Standard Practice for Measuring and Calculating Building Loss Features That Take Up Floor Area in Buildings

SIGNIFICANCE AND USE
4.1 Use this practice to identify and measure the amount of actual and effective floor area that will be unavailable to occupants for the placement of people’s workplaces, furniture, and equipment or for circulation.  
4.2 Findings from use of this practice are intended for optional inclusion with reports of floor area measured in accordance with Practice E1836/E1836M or in accordance with ANSI/BOMA Z65.1–1996.
Note 1: The choice between using Practice E1836/E1836M or ANSI/BOMA Z65.1–1996 as the basis for measurement depends on the objectives of the analysis. Practice E1836/E1836M is oriented to the traditional interests of design professionals and would be particularly suitable for single-tenant buildings whereas some categories of space measured by ANSI/BOMA Z65.1–1996 are oriented to the leasing of multi-tenant buildings by real estate professionals.  
4.3 this practice is not intended for use for regulatory purposes, nor for fire hazard assessment, nor for fire risk assessment.
SCOPE
1.1 This practice specifies how to measure certain characteristics of a building, known as building loss features, inside the exterior gross area of a floor and how to calculate the amount of actual and effective floor area that will be not be available for the placement of people’s workplaces, furniture, equipment, or for circulation, if using standard furnishings and orthogonal furniture systems.  
1.2 This practice can be used to specify a performance requirement to limit the amount of floor area that may be taken up by building loss features.  
1.3 This practice can be used to assess how well a design(s) for an office facility meets a performance requirement regarding floor area.  
1.4 This practice can be used to assess how well a constructed office building has met a performance requirement regarding floor area.  
1.5 This practice is not intended for and not suitable for use for regulatory purposes, fire hazard assessment, and fire risk assessment.  
1.6 Users of this practice should recognize that, in some situations, the amount of certain actual and effective floor area losses may be mitigated to some degree at some cost by custom-tailoring spaces and creating specially fitted furnishings and carpentry to get some value from space which would not otherwise be usable.  
1.7 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard.  
1.8 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.9 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

General Information

Status
Published
Publication Date
30-Sep-2017
Current Stage
Ref Project

Relations

Buy Standard

Standard
ASTM E2619/E2619M-17 - Standard Practice for Measuring and Calculating Building Loss Features That Take Up Floor Area in Buildings
English language
11 pages
sale 15% off
Preview
sale 15% off
Preview
Standard
REDLINE ASTM E2619/E2619M-17 - Standard Practice for Measuring and Calculating Building Loss Features That Take Up Floor Area in Buildings
English language
11 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the
Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
Designation: E2619/E2619M − 17
Standard Practice for
Measuring and Calculating Building Loss Features That
1
Take Up Floor Area in Buildings
ThisstandardisissuedunderthefixeddesignationE2619/E2619M;thenumberimmediatelyfollowingthedesignationindicatestheyear
of original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval.
A superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope responsibility of the user of this standard to establish appro-
priate safety, health, and environmental practices and deter-
1.1 This practice specifies how to measure certain charac-
mine the applicability of regulatory limitations prior to use.
teristics of a building, known as building loss features, inside
1.9 This international standard was developed in accor-
the exterior gross area of a floor and how to calculate the
dance with internationally recognized principles on standard-
amount of actual and effective floor area that will be not be
ization established in the Decision on Principles for the
available for the placement of people’s workplaces, furniture,
Development of International Standards, Guides and Recom-
equipment, or for circulation, if using standard furnishings and
mendations issued by the World Trade Organization Technical
orthogonal furniture systems.
Barriers to Trade (TBT) Committee.
1.2 This practice can be used to specify a performance
requirement to limit the amount of floor area that may be taken
2. Referenced Documents
up by building loss features.
2
2.1 ASTM Standards:
1.3 This practice can be used to assess how well a design(s)
E631 Terminology of Building Constructions
for an office facility meets a performance requirement regard-
E1836/E1836M Practice for Building Floor Area Measure-
ing floor area.
ments for Facility Management
3
1.4 This practice can be used to assess how well a con-
2.2 ANSI Standard:
structed office building has met a performance requirement
ANSI/BOMA Z65.1–1996 Standard Method for Measuring
regarding floor area.
Floor Area in Office Buildings
4
1.5 This practice is not intended for and not suitable for use
2.3 Other Standards:
for regulatory purposes, fire hazard assessment, and fire risk
ASHRAE 62.1–2007 Ventilation for Acceptable Indoor Air
assessment.
Quality
1.6 Users of this practice should recognize that, in some
5
3. Terminology
situations, the amount of certain actual and effective floor area
losses may be mitigated to some degree at some cost by
3.1 Definitions:
custom-tailoring spaces and creating specially fitted furnish-
3.1.1 facility, n—a physical setting used to serve a specific
ings and carpentry to get some value from space which would
purpose.
not otherwise be usable.
1.7 The values stated in either SI units or inch-pound units
2
are to be regarded separately as standard. The values stated in For referenced ASTM standards, visit the ASTM website, www.astm.org, or
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
each system may not be exact equivalents; therefore, each
Standards volume information, refer to the standard’s Document Summary page on
system shall be used independently of the other. Combining
the ASTM website.
3
values from the two systems may result in non-conformance
Available fromAmerican National Standards Institute (ANSI), 25 W. 43rd St.,
4th Floor, New York, NY 10036, http://www.ansi.org.
with the standard.
4
Available from American Society of Heating, Refrigerating, and Air-
1.8 This standard does not purport to address all of the
Conditioning Engineers, Inc. (ASHRAE), 1791 Tullie Circle, NE, Atlanta, GA
30329, http://www.ashrae.org.
safety concerns, if any, associated with its use. It is the
5
Certain definitions of terms in this practice were agreed in 2007 by a Working
Group established jointly by the Building Owners and Managers Association
1
This practice is under the jurisdiction of ASTM Committee E06 on Perfor- (BOMA) International and the International Facility Management Association
mance of Buildings and is the direct responsibility of Subcommittee E06.25 on (IFMA). Certain terms were derived from referenced ASTM standards or from
Whole Buildings and Facilities. referenced ANSI standard, or from published IFMA documents. Ownership of
Current edition approved Oct. 1, 2017. Published November 2017. Originally copyright to specific terms is indicated by footnotes. Certain terms are quoted from
ɛ1
approvedin2008.Lastpreviouseditionapprovedin2009asE2619/E2619M – 09 . other ASTM standards, in which case the ASTM source is identified at the end of
DOI: 10.1520/E2619_E2619M-17. the definition.
Copyri
...

This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
´1
Designation: E2619/E2619M − 09 E2619/E2619M − 17 An American National Standard
Standard Practice for
Measuring and Calculating Building Loss Features That
1
Take Up Floor Area in Buildings
This standard is issued under the fixed designation E2619/E2619M; the number immediately following the designation indicates the year
of original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval.
A superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1
ε NOTE—Units information and designation was corrected editorially in April 2009.
1. Scope
1.1 This practice specifies how to measure certain characteristics of a building, known as building loss features, inside the
exterior gross area of a floor and how to calculate the amount of actual and effective floor area that will be not be available for
the placement of people’s workplaces, furniture, equipment, or for circulation, if using standard furnishings and orthogonal
furniture systems.
1.2 This practice can be used to specify a performance requirement to limit the amount of floor area that may be taken up by
building loss features.
1.3 This practice can be used to assess how well a design(s) for an office facility meets a performance requirement regarding
floor area.
1.4 This practice can be used to assess how well a constructed office building has met a performance requirement regarding floor
area.
1.5 This practice is not intended for and not suitable for use for regulatory purposes, fire hazard assessment, and fire risk
assessment.
1.6 Users of this practice should recognize that, in some situations, the amount of certain actual and effective floor area losses
may be mitigated to some degree at some cost by custom-tailoring spaces and creating specially fitted furnishings and carpentry
to get some value from space which would not otherwise be usable.
1.7 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each
system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the
two systems may result in non-conformance with the standard.
1.8 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety safety, health, and healthenvironmental practices and determine the
applicability of regulatory limitations prior to use.
1.9 This international standard was developed in accordance with internationally recognized principles on standardization
established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued
by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
2. Referenced Documents
2
2.1 ASTM Standards:
E631 Terminology of Building Constructions
E1836/E1836M Practice for Building Floor Area Measurements for Facility Management
3
2.2 ANSI Standard:
ANSI/BOMA Z65.1–1996 Standard Method for Measuring Floor Area in Office Buildings
1
This practice is under the jurisdiction of ASTM Committee E06 on Performance of Buildings and is the direct responsibility of Subcommittee E06.25 on Whole Buildings
and Facilities.
Current edition approved April 1, 2009Oct. 1, 2017. Published October 2009November 2017. Originally approved in 2008. Last previous edition approved in 20082009
ɛ1
as E2619 – 08.E2619/E2619M – 09 . DOI: 10.1520/E2619_E2619M-09E01.10.1520/E2619_E2619M-17.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
3
Available from American National Standards Institute (ANSI), 25 W. 43rd St., 4th Floor, New York, NY 10036, http://www.ansi.org.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
E2619/E2619M − 17
4
2.3 Other Standards:
ASHRAE 62.1–2007 Ventilation for Acceptable Indoor Air Quality
5
3. Terminology
3.1 Definitions:
3.1.1 facility, n—a physical setting used to serve a specific purpose.
4
Available from American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc. (ASHRAE), 1791 Tullie Circle, NE, Atlanta, GA 30329,
http://www.ashrae.org.
5
Certain definitions of
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.