Standard Specification for Fine-Wire Bunch-Stranded and Rope-Lay Bunch-Stranded Copper Conductors for Use as Electrical Conductors

ABSTRACT
This specification deals with bare fine-wire bunch-stranded and rope-lay bunch-stranded copper conductors made from round copper wires finer than No. 40 AWG, either coated or uncoated with tin or silver, for use as electrical conductors. The conductor types covered in this specification are designated Type B for bunch-stranded conductors, and Type R for rope-lay bunch-stranded conductors. On the other hand, the wire classifications are assigned as: Class R, stranded conductors using wire 42 AWG; Class S, stranded conductors using wire 44 AWG; Class T, stranded conductors using wire 46 AWG; Class U, stranded conductors using wire 48 AWG; and Class V, stranded conductors using wire 50 AWG. Wires shall undergo tests that shall evaluated their conformance to physical and electrical properties such as wire cross-sectional area and diameter, coating thickness, tensile strength, elongation, and DC resistance.
SCOPE
1.1 This specification covers bare bunch-stranded and rope-lay bunch-stranded conductors made from round copper wires finer than No. 40 AWG with diameters less than 0.0031 in. (.078 mm), either coated or uncoated with tin or silver, for use as electrical conductors. (Explanatory Note 1).  
1.2 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.  
1.2.1 Exceptions—The SI values for density and temperature are to be regarded as standard.  
1.3 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

General Information

Status
Published
Publication Date
30-Sep-2018
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM B738-13(2018) - Standard Specification for Fine-Wire Bunch-Stranded and Rope-Lay Bunch-Stranded Copper Conductors for Use as Electrical Conductors
English language
6 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the
Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
Designation:B738 −13 (Reapproved 2018)
Standard Specification for
Fine-Wire Bunch-Stranded and Rope-Lay Bunch-Stranded
Copper Conductors for Use as Electrical Conductors
This standard is issued under the fixed designation B738; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision.Anumber in parentheses indicates the year of last reapproval.A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope Cross-Sectional Areas of AWG Sizes of Solid Round
Wires Used as Electrical Conductors
1.1 This specification covers bare bunch-stranded and rope-
B298Specification for Silver-Coated Soft orAnnealed Cop-
lay bunch-stranded conductors made from round copper wires
per Wire
finer than No. 40 AWG with diameters less than 0.0031 in.
B354Terminology Relating to Uninsulated Metallic Electri-
(.078 mm), either coated or uncoated with tin or silver, for use
cal Conductors
as electrical conductors. (Explanatory Note 1).
1.2 The values stated in inch-pound units are to be regarded
3. Classification
as standard. The values given in parentheses are mathematical
3.1 For the purposes of this specification, the following
conversions to SI units that are provided for information only
classifications have been assigned (Explanatory Note 2):
and are not considered standard.
3.1.1 Type:
1.2.1 Exceptions—The SI values for density and tempera-
3.1.1.1 Type B—Bunch-stranded conductors.
ture are to be regarded as standard.
3.1.1.2 Type R—Rope-lay bunch-stranded conductors.
1.3 This international standard was developed in accor-
3.1.2 Class:
dance with internationally recognized principles on standard-
3.1.2.1 Class R—Stranded conductors using wire 42 AWG
ization established in the Decision on Principles for the
(0.0025).
Development of International Standards, Guides and Recom-
3.1.2.2 Class S—Stranded conductors using wire 44 AWG
mendations issued by the World Trade Organization Technical
(0.0020).
Barriers to Trade (TBT) Committee.
3.1.2.3 Class T—Stranded conductors using wire 46 AWG
(0.00157).
2. Referenced Documents
3.1.2.4 Class U—Stranded conductors using wire 48 AWG
2.1 ASTM Standards:
(0.00124).
B33Specification for Tin-Coated Soft or Annealed Copper
3.1.2.5 Class V—Stranded conductors using wire 50 AWG
Wire for Electrical Purposes
(0.00099).
B49Specification for Copper Rod for Electrical Purposes
3.2 Detailed information on Type B Conductors is found in
B172Specification for Rope-Lay-Stranded Copper Conduc-
Table 1 and Table 2. Detailed information on Type R Conduc-
torsHavingBunch-StrandedMembers,forElectricalCon-
tors is found in Table 3 and Table 2.
ductors
B174Specification for Bunch-Stranded Copper Conductors
4. Ordering Information
for Electrical Conductors
4.1 Orders for materials under this specification shall in-
B193Test Method for Resistivity of Electrical Conductor
clude the following information:
Materials
4.1.1 Quantity of each size, class, and type,
B258Specification for Standard Nominal Diameters and
4.1.2 Conductor size—circular-mil area, dc resistance (7.1)
or AWG (5.2.1),
This specification is under the jurisdiction of ASTM Committee B01 on
4.1.3 Class and type (Section 3),
Electrical Conductors and is the direct responsibility of Subcommittee B01.04 on
4.1.4 Whether coated or uncoated; if coated, designate type
Conductors of Copper and Copper Alloys.
of coating (6.1); if silver coated, the minimum thickness of
Current edition approved Oct. 1, 2018. Published October 2018. Originally
silver (6.1.2), and whether tarnish protection is desired (11.3),
approved in 1984. Last previous edition approved in 2013 as B738–13. DOI:
10.1520/B0738-13R18.
4.1.5 Maximum length of lay (5.2.4), if required,
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
4.1.6 Temper (6.2),
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
4.1.7 Separators, if required (5.2.2),
Standards volume information, refer to the standard’s Document Summary page on
the ASTM website. 4.1.8 Package size (11.1),
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
B738−13 (2018)
TABLE 1 Classification of Type B Bunch-Stranded Conductors
6. Physical Properties
A
Class Wire Diameter, in. Conductor Sizes, AWG
6.1 Wire Coating—When coated, the coating of the wires of
R 0.0025 (No. 42 AWG) 24,26,28,30,32,34
the stranded conductor, before stranding, shall conform to the
S 0.0020 (No. 44 AWG) 26,28,30,32,34,36
requirements of 6.1.1 or 6.1.2.
T 0.00157 (No. 46 AWG) 28,30,32,34,36,38
U 0.00124 (No. 48 AWG) 30,32,34,36,38,40
6.1.1 Tin coating shall conform to the coating requirements
V 0.00099 (No. 50 AWG) 32,34,36,38,40
of Specification B33.
A
Sufficientquantitiesofwiresofthesediametersshallbeusedtoformconductors
6.1.2 Silver coating shall conform to the minimum thick-
having cross-sectional areas approximately equal to the AWG conductor sizes
ness requirements of the purchase document. Minimum thick-
listed.
ness shall be determined using the method for determining
plating thickness described in Specification B298.
6.1.3 The finished diameter and mass of the coated wires
used shall be substantially equal to those of the uncoated wires
4.1.9 Specialpackagemarking,ifrequired(Section10),and
of the same class.
4.1.10 Place of inspection (Section 9).
6.2 Temper—Unless otherwise specified, all coated conduc-
4.2 In addition, Supplementary Requirements shall apply
tors shall be furnished in the annealed temper. Uncoated
onlywhenspecifiedbythepurchaserintheinquiry,contract,or
conductors may be furnished either annealed or unannealed as
purchase order for direct procurement by agencies of the U.S.
ordered (see 4.1.6).
Government.
NOTE 1—The term unannealed as used in this specification means
cold-worked conductor as produced on commercial wire-drawing ma-
5. Materials and Manufacture
chines.
5.1 The material shall be copper of such quality and purity
6.3 Tensile Strength and Elongation—The stranded
that the finished product shall have the properties and charac-
conductor, in its finished form, shall conform to the following:
teristics described in this specification. Material meeting the
Tensile Strength, min. Elongation, min,
requirements of Specification B49 is such a material.
Finished State psi MPa 10 in. %
5.2 Construction: Unannealed 40 000 275 .
Annealed . . 10
5.2.1 Cross-Sectional Area—The cross-sectional area,
number, and diameter of wires for a variety of strand construc-
7. Electrical Properties
tions in general use are shown in Table 2.
7.1 DC Resistance—The dc resistance in Ω/1000 ft of the
5.2.2 Separators—If a separator is required to be furnished
bunch-stranded conductor shall not exceed the appropriate
with the conductor, it shall be specified by the purchaser at the
values specified in Table 5. The dc resistance inΩ/1000 ft of
time of the order as to the requirements for the kind and
the rope-lay bunch-stranded conductor shall not exceed the
thickness of material and its application details.
appropriate values specified in Table 6 (Explanatory Note 3
5.2.3 Joints:
and Note 4).
5.2.3.1 Necessary joints in wires shall be made in accor-
dance with accepted commercial practice.
8. Test Methods
5.2.3.2 Joints shall be so constructed and so disposed
throughout the conductor that the diameter or configuration of
8.1 Coating—Teststodetermineconformanceofthecoating
the completed conductor is not substantially affected, and that
totherequirementsofSpecificationB33orSpecificationB298
the flexibility of the completed conductor is not adversely
shall be performed on the individual wires before stranding
affected.
(see 6.1.1 to 6.1.3).
5.2.4 Lay:
8.2 Tensile Strength and Elongation:
5.2.4.1 Conductors of the same size and description fur-
8.2.1 Tests to determine conformance to the tensile strength
nished on one order shall have the same lay.
and elongation requirements of 6.3 shall be made on the
5.2.4.2 The direction of the lay of bunch-stranded conduc-
finished stranded conductor.
tors shall be at the option of the manufacturer unless otherwise
8.2.2 Determine tensile strength, T , expressed in pounds
s
specified by the purchaser.
per square inch as follows:
5.2.4.3 Unless otherwise specified by the purchaser, the
length of the lay of bare or coated bunch-stranded conductors L
T 5
s
shall conform to the requirements of Table 4. A
5.2.4.4 Thedirectionofthelayoftheouterlayerofrope-lay
where:
stranded conductors shall be lefthand, unless otherwise speci-
L = maximum load on the stranded conductor during the
fied by the purchaser.
tension test (see Explanatory Note 6), lbs, and
5.2.4.5 The length of the lay of the outer layer of rope-lay
A = original cross-sectional area of the stranded conductor,
stranded conductors shall be not less than 8 or more than 16
in. (see 8.2.3).
times the outside diameter of the completed conductor. The
length of the lay of the wires composing the bunch-stranded 8.2.3 The original cross-sectional area of the stranded con-
members shall be not more than 30 times the diameter of the ductor shall be considered to be the cross-sectional area of the
member. individualwirecalculatedfromthenominalwirediameter(see
B738−13 (2018)
A
TABLE 2 Construction Requirements of Bunch-Stranded and Rope-Lay Bunch-Stranded Conductors
CLASS R CLASS S CLASS T CLASS U CLASS V
Minimum Number Minimum Number Minimum Number Minimum Number Minimum Number
Nominal
Size, of Wires 0.0025 in. of Wires 0.0020 in. of Wires 0.00157 in. of Wires 0.00124 in. of Wires 0.00099 in.
Area,
AWG in Diameter in Diameter in Diameter in Diameter in Diameter
cmil
(No. 42 AWG) (No. 44 AWG) (No. 46 AWG) (No. 48 AWG) (No. 50 AWG)
B C
Type B Type R Type B Type R Type B Type R Type B Type R Type B Type R
2580 16 . . . 665 . . . . . .
1620 18 . . . 413 . . . . . .
1020 20 . 168 . 259 . . . . . .
640 22 . 105 . 168 . . . . . .
404 24 65 . . 105 . 168 . . . .
253 26 41 . 65 . . 105 . 168 . .
159 28 26 . 40 . 65 . . 105 . 168
100 30 16 . 25 . 40 . 65 . . 105
64 32 10 . 16 . 25 . 40 . 65 .
40 34 7 . 10 . 16 . 25 . 40 .
25 36 . . 7 . 10 . 16 . 25 .
16 38 . . . . 7 . 10 . 16 .
10 40 . . . . . . 7 . 10 .
A
This table shows a variety of strand constructions useful and generally adequate to meet the needs encountered. It is not intended that the constructions listed in this
tablebeexclusiveofotherconstructionsthatmayappeardurableincertainapplicationsemployingthesamenumberofwires.Theconstructionsshowninthistableprovide
for a finished, noncovered, stranded conductor approximately of the area indicated. When specified by the purchaser, usually to provide additional area to compensate
for draw-down during subsequent processing, the number or size of wires composing the uncovered conductor may be increased as required.
B
Type B Bunch-Stranded Conductors.
C
Type R Rope-Lay Bunch-Stranded Conductors.
TABLE 3 Classification of Type R Rope-Lay Bunch-Stranded
supplied package. Use a white card (as a background) to
A
Conductors
ascertain if any base metal is exposed through a break in the
B
Class Wire Diameter, in. Conductor Sizes, AWG
coating. Detection of any base metal constitutes rejection.
R 0.0025 (No. 42 AWG) 20,22
8.6 Examination for Workmanship of Finished Uninsulated
S 0.0020 (No. 44 AWG) 16,18,20,22,24
T 0.00157 (No. 46 AWG) 24,26
Stranded Conductor—Avisual inspection with 10× magnifica-
U 0.00124 (No. 48 AWG) 26,28
tionandawhitebackgroundshallbeperformedonaconductor
V 0.00099 (No. 50 AWG) 28,30
sample taken from the top of the supplied spool. The sample
A
Rope-lay bunch-stranded conductors 7 by bunch-stranded members.
B
shall be a minimum of 12 in. (30 cm) in length. The outer
Sufficientquantitiesofwiresofthesediametersshallbeusedtoformconductors
having cross-sectional areas approximately equal to the AWG conductor sizes
surface of all stranded constructions shall be examined.
listed.
Detection of excessive exposed base metal due to the
stranding process, such as indications along one side of the
sample due to excessive localized abrasion during stranding,
Table 5 and Table 6) multiplied by the number of wires in the
constitutes rejection. Continuous lines or patterns of exposed
stranded conductor (Explanatory Note 6).
base metals constitute rejection. Small, random point failures
8.2.4 Determine the elongation of the specimen as the
shall not be cause for rejection.
permanent increase in length, expressed in percent of the
9. Inspection
original length, due to the breaking of the specimen in tension,
by measurements made between the jaws of testing machine.
9.1 Unless otherwise specified in the contract or purchase
The zero length shall be the distance between the jaws at the
order, the manufacturer shall be responsible for the perfor-
start of the tension test, and shall be as near 10 in. (250 mm)
mance of all inspection and test requirements specified.
as practicable. The final length shall be the distance between
9.2 All inspection and tests shall be made at the place of
the jaws at the time of rupture. The fracture shall be between
manufacture unless otherwise especially agreed upon between
the jaws of the testing machine and not closer than 1 in. (25
the manufacturer and the purchaser at the time of purchase.
mm) to either jaw.
9.3 Themanufacturershallaffordtheinspectorrepresenting
8.3 Electrical—Tests to determine conformance to the elec-
the purchaser all reasonable manufacturer’s facilities to satisfy
trical resistance requirements of 7.1 shall be made on the
himthatthematerialisbeingfurnishedinaccordancewiththis
finished stranded conductor in accordance with Test Method
specification.
B193 (Explanatory Note 3).
8.4 Other Requirements—For the purpose of calculating 10. Product Marking
mass, cross-sectional area, and so forth, the density of the
10.1 The net mass, length (or lengths, and number of
3 3
coated copper shall be taken as 8.89 g/cm (0.32117 lb/in.)at
lengths, if more than one length is included in the package),
20°C (Explanatory Note 5).
size designation, type of conductor, purchase order number,
8.5 Examination for Workmanship of Finished Uninsulated and any other marks required by the purchase order shall be
StrandedConductor—Avisualinspectionwiththeunaidedeye marked on a tag attached to the reel and, optionally, to the end
shall be performed on the outer layer of the c
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.