Standard Practice for Emergency Joining of Booms with Incompatible Connectors

SIGNIFICANCE AND USE
3.1 The use of this practice for the emergency joining of booms will not guarantee the effective performance of the joined boom sections, since each boom design and the environmental conditions of each incident govern the overall performance.  
3.2 Historically, different types of end connectors have been produced. This practice addresses the operational need to connect different types, during spill incidents. (Warning—Use of this practice with similar or different sizes of boom may cause the transmission of unwanted loading such as, tension loading and bending moments on certain boom parts resulting in possible premature failure of the containment system.)  
3.3 There are a wide range of boom connector configurations presently in use. These connectors were based upon some or all of the following design criteria:  
3.3.1 Connect and transfer tensile loads between boom sections,  
3.3.2 Minimize oil leakage between boom sections,  
3.3.3 Be easily connectable in the presence of dirt, oil or ice, or a combination thereof,  
3.3.4 Be quickly and easily connected and disconnected, in and out of the water,  
3.3.5 Maintain boom performance (freeboard, heave response, conformance, stability, and so forth),  
3.3.6 Be unaffected by temperature extremes,  
3.3.7 Have no protruding parts that could snag, injure, or puncture,  
3.3.8 Be light weight and buoyant,  
3.3.9 Be operatively symmetrical,  
3.3.10 Require no special tools for installation or removal,  
3.3.11 Require no loose parts for connection,  
3.3.12 Extend to the full height and draft of the boom,  
3.3.13 Resist distortion (that is, winding boom on a reel), and  
3.3.14 Be inherently safe to personnel.
SCOPE
1.1 This practice provides a standard practice for the joining of oil spill containment boom connectors in emergencies.  
1.2 The use of this connection method may adversely affect the total tensile strength of the connected booms.  
1.3 These criteria are intended to define mating requirements that will allow the emergency or occasional connection of unlike connectors.  
1.4 This practice is not intended to replace Specification F962.  
1.5 This practice does not address the compatibility of spill control equipment with spill products. It is the user's responsibility to ensure that any equipment selected is compatible with the anticipated spilled material.  
1.6 There is no guarantee that all of the connectors in use today can accept the holes spaced as required without interfering with existing bolt holes or other connector features.  
1.7 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard. See Note 5 in Fig. 1—dimensions A and B are critical.
FIG. 1 Side View of a Typical Connector  
1.8 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. For a specific precautionary statement, see 3.2.  
1.9 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

General Information

Status
Historical
Publication Date
31-Mar-2018
Current Stage
Ref Project

Relations

Buy Standard

Standard
ASTM F1657/F1657M-96(2018) - Standard Practice for Emergency Joining of Booms with Incompatible Connectors
English language
3 pages
sale 15% off
Preview
sale 15% off
Preview
Standard
ASTM F1657/F1657M-96(2018) - Standard Practice for Emergency Joining of Booms with Incompatible Connectors
English language
3 pages
sale 15% off
Preview
sale 15% off
Preview
Standard
REDLINE ASTM F1657/F1657M-96(2018) - Standard Practice for Emergency Joining of Booms with Incompatible Connectors
English language
3 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the
Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
Designation: F1657/F1657M − 96 (Reapproved 2018)
Standard Practice for
Emergency Joining of Booms with Incompatible
Connectors
ThisstandardisissuedunderthefixeddesignationF1657/F1657M;thenumberimmediatelyfollowingthedesignationindicatestheyear
of original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval.
A superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope Development of International Standards, Guides and Recom-
mendations issued by the World Trade Organization Technical
1.1 This practice provides a standard practice for the joining
Barriers to Trade (TBT) Committee.
of oil spill containment boom connectors in emergencies.
1.2 The use of this connection method may adversely affect
2. Referenced Documents
the total tensile strength of the connected booms.
2.1 ASTM Standards:
1.3 These criteria are intended to define mating require-
F818 Terminology Relating to Spill Response Booms and
ments that will allow the emergency or occasional connection
Barriers
of unlike connectors.
F962 Specification for Oil Spill Response Boom Connec-
tion: Z-Connector
1.4 This practice is not intended to replace Specification
F962. F1093 Test Methods for Tensile Strength Characteristics of
Oil Spill Response Boom
1.5 This practice does not address the compatibility of spill
F1523 Guide for Selection of Booms in Accordance With
control equipment with spill products. It is the user’s respon-
Water Body Classifications
sibility to ensure that any equipment selected is compatible
with the anticipated spilled material.
3. Significance and Use
1.6 There is no guarantee that all of the connectors in use
3.1 The use of this practice for the emergency joining of
today can accept the holes spaced as required without interfer-
booms will not guarantee the effective performance of the
ing with existing bolt holes or other connector features.
joined boom sections, since each boom design and the envi-
1.7 The values stated in either SI units or inch-pound units
ronmental conditions of each incident govern the overall
are to be regarded separately as standard. The values stated in
performance.
each system may not be exact equivalents; therefore, each
3.2 Historically, different types of end connectors have been
system shall be used independently of the other. Combining
produced. This practice addresses the operational need to
values from the two systems may result in non-conformance
connect different types, during spill incidents. (Warning—Use
with the standard. See Note 5 in Fig. 1—dimensions A and B
of this practice with similar or different sizes of boom may
are critical.
cause the transmission of unwanted loading such as, tension
1.8 This standard does not purport to address all of the
loading and bending moments on certain boom parts resulting
safety concerns, if any, associated with its use. It is the
in possible premature failure of the containment system.)
responsibility of the user of this standard to establish appro-
3.3 There are a wide range of boom connector configura-
priate safety, health, and environmental practices and deter-
tions presently in use.These connectors were based upon some
mine the applicability of regulatory limitations prior to use.
or all of the following design criteria:
For a specific precautionary statement, see 3.2.
3.3.1 Connect and transfer tensile loads between boom
1.9 This international standard was developed in accor-
sections,
dance with internationally recognized principles on standard-
3.3.2 Minimize oil leakage between boom sections,
ization established in the Decision on Principles for the
3.3.3 Beeasilyconnectableinthepresenceofdirt,oilorice,
or a combination thereof,
This practice is under the jurisdiction of ASTM Committee F20 on Hazardous
Substances and Oil Spill Response and is the direct responsibility of Subcommittee
F20.11 on Control. For referenced ASTM standards, visit the ASTM website, www.astm.org, or
Current edition approved April 1, 2018. Published May 2018. Originally contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
ɛ1
approved in 1996. Last previous edition approved in 2012 as F1657 – 96 (2012) . Standards volume information, refer to the standard’s Document Summary page on
DOI: 10
...


NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: F1657/F1657M − 96 (Reapproved 2018)
Standard Practice for
Emergency Joining of Booms with Incompatible
Connectors
This standard is issued under the fixed designation F1657/F1657M; the number immediately following the designation indicates the year
of original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval.
A superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope Development of International Standards, Guides and Recom-
mendations issued by the World Trade Organization Technical
1.1 This practice provides a standard practice for the joining
Barriers to Trade (TBT) Committee.
of oil spill containment boom connectors in emergencies.
1.2 The use of this connection method may adversely affect
2. Referenced Documents
the total tensile strength of the connected booms.
2.1 ASTM Standards:
1.3 These criteria are intended to define mating require-
F818 Terminology Relating to Spill Response Booms and
ments that will allow the emergency or occasional connection
Barriers
of unlike connectors.
F962 Specification for Oil Spill Response Boom Connec-
1.4 This practice is not intended to replace Specification tion: Z-Connector
F1093 Test Methods for Tensile Strength Characteristics of
F962.
Oil Spill Response Boom
1.5 This practice does not address the compatibility of spill
F1523 Guide for Selection of Booms in Accordance With
control equipment with spill products. It is the user’s respon-
Water Body Classifications
sibility to ensure that any equipment selected is compatible
with the anticipated spilled material.
3. Significance and Use
1.6 There is no guarantee that all of the connectors in use
3.1 The use of this practice for the emergency joining of
today can accept the holes spaced as required without interfer-
booms will not guarantee the effective performance of the
ing with existing bolt holes or other connector features.
joined boom sections, since each boom design and the envi-
1.7 The values stated in either SI units or inch-pound units
ronmental conditions of each incident govern the overall
are to be regarded separately as standard. The values stated in
performance.
each system may not be exact equivalents; therefore, each
3.2 Historically, different types of end connectors have been
system shall be used independently of the other. Combining
produced. This practice addresses the operational need to
values from the two systems may result in non-conformance
connect different types, during spill incidents. (Warning—Use
with the standard. See Note 5 in Fig. 1—dimensions A and B
of this practice with similar or different sizes of boom may
are critical.
cause the transmission of unwanted loading such as, tension
1.8 This standard does not purport to address all of the
loading and bending moments on certain boom parts resulting
safety concerns, if any, associated with its use. It is the
in possible premature failure of the containment system.)
responsibility of the user of this standard to establish appro-
3.3 There are a wide range of boom connector configura-
priate safety, health, and environmental practices and deter-
tions presently in use. These connectors were based upon some
mine the applicability of regulatory limitations prior to use.
or all of the following design criteria:
For a specific precautionary statement, see 3.2.
3.3.1 Connect and transfer tensile loads between boom
1.9 This international standard was developed in accor-
sections,
dance with internationally recognized principles on standard-
3.3.2 Minimize oil leakage between boom sections,
ization established in the Decision on Principles for the
3.3.3 Be easily connectable in the presence of dirt, oil or ice,
or a combination thereof,
This practice is under the jurisdiction of ASTM Committee F20 on Hazardous
Substances and Oil Spill Response and is the direct responsibility of Subcommittee
F20.11 on Control. For referenced ASTM standards, visit the ASTM website, www.astm.org, or
Current edition approved April 1, 2018. Published May 2018. Originally contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
ɛ1
approved in 1996. Last previous edition approved in 2012 as F1657 – 96 (2012) . Standards volume information, refer to the standard’s Document Summary page on
DOI: 10.1520/F1657_F1657M-96R18. the ASTM website.
Copyright © ASTM International, 100 Bar
...


This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
´1
Designation: F1657/F1657M − 96 (Reapproved 2012) F1657/F1657M − 96 (Reapproved
2018)
Standard Practice for
Emergency Joining of Booms with Incompatible
Connectors
This standard is issued under the fixed designation F1657/F1657M; the number immediately following the designation indicates the year
of original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval.
A superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
ε NOTE—Units information was editorially corrected in April 2012.
1. Scope
1.1 This practice provides a standard practice for the joining of oil spill containment boom connectors in emergencies.
1.2 The use of this connection method may adversely affect the total tensile strength of the connected booms.
1.3 These criteria are intended to define mating requirements that will allow the emergency or occasional connection of unlike
connectors.
1.4 This practice is not intended to replace Specification F962.
1.5 This practice does not address the compatibility of spill control equipment with spill products. It is the user’s responsibility
to ensure that any equipment selected is compatible with the anticipated spilled material.
1.6 There is no guarantee that all of the connectors in use today can accept the holes spaced as required without interfering with
existing bolt holes or other connector features.
1.7 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each
system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the
two systems may result in non-conformance with the standard. See Note 5 in Fig. 1—dimensions A and B are critical.
1.8 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety safety, health, and healthenvironmental practices and determine the
applicability of regulatory limitations prior to use. For a specific precautionary statement, see 3.2.
1.9 This international standard was developed in accordance with internationally recognized principles on standardization
established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued
by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
2. Referenced Documents
2.1 ASTM Standards:
F818 Terminology Relating to Spill Response Booms and Barriers
F962 Specification for Oil Spill Response Boom Connection: Z-Connector
F1093 Test Methods for Tensile Strength Characteristics of Oil Spill Response Boom
F1523 Guide for Selection of Booms in Accordance With Water Body Classifications
3. Significance and Use
3.1 The use of this practice for the emergency joining of booms will not guarantee the effective performance of the joined boom
sections, since each boom design and the environmental conditions of each incident govern the overall performance.
3.2 Historically, different types of end connectors have been produced. This practice addresses the operational need to connect
different types, during spill incidents. (Warning—Use of this practice with similar or different sizes of boom may cause the
This practice is under the jurisdiction of ASTM Committee F20 on Hazardous Substances and Oil Spill Response and is the direct responsibility of Subcommittee F20.11
on Control.
Current edition approved April 1, 2007April 1, 2018. Published April 2012May 2018. Originally approved in 1996. Last previous edition approved in 20072012 as
ɛ1
F1657 – 96 (2007).(2012) . DOI: 10.1520/F1657_F1657M-96R12E01.10.1520/F1657_F1657M-96R18.
For referenced ASTM standards, visit the ASTM website, www.astm.org, or contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
F1657/F1657M − 96 (2018)
FIG. 1 Side View of a Typical Connector
transmission of unwanted loading such as, tension loading and bending moments on certain boom parts result
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.