ASTM C1283-07a
(Practice)Standard Practice for Installing Clay Flue Lining
Standard Practice for Installing Clay Flue Lining
ABSTRACT
This practice covers the minimum requirements for installing clay flue lining for residential concrete or masonry chimneys. Footings shall be constructed of concrete or solid masonry and the foundation shall be placed with respect to adjacent structures to minimize the possibility of damage. Both the concrete footings and foundations shall conform to local building codes. Flue liners shall be installed using refractory mortar in such a manner as to minimize ledges or steps within the flue passageway and shall be surrounded by masonry on all sides with a separation not exceeding the flue liner wall thickness. Materials used for chimney construction shall comprise of the following: flue linings, refractory mortar, concrete block, brick, mortar, firebrick, and natural stone. Chimney connection shall be made by either a metal or clay thimble while the chimney caps shall be made of precast or cast-in-place concrete, metal, or stone caps. Combustible materials shall be permitted to abut the masonry chimney sidewalls; wherein, the minimum air space clearance between the interior or exterior masonry chimneys and the combustible materials shall be met.
SCOPE
1.1 This practice covers the minimum requirements for installing clay flue lining for residential concrete or masonry chimneys.
1.2 The values stated in inch-pound units are to be regarded as the standard. The values stated in parentheses are for informational purposes only.
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
General Information
Relations
Standards Content (Sample)
NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation:C1283–07a
Standard Practice for
1
Installing Clay Flue Lining
This standard is issued under the fixed designation C1283; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope C652 Specification for Hollow Brick (Hollow Masonry
Units Made From Clay or Shale)
1.1 This practice covers the minimum requirements for
C896 Terminology Relating to Clay Products
installing clay flue lining for residential concrete or masonry
C1184 Specification for Structural Silicone Sealants
chimneys.
1.2 The values stated in inch-pound units are to be regarded
3. Terminology
as the standard. The values stated in parentheses are for
3.1 General—Terminology C896 should be used for clari-
informational purposes only.
fication of definitions in this practice.
1.3 This standard does not purport to address all of the
3.2 Definitions of Terms Specific to This Standard:
safety concerns, if any, associated with its use. It is the
3.2.1 chimney connector—tubular unit or pipe used to
responsibility of the user of this standard to establish appro-
convey products of combustion from a heating or cooking
priate safety and health practices and determine the applica-
appliance to the chimney.
bility of regulatory limitations prior to use.
3.2.2 flue—passageway within a chimney through which
2. Referenced Documents products of combustion are conveyed.
2
3.2.3 flue liner—manufactured tubular nonloadbearing fired
2.1 ASTM Standards:
clay unit, normally used for conveying hot gases in chimneys.
C24 Test Method for Pyrometric Cone Equivalent (PCE) of
3.2.4 masonry chimney—vertical structure constructed of
Fireclay and High Alumina Refractory Materials
brick, concrete, concrete masonry units, or stone, which
C27 Classification of Fireclay and High-Alumina Refrac-
contains one or more flues, and conveys products of combus-
tory Brick
tion from a heat source or cooking appliance.
C55 Specification for Concrete Building Brick
3.2.5 smoke chamber—section of a fireplace above the
C90 Specification for Loadbearing Concrete Masonry Units
throat and below the flue, which is an area of transition from
C99 Test Method for Modulus of Rupture of Dimension
the shape of the throat to the shape of the flue.
Stone
3.2.6 thimble—manufactured tubular nonloadbearing fired
C129 Specification for Nonloadbearing Concrete Masonry
clayunitnormallyusedtoconnectthechimneyconnectorfrom
Units
an appliance through the wall of the chimney to the flue.
C170 Test Method for Compressive Strength of Dimension
Stone
4. Footings and Foundations
C199 Test Method for Pier Test for Refractory Mortars
4.1 Footings for masonry chimneys shall be constructed of
C216 Specification for Facing Brick (Solid Masonry Units
concrete or solid masonry at least 12 in. (305 mm) thick, and
Made from Clay or Shale)
it shall extend at least 6 in. (150 mm) beyond the face of the
C270 Specification for Mortar for Unit Masonry
foundation or support wall on all sides. Footings shall be
C315 Specification for Clay Flue Liners and Chimney Pots
founded below frost depth on natural undisturbed earth or
engineeredfill.Inareasnotsubjectedtofreezing,footingsshall
1
This practice is under the jurisdiction of ASTM Committee C04 on Vitrified
be founded at least 12 in. (305 mm) below finished grade.
Clay Pipe and is the direct responsibility of Subcommittee C04.20 on Methods of
4.2 The foundation shall be placed, with respect to adjacent
Test and Specifications.
structures existing or anticipated, to minimize the possibility of
Current edition approved Dec. 1, 2007. Published December 2007. Originally
approved in 1994. Last previous edition approved in 2007 as C1283 – 07. DOI:
damage by construction operations or by transmission of
10.1520/C1283-07A.
additional loads to the supporting soils.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
4.3 Concrete footings and foundations shall conform to
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
local building codes.
Standards volume information, refer to the standard’s Document Summary page on
the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1
---------------------- Page: 1 ----------------------
C1283–07a
4.3.1 In the absence of a local building code, concrete with 5.8.1 When fabricating custom size flue liners, the aspect
a minimum 28 day compressive strength of 3000 psi (21 MPa) ratio shall not exceed 2:1 and the vertical joint shall be sealed
shall be used. with refractory mortar as required in 5.4.
4.4 Where a chimney or fireplace is add
...
This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation:C1283–07 Designation: C 1283 – 07a
Standard Practice for
1
Installing Clay Flue Lining
This standard is issued under the fixed designation C 1283; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (e) indicates an editorial change since the last revision or reapproval.
1. Scope
1.1 This practice covers the minimum requirements for installing clay flue lining for residential concrete or masonry chimneys.
1.2 The values stated in inch-pound units are to be regarded as the standard. The values stated in parentheses are for
informational purposes only.
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory
limitations prior to use.
2. Referenced Documents
2
2.1 ASTM Standards:
C 24Specification for Laboratory Glass VolumetricApparatus Test Method for Pyrometric Cone Equivalent (PCE) of Fireclay
and High Alumina Refractory Materials
C 27Specification for Laboratory Glass Volumetric Apparatus Classification of Fireclay and High-Alumina Refractory Brick
C 55Specification for Laboratory Glass Volumetric Apparatus Specification for Concrete Building Brick
C 90Specification for Laboratory Glass Volumetric Apparatus Specification for Loadbearing Concrete Masonry Units
C 99Specification for Laboratory Glass Volumetric Apparatus Test Method for Modulus of Rupture of Dimension Stone
C 129Specification for Laboratory Glass Volumetric Apparatus Specification for Nonloadbearing Concrete Masonry Units
C 170Specification for Laboratory Glass Volumetric Apparatus Test Method for Compressive Strength of Dimension Stone
C 199Specification for Laboratory Glass Volumetric Apparatus Test Method for Pier Test for Refractory Mortars
C 216Specification for Laboratory Glass Volumetric Apparatus Specification for Facing Brick (Solid Masonry Units Made
from Clay or Shale)
C 270Specification for Laboratory Glass Volumetric Apparatus Specification for Mortar for Unit Masonry
C 315Specification for Laboratory Glass Volumetric Apparatus Specification for Clay Flue Liners and Chimney Pots
C 652Specification for Laboratory Glass Volumetric Apparatus Specification for Hollow Brick (Hollow Masonry Units Made
From Clay or Shale)
C 896Specification for Laboratory Glass Volumetric Apparatus Terminology Relating to Clay Products
C1184Specification for Laboratory Glass Volumetric Apparatus 1184 Specification for Structural Silicone Sealants
3. Terminology
3.1 General—Terminology C 896 should be used for clarification of definitions in this practice.
3.2 Definitions of Terms Specific to This Standard:
3.2.1 chimney connector—tubular unit or pipe used to convey products of combustion from a heating or cooking appliance to
the chimney.
3.2.2 flue—passageway within a chimney through which products of combustion are conveyed.
3.2.3 flue liner—manufactured tubular nonloadbearing fired clay unit, normally used for conveying hot gases in chimneys.
3.2.4 masonry chimney—vertical structure constructed of brick, concrete, concrete masonry units, or stone, which contains one
or more flues, and conveys products of combustion from a heat source or cooking appliance.
3.2.5 smoke chamber—section of a fireplace above the throat and below the flue, which is an area of transition from the shape
of the throat to the shape of the flue.
3.2.6 thimble—manufactured tubular nonloadbearing fired clay unit normally used to connect the chimney connector from an
appliance through the wall of the chimney to the flue.
1
This practice is under the jurisdiction ofASTM Committee C04 on Vitrified Clay Pipe and is the direct responsibility of Subcommittee C04.20 on Methods of Test and
Specifications.
Current edition approvedAprilDec. 1, 2007. PublishedAprilDecember 2007. Originally approved in 1994. Last previous edition approved in 20062007 as C 1283 – 067.
2
For referencedASTM standards, visit theASTM website, www.astm.org, or contactASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1
---------------------- Page: 1 ----------------------
C 1283 – 07a
4. Footings and Fou
...
Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.