Standard Practice for On-Site Inspection of Installed Fire Stops

SIGNIFICANCE AND USE
This practice is intended to provide a standard set of guidelines that are to be followed when conducting and reporting on inspections of installed fire stops.
This practice is intended to provide a means to verify compliance of the installed fire stops to the inspection documents.
This practice is not intended to provide a basis for selecting installers or products or both.
This practice is not intended to establish any performance criteria of the inspected fire stops.
SCOPE
1.1 This practice covers the establishing of procedures to inspect fire stops, including methods for field verification and inspection.
1.2 This practice addresses all types of fire stops installed through or into fire resistive assemblies.
Note 1—Fire stop is defined in Test Method E814.
1.3 This practice provides methods by which qualified inspectors verify that required fire stops on a project have been installed and that their installations are in accordance with the inspection documents.
1.4 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
1.6 The text of this standard references notes and footnotes that provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard.

General Information

Status
Historical
Publication Date
30-Apr-2010
Technical Committee
Drafting Committee
Current Stage
Ref Project

Relations

Buy Standard

Standard
ASTM E2174-10ae1 - Standard Practice for On-Site Inspection of Installed Fire Stops
English language
6 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
´1
Designation: E2174 − 10a
StandardPractice for
1
On-Site Inspection of Installed Fire Stops
This standard is issued under the fixed designation E2174; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1
ε NOTE—Editorial corrections were made to Note 3 in November 2011.
1. Scope Testing, Quality Assurance, and Evaluating of Building
Components
1.1 This practice covers the establishing of procedures to
E814 Test Method for Fire Tests of Penetration Firestop
inspect fire stops, including methods for field verification and
Systems
inspection.
3
2.2 Other Standards:
1.2 This practice addresses all types of fire stops installed
UL 1479-94 Fire Tests of Through-Penetration Fire Stops
through or into fire resistive assemblies.
4
2.3 Other Documents:
NOTE 1—Fire stop is defined in Test Method E814.
International Building Code
1.3 This practice provides methods by which qualified
3. Terminology
inspectors verify that required fire stops on a project have been
installed and that their installations are in accordance with the
3.1 Definitions—Terms defined in Terminology E631, Ter-
inspection documents.
minology E176, and Practice E699 will prevail for terms not
defined in this document.
1.4 The values stated in inch-pound units are to be regarded
as standard. The values given in parentheses are mathematical
3.2 Definitions of Terms Specific to This Standard:
conversions to SI units that are provided for information only
3.2.1 authorizing authority (AA)—the designated person, or
and are not considered standard.
organization, or their duly authorized representative, charged
1.5 This standard does not purport to address all of the with the administration and enforcement of the provisions of
safety concerns, if any, associated with its use. It is the this inspection document.
responsibility of the user of this standard to establish appro-
NOTE 2—Examples of the AA include the responsible architect,
priate safety and health practices and determine the applica-
engineer, building owner, or their representative.
bility of regulatory limitations prior to use.
3.2.2 authority having jurisdiction (AHJ)—the designated
1.6 The text of this standard references notes and footnotes
authority, or their duly authorized representative, charged with
that provide explanatory material. These notes and footnotes
the administration and enforcement of the local fire code or
(excluding those in tables and figures) shall not be considered
building code, or both.
as requirements of the standard.
3.2.3 accredited testing laboratory—a company engaged in
conducting testing and possesses a valid evaluation report for
2. Referenced Documents
testing services and is recognized by the AHJ.
2
2.1 ASTM Standards:
3.2.4 evaluation report—an approved document issued by
E176 Terminology of Fire Standards
the Model Code Body Evaluation Service or by the AHJ.
E631 Terminology of Building Constructions
3.2.5 inspection document—anyinformationprovidedtothe
E699 Practice for Evaluation of Agencies Involved in
inspector by the AA that is to be used as the basis for the
inspection process. This information shall include, but is not
limited to, project specifications, contract drawings, Listed
1
This practice is under the jurisdiction of ASTM Committee E06 on Perfor-
Designs, judgments, manufacturer’s instructions and designs,
mance of Buildings and is the direct responsibility of Subcommittee E06.21 on
Serviceability.
building codes, and other documentation.
Current edition approved May 1, 2010. Published August 2010. Originally
approved in 2001. Last previous edition approved in 2010 as E2174 – 10. DOI:
10.1520/E2174-10AE01.
2 3
For referenced ASTM standards, visit the ASTM website, www.astm.org, or Available from Underwriters Laboratories (UL), Corporate Progress, 333
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Pfingsten Rd., Northbrook, IL 60062, http://www.ul.com.
4
Standards volume information, refer to the standard’s Document Summary page on Available from International Code Council (ICC), 500 New Jersey Ave., NW,
the ASTM website. 6th Floor, Washington, DC 20001-2070, http://www.iccsafe.org.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
´1
E2174 − 10a
NOTE 3—The approved fire stop submittal typically includes the fire
6. Inspector
stop manufacturer’s product data, a design listing of the tested fire stop or
6.1 Qualifications—An inspector shall be acceptable to the
the engineering judgment design with illustrat
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.