This document specifies the standard test method to assess the performance of dust collectors utilizing integrated fans (compact type dust collector), at the time of manufacture, after being used for a certain period. This document adopts the black box concept that the dust collector to be tested is operated with the specification determined by the manufacturer except test dust condition and the pulse interval during ageing. This document is applicable to small dust collectors utilizing cartridge filters including molded filters or bag filters with pulse cleaning equipment as filtration media for dry dust collection. Mist and fumes collectors are excluded from this test. The performance obtained from this test does not guarantee the performance of the system. This document is not intended to offer the superiority or inferiority of performance between dust collectors, but specifies a standard test method that provides users with performance under simulated conditions of use for a certain duration.

  • Standard
    31 pages
    English language
    sale 15% off
  • Standard
    34 pages
    French language
    sale 15% off

This document specifies the laboratory test methods and test requirements for the testing of aerodynamic, thermal, acoustic and electrical performance characteristics of ducted mechanical supply and exhaust residential ventilation units.
NOTE   Such units are referred to as bidirectional ventilation units in EN 13142:2021.
This document is applicable to unit that contain at least, within one or more casing:
—   fans for mechanical supply and exhaust;
—   air filters;
—   air-to-air heat exchanger and/or air-to-air heat pump for air heat recovery;
—   control system.
Such unit can be provided in more than one assembly, the separate assemblies of which are designed to be used together.
Examples of different possible arrangements of heat recovery, heat exchangers and/or heat pumps are described in Annex A.
This document covers ventilation units with continuous mass flows for each setting point.
This document does not deal with non-ducted units that are treated in prEN 13141 8:2021.
This document does not cover ventilation systems that may also provide water space heating and hot water that are treated in EN 16573.
This document does not cover units including combustion engine driven compression heat pumps and absorption heat pumps.
Electrical safety requirements are given in EN 60335 2 40 and EN 60335 2 80.

  • Standard
    55 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies the laboratory test methods and test requirements for the testing of aerodynamic, thermal, acoustic and electrical performance characteristics of ducted mechanical supply and exhaust residential ventilation units.
NOTE   Such units are referred to as bidirectional ventilation units in EN 13142:2021.
This document is applicable to unit that contain at least, within one or more casing:
—   fans for mechanical supply and exhaust;
—   air filters;
—   air-to-air heat exchanger and/or air-to-air heat pump for air heat recovery;
—   control system.
Such unit can be provided in more than one assembly, the separate assemblies of which are designed to be used together.
Examples of different possible arrangements of heat recovery, heat exchangers and/or heat pumps are described in Annex A.
This document covers ventilation units with continuous mass flows for each setting point.
This document does not deal with non-ducted units that are treated in prEN 13141 8:2021.
This document does not cover ventilation systems that may also provide water space heating and hot water that are treated in EN 16573.
This document does not cover units including combustion engine driven compression heat pumps and absorption heat pumps.
Electrical safety requirements are given in EN 60335 2 40 and EN 60335 2 80.

  • Standard
    55 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies the terms and definitions, the test conditions and the test methods for the rating and performance of rooftop units. It also specifies the determination of capacities and the calculation methods considering rooftop units features, such as free cooling and air flow mixtures, for the determination of seasonal energy efficiencies in cooling and heating.
This document covers only space heating and/or cooling for comfort applications (process applications are outside the scope of this document). It applies to air-to-air and water(brine)-to-air rooftop units with electrically driven compressor(s), which may be equipped with a supplementary heater using electrical resistance or combustion of fossil fuel. This document does not cover rooftop units with remote condensers.
This document covers the features of free cooling, mixing air flows (on both sides) and internal heat recovery, as illustrated in Annex A. Annex B provides additional definitions and methods for determining seasonal performances for space cooling/heating with a minimum mixture of outdoor air and recycled air.

  • Standard
    108 pages
    English language
    sale 10% off
    e-Library read for
    1 day

document specifies the terms and definitions, the test conditions and the test methods of air-sourced
and water-cooled roof-top units, driven by electric compressor(s), which may be equipped with a
supplementary heater using electrical resistance or combustion of fossil fuel.
This document covers roof-top units with 2, 3 or 4 dampers, including several features as the free-cooling,
mixing air flows (on both sides) and heat recovery.
This document deals with roof-top units providing space heating and/or cooling for comfort application.
Process applications are not covered by this document.
This document provides the part load conditions and the calculation methods taking into account roof-top
units features for the determination of seasonal energy efficiency SEER and SEERon, seasonal space
cooling energy efficiency ηs,c, seasonal coefficient of performance SCOP, SCOPon and SCOPnet,
seasonal space heating energy efficiency ηs,h and the overall annual efficiency.
Such calculation methods may be based on calculated or measured values.
In case of measured values, this document covers the test methods for determination of capacities, EER
and COP values during active mode at part load conditions. It also covers test methods for the
determination of power input during thermostat-off mode, standby mode, off-mode and crankcase heater
mode.
A roof-top unit that is not using at least the thermodynamic cycle for space heating is considered as a
cooling only unit.
Roof-top units equipped with additional air heating and/or cooling heat exchangers will be rated without
operation of these heat exchangers.

  • Standard
    108 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies design criteria for closed water-based cooling systems in buildings and the design of such systems is described. The definitions are aimed at achieving an appropriate level of technical quality and maintaining the desired thermal indoor climate with minimum energy consumption.
This document does not apply to systems for dissipating process heat from industrial processes. It also does not apply to and does not amend product standards or product installation requirements.
This document is applicable to cooling systems of the following type (see also Figure 1):
1)   devices for the water-based heat rejection of the chilling system;
2)   devices for chilling and storage of chilled water;
3)   devices for the distribution of chilled water;
4)   devices for the absorption of heat ("cooling emission");
5)   control devices;
6)   safety devices.
Figure 1 - Schematic example of a water-based cooling system
This document does not cover additional safety aspects for water-based cooling systems with local operating temperatures ≤ 0 °C. The other clauses of this document are still valid for systems with local operating temperatures ≤ 0 °C.
This document also does not cover the chilling system itself, but only the parts of the chilling system which are an integral part of the cooling system, including determination of the design performance. Furthermore, this document does not cover:
-   the requirements for installation or instructions for operation, maintenance and use;
-   the design of the system components (e.g. recooler, chilling system, coolers, pipes, safety devices etc.).

  • Standard
    37 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies general requirements and gives guidelines for ventilation systems except for industrial, medical and laboratory facilities.
This document also specifies cleanliness criteria and procedures necessary in assessing and maintaining the cleanliness of ventilation systems over their lifetime from design and installation to maintenance.
This document is applicable to both new and existing ventilation systems with, and without, air conditioning and kitchen extract systems.

  • Standard
    44 pages
    English language
    sale 10% off
    e-Library read for
    1 day

1.1   Scope of EN 12309
Appliances covered by this document include one or a combination of the following:
-   gas-fired sorption chiller;
-   gas-fired sorption chiller/heater;
-   gas-fired sorption heat pump.
This document applies to appliances designed to be used for space heating or cooling or refrigeration with or without heat recovery.
This document applies to appliances having flue gas systems of Type B and Type C (according to EN 1749:2020) and to appliances designed for outdoor installations, including Type A. EN 12309 does not apply to air conditioners, it only applies to appliances having:
-   integral burners under the control of fully automatic burner control systems,
-   closed system refrigerant circuits in which the refrigerant does not come into direct contact with the water or air to be cooled or heated,
-   mechanical means to assist transportation of the combustion air and/or the flue gas.
The above appliances can have one or more primary or secondary functions (i.e. heat recovery - see definitions in EN 12309-1:2023).
In the case of packaged units (consisting of several parts), this document applies only to those designed and supplied as a complete package.
The appliances having their condenser cooled by air and by the evaporation of external additional water are not covered by EN 12309.
Installations used for heating and/or cooling of industrial processes are not within the scope of EN 12309.
All the symbols given in this document are used regardless of the language used.
1.2   Scope of this Part 6 to EN 12309
This part of EN 12309 specifies the calculation methods of seasonal performances for gas-fired sorption appliances for heating and/or cooling with a net heat input not exceeding 70 kW. It deals in particular with the calculation methods of reference seasonal performances in cooling and heating mode for monovalent and bivalent appliances.

  • Standard
    45 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies design criteria for closed water-based cooling systems in buildings and the design of such systems is described. The definitions are aimed at achieving an appropriate level of technical quality and maintaining the desired thermal indoor climate with minimum energy consumption.
This document does not apply to systems for dissipating process heat from industrial processes. It also does not apply to and does not amend product standards or product installation requirements.
This document is applicable to cooling systems of the following type (see also Figure 1):
1)   devices for the water-based heat rejection of the chilling system;
2)   devices for chilling and storage of chilled water;
3)   devices for the distribution of chilled water;
4)   devices for the absorption of heat ("cooling emission");
5)   control devices;
6)   safety devices.
Figure 1 - Schematic example of a water-based cooling system
This document does not cover additional safety aspects for water-based cooling systems with local operating temperatures ≤ 0 °C. The other clauses of this document are still valid for systems with local operating temperatures ≤ 0 °C.
This document also does not cover the chilling system itself, but only the parts of the chilling system which are an integral part of the cooling system, including determination of the design performance. Furthermore, this document does not cover:
-   the requirements for installation or instructions for operation, maintenance and use;
-   the design of the system components (e.g. recooler, chilling system, coolers, pipes, safety devices etc.).

  • Standard
    37 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document provides basic performance requirements and corresponding test methods for containment high efficiency filtration units (CHEFUs). This document is applicable to the devices used to remove harmful bio-aerosol in biosafety facilities and similar controlled environment. This document is not applicable to a filtration unit for removing radioactive aerosol.

  • Standard
    21 pages
    English language
    sale 15% off

This document specifies general requirements and gives guidelines for ventilation systems except for industrial, medical and laboratory facilities.
This document also specifies cleanliness criteria and procedures necessary in assessing and maintaining the cleanliness of ventilation systems over their lifetime from design and installation to maintenance.
This document is applicable to both new and existing ventilation systems with, and without, air conditioning and kitchen extract systems.

  • Standard
    44 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies laboratory test methods, test requirements and classifications for the casings of non-residential air handling units (AHU). For the leakage tests, a method for on-site testing is also included.
The test methods and requirements are applicable to both model boxes and real units, except for the thermal and acoustic performance of the casing.
The test method for the thermal performance of the casing is applicable to the comparison of different casing constructions, but not for the calculation of thermal losses through casing or the risk of condensation.
The test method for the acoustic performance of the casing is applicable for the comparison of different constructions, but not for the provision of accurate acoustic data for specific units.
This document is not applicable for fan-coil units and similar products.
The filter bypass test specified in this document is not applicable to high efficiency particulate air (HEPA) filter installations.

  • Standard
    56 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies laboratory test methods, test requirements and classifications for the casings of non-residential air handling units (AHU). For the leakage tests, a method for on-site testing is also included.
The test methods and requirements are applicable to both model boxes and real units, except for the thermal and acoustic performance of the casing.
The test method for the thermal performance of the casing is applicable to the comparison of different casing constructions, but not for the calculation of thermal losses through casing or the risk of condensation.
The test method for the acoustic performance of the casing is applicable for the comparison of different constructions, but not for the provision of accurate acoustic data for specific units.
This document is not applicable for fan-coil units and similar products.
The filter bypass test specified in this document is not applicable to high efficiency particulate air (HEPA) filter installations.

  • Standard
    56 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document applies to the design, energy performance of buildings and implementation of ventilation, air conditioning and room conditioning systems for non-residential buildings subject to human occupancy, excluding applications like industrial processes. It focuses on the definitions of the various parameters that are relevant for such systems.
The guidance for design given in this document and accompanying CEN/TR 16798-4 are mainly applicable to mechanical supply and/or exhaust ventilation systems. Natural ventilation systems or natural parts of hybrid ventilation systems are not covered by this document.
Applications for residential ventilation are not covered in this document. Performance of ventilation systems in residential buildings is covered in EN 15665 and CEN/TR 14788.
The classification uses different categories. For some values, examples are given and, for requirements, typical ranges with default values are presented. The default values are given in Annex B and a template for national specification is given in Annex A. It is important that the classification is always appropriate to the type of building and its intended use, and that the basis of the classification is explained if the examples given in this document are not used.
NOTE 1   Different standards can express the categories for the same parameters in a different way, and also the category symbols can be different.
Table 1 shows the relative position of this document within the set of EPB standards in the context of the modular structure as set out in EN ISO 52000-1.
NOTE 2   In CEN ISO/TR 52000-2 the same Table can be found, with, for each module, the numbers of the relevant EPB standards and accompanying technical reports that are published or in preparation.
NOTE 3   The modules represent EPB standards, although one EPB standard might cover more than one module and one module might be covered by more than one EPB standard, for instance a simplified and a detailed method respectively. See also Clause 2 and Table A.1 and Table B.1.
Table 1 - Position of this standard (in case M5-1, M5-4), within the modular structure of the set of EPB standards

  • Standard
    82 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document applies to the design, energy performance of buildings and implementation of ventilation, air conditioning and room conditioning systems for non-residential buildings subject to human occupancy, excluding applications like industrial processes. It focuses on the definitions of the various parameters that are relevant for such systems.
The guidance for design given in this document and accompanying CEN/TR 16798-4 are mainly applicable to mechanical supply and/or exhaust ventilation systems. Natural ventilation systems or natural parts of hybrid ventilation systems are not covered by this document.
Applications for residential ventilation are not covered in this document. Performance of ventilation systems in residential buildings is covered in EN 15665 and CEN/TR 14788.
The classification uses different categories. For some values, examples are given and, for requirements, typical ranges with default values are presented. The default values are given in Annex B and a template for national specification is given in Annex A. It is important that the classification is always appropriate to the type of building and its intended use, and that the basis of the classification is explained if the examples given in this document are not used.
NOTE 1   Different standards can express the categories for the same parameters in a different way, and also the category symbols can be different.
Table 1 shows the relative position of this document within the set of EPB standards in the context of the modular structure as set out in EN ISO 52000-1.
NOTE 2   In CEN ISO/TR 52000-2 the same Table can be found, with, for each module, the numbers of the relevant EPB standards and accompanying technical reports that are published or in preparation.
NOTE 3   The modules represent EPB standards, although one EPB standard might cover more than one module and one module might be covered by more than one EPB standard, for instance a simplified and a detailed method respectively. See also Clause 2 and Table A.1 and Table B.1.
Table 1 - Position of this standard (in case M5-1, M5-4), within the modular structure of the set of EPB standards

  • Standard
    82 pages
    English language
    sale 10% off
    e-Library read for
    1 day

1.1   Scope of EN 12309
Appliances covered by this document include one or a combination of the following:
-   gas-fired sorption chiller;
-   gas-fired sorption chiller/heater;
-   gas-fired sorption heat pump.
This document applies to appliances designed to be used for space heating or cooling or refrigeration with or without heat recovery.
This document applies to appliances having flue gas systems of Type B and Type C (according to EN 1749:2020) and to appliances designed for outdoor installations, including Type A. EN 12309 does not apply to air conditioners, it only applies to appliances having:
-   integral burners under the control of fully automatic burner control systems,
-   closed system refrigerant circuits in which the refrigerant does not come into direct contact with the water or air to be cooled or heated,
-   mechanical means to assist transportation of the combustion air and/or the flue gas.
The above appliances can have one or more primary or secondary functions (i.e. heat recovery - see definitions in EN 12309-1:2023).
In the case of packaged units (consisting of several parts), this document applies only to those designed and supplied as a complete package.
The appliances having their condenser cooled by air and by the evaporation of external additional water are not covered by EN 12309.
Installations used for heating and/or cooling of industrial processes are not within the scope of EN 12309.
All the symbols given in this document are used regardless of the language used.
1.2   Scope of this Part 6 to EN 12309
This part of EN 12309 specifies the calculation methods of seasonal performances for gas-fired sorption appliances for heating and/or cooling with a net heat input not exceeding 70 kW. It deals in particular with the calculation methods of reference seasonal performances in cooling and heating mode for monovalent and bivalent appliances.

  • Standard
    45 pages
    English language
    sale 10% off
    e-Library read for
    1 day

1.1   Scope of EN 12309 series
Appliances covered by this document include one or a combination of the following:
-   gas-fired sorption chiller;
-   gas-fired sorption chiller/heater;
-   gas-fired sorption heat pump;
-   hybrids based on gas sorption appliances.
This document applies to appliances designed to be used for space heating or cooling or refrigeration with or without heat recovery.
This document applies to appliances having flue gas systems of Type B and Type C (according to EN 1749:2020) and to appliances designed for outdoor installations, including Type A.
EN 12309 does not apply to air conditioners, it only applies to appliances having:
-   integral burners under the control of fully automatic burner control systems;
-   closed system refrigerant circuits in which the refrigerant does not come into direct contact with the water or air to be cooled or heated;
-   mechanical means to assist transportation of the combustion air and/or the flue gas.
The above appliances can have one or more primary or secondary functions (i.e. heat recovery - see definitions in EN 12309-1:2023).
In the case of packaged units (consisting of several parts), this document applies only to those designed and supplied as a complete package.
The appliances having their condenser cooled by air and by the evaporation of external additional water are not covered by EN 12309.
Installations used for heating and/or cooling of industrial processes are not within the scope of EN 12309. All the symbols given in this text are to be used regardless of the language used.
1.2   Scope of this Part 3 of EN 12309
This part of EN 12309 specifies the requirements, test methods and conditions for gas-fired sorption appliances for heating and/or cooling with a net heat input not exceeding 70 kW.
This part of EN 12309 deals particularly with test protocols and tools to calculate the capacity, the gas utilization efficiency and the electrical power input of the appliance. This data can be used in particular to calculate the seasonal efficiency of the appliance.

  • Standard
    75 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies methods for the measurement of air flow rates on site. It provides a description of the air flow rate measurement methods and how measurements are performed within the margins of stipulated method uncertainties. It gives the necessary measurement conditions (e.g. length of straight duct, uniform velocity profile) to achieve the stipulated measurement uncertainties.
The methods for measuring the air flow rate inside ducts do not apply to:
-   ducts that are not circular or rectangular (e.g. oblong ducts);
-   flexible ducts.

  • Standard
    62 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies methods for the measurement of air flow rates on site. It provides a description of the air flow rate measurement methods and how measurements are performed within the margins of stipulated method uncertainties. It gives the necessary measurement conditions (e.g. length of straight duct, uniform velocity profile) to achieve the stipulated measurement uncertainties.
The methods for measuring the air flow rate inside ducts do not apply to:
-   ducts that are not circular or rectangular (e.g. oblong ducts);
-   flexible ducts.

  • Standard
    62 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This part of EN 1366 specifies a test method for determining the fire resistance of smoke extraction ducts that are used for single compartment applications only. In such applications, the smoke extraction system is only intended to function up to flashover (typically 600 °C).
This method of test is only suitable for ducts constructed from non-combustible materials (class A1 and A2-s1, d0 according to EN 13501-1).
It is applicable only to four sided and circular ducts. One-, two- and three-sided ducts are not covered. This document is applicable only for the standard sizes or smaller as described.
This test method of part 9 is applicable only to smoke extraction ducts that do not pass into other fire compartments. For smoke extraction ducts that pass into other compartments, the method of test described in EN 1366-8 is used.
The smoke extraction duct is part of the smoke extraction system which also includes smoke control dampers and smoke extract fans.

  • Standard
    49 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This part of EN 1366 specifies a test method for determining the fire resistance of smoke extraction ducts that are used for single compartment applications only. In such applications, the smoke extraction system is only intended to function up to flashover (typically 600 °C).
This method of test is only suitable for ducts constructed from non-combustible materials (class A1 and A2-s1, d0 according to EN 13501-1).
It is applicable only to four sided and circular ducts. One-, two- and three-sided ducts are not covered. This document is applicable only for the standard sizes or smaller as described.
This test method of part 9 is applicable only to smoke extraction ducts that do not pass into other fire compartments. For smoke extraction ducts that pass into other compartments, the method of test described in EN 1366-8 is used.
The smoke extraction duct is part of the smoke extraction system which also includes smoke control dampers and smoke extract fans.

  • Standard
    49 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies test methods for smoke control dampers to assess their performance under elevated temperature or fire conditions, as well as at ambient temperatures.
Smoke control damper tests are used to confirm that the furnace testing requirements of EN 12101-8 are met and EN 12101-8 is for consideration before carrying out these tests.
Smoke control dampers tested to this document are expected to be classified using EN 13501-4 and this document is expected to be considered before carrying out these tests.
NOTE   Some smoke control dampers to be tested might require testing following the information given in EN 1366-2 and this needs consideration before carrying out testing.
This document is expected to be read in conjunction with EN 12101-8, EN 13501-4, EN 1366-2 and EN 1363-1, the latter giving further details for fire resistance testing.
For installation details, the requirements for smoke extraction ducts are for consideration and these are defined in EN 1366-8 and EN 1366-9.

  • Standard
    99 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies the test equipment and the test methods used for measuring the gravimetric efficiency and resistance to air flow of air filter for general ventilation.
It is intended for use in conjunction with ISO 16890-1, ISO 16890-2 and ISO 16890-4.
The test method described in this document is applicable for air flow rates between 0,25 m3/s (900 m3/h, 530 ft3/min) and 1,5 m3/s (5 400 m3/h, 3 178 ft3/min), referring to a test rig with a nominal face area of 610 mm × 610 mm (24 in × 24 in).
This document refers to particulate air filter elements for general ventilation having an ePM1 efficiency less than or equal to 99 % and an ePM10 efficiency greater than 20 % when tested as per the procedures defined in the ISO 16890 series.
NOTE            The lower limit for this test procedure is set at a minimum ePM10 efficiency of 20 % since it is very difficult for a test filter element below this level to meet the statistical validity requirements of this procedure.
This document does not apply to filter elements used in portable room-air cleaners.

  • Standard
    31 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies test methods for smoke control dampers to assess their performance under elevated temperature or fire conditions, as well as at ambient temperatures.
Smoke control damper tests are used to confirm that the furnace testing requirements of EN 12101-8 are met and EN 12101-8 is for consideration before carrying out these tests.
Smoke control dampers tested to this document are expected to be classified using EN 13501-4 and this document is expected to be considered before carrying out these tests.
NOTE   Some smoke control dampers to be tested might require testing following the information given in EN 1366-2 and this needs consideration before carrying out testing.
This document is expected to be read in conjunction with EN 12101-8, EN 13501-4, EN 1366-2 and EN 1363-1, the latter giving further details for fire resistance testing.
For installation details, the requirements for smoke extraction ducts are for consideration and these are defined in EN 1366-8 and EN 1366-9.

  • Standard
    99 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies the test equipment and the test methods used for measuring the gravimetric efficiency and resistance to air flow of air filter for general ventilation.
It is intended for use in conjunction with ISO 16890-1, ISO 16890-2 and ISO 16890-4.
The test method described in this document is applicable for air flow rates between 0,25 m3/s (900 m3/h, 530 ft3/min) and 1,5 m3/s (5 400 m3/h, 3 178 ft3/min), referring to a test rig with a nominal face area of 610 mm × 610 mm (24 in × 24 in).
This document refers to particulate air filter elements for general ventilation having an ePM1 efficiency less than or equal to 99 % and an ePM10 efficiency greater than 20 % when tested as per the procedures defined in the ISO 16890 series.
NOTE            The lower limit for this test procedure is set at a minimum ePM10 efficiency of 20 % since it is very difficult for a test filter element below this level to meet the statistical validity requirements of this procedure.
This document does not apply to filter elements used in portable room-air cleaners.

  • Standard
    31 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies the test equipment and the test methods used for measuring the gravimetric efficiency and resistance to air flow of air filter for general ventilation. It is intended for use in conjunction with ISO 16890-1, ISO 16890-2 and ISO 16890-4. The test method described in this document is applicable for air flow rates between 0,25 m3/s (900 m3/h, 530 ft3/min) and 1,5 m3/s (5 400 m3/h, 3 178 ft3/min), referring to a test rig with a nominal face area of 610 mm × 610 mm (24 in × 24 in). This document refers to particulate air filter elements for general ventilation having an ePM1 efficiency less than or equal to 99 % and an ePM10 efficiency greater than 20 % when tested as per the procedures defined in the ISO 16890 series. NOTE The lower limit for this test procedure is set at a minimum ePM10 efficiency of 20 % since it is very difficult for a test filter element below this level to meet the statistical validity requirements of this procedure. This document does not apply to filter elements used in portable room-air cleaners.

  • Standard
    22 pages
    English language
    sale 15% off
  • Standard
    22 pages
    French language
    sale 15% off

This document defines terms related to the air filtration industry.
This document is applicable to particulate matter and gas phase air filters and air cleaners used for the general ventilation of inhabited enclosed spaces. It is also applicable to air inlet filters for static or seaborne rotary machines, cleanable filters, UV-C germicidal devices, and stand-alone electrically-powered air cleaners.
It is not applicable to cabin filters for road vehicles or air inlet filters for mobile internal combustion engines for which separate arrangements exist. Dust separators for the purpose of air pollution control are also excluded.

  • Standard
    48 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document establishes a classification of filters based on their performance, as determined in accordance with ISO 29463-3, ISO 29463-4 and ISO 29463-5. It also provides an overview of the test procedures and specifies general requirements for assessing and marking the filters, as well as for documenting the test results. It is intended to be used in conjunction with ISO 29463-2, ISO 29463-3, ISO 29463-4 and ISO 29463-5.

  • Standard
    27 pages
    English language
    sale 15% off

This document defines terms related to the air filtration industry.
This document is applicable to particulate matter and gas phase air filters and air cleaners used for the general ventilation of inhabited enclosed spaces. It is also applicable to air inlet filters for static or seaborne rotary machines, cleanable filters, UV-C germicidal devices, and stand-alone electrically-powered air cleaners.
It is not applicable to cabin filters for road vehicles or air inlet filters for mobile internal combustion engines for which separate arrangements exist. Dust separators for the purpose of air pollution control are also excluded.

  • Standard
    48 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies the technology of biological exhaust air purification. The relevant requirements for a possible application are specified. The different variants of this technique are also presented. NOTE The process principles of this method are described in Clause 4.

  • Standard
    20 pages
    English language
    sale 15% off

This document specifies a method for determining the fire resistance of vertical and horizontal ventilation ducts under standardized fire conditions. The test examines the behaviour of ducts exposed to fire from the outside (duct A) and fire inside the duct (duct B). This document is intended to be used in conjunction with ISO 834-1. This document is not applicable to: a) ducts whose fire resistance depends on the fire resistance performance of a ceiling; b) ducts containing fire dampers at points where they pass through fire separations; c) doors of inspection openings, unless included in the duct to be tested; d) two-sided or three-sided ducts; e) the fixing of suspension devices to floors or walls; f) kitchen extract ducts (see ISO 6944-2). NOTE Annex A provides general guidance and gives background information.

  • Standard
    31 pages
    English language
    sale 15% off

This document is applicable to technical insulation systems of operational installations in industry and the building services, such as pipes, ducts, vessels, equipment and built-in components.
The document specifies methods for the energy efficiency classification of insulation systems for the abovementioned components with an operational temperature range of −30 °C up to 650 °C.
The document addresses plant operators, engineers of operational installations, as well as the involved contractors such as insulation contractors and pipefitting contractors.
The design of safe surface temperatures for personal protection, as well as the prevention of condensation, is outside the scope of this document.
This document also does not apply to water-based heating and cooling systems in buildings and does not apply to directly buried district heating and district cooling pipes.

  • Standard
    29 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies a measuring method for the distribution of thickness, area mass, gas permeability and collection efficiency in the filter medium, and applies to both woven and non-woven filter medium. This document provides a method for sampling specimen (position, size and number) from the filter medium required to obtain its performance distribution accurately. The purpose of this document is to provide more accurate information about the morphology of the filter medium for users, and not to compare grade the performance of the filter medium.

  • Standard
    18 pages
    English language
    sale 15% off

This document is applicable to technical insulation systems of operational installations in industry and the building services, such as pipes, ducts, vessels, equipment and built-in components.
The document specifies methods for the energy efficiency classification of insulation systems for the abovementioned components with an operational temperature range of −30 °C up to 650 °C.
The document addresses plant operators, engineers of operational installations, as well as the involved contractors such as insulation contractors and pipefitting contractors.
The design of safe surface temperatures for personal protection, as well as the prevention of condensation, is outside the scope of this document.
This document also does not apply to water-based heating and cooling systems in buildings and does not apply to directly buried district heating and district cooling pipes.

  • Standard
    29 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies methods for the testing and rating of dampers and valves used in air distribution systems with pressure differences up to 2 000 Pa.
The tests incorporated in this document will address:
-   leakage past a closed damper or valve (for classification, see Annex C);
-   casing leakage (for classification, see Annex C);
-   flow rate/pressure requirement characteristics;
-   torque: (see Annex A);
-   thermal transmittance: (see Annex B).
The tests specified above are applicable to the following:
-   measurement of leakage past a closed damper or valve;
-   measurement of casing leakage;
-   determination of flow rate and pressure requirements;
-   measurement of torque characteristics (see Annex A);
-   measurement of thermal transfer characteristics to determine insulation properties (see Annex B).
This document does not apply to the acoustic testing of dampers and valves.
NOTE   Certain aspects of the dynamic performance of dampers and/or valves are dependent upon the air distribution system to which they are connected and are, therefore, difficult to measure in isolation. Such considerations have led to the omission of these aspects of the dynamic performance measurements from this document. Also, in common with other air distribution components, the results from tests carried out in accordance with this document might not be directly applicable if the damper or valve is situated in an area of non-uniform flow.

  • Standard
    30 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies methods for the testing and rating of dampers and valves used in air distribution systems with pressure differences up to 2 000 Pa.
The tests incorporated in this document will address:
-   leakage past a closed damper or valve (for classification, see Annex C);
-   casing leakage (for classification, see Annex C);
-   flow rate/pressure requirement characteristics;
-   torque: (see Annex A);
-   thermal transmittance: (see Annex B).
The tests specified above are applicable to the following:
-   measurement of leakage past a closed damper or valve;
-   measurement of casing leakage;
-   determination of flow rate and pressure requirements;
-   measurement of torque characteristics (see Annex A);
-   measurement of thermal transfer characteristics to determine insulation properties (see Annex B).
This document does not apply to the acoustic testing of dampers and valves.
NOTE   Certain aspects of the dynamic performance of dampers and/or valves are dependent upon the air distribution system to which they are connected and are, therefore, difficult to measure in isolation. Such considerations have led to the omission of these aspects of the dynamic performance measurements from this document. Also, in common with other air distribution components, the results from tests carried out in accordance with this document might not be directly applicable if the damper or valve is situated in an area of non-uniform flow.

  • Standard
    30 pages
    English language
    sale 10% off
    e-Library read for
    1 day

1.1   Scope of EN 12309 series
Appliances covered by this document include one or a combination of the following:
-   gas-fired sorption chiller;
-   gas-fired sorption chiller/heater;
-   gas-fired sorption heat pump;
-   hybrids based on gas sorption appliances.
This document applies to appliances designed to be used for space heating or cooling or refrigeration with or without heat recovery.
This document applies to appliances having flue gas systems of Type B and Type C (according to EN 1749:2020) and to appliances designed for outdoor installations, including Type A.
EN 12309 does not apply to air conditioners, it only applies to appliances having:
-   integral burners under the control of fully automatic burner control systems;
-   closed system refrigerant circuits in which the refrigerant does not come into direct contact with the water or air to be cooled or heated;
-   mechanical means to assist transportation of the combustion air and/or the flue gas.
The above appliances can have one or more primary or secondary functions (i.e. heat recovery - see definitions in EN 12309-1:2023).
In the case of packaged units (consisting of several parts), this document applies only to those designed and supplied as a complete package.
The appliances having their condenser cooled by air and by the evaporation of external additional water are not covered by EN 12309.
Installations used for heating and/or cooling of industrial processes are not within the scope of EN 12309. All the symbols given in this text are to be used regardless of the language used.
1.2   Scope of this Part 3 of EN 12309
This part of EN 12309 specifies the requirements, test methods and conditions for gas-fired sorption appliances for heating and/or cooling with a net heat input not exceeding 70 kW.
This part of EN 12309 deals particularly with test protocols and tools to calculate the capacity, the gas utilization efficiency and the electrical power input of the appliance. This data can be used in particular to calculate the seasonal efficiency of the appliance.

  • Standard
    75 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document provides the general requirements associated with the specific characteristics of high efficiency particulate air (HEPA) filters used in nuclear facilities. This document provides the manufacturer with general requirements for the performance, design, construction, acceptance testing and quality assurance for HEPA filters used in nuclear facilities (for qualification and production tests). All types of HEPA filter used in such applications are covered, from the large size HEPA filters in exhaust HVAC systems to small size low flow rate cylindrical HEPA filters for glove boxes. The design, fabrication, inspection and testing, certificates with regards to their expected performances are mentioned. This document does not provide the specific conditions against which the nuclear filters are designed, tested and qualified. This document applies only to the filters used for nuclear heating ventilation air conditioning (HVAC) or control rooms habitability applications or applications related to the exposure to radioactive ionizing radiations (e.g. medical or radioactive aerosols applications) in the severe conditions (e.g. fire, high radioactive challenge). Filter housing qualification is not part of this document.

  • Standard
    15 pages
    English language
    sale 15% off
  • Standard
    17 pages
    French language
    sale 15% off

This document specifies procedures and conditions to enable the heat flux in electrical surface heating systems to be determined relative to the medium differential temperature for systems. The determination of thermal performance electrical surface heating systems and their conformity to this document is carried out by calculation in accordance with design documents and a model. This enables a uniform assessment and calculation surface heating systems.
The surface temperature and the temperature uniformity of the heated surface, nominal heat flux density between electrical heated layer and space are given as the result.
The ISO 11855 series is applicable to water based embedded surface heating and cooling systems in residential, commercial and industrial buildings[1]. The methods apply to systems integrated into the wall, floor or ceiling construction without any open-air gaps. It does not apply to ceiling mounted panel systems with open air gaps which are not integrated into the building structure.
The ISO 11855 series also applies, as appropriate, to the use of fluids other than water as a heating or cooling medium. The ISO 11855 series is not applicable for testing of systems. The methods do not apply to heated or chilled ceiling panels or beams.
[1]  ISO 11855-7 can also be used for electrical heated embedded systems.

  • Standard
    17 pages
    English language
    sale 10% off
    e-Library read for
    1 day

1.1   Scope of EN 12309
Appliances covered by this document include one or a combination of the following:
-   gas-fired sorption chiller;
-   gas-fired sorption chiller/heater;
-   gas-fired sorption heat pump;
-   hybrids based on gas sorption appliances.
This document applies to appliances designed to be used for space heating or cooling or refrigeration with or without heat recovery.
This document applies to appliances having flue gas systems of type B and C (according to EN 1749) and to appliances designed for outdoor installations. EN 12309 does not apply to air conditioners, it only applies to appliances having:
-   integral burners under the control of fully automatic burner control systems,
-   closed system refrigerant circuits in which the refrigerant does not come into direct contact with the water or air to be cooled or heated,
-   mechanical means to assist transportation of the combustion air and/or the flue gas.
The above appliances can have one or more primary or secondary functions (i.e. heat recovery).
In the case of packaged units (consisting of several parts), this standard applies only to those designed and supplied as a complete package.
The appliances having their condenser cooled by air and by the evaporation of external additional water are not covered by EN 12309.
Installations used for heating and/or cooling of industrial processes are not within the scope of EN 12309.
All the symbols given in this text are used regardless of the language used.
1.2   Scope of this Part 1 of EN 12309
This part of this document specifies the terms and definitions for gas-fired sorption appliances for heating and/or cooling with a net heat input not exceeding 70 kW.

  • Standard
    33 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies the requirements and application guidance for biological deodorization systems in wastewater treatment plants (WWTPs). The specific requirements include odour gas characterization, process selection, equipment manufacture and installation, start-up and operation, performance evaluation, security and secondary pollution control. The guidance can help the development and maintenance of biological deodorization systems in WWTPs and benefits the owners and operators of WWTPs.

  • Standard
    10 pages
    English language
    sale 15% off

1.1   Scope of EN 12309
Appliances covered by this document include one or a combination of the following:
-   gas-fired sorption chiller;
-   gas-fired sorption chiller/heater;
-   gas-fired sorption heat pump;
-   hybrids based on gas sorption appliances.
This document applies to appliances designed to be used for space heating or cooling or refrigeration with or without heat recovery.
This document applies to appliances having flue gas systems of type B and C (according to EN 1749) and to appliances designed for outdoor installations. EN 12309 does not apply to air conditioners, it only applies to appliances having:
-   integral burners under the control of fully automatic burner control systems,
-   closed system refrigerant circuits in which the refrigerant does not come into direct contact with the water or air to be cooled or heated,
-   mechanical means to assist transportation of the combustion air and/or the flue gas.
The above appliances can have one or more primary or secondary functions (i.e. heat recovery).
In the case of packaged units (consisting of several parts), this standard applies only to those designed and supplied as a complete package.
The appliances having their condenser cooled by air and by the evaporation of external additional water are not covered by EN 12309.
Installations used for heating and/or cooling of industrial processes are not within the scope of EN 12309.
All the symbols given in this text are used regardless of the language used.
1.2   Scope of this Part 1 of EN 12309
This part of this document specifies the terms and definitions for gas-fired sorption appliances for heating and/or cooling with a net heat input not exceeding 70 kW.

  • Standard
    33 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document gives guidelines for fulfilling the requirements contained in ISO 6183:2022, 6.4.1 and 7.4.1 and ISO 14520‑1:2023, 5.2.1 h) and 5.3 h), in respect to over- and under-pressurization venting and post-discharge extract.
It considers the design, selection and installation of vents to safeguard the structural integrity of enclosures protected by fixed gaseous extinguishing systems and the post-discharge venting provisions where used.

  • Standard
    45 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This standard applies to the natural ventilation and fan-assisted ventilation of residential buildings,
dwellings and similarly used units which are predominantly used for living purposes, including halls of
residence, retirement homes and nursing homes, and similar institutions during the heating period and throughout the entire year in basements (see Annex F) in residential buildings.
The ventilation concept specified in Clause 4 and Clause 5 applies to new buildings and to existing buildings in which modifications are made relevant to the ventilation regime. Where there is no moisture-protection ventilation, or if additional requirements (e. g. noise protection, hygiene, air quality, etc.) are to be taken into consideration, then suitable ventilation measures are suggested in Clauses 7 to 9.
In Clauses 6 to 9 this standard specifies requirements for natural ventilation systems (cross ventilation, shaft ventilation), fan-assisted ventilation systems, and combinations thereof, taking into consideration the maintenance of the necessary indoor air quality while ensuring moisture protection.
Ensuring ventilation for the purposes of moisture protection by manually opening windows is not covered by this standard. Manual opening of windows is taken into consideration for ventilation levels that are not explicitly designed for.
This standard specifies requirements on the planning, design and commissioning, and the operation and maintenance of the required ventilation components and/or units for natural ventilation systems and fan-assisted ventilation systems with user-independent moisture protection in each case, making due allowance for aspects of construction engineering physics, ventilation, hygiene and energy utilization.
The design recommendations of this standard apply for dwellings with low emissions of harmful substances.Unduly high emissions from the building and in the building environment may require additional measures.
This standard does not apply to active cooling1 air treatment methods nor to active humidification and dehumidification.
As regards the ventilation of windowless rooms, the Bauaufsichtliche Richtlinie über die Lüftung fensterloser Küchen, Bäder und Toilettenräume (Code of practice on ventilation of windowless kitchens, bathrooms and toilet rooms) and DIN 18017-3 apply to the ventilation of windowless kitchens, bathrooms and WCs in dwellings

  • Standard
    108 pages
    German language
    sale 10% off
    e-Library read for
    1 day
  • Standard – translation
    111 pages
    Slovenian language
    sale 10% off
    e-Library read for
    1 day

This document gives guidelines for fulfilling the requirements contained in ISO 6183:2022, 6.4.1 and 7.4.1 and ISO 14520‑1:2023, 5.2.1 h) and 5.3 h), in respect to over- and under-pressurization venting and post-discharge extract.
It considers the design, selection and installation of vents to safeguard the structural integrity of enclosures protected by fixed gaseous extinguishing systems and the post-discharge venting provisions where used.

  • Standard
    45 pages
    English language
    sale 10% off
    e-Library read for
    1 day