Standard Test Method for Flash Point by Modified Continuously Closed Cup (MCCCFP) Tester

SIGNIFICANCE AND USE
5.1 The flash point temperature is one measure of the tendency of the test specimen to form a flammable mixture with air under controlled laboratory conditions. It is only one of a number of properties which must be considered in assessing the overall flammability hazard of a material.  
5.2 Flash point is used in shipping and safety regulations to define flammable and combustible materials and for classification purposes. This definition may vary from regulation to regulation. Consult the particular regulation involved for precise definitions of these classifications.  
5.3 This test method can be used to measure and describe the properties of materials in response to heat and an ignition source under controlled laboratory conditions and shall not be used to describe or appraise the fire hazard or fire risk of materials under actual fire conditions. However, results of this test method may be used as elements of a fire risk assessment, which takes into account all of the factors which are pertinent to an assessment of the fire hazard of a particular end use.  
5.4 Flash point can also indicate the possible presence of highly volatile and flammable materials in a relatively nonvolatile or nonflammable material, such as the contamination of lubricating oils by small amounts of diesel fuel or gasoline. This test method was designed to be more sensitive to potential contamination than Test Method D6450.
SCOPE
1.1 This test method covers the determination of the flash point of fuels, lube oils, solvents and other liquids by a continuously closed cup tester utilizing a specimen size of 2 mL, cup size of 7 mL, with a heating rate of 2.5 °C per minute.  
1.1.1 Apparatus requiring a specimen size of 1 mL, cup size of 4 mL, and a heating rate of 5.5 °C per minute must be run according to Test Method D6450.  
1.2 This flash point test method is a dynamic method and depends on definite rates of temperature increase. It is one of the many flash point test methods available and every flash point test method, including this one, is an empirical method.
Note 1: Flash point values are not a constant physical chemical property of materials tested. They are a function of the apparatus design, the condition of the apparatus used, and the operational procedure carried out. Flash point can, therefore, only be defined in terms of a standard test method and no general valid correlation can be guaranteed between results obtained by different test methods or where different test apparatus is specified.  
1.3 This test method utilizes a closed but unsealed cup with air injected into the test chamber.  
1.4 This test method is suitable for testing samples with a flash point from 35 °C to 225 °C.
Note 2: Flash point determinations below 35 °C and above 225 °C may be performed; however, the precision has not been determined below and above these temperatures.  
1.5 If the user’s specification requires a defined flash point method other than this method, neither this method nor any other test method should be substituted for the prescribed test method without obtaining comparative data and an agreement from the specifier.  
1.6 The values stated in SI units are to be regarded as standard. No other units of measurement are included in this standard. Temperatures are in degrees Celsius, pressure in kilo-Pascals.  
1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. For specific warning statements, see 7.2, 8.5, and 10.1.2.

General Information

Status
Historical
Publication Date
31-May-2016
Current Stage
Ref Project

Relations

Effective Date
01-Jun-2016
Effective Date
01-Jun-2016
Effective Date
01-Jun-2016

Buy Standard

Standard
ASTM D7094-16 - Standard Test Method for Flash Point by Modified Continuously Closed Cup (MCCCFP) Tester
English language
8 pages
sale 15% off
Preview
sale 15% off
Preview
Standard
REDLINE ASTM D7094-16 - Standard Test Method for Flash Point by Modified Continuously Closed Cup (MCCCFP) Tester
English language
8 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation:D7094 −16
Standard Test Method for
Flash Point by Modified Continuously Closed Cup
1
(MCCCFP) Tester
This standard is issued under the fixed designation D7094; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope* 1.7 This standard does not purport to address all of the
safety concerns, if any, associated with its use. It is the
1.1 This test method covers the determination of the flash
responsibility of the user of this standard to establish appro-
point of fuels, lube oils, solvents and other liquids by a
priate safety and health practices and determine the applica-
continuously closed cup tester utilizing a specimen size of
bility of regulatory limitations prior to use. For specific
2 mL, cup size of 7 mL, with a heating rate of 2.5 °C per
warning statements, see 7.2, 8.5, and 10.1.2.
minute.
1.1.1 Apparatus requiring a specimen size of 1 mL, cup size
2. Referenced Documents
of 4 mL, and a heating rate of 5.5 °C per minute must be run
2
2.1 ASTM Standards:
according to Test Method D6450.
D93 Test Methods for Flash Point by Pensky-Martens
1.2 This flash point test method is a dynamic method and
Closed Cup Tester
depends on definite rates of temperature increase. It is one of
D4057 Practice for Manual Sampling of Petroleum and
the many flash point test methods available and every flash
Petroleum Products
point test method, including this one, is an empirical method.
D4177 Practice for Automatic Sampling of Petroleum and
NOTE 1—Flash point values are not a constant physical chemical
Petroleum Products
property of materials tested. They are a function of the apparatus design,
D6450 Test Method for Flash Point by Continuously Closed
the condition of the apparatus used, and the operational procedure carried
out. Flash point can, therefore, only be defined in terms of a standard test Cup (CCCFP) Tester
methodandnogeneralvalidcorrelationcanbeguaranteedbetweenresults
D6708 Practice for StatisticalAssessment and Improvement
obtained by different test methods or where different test apparatus is
of Expected Agreement Between Two Test Methods that
specified.
Purport to Measure the Same Property of a Material
1.3 This test method utilizes a closed but unsealed cup with
E300 Practice for Sampling Industrial Chemicals
air injected into the test chamber. 3
2.2 ISO Standards:
1.4 This test method is suitable for testing samples with a
ISO Guide 34 Quality Systems Guidelines for the Produc-
flash point from 35 °C to 225 °C.
tion of Reference Materials
NOTE 2—Flash point determinations below 35 °C and above 225 °C
ISOGuide35 CertificationofReferenceMaterials—General
may be performed; however, the precision has not been determined below
and Statistical Principles
and above these temperatures.
1.5 If the user’s specification requires a defined flash point 3. Terminology
method other than this method, neither this method nor any
3.1 Definitions:
other test method should be substituted for the prescribed test
3.1.1 flash point, n—in flash point test methods, the lowest
method without obtaining comparative data and an agreement
temperature of the test specimen, adjusted to account for
from the specifier.
variations in atmospheric pressure from 101.3 kPa, at which
1.6 The values stated in SI units are to be regarded as application of an ignition source causes the vapors of the test
standard. No other units of measurement are included in this specimen to ignite under specified conditions of test.
standard. Temperatures are in degrees Celsius, pressure in 3.1.1.1 Discussion—For the purpose of this test method, the
kilo-Pascals. test specimen is deemed to have flashed when the hot flame of
1 2
This test method is under the jurisdiction of ASTM Committee D02 on For referenced ASTM standards, visit the ASTM website, www.astm.org, or
Petroleum Products, Liquid Fuels, and Lubricants and is the direct responsibility of contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
Subcommittee D02.08 on Volatility. Standards volume information, refer to the standard’s Document Summary page on
CurrenteditionapprovedJune1,2016.PublishedJuly2016.Originallyapproved the ASTM website.
ɛ1 3
in 2004. Last previous edition approved in 2012 as D7094 – 2012 . DOI: Available fromAmerican National Standards Institute (ANSI), 25 W. 43rd St.,
10.1520/D7094-16. 4th Floor, New York, NY 10036, http://www.ansi.org.
*A Summary of Changes section appears at the end of this standard
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------
...

This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
´1
Designation: D7094 − 12 D7094 − 16
Standard Test Method for
Flash Point by Modified Continuously Closed Cup
1
(MCCCFP) Tester
This standard is issued under the fixed designation D7094; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1
ε NOTE—Editorially removed sole source of supply footnote from 6.1 in February 2014.
1. Scope*
1.1 This test method covers the determination of the flash point of fuels, lube oils, solvents and other liquids by a continuously
closed cup tester utilizing a specimen size of 2 mL, 2 mL, cup size of 7 mL, 7 mL, with a heating rate of 2.5°C2.5 °C per minute.
1.1.1 Apparatus requiring a specimen size of 1 mL, 1 mL, cup size of 4 mL, 4 mL, and a heating rate of 5.5°C5.5 °C per minute
must be run according to Test Method D6450.
1.2 This flash point test method is a dynamic method and depends on definite rates of temperature increase. It is one of the many
flash point test methods available and every flash point test method, including this one, is an empirical method.
NOTE 1—Flash point values are not a constant physical chemical property of materials tested. They are a function of the apparatus design, the condition
of the apparatus used, and the operational procedure carried out. Flash point can, therefore, only be defined in terms of a standard test method and no
general valid correlation can be guaranteed between results obtained by different test methods or where different test apparatus is specified.
1.3 This test method utilizes a closed but unsealed cup with air injected into the test chamber.
1.4 This test method is suitable for testing samples with a flash point from 3535 °C to 225°C.225 °C.
NOTE 2—Flash point determinations below 35°C35 °C and above 225°C225 °C may be performed; however, the precision has not been determined
below and above these temperatures.
1.5 If the user’s specification requires a defined flash point method other than this method, neither this method nor any other
test method should be substituted for the prescribed test method without obtaining comparative data and an agreement from the
specifier.
1.6 The values stated in SI units are to be regarded as standard. No other units of measurement are included in this standard.
Temperatures are in degrees Celsius, pressure in kilo-Pascals.
1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory
limitations prior to use. For specific warning statements, see 7.2, 8.5, and 10.1.2.
2. Referenced Documents
2
2.1 ASTM Standards:
D93 Test Methods for Flash Point by Pensky-Martens Closed Cup Tester
D4057 Practice for Manual Sampling of Petroleum and Petroleum Products
D4177 Practice for Automatic Sampling of Petroleum and Petroleum Products
D6450 Test Method for Flash Point by Continuously Closed Cup (CCCFP) Tester
D6708 Practice for Statistical Assessment and Improvement of Expected Agreement Between Two Test Methods that Purport
to Measure the Same Property of a Material
E300 Practice for Sampling Industrial Chemicals
3
2.2 ISO Standards:
ISO Guide 34 Quality Systems Guidelines for the Production of Reference Materials
ISO Guide 35 Certification of Reference Materials—General and Statistical Principles
1
This test method is under the jurisdiction of ASTM Committee D02 on Petroleum Products, Liquid Fuels, and Lubricants and is the direct responsibility of Subcommittee
D02.08 on Volatility.
Current edition approved Dec. 1, 2012June 1, 2016. Published March 2013July 2016. Originally approved in 2004. Last previous edition approved in 20092012 as
ɛ1
D7094–04(2009).D7094 – 2012 . DOI: 10.1520/D7094-12.10.1520/D7094-16.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
3
Available from American National Standards Institute (ANSI), 25 W. 43rd St., 4th Floor, New York, NY 10036, http://www.ansi.org.
*A Summary of Changes section appears at the end of this standard
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-
...