Standard Test Method for Hydrostatic Infiltration Testing of Vitrified Clay Pipe Lines

SIGNIFICANCE AND USE
The tests called for herein, for their results, indicate the acceptability of installed vitrified clay pipelines.
SCOPE
1.1 This test method defines procedures for hydrostatic infiltration testing of new installations of vitrified clay pipe lines, to demonstrate the structural integrity of the installed line. Refer to Practice C 12.  
1.2 This test method is suitable for testing gravity-flow pipe lines constructed of vitrified clay pipe or combinations of clay pipe and other pipe materials.
1.3 This test method is applicable to the testing of the pipe lines only. Manholes or other structures should be tested separately.  
1.4 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.5 This standard does not purport to address all of the safety problems, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

General Information

Status
Historical
Publication Date
31-Oct-2008
Current Stage
Ref Project

Relations

Buy Standard

Standard
ASTM C1091-03a(2008) - Standard Test Method for Hydrostatic Infiltration Testing of Vitrified Clay Pipe Lines
English language
2 pages
sale 15% off
Preview
sale 15% off
Preview
Standard
REDLINE ASTM C1091-03a(2008) - Standard Test Method for Hydrostatic Infiltration Testing of Vitrified Clay Pipe Lines
English language
2 pages
sale 15% off
Preview
sale 15% off
Preview
Standard
REDLINE ASTM C1091-03a(2008) - Standard Test Method for Hydrostatic Infiltration Testing of Vitrified Clay Pipe Lines
English language
2 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation:C1091 −03a(Reapproved 2008)
Standard Test Method for
Hydrostatic Infiltration Testing of Vitrified Clay Pipe Lines
This standard is issued under the fixed designation C1091; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope 4. Summary of Test Method
1.1 This test method defines procedures for hydrostatic 4.1 This test method shall be performed on lines after
connection laterals, if any, have been plugged and adequately
infiltration testing of new installations of vitrified clay pipe
braced to withstand the test pressure, and after the trenches
lines, to demonstrate the structural integrity of the installed
have been backfilled and compacted.
line. Refer to Practice C12.
1.2 This test method is suitable for testing gravity-flow pipe
5. Significance and Use
lines constructed of vitrified clay pipe or combinations of clay
5.1 The tests called for herein, for their results, indicate the
pipe and other pipe materials.
acceptability of installed vitrified clay pipelines.
1.3 This test method is applicable to the testing of the pipe
6. Preparation of the Line
lines only. Manholes or other structures should be tested
separately. 6.1 To ensure the proper seating of the test plugs and the
accuracyofthetest,thelinesshouldbecleanedpriortotesting.
1.4 The values stated in inch-pound units are to be regarded
6.2 Examples of methods for cleaning the lines are the
as standard. The values given in parentheses are mathematical
conversions to SI units that are provided for information only sewer cleaning ball and high pressure flushing equipment.
and are not considered standard.
7. Procedure
1.5 This standard does not purport to address all of the
7.1 The hydrostatic infiltration test procedure is applicable
safety problems, if any, associated with its use. It is the
where the measured water table is 2 ft (610 mm) or greater
responsibility of the user of this standard to establish appro-
above the pipe barrel at the lower manhole of the test section.
priate safety and health practices and determine the applica-
Where the ground water elevation is indeterminate, less than 2
bility of regulatory limitations prior to use.
ft (610 mm) above the top of the pipe barrel, or the line is
partially below the water table, use a combination of both the
2. Referenced Documents
air test and infiltration procedure.
2.1 ASTM Standards:
NOTE 1—The most practical method for testing is Test Method C828,
C12 Practice for Installing Vitrified Clay Pipe Lines
and is recommended. However, where ground water is present and meets
C828 Test Method for Low-Pressure Air Test of Vitrified
thecriteriaestablishedin7.1,theinfiltrationtestprocedureoutlinedinthis
Clay Pipe Lines
practice is recommended.
C896 Terminology Relating to Clay Products
7.2 Determine the allowable infiltration rate for the test
section using Table 1.
3. Terminology
NOTE 2—What can be called false infiltration represents condensate on
3.1 Terminology C896 can be used for clarifications of
the pipe walls.
terminology in this test method.
7.3 The test rate table is based on the standard of 50 gal/in.
diameter·mile·day (4.6 L/mm diameter·kilometre·day).
7.4 Table 1 shows the allowable infiltration rate in
This test method is under the jurisdiction ofASTM Committee C04 on Vitrified
gallons · 100 ft of pipe · hour (litres per 30.5 metres · hour) for
Clay Pipe and is the direct responsibility of Subcommittee C04.20 on Methods of
each nominal pipe size.
Test and Specifications.
Current edition approved Nov. 1, 2008. Published November 2008. Originally
7.
...


This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation:C1091–03a Designation: C 1091 – 03a (Reapproved 2008)
Standard Test Method for
Hydrostatic Infiltration Testing of Vitrified Clay Pipe Lines
This standard is issued under the fixed designation C 1091; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope
1.1 This test method defines procedures for hydrostatic infiltration testing of new installations of vitrified clay pipe lines, to
demonstrate the structural integrity of the installed line. Refer to Practice C 12.
1.2 This test method is suitable for testing gravity-flow pipe lines constructed of vitrified clay pipe or combinations of clay pipe
and other pipe materials.
1.3 This test method is applicable to the testing of the pipe lines only. Manholes or other structures should be tested separately.
1.4The values stated in inch-pound units are to be regarded as the standard. The values given in parentheses are provided for
information only.
1.4 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical
conversions to SI units that are provided for information only and are not considered standard.
1.5 This standard does not purport to address all of the safety problems, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory
limitations prior to use.
2. Referenced Documents
2.1 ASTM Standards:
C12 Practice for Installing Vitrified Clay Pipe Lines
C 828 Test Method for Low-Pressure Air Test of Vitrified Clay Pipe Lines
C 896 Terminology Relating to Clay Products
3. Terminology
3.1 Terminology C 896 can be used for clarifications of terminology in this test method.
4. Summary of Test Method
4.1 This test method shall be performed on lines after connection laterals, if any, have been plugged and adequately braced to
withstand the test pressure, and after the trenches have been backfilled and compacted.
5. Significance and Use
5.1 The tests called for herein, for their results, indicate the acceptability of installed vitrified clay pipelines.
6. Preparation of the Line
6.1 To ensure the proper seating of the test plugs and the accuracy of the test, the lines should be cleaned prior to testing.
6.2 Examples of methods for cleaning the lines are the sewer cleaning ball and high pressure flushing equipment.
7. Procedure
7.1 The hydrostatic infiltration test procedure is applicable where the measured water table is 2 ft (610 mm) or greater above
the pipe barrel at the lower manhole of the test section.Where the ground water elevation is indeterminate, less than 2 ft (610 mm)
above the top of the pipe barrel, or the line is partially below the water table, use a combination of both the air test and infiltration
procedure.
NOTE 1—The most practical method for testing is Test Method C 828, and is recommended. However, where ground water is present and meets the
This test method is under the jurisdiction of ASTM Committee C04 on Vitrified Clay Pipe and is the direct responsibility of Subcommittee C04.20 on Methods of Test
and Specifications.
Current edition approved OctoberNov. 1, 2003.2008. Published October 2003.November 2008. Originally published in 1988. Last previous edition approved in 2003 as
C 1091 – 03a.
For referencedASTM standards, visit theASTM website, www.astm.org, or contactASTM Customer Service at service@astm.org. ForAnnual Boo
...


This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation:C1091–03 Designation: C 1091 – 03a (Reapproved 2008)
Standard Test Method for
Hydrostatic Infiltration and Exfiltration Testing of Vitrified
Clay Pipe Lines
This standard is issued under the fixed designation C 1091; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope
1.1 This test method defines procedures for hydrostatically hydrostatic infiltration testing of new installations of vitrified clay
pipe lines, to demonstrate the structural integrity of the installed line. Refer to Practice C 12.
1.2 This test method is suitable for testing gravity-flow pipe lines constructed of vitrified clay pipe or combinations of clay pipe
and other pipe materials.
1.3 This test method is applicable to the testing of the pipe lines only. Manholes or other structures should be tested separately.
1.4The values stated in inch-pound units are to be regarded as the standard. The values given in parentheses are provided for
information only.
1.4 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical
conversions to SI units that are provided for information only and are not considered standard.
1.5 This standard does not purport to address all of the safety problems, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory
limitations prior to use.
2. Referenced Documents
2.1 ASTM Standards:
C 12 Practice for Installing Vitrified Clay Pipe Lines
C 828 Test Method for Low-Pressure Air Test of Vitrified Clay Pipe Lines
C 896 Terminology Relating to Clay Products
3. Terminology
3.1 Terminology C 896 can be used for clarifications of terminology in this test method.
4. Summary of Test Method
4.1This test method shall be performed on lines after connection laterals, if any, have been plugged and adequately braced to
withstand the test pressure, and after the trenches have been backfilled for a sufficient time to generate a significant portion of the
ultimate trench load on the pipe line. The time between completion of the backfill operation and hydrostatic testing shall be
established by the approving authority.
4.1 This test method shall be performed on lines after connection laterals, if any, have been plugged and adequately braced to
withstand the test pressure, and after the trenches have been backfilled and compacted.
5. Significance and Use
5.1 The tests called for herein, for their results, indicate the acceptability of installed vitrified clay pipelines.
6. Preparation of the Line
6.1 To ensure the proper seating of the test plugs and the accuracy of the test, the lines should be cleaned prior to testing.
6.2 Examples of methods for cleaning the lines are the sewer cleaning ball and high pressure flushing equipment.
This test method is under the jurisdiction of ASTM Committee C04 on Vitrified Clay Pipe and is the direct responsibility of Subcommittee C04.20 on Methods of Test
and Specifications.
Current edition approved February 10, 2003. Published May 2003. Originally published in 1988. Last previous edition approved in 1999 as C1091–99.
Current edition approved Nov. 1, 2008. Published November 2008. Originally published in 1988. Last previous edition approved in 2003 as C 1091 – 03a.
Annual Book of ASTM Standards, Vol 04.05.
For referencedASTM standards, visit theASTM website, www.astm.org, or contactASTM Customer Service at service@astm.org. ForAnnual Book ofASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
C 1091 – 03a (2008)
7. Procedure
7.1 Infiltration Testing:
7.1.1ThisThe hydrostatic infiltration test procedure is applicable where the measured water table is 2 ft (610 mm) or greater
above the pipe barrel at the midpoint lower manhole of the test section (see Note 1). section. Where the ground water elevation
is indeterminate, less than 2 ft (610 mm) above the top of the pipe barrel, or the line is partially below the water table, use a
combination of both the air test and infiltration procedure.
NOTE1—What can be called false infiltration represents condensate on the pipe walls. This may amount to as much as 50 gal/in. diameter·mile·day (4.6
L/mm diameter·kilometre·day). Thus, evaluate flow in the pipeline for this condition.
7.1.2Determine the allowable infiltration rate for the test section using 1—The most practical method for testing isTest Method
C 828, and is recommended. However, where ground water is present and meets the criteria established in 7.1, the infiltration test
procedure outlined in this practice is recommended.
7.2 Determine the allowable infiltration rate for the test section using Table 1.
7.1.3Discontinue all pumping of ground water for a period of 24 h prior to testing.
7.1.4Plug the inlet to the test section to be tested. It is usually necessary to also plug the inlet of the upper manhole to prevent
the manhole from filling with water or provide a method of de-watering the manhole or remotely removing the plug at the inlet
to the test section. Securely plug all lateral inlets to the line.
7.1.5To determine the infiltration rate, measure the flow at the outlet of the test section.
7.1.5.1At the outlet of the test section, collect the water and measure the quantity collected within a specific time. Achieve
collection and measurement with the use of a plug having a pipe outlet and a calibrated container after constant flow is generated
at the pipe outlet.
7.1.5.2An alternate method of measurement is to use a calibrated weir (see Note 2) installed at the outlet of the test section and
directly read the rate of flow.
NOTE2—The apex of weir should be as near to the pipe invert as practical.
7.1.6If the allowable infiltration rate (see 2—What can be called false infiltration represents condensate on the pipe walls.
7.3 The test rate table is based on
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.