Standard Specification for Poly (Vinyl Chloride)(PVC) Closed Profile Gravity Pipe and Fittings Based on Controlled Inside Diameter (Withdrawn 2015)

ABSTRACT
This specification covers the requirements for poly(vinyl chloride) closed profile gravity sewer pipe and fittings with integral bell and elastomeric seal joints or plain end pipe with couplings based on a controlled inside diameter intended for non-pressure drainage of sewage and surface water. The integral bell gasketed joint, coupling, or fitting joints shall be designed in such a way that when assembled, the gasket (which is attached to either the bell or the spigot) will be compressed radially on the pipe spigot or in the bell to form a water-tight seal. The pipe and fittings shall comply with the following requirements: inside diameter, wall thickness, bell wall thickness, stiffness, flattening, impact strength, low head application of gasket, joint tightness, and resistance of exposed channels to infiltration, exfiltration, and sewer or drainage environments. Acetone immersion and air tests shall be performed to determine the degree of fusion of extruded plastic pipe and the air tightness or the minimum dwell period of the specimen, respectively.
SCOPE
1.1 This specification covers requirements for poly(vinyl chloride) (PVC) closed profile sewer pipe and fittings with integral bell and elastomeric seal joints or plain end pipe with couplings in sizes (18 to 60 in.) based on a controlled inside diameter.
1.2 The values stated in inch-pound units are to be regarded as the standard. The values given in parentheses are for information only.
The following safety hazard caveat pertains only to the test methods portion, Section , of this specification: This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.Note 1
Pipe and fittings produced to this specification should be installed in accordance with Practice D 2321.
WITHDRAWN RATIONALE
This specification covers requirements for poly(vinyl chloride) (PVC) closed profile sewer pipe and fittings with integral bell and elastomeric seal joints or plain end pipe with couplings in sizes (18 to 60 in.) based on a controlled inside diameter.
Formerly under the jurisdiction of Committee F17 on Plastic Piping Systems, this specification was withdrawn in January 2015 in accordance with section 10.6.3 of the Regulations Governing ASTM Technical Committees, which requires that standards shall be updated by the end of the eighth year since the last approval date.

General Information

Status
Historical
Publication Date
31-Mar-2006
Withdrawal Date
13-Jan-2015
Technical Committee
Drafting Committee
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM F1803-06 - Standard Specification for Poly (Vinyl Chloride)(PVC) Closed Profile Gravity Pipe and Fittings Based on Controlled Inside Diameter (Withdrawn 2015)
English language
5 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation:F1803 −06 AnAmerican National Standard
Standard Specification for
Poly (Vinyl Chloride)(PVC) Closed Profile Gravity Pipe and
1
Fittings Based on Controlled Inside Diameter
This standard is issued under the fixed designation F1803; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope D2321 PracticeforUndergroundInstallationofThermoplas-
tic Pipe for Sewers and Other Gravity-Flow Applications
1.1 This specification covers requirements for poly(vinyl
D2412 Test Method for Determination of External Loading
chloride) (PVC) closed profile sewer pipe and fittings with
Characteristics of Plastic Pipe by Parallel-Plate Loading
integral bell and elastomeric seal joints or plain end pipe with
D2444 Test Method for Determination of the Impact Resis-
couplings in sizes (18 to 60 in.) based on a controlled inside
tance of Thermoplastic Pipe and Fittings by Means of a
diameter.
Tup (Falling Weight)
1.2 The values stated in inch-pound units are to be regarded
D2855 Practice for Making Solvent-Cemented Joints with
as the standard. The values given in parentheses are for
Poly(Vinyl Chloride) (PVC) Pipe and Fittings
information only.
D3212 Specification for Joints for Drain and Sewer Plastic
1.3 The following safety hazard caveat pertains only to the
Pipes Using Flexible Elastomeric Seals
test methods portion, Section 8, of this specification:This F402 Practice for Safe Handling of Solvent Cements,
standard does not purport to address all of the safety concerns,
Primers, and Cleaners Used for Joining Thermoplastic
if any, associated with its use. It is the responsibility of the user Pipe and Fittings
of this standard to establish appropriate safety and health
F412 Terminology Relating to Plastic Piping Systems
practices and determine the applicability of regulatory limita- F477 Specification for Elastomeric Seals (Gaskets) for Join-
tions prior to use.
ing Plastic Pipe
F679 Specification for Poly(Vinyl Chloride) (PVC) Large-
NOTE 1—Pipe and fittings produced to this specification should be
Diameter Plastic Gravity Sewer Pipe and Fittings
installed in accordance with Practice D2321.
3
2.2 Federal Standard:
Fed. Std. No. 123 Marking for Shipment (Civil Agencies)
2. Referenced Documents
3
2 2.3 Military Standard:
2.1 ASTM Standards:
MIL-STD-129 Marking for Shipment and Storage
D618 Practice for Conditioning Plastics for Testing
D1600 Terminology forAbbreviatedTerms Relating to Plas-
3. Terminology
tics
3.1 Definitions—Definitions are in accordance with Termi-
D1784 Specification for Rigid Poly(Vinyl Chloride) (PVC)
nology F412, and abbreviations are in accordance with Termi-
Compounds and Chlorinated Poly(Vinyl Chloride)
nologyD1600,unlessotherwisespecified.Theabbreviationfor
(CPVC) Compounds
poly(vinyl chloride) is PVC.
D2122 Test Method for Determining Dimensions of Ther-
moplastic Pipe and Fittings
3.2 Definitions of Terms Specific to This Standard:
D2152 Test Method for Adequacy of Fusion of Extruded
3.2.1 closed profile (CP) gravity sewer pipe, n—a pipe
Poly(Vinyl Chloride) (PVC) Pipe and Molded Fittings by
product consisting of an essentially smooth waterway braced
Acetone Immersion
circumferentially or spirally with projections or ribs that are
joined by an essentially smooth outer wall (see Fig. 1).
4. Significance and Use
1
This specification is under the jurisdiction ofASTM Committee F17 on Plastic
Piping Systems and is the direct responsibility of Subcommittee F17.62 on Sewer.
4.1 The requirements of this specification are intended to
Current edition approved April 1, 2006. Published April 2006. Originally
provide pipe and fittings suitable for nonpressure drainage of
approved in 1997. Last previous edition approved in 2004 as F1803 – 04. DOI:
sewage and surface water.
10.1520/F1803-06.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
3
Standards volume information, refer to the standard’s Document Summary page on Available from Standardization Documents Order Desk, DODSSP, Bldg. 4,
the ASTM website. Section D, 700 Robbins Ave., Philadelphia, PA 19111-5098.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
F1803−06
6.2 Couplings shall form a water-tight seal when assembled
with plain end pipe and show no sign of leakage when tested
in accordance with 7.7 when assembled with pipe for which
they are intended.
NOTE 3—The outside diameters of products manufactured to this
FIG. 1Typical Closed Profi
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.