
    51 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document applies to pressure differential system kits, positioned on the market and intended to operate as part of a pressure differential system. The purpose of a pressure differential system is to prevent protected spaces from smoke spread by using pressure difference and airflow. This document specifies characteristics and test methods for components and kits for pressure differential systems to produce and control the required pressure differential and airflow between protected and unprotected space.

  • Standard
    65 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document gives guidance and requirements for the design and calculation methods, installation, acceptance testing, routine testing and maintenance for pressure differential systems (PDS).
PDSs are designed to hold back smoke at a leaky physical barrier in a building, such as a door (either open or closed) or other similarly restricted openings and to keep tenable conditions in escape and access routes depending on the application.
It covers systems intended to protect means of escape e.g. staircases, corridors, lobbies, as well as systems intended to provide a protected firefighting bridgehead for the fire services.
It provides details on the critical features and relevant procedures for the installation.
It describes the commissioning procedures and acceptance testing criteria required to confirm that the calculated design is achieved in the building.
This document gives complete rules, requirements and procedures to design PDS for buildings up to 60 m.
For buildings taller than 60 m the same requirements are given (e.g. Table 1), but additional calculations and verification methods are necessary. Requirements for such methods and verification are given in Annex D, but the methods fall outside the scope of this document [e.g. Computational Fluid Dynamics (CFD)].
Routine testing and maintenance requirements are also defined in the document.
In the absence of national requirements and under expected ambient and outside conditions, the requirements in Table 1 are fulfilled by the PDS.

  • Standard
    118 pages
    English language
    sale 10% off
    e-Library read for
    1 day

The purpose of this document is to provide the principles and guidance for the preparation of extended application documents for combined penetration seals where the systems were tested in accordance with (EN 1366-3 and EN 1366-1) or (EN 1366-3 and EN 1366-2). The field of the extended application document is additional to the direct field of application given within EN 1366-1, EN 1366-2 and EN 1366-3 and can be applied on a number of tests from each standard, which provide the relevant information for the formulation of an extended application.
This EXAP is intended to allow the penetration sealing of more than one service (e.g. cables, pipes, conduits) and four-sided fire resisting ducts (ventilation ducts) or fire dampers in the same penetration.
This EXAP is not used for extended applications in accordance with EN 1366-8, EN 1366-10 and/or EN 1366-12 (this will be dealt with in the next revision of the standard).

  • Standard
    37 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document applies to pressure differential system kits and components, positioned on the market and intended to operate as part of a pressure differential system. The purpose of a pressure differential system is to prevent protected spaces from smoke spread by using pressure difference and airflow. This document specifies characteristics and test methods for components and kits for pressure differential systems to produce and control the required pressure differential and airflow between protected and unprotected space.

  • Standard
    65 pages
    English language
    sale 10% off
    e-Library read for
    1 day

IEC 60695-6-1:2021 is available as IEC 60695-6-1:2021 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.IEC 60695-6-1:2021 gives guidance on: a) the optical measurement of obscuration of smoke; b) general aspects of optical smoke test methods; c) consideration of test methods; d) expression of smoke test data; e) the relevance of optical smoke data to hazard assessment. This basic safety publication focusing on safety guidance is primarily intended for use by technical committees in the preparation of safety publications in accordance with the principles laid down in IEC Guide 104 and ISO/IEC Guide 51. One of the responsibilities of a technical committee is, wherever applicable, to make use of basic safety publications in the preparation of its publications. This third edition cancels and replaces the second edition of IEC 60695-6-1 published in 2005 and Amendment 1:2010. It constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition: - References to IEC TS 60695-6-30 (withdrawn in 2016) have been removed. - References to IEC TS 60695-6-31 (withdrawn in 2016) have been removed. - References to ISO 5659-2 have been inserted. - The scope contains some additional text. - Terms and definitions have been updated. - Subclause 3.2 has been updated. - Subclause 7.1 has been updated. It has the status of a basic safety publication in accordance with IEC Guide 104 and ISO/IEC Guide 51. This International Standard is to be used in conjunction with IEC 60695-6-2.

  • Standard
    36 pages
    English language
    sale 10% off
    e-Library read for
    1 day

IEC 60695-6-1:2021 is available as IEC 60695-6-1:2021 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.
IEC 60695-6-1:2021 gives guidance on:
a) the optical measurement of obscuration of smoke;
b) general aspects of optical smoke test methods;
c) consideration of test methods;
d) expression of smoke test data;
e) the relevance of optical smoke data to hazard assessment.
This basic safety publication focusing on safety guidance is primarily intended for use by technical committees in the preparation of safety publications in accordance with the principles laid down in IEC Guide 104 and ISO/IEC Guide 51.
One of the responsibilities of a technical committee is, wherever applicable, to make use of basic safety publications in the preparation of its publications.
This third edition cancels and replaces the second edition of IEC 60695-6-1 published in 2005 and Amendment 1:2010. It constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous edition:
- References to IEC TS 60695-6-30 (withdrawn in 2016) have been removed.
- References to IEC TS 60695-6-31 (withdrawn in 2016) have been removed.
- References to ISO 5659-2 have been inserted.
- The scope contains some additional text.
- Terms and definitions have been updated.
- Subclause 3.2 has been updated.
- Subclause 7.1 has been updated.
It has the status of a basic safety publication in accordance with IEC Guide 104 and ISO/IEC Guide 51. This International Standard is to be used in conjunction with IEC 60695-6-2.

  • Standard
    101 pages
    English language
    sale 15% off
  • Standard
    65 pages
    English and French language
    sale 15% off

IEC 60695-6-2:2018 provides a summary of commonly used test methods for the assessment of smoke obscuration. It presents a brief summary of static and dynamic test methods in common use, either as international standards or national or industry standards. It includes special observations on their relevance to electrotechnical products and their materials and to fire scenarios, and gives recommendations on their use. This basic safety publication is primarily intended for use by technical committees in the preparation of standards in accordance with the principles laid down in IEC Guide 104 and ISO/IEC Guide 51. It is not intended for use by manufacturers or certification bodies. It has the status of a basic safety publication in accordance with IEC Guide 104 and ISO/IEC Guide 51. This standard is to be used in conjunction with IEC 60695-6-1. This standard cancels and replaces IEC 60695-6-2 published in 2011. This second edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition: a) updated introduction; b) updated normative references; c) new text in 4.1; d) deletion of references to IEC 60695-6-30 and -31 (withdrawn) e) updates with respect to ISO 5659-2; f) deletion of references to BS 6853 and CEI 20-37-3 (superseded); g) deletion of references to ISO/TR 5924 (withdrawn); h) updated text with respect to EN 50399; i) updated text with respect to ISO 5660-1; j) addition of new Subclause 7.5 k) deletion of Annex B; l) deletion of Annex E; m) additional bibliographic references. Key words: Fire Hazard, Smoke Obscuration

  • Standard
    35 pages
    English language
    sale 10% off
    e-Library read for
    1 day

IEC TS 60695-5-2:2021 is available as IEC TS 60695-5-2:2021 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.IEC TS 60695-5-2:2021 gives a summary of the test methods that are used in the assessment of the corrosivity of fire effluent. It presents a brief summary of test methods in common use, either as international standards or national or industry standards. It includes special observations on their relevance, for electrotechnical products and their materials, to real fire scenarios and gives recommendations on their use.
One of the responsibilities of a technical committee is, wherever applicable, to make use of basic safety publications in the preparation of its publications. The requirements, test methods or test conditions of this publication will not apply unless specifically referred to or included in the relevant publications.
This third edition cancels and replaces the second edition published in 2002.
The main changes with respect to the previous edition are listed below:
– References to IEC TS 60695-5-3 (withdrawn in 2014) have been removed.
– ISO/TR 9122-1 has been revised by ISO 19706.
– References to ISO 11907-2 and ISO 11907-3 have been removed.
– Terms and definitions have been updated.
– Text in 5.4 has been updated.
– Text in 5.5.8 (5.7.8 in Ed. 2) has been updated.
– Text in Clause 6 (7 in Ed. 2) has been updated.
– Bibliographic references have been updated.
It has the status of a basic safety publication in accordance with IEC Guide 104 and ISO/IEC Guide 51.
This technical specification is to be read in conjunction with IEC 60695-5-1.

  • Technical specification
    23 pages
    English language
    sale 15% off
  • Technical specification
    57 pages
    English language
    sale 15% off

This document assesses the utility of physical fire models that have been standardized, are commonly used, and/or are cited in national or international standards, for generating fire effluent toxicity data of known accuracy. This is achieved by using the criteria established in ISO 16312-1 and the guidelines established in ISO 19706. The aspects of the models that are considered are: the intended application of the model, the combustion principles it manifests, the fire stage(s) that the model attempts to replicate, the types of data generated, the nature and appropriateness of the combustion conditions to which test specimens are exposed, and the degree of validity established for the model.

  • Technical report
    45 pages
    English language
    sale 15% off
  • Technical report
    45 pages
    English language
    sale 15% off
  • Technical report
    50 pages
    French language
    sale 15% off
  • Technical report
    50 pages
    French language
    sale 15% off

2021: CLC legacy converted by DCLab NISOSTS

  • Amendment
    4 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies the required characteristics and test procedures for fire resistant or fire proof
electrical cables for use in aircraft electrical systems. They shall be operated at a rated AC voltage of
600 V ac, a frequency of maximum 2 000 Hz and a long term temperature of up to 260 °C (ambient
temperature plus temperatures rise in conductor).
These cables shall also maintain a specific dielectric strength when they are subjected to a flame of
1 100 °C after five (5) minutes (fire resistant) or 15 minutes (fire proof) exposure.

  • Standard
    13 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This International Standard presents a range of sampling and chemical analytical methods suitable for
the analysis of individual chemical species in fire atmospheres. The procedures relate to the analysis of
samples extracted from an apparatus or effluent flow from a fire test rig or physical fire test model and
are not concerned with the specific nature of the fire test.
This International Standard doesn’t cover aerosols (detailed in Reference [3]) and FTIR technique
(detailed in Reference [4]). The gases of environmental interest, such as PAH, dioxins, furans, endocrinal
disturbers, will be developed in a future document by ISO TC92/SC3.

  • Standard
    117 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Standard
    112 pages
    English language
    sale 15% off
  • Standard
    112 pages
    English language
    sale 15% off
  • Standard
    112 pages
    French language
    sale 15% off
  • Standard
    112 pages
    French language
    sale 15% off

This International Standard provides a means for estimating the lethal toxic potency of the fire effluent
produced from a material while exposed to the specific combustion conditions of a physical fire model.
The lethal toxic potency values are specifically related to the fire model selected, the exposure scenario
and the material evaluated.
Lethal toxic potency values associated with 30-min exposures of rats are predicted using calculations
which employ combustion atmosphere analytical data for carbon monoxide (CO), carbon dioxide (CO2),
oxygen (O2) (vitiation) and, if present, hydrogen cyanide (HCN), hydrogen chloride (HCl), hydrogen
bromide (HBr), hydrogen fluoride (HF), sulfur dioxide (SO2), nitrogen dioxide (NO2), acrolein and
formaldehyde. The chemical composition of the test specimen may suggest additional combustion
products to be quantified and included. If the fire effluent toxic potency cannot be attributed to the
toxicants analysed (Annex A), this is an indication that other toxicants or factors must be considered.
This International Standard is applicable to the estimation of the lethal toxic potency of fire effluent
atmospheres produced from materials, products or assemblies under controlled laboratory conditions
and should not be used in isolation to describe or appraise the toxic hazard or risk of materials, products
or assemblies under actual fire conditions. However, results of this test may be used as elements of a
fire hazard assessment that takes into account all of the factors which are pertinent to an assessment of
the fire hazard of a particular end use; see ISO 19706.
The intended use of fire safety-engineering calculations is for life-safety prediction for people and is
most frequently for time intervals somewhat shorter than 30 min. This extrapolation across species
and exposure intervals is outside the scope of this International Standard.
This International Standard does not purport to address all of the safety problems associated with its
use. It is the responsibility of the user of this International Standard to establish appropriate safety and
health practices.

  • Standard
    18 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Standard
    13 pages
    English language
    sale 15% off
  • Standard
    13 pages
    English language
    sale 15% off
  • Standard
    13 pages
    French language
    sale 15% off
  • Standard
    13 pages
    French language
    sale 15% off
  • Standard
    13 pages
    French language
    sale 15% off

IEC 60695-6-2:2018 provides a summary of commonly used test methods for the assessment of smoke obscuration. It presents a brief summary of static and dynamic test methods in common use, either as international standards or national or industry standards. It includes special observations on their relevance to electrotechnical products and their materials and to fire scenarios, and gives recommendations on their use.
This basic safety publication is primarily intended for use by technical committees in the preparation of standards in accordance with the principles laid down in IEC Guide 104 and ISO/IEC Guide 51. It is not intended for use by manufacturers or certification bodies.
It has the status of a basic safety publication in accordance with IEC Guide 104 and ISO/IEC Guide 51.
This standard is to be used in conjunction with IEC 60695-6-1.
This standard cancels and replaces IEC 60695-6-2 published in 2011. This second edition constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous edition:
a) updated introduction;
b) updated normative references;
c) new text in 4.1;
d) deletion of references to IEC 60695-6-30 and -31 (withdrawn)
e) updates with respect to ISO 5659-2;
f) deletion of references to BS 6853 and CEI 20-37-3 (superseded);
g) deletion of references to ISO/TR 5924 (withdrawn);
h) updated text with respect to EN 50399;
i) updated text with respect to ISO 5660-1;
j) addition of new Subclause 7.5
k) deletion of Annex B;
l) deletion of Annex E;
m) additional bibliographic references.
Key words: Fire Hazard, Smoke Obscuration

  • Standard
    65 pages
    English and French language
    sale 15% off

ISO 16852:2016 specifies the requirements for flame arresters that prevent flame transmission when explosive gas-air or vapour-air mixtures are present. It establishes uniform principles for the classification, basic construction and information for use, including the marking of flame arresters, and specifies test methods to verify the safety requirements and determine safe limits of use.
This International Standard is valid for pressures ranging from 80 kPa to 160 kPa and temperatures ranging from −20 °C to + 150 °C.
NOTE 1       For flame arresters with operational conditions inside the scope, but outside atmospheric conditions, see 7.4.
NOTE 2       In designing and testing flame arresters for operation under conditions other than those specified above, this International Standard can be used as a guide. However, additional testing related specifically to the intended conditions of use is advisable. This is particularly important when high temperatures and pressures are applied. The test mixtures might need to be modified in these cases.
NOTE 3       An additional standard IMO MSC/Circ. 677 for maritime application from IMO (International Maritime Organization) exists.
ISO 16852:2016 is not applicable to the following:
-      external safety-related measurement and control equipment that might be required to keep the operational conditions within the established safe limits;
NOTE 4       Integrated measurement and control equipment, such as integrated temperature and flame sensors as well as parts which, for example, intentionally melt (retaining pin), burn away (weather hoods) or bend (bimetallic strips), is within the scope of this International Standard.
-      flame arresters used for explosive mixtures of vapours and gases, which tend to self-decompose (e.g. acetylene) or which are chemically unstable;
-      flame arresters used for carbon disulphide, due to its special properties;
-      flame arresters whose intended use is for mixtures other than gas-air or vapour-air mixtures (e.g. higher oxygen-nitrogen ratio, chlorine as oxidant, etc.);
-      flame arrester test procedures for internal-combustion compression ignition engines;
-      fast acting valves, extinguishing systems and other explosion isolating systems.

  • Standard
    62 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard specifies the products characteristics of powered smoke and heat control ventilators (fans) intended to be used as part of a powered smoke and heat control ventilation system in construction works.
It provides test and assessment methods of the characteristics and the compliance criteria of the test assessment results.
This European Standard applies to the following:
a)   fans for smoke and heat control ventilation;
b)   impulse/jet fans for smoke and heat control ventilation;

  • Standard
    100 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard applies to natural smoke and heat exhaust ventilators (NSHEV) operating as part of smoke and heat exhaust systems (NSHEVS), placed on the market. This standard specifies requirements and gives test methods for natural smoke and heat exhaust ventilators which are intended to be installed in smoke and heat control systems in buildings.

  • Standard
    88 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard specifies the general requirements for the minimum quality level of service provided by companies as well as the competencies of their involved staff charged with the planning, design, installation, commissioning, verification, handover or maintenance of fire safety systems and/or security systems, regardless whether these services are provided on-site or remotely.
This European Standard is applicable to services for fire safety systems and/or security systems, which are fire detection and fire alarm systems, security alarm systems including those parts of an alarm transmission system that the service provider has contractually accepted responsibility for (except social alarm systems, alarm receiving centres and the remaining parts of alarm transmission systems) and fixed fire fighting systems and combination of such systems.
This standard applies regardless of project size or company structure or size.

  • Standard
    14 pages
    English language
    sale 10% off
    e-Library read for
    1 day

ISO 16312-1:2016 provides technical criteria and guidance for evaluating physical fire models (i.e. laboratory combustion devices and operating protocols) used in effluent toxicity studies for obtaining data on the effluent from products and materials under fire conditions relevant to life safety.[9] Relevant analytical methods, calculation methods, bioassay procedures and prediction of the toxic effects of fire effluents can be referenced in ISO 19701, ISO 19702, ISO 19703, ISO 19706 and ISO 13344. Comparisons are detailed in ISO 29903. Prediction of the toxic effects of fire effluents can be referenced in ISO 13571 and ISO/TR 13571‑2.

  • Standard
    11 pages
    English language
    sale 15% off
  • Standard
    11 pages
    English language
    sale 15% off
  • Standard
    13 pages
    French language
    sale 15% off
  • Standard
    13 pages
    French language
    sale 15% off

2021: CLC legacy converted by DCLab NISOSTS

  • Amendment
    4 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This Technical Report is aimed primarily at persons who are responsible for the safe design and operation of installations and equipment using flammable liquids, vapours or gases.
This document applies to both industrial and mining applications
This document describes possible risks and gives proposals for the protection against these risks by the use of flame arresters.
This document gives some guidance to choice of flame arresters according to EN ISO 16852 for different common scenarios and it gives best practice for the installation and maintenance of these flame arresters.

  • Technical report
    33 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This Technical Report is aimed primarily at persons who are responsible for the safe design and operation of installations and equipment using flammable liquids, vapours or gases.
This document applies to both industrial and mining applications
This document describes possible risks and gives proposals for the protection against these risks by the use of flame arresters.
This document gives some guidance to choice of flame arresters according to EN ISO 16852 for different common scenarios and it gives best practice for the installation and maintenance of these flame arresters.

  • Technical report
    33 pages
    English language
    sale 10% off
    e-Library read for
    1 day

ISO 13344:2015 provides a means for estimating the lethal toxic potency of the fire effluent produced from a material while exposed to the specific combustion conditions of a physical fire model. The lethal toxic potency values are specifically related to the fire model selected, the exposure scenario and the material evaluated. Lethal toxic potency values associated with 30-min exposures of rats are predicted using calculations which employ combustion atmosphere analytical data for carbon monoxide (CO), carbon dioxide (CO2), oxygen (O2) (vitiation) and, if present, hydrogen cyanide (HCN), hydrogen chloride (HCl), hydrogen bromide (HBr), hydrogen fluoride (HF), sulfur dioxide (SO2), nitrogen dioxide (NO2), acrolein and formaldehyde. The chemical composition of the test specimen may suggest additional combustion products to be quantified and included. If the fire effluent toxic potency cannot be attributed to the toxicants analysed, this is an indication that other toxicants or factors must be considered. ISO 13344:2015 is applicable to the estimation of the lethal toxic potency of fire effluent atmospheres produced from materials, products or assemblies under controlled laboratory conditions and should not be used in isolation to describe or appraise the toxic hazard or risk of materials, products or assemblies under actual fire conditions. However, results of this test may be used as elements of a fire hazard assessment that takes into account all of the factors which are pertinent to an assessment of the fire hazard of a particular end use; see ISO 19706. The intended use of fire safety-engineering calculations is for life-safety prediction for people and is most frequently for time intervals somewhat shorter than 30 min. This extrapolation across species and exposure intervals is outside the scope of ISO 13344:2015. ISO 13344:2015 does not purport to address all of the safety problems associated with its use. It is the responsibility of the user of ISO 13344:2015 to establish appropriate safety and health practices.

  • Standard
    18 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Standard
    13 pages
    English language
    sale 15% off
  • Standard
    13 pages
    English language
    sale 15% off
  • Standard
    13 pages
    French language
    sale 15% off
  • Standard
    13 pages
    French language
    sale 15% off
  • Standard
    13 pages
    French language
    sale 15% off

This European Standard specifies a test method for determining the ability of a vertical protective membrane, when used as a fire resistant barrier, to contribute to the fire resistance (loadbearing capacity R) of loadbearing vertical structural building members fabricated from steel, concrete, steel/concrete composites or timber. The method described is applicable to any type of vertical protective membrane, which can be associated with a separate bracing membrane.
The vertical protective membrane can be either separated from or attached to the structural building member and is self-supporting. This test method is applicable to vertical protective membranes where there is a gap and a cavity between the vertical protective membrane and the structural building member, otherwise alternative test methods prEN 13381-3, EN 13381-4, EN 13381-6 or prEN 13381-7 should be used as appropriate.
This test method and assessment is not applicable to the following:
a) all situations where the cavity is to be used as a service or ventilation shaft;
b) all situations where the vertical protective membrane acts as a bracing membrane.
This European Standard contains the fire test which specifies the tests which shall be carried out whereby the vertical protective membrane together with the structural member to be protected is exposed to the specified fire. The fire exposure, to the standard temperature/time curve given in EN 1363-1, is applied to the side which would be exposed in practice.
The test method makes provision, through specified optional additional procedures, for the collection of data which can be used as direct input to the calculation of fire resistance according to the processes given in EN 1992-1-2, EN 1993-1-2, EN 1994-1-2 and EN 1995-1-2.
This European Standard also contains the assessment which provides information relative to the analysis of the test data and gives guidance for the interpretation of the results of the fire test, in terms of loadbearing capacity criteria of the protected vertical structural member.
The results of the fire test and the assessment can be applied, with certain defined provisions, to vertical structural building members which can be beams, columns or a combination of both and / or which could form part of a separating element or partition.
The limits of applicability of the results of the assessment arising from the fire test are defined, together with permitted direct application of the results to different structures, membranes and fittings.
In special circumstances, where specified in national building regulations, there can be a need to subject the protection material to a smouldering curve. The test for this and the special circumstances for its use are detailed in Annex B.
Tests should be carried out without additional combustible materials in the cavity.

  • Standard
    35 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard defines requirements for running capability under fire conditions which are applicable to passenger carrying railway rolling stock. In particular, technical measures are specified, compliance with which will contribute to conformity with the Directive and the relevant Technical Specifications for Interoperability (TSI). The standard specifies the fire conditions: - for which it is not necessary to define running capability requirements as there is no significant potential for serious injury or threat to life; - for which it is reasonable to expect trains to continue to run in a controlled manner; - for which it is not reasonably practicable to define requirements which give complete assurance of running in a controlled manner, due to the exceptional nature of the fire incident. The TSI SRT defines running capability requirements in respect of fires within technical areas/equipment only. However for general guidance the scope of this standard is extended to include fires from non-technical causes within passenger/staff areas which may impact train system functions adjacent to and/or passing through the affected area. This extension of applicability significantly increases the number of system functions which are potentially at risk and therefore requires that the "reasonably practicable" principles be extended to this new condition. The standard does not consider situations where a primary non-fire incident is likely to immobilise the train by definition; for example major mechanical defect leading to derailment, even when fire then occurs.

  • Corrigendum
    1 page
    English language
    sale 10% off
    e-Library read for
    1 day

This part of IEC 60695 gives guidance on:
a) optical measurement of smoke obscuration;
b) general aspects of optical smoke test methods;
c) consideration of test methods;
d) expression of smoke test data;
e) relevance of optical smoke data to hazard assessment.
One of the responsibilities of a technical committee is, wherever applicable, to make use of basic safety publications in the preparation of its publications.

  • Amendment
    17 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European standard specifies rules and prescribes the methodology for the preparation of extended application reports for linear joint sealing systems tested in accordance with EN 1366-4. The field of the extended application reports is additional to the direct field of application given in EN 1366-4. It may be applied to or based on a single test, or a number of tests, which provide the relevant information for the formulation of an extended application.
Mechanical metal seals are not part of the scope of this European standard.

  • Standard
    12 pages
    English language
    sale 10% off
    e-Library read for
    1 day

IEC 60669-2-6:2012 is applicable to fireman's switches used for the breaking of the low-voltage circuits for exterior and interior signs and luminaires e.g. neon signs for a.c. only with a rated voltage not exceeding 440 V and a rated current not exceeding 125 A.   This publication is to be read in conjunction with IEC 60669-1:1998.

  • Standard
    28 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard specifies the characteristics of gauge 24 two-core lightweight fire proof, screened, electrical cables for data transmission systems of aircraft at operating temperature between - 65 °C and 260 °C.
These cables are UV Laser printable in accordance with EN 3838.

  • Standard
    10 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard specifies the characteristics of a light weight fire resistant, screened, electrical cables for use in the on-board electrical systems of aircraft at operating temperature between - 65°C and 260°C. These cables are UV Laser printable in accordance with EN 3838.

  • Standard
    10 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard defines requirements for running capability under fire conditions which are applicable to passenger carrying railway rolling stock. In particular, technical measures are specified, compliance with which will contribute to conformity with the Directive and the relevant Technical Specifications for Interoperability (TSI). The standard specifies the fire conditions: - for which it is not necessary to define running capability requirements as there is no significant potential for serious injury or threat to life; - for which it is reasonable to expect trains to continue to run in a controlled manner; - for which it is not reasonably practicable to define requirements which give complete assurance of running in a controlled manner, due to the exceptional nature of the fire incident. The TSI SRT defines running capability requirements in respect of fires within technical areas/equipment only. However for general guidance the scope of this standard is extended to include fires from non-technical causes within passenger/staff areas which may impact train system functions adjacent to and/or passing through the affected area. This extension of applicability significantly increases the number of system functions which are potentially at risk and therefore requires that the "reasonably practicable" principles be extended to this new condition. The standard does not consider situations where a primary non-fire incident is likely to immobilise the train by definition; for example major mechanical defect leading to derailment, even when fire then occurs.

  • Standard
    38 pages
    English language
    sale 10% off
    e-Library read for
    1 day

IEC 60695-6-2:2011 provides a summary of the test methods that are used in the assessment of smoke obscuration. It presents a brief summary of static and dynamic test methods in common use, either as international standards or national or industry standards. It includes special observations on their relevance to electrotechnical products and their materials and to fire scenarios, and it gives recommendations on their use. This standard cancels and replaces IEC/TS 60695-6-2 published in 2005. This first edition constitutes a technical revision. The main changes with respect to the previous edition are listed below:
- this publication has been re-designated as an International Standard;
- updated normative references;
- updated terms and definitions; new test method Clause 7.3.2;
- numerous editorial changes of a technical nature throughout the publication.
It has the status of a horizontal standard in accordance with IEC Guide 104 and ISO/IEC Guide 51.
This publication is to be read in conjunction with  IEC 60695-6-1:2005.

  • Standard
    69 pages
    English and French language
    sale 15% off

This European Standard applies to smoke control duct sections, placed on the market and intended to operate as part of a pressure differential system or smoke and heat exhaust system. This standard specifies requirements and gives reference to the test methods defined for smoke control duct sections and their associated components (for example, hangers and other items proven at the time of testing), which are intended to be installed in such systems in buildings. It also provides for the evaluation of conformity of the products to the requirements of this standard. Furthermore, marking and information on installation and maintenance of these products are also given in this European Standard.
To avoid duplication, reference is made to a variety of other standards. To this end, this standard is to be read in conjunction with EN 1366-8, EN 1366-9 and EN 1366-1, for details of the fire resistance testing and EN 13501-4 for corresponding classification.
This standard has not considered in detail the detrimental and/or corrosive effects that may be caused by process chemicals present in the atmosphere, which are drawn through the system intentionally or inadvertently.
This European Standard also governs associated components used together with smoke control duct sections such as turning vanes and silencers, with the exception of natural and powered smoke ventilators and smoke control dampers, which are covered by separate standards.
Ducts for use other than in smoke and heat exhaust/control systems are not covered by this standard.

  • Standard
    30 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard applies to smoke control dampers, placed on the market and intended to operate as part of a pressure differential system or smoke and heat control system. This standard specifies requirements and gives reference to the test methods defined for smoke control dampers and their associated components, such as actuators which are intended to be installed in such systems in buildings. It also provides for the evaluation of conformity of these products to the requirements of this standard. Furthermore, provision on marking and information on installation and maintenance of these products are also given.
This European Standard distinguish between two categories of smoke control dampers, i.e. single compartment smoke control dampers and multi-compartment fire resisting smoke control dampers.
Smoke control dampers covered by this European Standard can be installed into smoke control system ducts or onto the ducts´ surface. They can be installed also into a wall, floor or ceiling/roof elements or onto the surface of these elements.
To avoid duplication, reference is made to a variety of other standards. To this end, this standard is to be read in conjunction with EN 13501-4, prEN 1366-10 and EN 1366-2, for details of the furnace testing.
This standard does not consider in detail the detrimental and/or corrosive effects that may be caused by process chemicals present in the atmosphere, which are drawn through the system intentionally or inadvertently.

  • Standard
    38 pages
    English language
    sale 10% off
    e-Library read for
    1 day

IEC 60695-6-1:2005 Gives guidance on:
a) optical measurement of smoke obscuration;
b) general aspects of optical smoke test methods;
c) consideration of test methods;
d) expression of smoke test data;
e) relevance of optical smoke data to hazard assessment.
The main changes with respect to the previous edition are listed below:
- Modified title.
- Updated normative references.
- Expanded terms and definitions.
- Numerous editorial changes of a technical nature throughout the publication.
- A flowchart has been added for the evaluation and consideration of smoke test methods.

  • Standard
    61 pages
    English and French language
    sale 15% off
  • Standard
    84 pages
    English and French language
    sale 15% off

IEC 60695-6-1:2005+A1:2010 Gives guidance on:
a) optical measurement of smoke obscuration;
b) general aspects of optical smoke test methods;
c) consideration of test methods;
d) expression of smoke test data;
e) relevance of optical smoke data to hazard assessment.
The main changes with respect to the previous edition are listed below:
- Modified title.
- Updated normative references.
- Expanded terms and definitions.
- Numerous editorial changes of a technical nature throughout the publication.
- A flowchart has been added for the evaluation and consideration of smoke test methods.
Has the status of a basic safety publication in accordance with IEC Guide 104.
This publication is to be read in conjunction with  IEC 60695-6-2:2005.
This consolidated version consists of the second edition (2005) and its amendment 1 (2010). Therefore, no need to order amendment in addition to this publication.

  • Standard
    84 pages
    English and French language
    sale 15% off

Applies to capacitors and resistors with unidirectional terminations intended for use in electronic equipment.

  • Standard
    27 pages
    English and French language
    sale 15% off

This standard specifies the list of product standards and common characteristics of fire resistant or fire proof, screened, electrical cables for use in aircraft electrical systems at operating temperature between - 65 °C and 260 °C.

  • Standard
    6 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This Technical Report applies to SHEVS when installed in a building. This Technical Report specifies the ability of the system to meet the required performances of the SHEVS as specified by the design of the system. This Technical Report is to help to translate the detailed engineering plan into an installed system, but it does not state how the design is made. This Technical Report also covers requirements for components and compatibility between components to ensure that the requirements on the installed system will be met. This Technical report includes requirements for the assembly, installation, commissioning, function testing, maintenance, periodic servicing and routine testing of SHEVS.

  • Technical report
    51 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This part of EN 12101 specifies the product performance requirements, classifications and test methods for smoke barriers, which comprise the barrier itself, with or without associated activation and drive devices, designed for use in smoke and heat control systems. It covers only barriers installed in buildings, i.e. it does not cover barriers made of part of the building's structure. This standard provides the test methods for, and evaluation of conformity of, the smoke barrier systems.

  • Standard
    51 pages
    English language
    sale 10% off
    e-Library read for
    1 day

ISO 27368:2008 details analytical methods suitable for analysing the two primary toxic combustion gases, carbon monoxide (CO) and hydrogen cyanide (HCN), in blood samples collected from fire casualties. In blood, CO is measured as carboxyhaemoglobin (COHb) and HCN as cyanide ion (CN-). Although numerous methods are reported in the literature for performing blood COHb and CN- analyses, the analytical methods included herein are based upon their suitability for performing the analysis on ante-mortem and post-mortem blood samples from fire casualties. The analytical principle, analysis time, repeatability, reproducibility, robustness, effectiveness and instruments used are considered for those methods. Some of the methods described in ISO 27368:2008 might not be suitable for analysing putrid or clotted blood. Burned (solid) blood can be analysed after homogenization.

  • Standard
    57 pages
    English language
    sale 15% off

Gives guidance on: a) optical measurement of smoke obscuration; b) general aspects of optical smoke test methods; c) consideration of test methods; d) expression of smoke test data; e) relevance of optical smoke data to hazard assessment. The main changes with respect to the previous edition are listed below: - Modified title. - Updated normative references. - Expanded terms and definitions. - Numerous editorial changes of a technical nature throughout the publication. - A flowchart has been added for the evaluation and consideration of smoke test methods. Has the status of a basic safety publication in accordance with IEC Guide 104

  • Standard
    34 pages
    English language
    sale 10% off
    e-Library read for
    1 day

TC - Modification to 5.2.5.2 and 5.2.5.3

  • Corrigendum
    2 pages
    English, French and German language
    sale 10% off
    e-Library read for
    1 day

This European Standard specifies requirements and gives test methods for primary and secondary electrical and pneumatic power supply equipment, designed for use in smoke and heat control systems in buildings. It also provides for the evaluation of conformity of such equipment to the requirements of this European Standard.
NOTE   A summary of functions is given in Annex A.

  • Standard
    51 pages
    English language
    sale 10% off
    e-Library read for
    1 day