ASTM D2220-17
(Specification)Standard Specification for Poly(Vinyl Chloride) Insulation for Wire and Cable, 75°C Operation
Standard Specification for Poly(Vinyl Chloride) Insulation for Wire and Cable, 75°C Operation
ABSTRACT
This specification covers a thermoplastic poly(vinyl chloride) insulation for wire and cable at the prescribed temperature. This insulation is recommended for use in power and control circuits at the specified thickness and voltage ratings and to dry locations. Tests are done on insulated wire or cable in this specification solely to determine the relevant property of the insulation material and not to test the conductor or completed cable. The insulation shall conform to the physical property requirements prescribed for the following: (1) tensile strength and elongation for unaged specimen and aged (using air oven test) tubular and buffed die-cut specimen, (2) heat shock, (3) heat distortion, (4) vertical flame test, (5) tensile strength and elongation for oil resistance test, and (6) cold bond test. Electrical tests shall be performed in the following order: ac voltage test, insulation resistance test, and dc voltage test. The insulation shall conform to the other electrical requirements such as accelerated water absorption (including permittivity and capacitance) and dielectric strength, and shall meet the prescribed thickness as well.
SCOPE
1.1 This specification covers a thermoplastic insulation of poly(vinyl chloride) or the copolymer of vinyl chloride and vinyl acetate.
1.2 This insulation is recommended for use in power and control circuits at temperatures not higher than 75°C. At a thickness of 15 mils (0.38 mm), application is limited to voltage ratings below 300 V, and to dry locations. At a thickness of 30 mils, the application range is widened to dry or wet applications, and to a voltage rating of 600 V.
1.3 In many instances the insulation material cannot be tested unless it has been formed around a conductor or cable. Therefore, tests are done on insulated wire or cable in this specification solely to determine the relevant property of the insulation material and not to test the conductor or completed cable.
1.4 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.4.1 In come cases (including the title), temperatures are described in degrees Celsius only.
General Information
Buy Standard
Standards Content (Sample)
NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation:D2220 −17
Standard Specification for
Poly(Vinyl Chloride) Insulation for Wire and Cable, 75°C
1
Operation
This standard is issued under the fixed designation D2220; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope* G155 Practice for Operating XenonArc LightApparatus for
Exposure of Non-Metallic Materials
1.1 This specification covers a thermoplastic insulation of
poly(vinyl chloride) or the copolymer of vinyl chloride and
3. Terminology
vinyl acetate.
3.1 Definitions:
1.2 This insulation is recommended for use in power and
3.1.1 Fordefinitionsoftermsusedinthisspecification,refer
control circuits at temperatures not higher than 75°C. At a
to Terminology D1711.
thickness of 15 mils (0.38 mm), application is limited to
3.2 Definitions of Terms Specific to This Standard:
voltage ratings below 300 V, and to dry locations. At a
3.2.1 aging (act of), n—exposure of materials to air or oil at
thickness of 30 mils, the application range is widened to dry or
a temperature and a time as specified in Table 1.
wet applications, and to a voltage rating of 600 V.
4. Physical Properties
1.3 In many instances the insulation material cannot be
tested unless it has been formed around a conductor or cable.
4.1 The insulation shall conform to the requirements for
Therefore, tests are done on insulated wire or cable in this
physical properties prescribed in Table 1.
specification solely to determine the relevant property of the
5. Electrical Requirements
insulation material and not to test the conductor or completed
cable.
5.1 Perform the ac voltage, insulation resistance, and dc
voltage tests in that order when any of these tests are required.
1.4 The values stated in inch-pound units are to be regarded
The sequence for other testing is not specified.
as standard. The values given in parentheses are mathematical
conversions to SI units that are provided for information only
5.2 AC Voltage Test—Test the insulated conductor at the ac
and are not considered standard.
withstand voltage as specified in Table 2. Unless otherwise
1.4.1 In come cases (including the title), temperatures are
specified, omit this test if the dc withstand voltage test
described in degrees Celsius only.
described in 5.4 is performed.
5.2.1 For cables or conditions of service where mechanical
2. Referenced Documents
stresses govern, such as in submarine cables or long vertical
2
2.1 ASTM Standards:
risers, it is possible that the minimum conductor sizes in Table
D1711 Terminology Relating to Electrical Insulation
2 are not strong enough.
D2633 Test Methods for Thermoplastic Insulations and
5.2.2 The thicknesses given in Table 2 apply to aerial cables
Jackets for Wire and Cable
andtosingleconductorsinstalledinconduitsabovegroundand
D2633 Test Methods for Thermoplastic Insulations and
to the individual conductors of all multiple-conductor cables
Jackets for Wire and Cable
having a common jacket metallic sheath or protective covering
G153 Practice for Operating Enclosed Carbon Arc Light
over the assembly, except as shown in 5.2.2.1.
Apparatus for Exposure of Nonmetallic Materials
5.2.2.1 For single-conductor cables for installation in under-
ground ducts or direct earth burial, add 15 mils (0.38 mm) to
theinsulationthicknessesgiveninTable2whensuchcablesdo
1
This specification is under the jurisdiction of ASTM Committee D09 on
not have a thermoplastic jacket or metallic sheath over the
Electrical and Electronic Insulating Materials and is the direct responsibility of
Subcommittee D09.07 on Electrical Insulating Materials.
assembly.
Current edition approved March 1, 2017. Published March 2017. Originally
5.2.3 Where the thickness of the insulation is increased for
approved in 1963. Last previous edition approved in 2011 as D2220 – 11. DOI:
mechanical reasons or for special service conditions, determine
10.1520/D2220-17.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or the test voltage in Table 2 by the size of the conductor and the
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
rated voltage.
Standards volume information, refer to the standard’s Document Summary page on
the ASTM website. 5.3 Insulation Resistance:
*A Summary of Changes section appears at the end of this standard
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1
---------------------- Page: 1 ----------------------
D2220−17
TABLE 1 Physical Properties Requirements
5 min at a dc withstand voltage which is three times the ac test
Unaged Requirements: voltage spe
...
This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation: D2220 − 11 D2220 − 17
Standard Specification for
Poly(Vinyl Chloride) Insulation for Wire and Cable, 75°C
1
Operation
This standard is issued under the fixed designation D2220; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope*
1.1 This specification covers a thermoplastic insulation of poly(vinyl chloride) or the copolymer of vinyl chloride and vinyl
acetate.
1.2 This insulation is recommended for use in power and control circuits at temperatures not higher than 75°C. At a thickness
of 15 mils (0.38 mm), application is limited to voltage ratings below 300 V, and to dry locations. At a thickness of 30 mils, the
application range is widened to dry or wet applications, and to a voltage rating of 600 V.
1.3 In many instances the insulation material cannot be tested unless it has been formed around a conductor or cable. Therefore,
tests are done on insulated wire or cable in this specification solely to determine the relevant property of the insulation material
and not to test the conductor or completed cable.
1.4 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical
conversions to SI units that are provided for information only and are not considered standard.
1.4.1 In come cases (including the title), temperatures are described in degrees Celsius only.
2. Referenced Documents
2
2.1 ASTM Standards:
D1711 Terminology Relating to Electrical Insulation
D2633 Test Methods for Thermoplastic Insulations and Jackets for Wire and Cable
D2633 Test Methods for Thermoplastic Insulations and Jackets for Wire and Cable
G153 Practice for Operating Enclosed Carbon Arc Light Apparatus for Exposure of Nonmetallic Materials
G155 Practice for Operating Xenon Arc Light Apparatus for Exposure of Non-Metallic Materials
3. Terminology
3.1 Definitions:
3.1.1 For definitions of terms used in this specification, refer to Terminology D1711.
3.2 Definitions of Terms Specific to This Standard:
3.2.1 aging (act of), n—exposure of materials to air or oil at a temperature and a time as specified in Table 1.
4. Physical Properties
4.1 The insulation shall conform to the requirements for physical properties prescribed in Table 1.
5. Electrical Requirements
5.1 Perform the ac voltage, insulation resistance, and dc voltage tests in that order when any of these tests are required. The
sequence for other testing is not specified.
5.2 AC Voltage Test—Test the insulated conductor at the ac withstand voltage as specified in Table 2. Unless otherwise specified,
omit this test if the dc withstand voltage test described in 5.4 is performed.
1
This specification is under the jurisdiction of ASTM Committee D09 on Electrical and Electronic Insulating Materials and is the direct responsibility of Subcommittee
D09.07 on Electrical Insulating Materials.
Current edition approved Aug. 1, 2011March 1, 2017. Published August 2011March 2017. Originally approved in 1963. Last previous edition approved in 20072011 as
ε1
D2220 – 02 (2007)D2220 – 11. . DOI: 10.1520/D2220-11.10.1520/D2220-17.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
*A Summary of Changes section appears at the end of this standard
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1
---------------------- Page: 1 ----------------------
D2220 − 17
TABLE 1 Physical Properties Requirements
Unaged Requirements:
Tensile strength, min, psi (MPa) 2000 (13.8)
Elongation at rupture, min, % 150
Aged Requirements:
After air oven test at 121± 1°C for 168 h:
2
Tubular Specimens—up to size AWG 6 (13.3 mm )
Tensile strength, min, % of unaged value 80
Elongation, min, % of unaged value 75
Buffed die-cut Specimens—sizes AWG 6 and larger
Tensile strength, min, % of unaged value 75
Elongation, min, % of unaged value 50
Heat shock, 121 ± 1°C no cracks
Heat distortion, 121 ± 1°C, max, % decrease 25
Vertical flame test, after passes
five 15-s applications
Oil resistance test:
After oil immersion at 70± 1°C for 4 h:
2
Tubular Specimens—up to size AWG 6 (13.3 mm )
Tensile strength, min, % of unaged value 8
...
Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.