ASTM F2561-11
(Practice)Standard Practice for Rehabilitation of a Sewer Service Lateral and Its Connection to the Main Using a One Piece Main and Lateral Cured-in-Place Liner
Standard Practice for Rehabilitation of a Sewer Service Lateral and Its Connection to the Main Using a One Piece Main and Lateral Cured-in-Place Liner
SIGNIFICANCE AND USE
This practice is for use by designers and specifiers, regulatory agencies, owners, and inspection organizations who are involved in the rehabilitation of sewer service laterals and its connection to the main through the use of a resin-impregnated tube installed within an existing sewer lateral. As for any practice, modifications may be required for specific job conditions.
SCOPE
1.1 This practice covers requirements and test methods for the reconstruction of a sewer service lateral pipe having an inner diameter of 3 to 12 in. and its connection to the main pipe having an inner diameter of 6 to 24 in. without excavation. The lateral pipe is accessed remotely from the main pipe and from a lateral cleanout. This will be accomplished by the installation of a resin impregnated one-piece main and lateral cured in-place lining (MLCIPL) by means of air or water inflation and inversion. The MLCIPL is pressed against the host pipe by pressurizing a bladder and is held in place until the thermoset resins have cured. When cured, the MLCIPL shall be a continuous, one piece, tight fitting, corrosion resistant lining extending over a predetermined length of the lateral pipe and the adjacent section of the main pipe providing a verifiable non-leaking structural connection and seal.
1.2 The values stated in inch-pound units are to be regarded as the standard. The values given in parentheses are provided for information only.
1.3 There is no similar or equivalent ISO Standard.
This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. Particular attention is drawn to those safety regulations and requirements involving entering into and working in confined spaces.
General Information
Relations
Buy Standard
Standards Content (Sample)
NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: F2561 − 11
StandardPractice for
Rehabilitation of a Sewer Service Lateral and Its Connection
to the Main Using a One Piece Main and Lateral Cured-in-
1,2
Place Liner
This standard is issued under the fixed designation F2561; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope 2. Referenced Documents
3
1.1 This practice covers requirements and test methods for 2.1 ASTM Standards:
the reconstruction of a sewer service lateral pipe having an D618 Practice for Conditioning Plastics for Testing
innerdiameterof3to12in.anditsconnectiontothemainpipe D790 Test Methods for Flexural Properties of Unreinforced
having an inner diameter of 6 to 24 in. without excavation.The and Reinforced Plastics and Electrical Insulating Materi-
lateral pipe is accessed remotely from the main pipe and from als
a lateral cleanout.This will be accomplished by the installation D1600 Terminology forAbbreviatedTerms Relating to Plas-
of a resin impregnated one-piece main and lateral cured tics
in-place lining (MLCIPL) by means of air or water inflation D3681 Test Method for Chemical Resistance of “Fiberglass”
and inversion.The MLCIPLis pressed against the host pipe by (Glass–Fiber–Reinforced Thermosetting-Resin) Pipe in a
pressurizing a bladder and is held in place until the thermoset Deflected Condition
resins have cured. When cured, the MLCIPL shall be a D5813 Specification for Cured-In-Place Thermosetting
continuous, one piece, tight fitting, corrosion resistant lining Resin Sewer Piping Systems
extending over a predetermined length of the lateral pipe and F412 Terminology Relating to Plastic Piping Systems
the adjacent section of the main pipe providing a verifiable F1216 Practice for Rehabilitation of Existing Pipelines and
non-leaking structural connection and seal. Conduits by the Inversion and Curing of a Resin-
Impregnated Tube
1.2 The values stated in inch-pound units are to be regarded
4
2.2 NASSCO Guidelines:
as standard. The values given in parentheses are mathematical
Recommended Specifications for Sewer Collection System
conversions to SI units that are provided for information only
Rehabilitation
and are not considered standard.
1.3 There is no similar or equivalent ISO Standard.
3. Terminology
1.4 This standard does not purport to address all of the
3.1 Definitions—Unless otherwise indicated, definitions are
safety concerns, if any, associated with its use. It is the
inaccordancewithTerminologyF412,andabbreviationsarein
responsibility of the user of this standard to establish appro-
accordance with Terminology D1600.
priate safety and health practices and determine the applica-
3.2 Definitions of Terms Specific to This Standard:
bilityofregulatorylimitationspriortouse.Particularattention
3.2.1 access point—an existing manhole at either the up-
is drawn to those safety regulations and requirements involving
stream or downstream end of a sewer main or a cleanout
entering into and working in confined spaces.
located on the lateral pipe.
3.2.2 bladder—a transparent flexible plastic hose that when
1
This practice is under the jurisdiction of ASTM Committee F17 on Plastic
pressurized, causes the main sheet to be pressed against the
Piping Systems and is the direct responsibility of Subcommittee F17.67 on
Trenchless Plastic Pipeline Technology.
main pipe walls and the lateral tube to invert up into the sewer
Current edition approved Dec. 1, 2011. Published December 2011. Originally
service lateral. The bladder joined with the textile lining
approved in 2006. Last previous edition approved in D2561–06. DOI: 10.1520/
creates a liner/bladder assembly.
F2561-11.
2
Therehabilitationofasewerservicelateralanditsconnectiontothemainusing
a one-piece main and lateral cured-in-place liner is covered by patents (LMK
3
Enterprises, Inc. 1779 Chessie Lane, Ottawa, IL 61350). Interested parties are For referenced ASTM standards, visit the ASTM website, www.astm.org, or
invited to submit information regarding the identification of acceptable alternatives contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
to this patented item to the Committee on Standards,ASTM Headquarters, 100 Barr Standards volume information, refer to the standard’s Document Summary page on
Harbor Drive, West Conshohocken, PA 19428-2959. Your comments will receive the ASTM website.
4
carefulconsiderationatameetingoftheresponsibletechnicalcommitteewhichmay NASSCO, Inc. 11521 Cronridge Drive, Suite J, Owings Mills, MD 21117.
attend. www.nassco.org
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428
...
This document is not anASTM standard and is intended only to provide the user of anASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
An American National Standard
Designation:F2561–06 Designation:F2561–11
Standard Practice for
Rehabilitation of a Sewer Service Lateral and Its Connection
to the Main Using a One Piece Main and Lateral Cured-in-
,
1 2
Place Liner
This standard is issued under the fixed designation F2561; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope
1.1 This practice covers requirements and test methods for the reconstruction of a sewer service lateral pipe having an inner
diameter of 3 to 12 in. and its connection to the main pipe having an inner diameter of 6 to 24 in. without excavation. The lateral
pipe is accessed remotely from the main pipe and from a lateral cleanout. This will be accomplished by the installation of a resin
impregnated one-piece main and lateral cured in-place lining (MLCIPL) by means of air or water inflation and inversion. The
MLCIPLis pressed against the host pipe by pressurizing a bladder and is held in place until the thermoset resins have cured.When
cured, the MLCIPLshall be a continuous, one piece, tight fitting, corrosion resistant lining extending over a predetermined length
of the lateral pipe and the adjacent section of the main pipe providing a verifiable non-leaking structural connection and seal.
1.2The values stated in inch-pound units are to be regarded as the standard. The values given in parentheses are provided for
information only.
1.2 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical
conversions to SI units that are provided for information only and are not considered standard.
1.3 There is no similar or equivalent ISO Standard.
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory
limitations prior to use. Particular attention is drawn to those safety regulations and requirements involving entering into and
working in confined spaces.
2. Referenced Documents
3
2.1 ASTM Standards:
D618 Practice for Conditioning Plastics for Testing
D790 Test Methods for Flexural Properties of Unreinforced and Reinforced Plastics and Electrical Insulating Materials
D1600 Terminology for Abbreviated Terms Relating to Plastics
D3681 Test Method for Chemical Resistance of Fiberglass (GlassFiberReinforced Thermosetting-Resin) Pipe in a Deflected
Condition
D5813 Specification for Cured-In-Place Thermosetting Resin Sewer Piping Systems
F412 Terminology Relating to Plastic Piping Systems
F1216 Practice for Rehabilitation of Existing Pipelines and Conduits by the Inversion and Curing of a Resin-ImpregnatedTube
4
2.2 NASSCO Guidelines:
Recommended Specifications for Sewer Collection System Rehabilitation
1
This practice is under the jurisdiction ofASTM Committee F17 on Plastic Piping Systems and is the direct responsibility of Subcommittee F17.67 on Trenchless Plastic
Pipeline Technology.
Current edition approved June 1, 2006. Published June 2006. DOI: 10.1520/F2561-06.
Current edition approved Dec. 1, 2011. Published December 2011. Originally approved in 2006. Last previous edition approved in D2561–06. DOI: 10.1520/F2561-11.
2
Therehabilitationofasewerservicelateralanditsconnectiontothemainusingaone-piecemainandlateralcured-in-placelineriscoveredbypatents(LMKEnterprises,
Inc. 1779 Chessie Lane, Ottawa, IL 61350). Interested parties are invited to submit information regarding the identification of acceptable alternatives to this patented item
to the Committee on Standards, ASTM Headquarters, 100 Barr Harbor Drive, West Conshohocken, PA 19428-2959. Your comments will receive careful consideration at a
meeting of the responsible technical committee which may attend.
3
For referencedASTM standards, visit theASTM website, www.astm.org, or contactASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
4
NASSCO, 1314 Bedford Ave., Suite 201 Baltimore, MD 21208
4
NASSCO, Inc. 11521 Cronridge Drive, Suite J, Owings Mills, MD 21117. www.nassco.org
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United
...