Standard Specification for Crosslinked Polyethylene (PEX) Plastic Hot- and Cold-Water Distribution Systems

SCOPE
1.1 This specification covers requirements, test methods, and methods of marking for crosslinked polyethylene plastic hot- and cold-water distribution systems components made in one standard dimension ratio and intended for 100 psi (0.69 MPa) water service up to and including a maximum working temperature of 180°F (82°C). Components are comprised of tubing and fittings. Requirements and test methods are included for materials, workmanship, dimensions and tolerances, burst pressure, sustained pressure, excessive temperature and pressure, temperature cycling tests, and bend strength. Also included are tests related to system malfunctions. The components covered by this specification are intended for use in residential and commercial, hot and cold, potable water distribution systems as well as sealed central heating, including under-floor heating systems.
1.2 The text of this specification references notes, footnotes, and appendixes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the specification.
1.3 The values stated in inch-pound units are to be regarded as the standard. The values stated in parentheses are provided for information only.
Note 1—Suggested hydrostatic design stresses and hydrostatic pressure ratings for tubing and fittings are listed in Appendix X1. Design, assembly, and installation considerations are discussed in Appendix X2. An optional performance qualification and an in-plant quality control program are recommended in Appendix X3.
1.4 The following safety hazards caveat pertains only to the test method portion, Section 7, of this specification: This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

General Information

Status
Historical
Publication Date
09-Oct-2002
Technical Committee
Drafting Committee
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM F877-02a - Standard Specification for Crosslinked Polyethylene (PEX) Plastic Hot- and Cold-Water Distribution Systems
English language
8 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
An American National Standard
Designation: F 877 – 02a
Standard Specification for
Crosslinked Polyethylene (PEX) Plastic Hot- and Cold-Water
1
Distribution Systems
This standard is issued under the fixed designation F 877; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (e) indicates an editorial change since the last revision or reapproval.
1. Scope 2. Referenced Documents
1.1 This specification covers requirements, test methods, 2.1 ASTM Standards:
2
and methods of marking for crosslinked polyethylene plastic D 618 Practice for Conditioning Plastics for Testing
hot- and cold-water distribution systems components made in D 1598 Test Method for Time-to-Failure of Plastic Pipe
3
one standard dimension ratio and intended for 100 psi (0.69 Under Constant Internal Pressure
MPa) water service up to and including a maximum working D 1599 TestMethodforShort-TimeHydraulicFailurePres-
3
temperature of 180°F (82°C). Components are comprised of sure of Plastic Pipe, Tubing, and Fittings
tubing and fittings. Requirements and test methods are in- D 1600 Terminology for Abbreviated Terms Relating to
2
cluded for materials, workmanship, dimensions and tolerances, Plastics
2
burst pressure, sustained pressure, excessive temperature and D 1898 Practice for Sampling of Plastics
3
pressure, temperature cycling tests, and bend strength. Also D 2749 Symbols for Dimensions of Plastic Pipe Fittings
included are tests related to system malfunctions. The compo- D 2837 Test Method for Obtaining Hydrostatic Design
3
nents covered by this specification are intended for use in Basis for Thermoplastic Pipe Materials
3
residential and commercial, hot and cold, potable water distri- D 3140 Practice for Flaring Polyolefin Pipe and Tubing
3
bution systems as well as sealed central heating, including F 412 Terminology Relating to Plastic Piping Systems
under-floor heating systems. F 876 Specification for Crosslinked Polyethylene (PEX)
3
1.2 The text of this specification references notes, footnotes, Tubing
and appendixes which provide explanatory material. These F 1960 Specification for Cold Expansion Fittings with PEX
notesandfootnotes(excludingthoseintablesandfigures)shall Reinforcing Rings for Use with Cross-linked Polyethlene
3
not be considered as requirements of the specification. (PEX) Tubing
1.3 The values stated in inch-pound units are to be regarded F 1961 Specification for Metal Mechanical Cold Flare
as the standard. The values stated in parentheses are provided Compression Fittings with Disc Spring for Cross-linked
3
for information only. Polyethlene (PEX) Tubing
F 1807 Specification for Metal Insert Fittings Utilizing a
NOTE 1—Suggested hydrostatic design stresses and hydrostatic pres-
Copper Crimp Ring for SDR9 Cross-linked Polyethylene
sure ratings for tubing and fittings are listed in Appendix X1. Design,
4
(PEX) Tubing
assembly, and installation considerations are discussed in Appendix X2.
F 1865 Specification for Mechanical Cold Expansion Fit-
An optional performance qualification and an in-plant quality control
program are recommended in Appendix X3.
tings with Compression Sleeve for Cross-linked (PEX)
5
Tubing
1.4 The following safety hazards caveat pertains only to the
2.2 ANSI Standards:
test method portion, Section 7, of this specification: This
6
B 36.10 Welded and Seamless Wrought Steel Pipe
standard does not purport to address all of the safety concerns,
6
Z 17.1 Preferred Numbers
if any, associated with its use. It is the responsibility of the user
2.3 AWWA Standard:
of this standard to establish appropriate safety and health
7
Manual M-11, Steel Pipe Design and Installation
practices and determine the applicability of regulatory limita-
2.4 Federal Standard:
tions prior to use.
2
Annual Book of ASTM Standards, Vol 08.01.
3
Annual Book of ASTM Standards, Vol 08.04.
4
1
Annual Book of ASTM Standards, Vol 10.03.
This specification is under the jurisdiction ofASTM Committee F17 on Plastic
5
Annual Book of ASTM Standards, Vol 04.04.
Piping Systems and is the direct responsibility of Subcommittee F17.61 on Water.
6
Available from American National Standards Institute, 11 West 42nd Street,
Current edition approved Oct. 10, 2002. Published January 2003. Originally
13th Floor, New York, NY 10036.
approved in 1984. Last previous approved 2002 as F 877 – 02.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1

---------------------- Page: 1 ----------------------
F 877 – 02a
8
Fed Std. No. 123 Marking for Shipment (Civil Agencies) primarily defined by two criteria namely, basic short-term
2.5 Military Standard: properties and long-term h
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.