Standard Specification for Vitrified Clay Pipe, Extra Strength, Standard Strength, and Perforated

ABSTRACT
This specification covers extra strength and standard strength vitrified clay pipe and fittings to be used for the conveyance of sewage, industrial wastes, and storm water; and extra strength perforated and standard strength perforated vitrified clay pipe to be used for underdrainage, filter fields, leaching fields, and similar subdrainage installations. Vitrified clay pipe shall be manufactured from fire clay, shale, surface clay, or a combination of these materials that, when formed into pipe and fired to suitable temperatures. Pipe shall meet the bearing strength requirements prescribed. The manufacturer shall at his option, apply either a hydrostatic pressure test or an absorption test to all of the test specimens in each size and run of the pipe. The absorption of vitrified clay pipe shall not exceed 8%. The acid resistance test is used to determine the resistance of pipe to the action of acids encountered in sanitary sewers.
SCOPE
1.1 This specification establishes the criteria for acceptance, prior to installation, of extra strength and standard strength vitrified clay pipe and fittings to be used for the conveyance of sewage, industrial wastes, and storm water; and extra strength perforated and standard strength perforated vitrified clay pipe to be used for underdrainage, filter fields, leaching fields, and similar subdrainage installations.  
1.2 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
Note 1: Attention is called to Specification C425, Test Method C828, Test Method C1091, Test Methods C301, and Terminology C896.  
1.3 The following precautionary caveat pertains only to the Test Method portion, 5.2 – 5.2.3.2 of this standard: This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.  
1.4 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

General Information

Status
Published
Publication Date
31-Aug-2022
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM C700-18(2022) - Standard Specification for Vitrified Clay Pipe, Extra Strength, Standard Strength, and Perforated
English language
4 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the
Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
Designation: C700 −18 (Reapproved 2022)
Standard Specification for
Vitrified Clay Pipe, Extra Strength, Standard Strength, and
Perforated
This standard is issued under the fixed designation C700; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the U.S. Department of Defense.
1. Scope C425 Specification for Compression Joints forVitrified Clay
Pipe and Fittings
1.1 This specification establishes the criteria for acceptance,
C828 Test Method for Low-Pressure Air Test of Vitrified
prior to installation, of extra strength and standard strength
Clay Pipe Lines
vitrified clay pipe and fittings to be used for the conveyance of
C896 Terminology Relating to Clay Products
sewage, industrial wastes, and storm water; and extra strength
C1091 Test Method for Hydrostatic Infiltration Testing of
perforated and standard strength perforated vitrified clay pipe
Vitrified Clay Pipe Lines
to be used for underdrainage, filter fields, leaching fields, and
similar subdrainage installations.
3. Terminology
1.2 The values stated in inch-pound units are to be regarded
3.1 Definitions—Clay, fire clay, shale, and surface clay are
as standard. The values given in parentheses are mathematical
as defined in Terminology C896.
conversions to SI units that are provided for information only
and are not considered standard.
4. Materials and Manufacture
NOTE 1—Attention is called to Specification C425, Test Method C828, 4.1 Vitrified clay pipe shall be manufactured from fire clay,
Test Method C1091, Test Methods C301, and Terminology C896.
shale, surface clay, or a combination of these materials that,
1.3 The following precautionary caveat pertains only to the when formed into pipe and fired to suitable temperatures,
Test Method portion, 5.2 – 5.2.3.2 of this standard: This
yields a product that conforms to this specification.
standard does not purport to address all of the safety concerns,
5. Physical Properties
if any, associated with its use. It is the responsibility of the user
of this standard to establish appropriate safety, health, and
5.1 Bearing Strength:
environmental practices and determine the applicability of
5.1.1 Pipe shall meet the bearing strength requirements of
regulatory limitations prior to use.
Table 1.
1.4 This international standard was developed in accor-
5.1.2 The number of specimens to be tested shall not exceed
dance with internationally recognized principles on standard-
0.5 % of the number of pipe of each size furnished, except that
ization established in the Decision on Principles for the
no less than two specimens shall be tested.
Development of International Standards, Guides and Recom-
5.1.3 If any of the test specimens fail to meet the
mendations issued by the World Trade Organization Technical
requirements, the manufacturer will be allowed a retest on two
Barriers to Trade (TBT) Committee.
additional specimens for each one that failed. The pipe will be
acceptable if all the retest specimens meet the test requirement.
2. Referenced Documents
5.1.4 If, subsequent to an initial pipe strength failure, the
2.1 ASTM Standards:
accuracy of the testing equipment is questioned, at the request
C301 Test Methods for Vitrified Clay Pipe
of the manufacturer, the equipment shall be recalibrated and a
retest made or a retest made upon equipment of known
accuracy.
This specification is under the jurisdiction of ASTM Committee C04 on
Vitrified Clay Pipe and is the direct responsibility of Subcommittee C04.20 on
5.2 Hydrostatic Pressure Test or Absorption Test:
Methods of Test and Specifications.
5.2.1 The manufacturer shall at his option, apply either a
Current edition approved Sept. 1, 2022. Published September 2022. Originally
hydrostatic pressure test or an absorption test to all of the test
approved in 1971. Last previous edition approved in 2018 as C700 – 18. DOI:
10.1520/C0700-18R22.
specimens in each size and run of the pipe.
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
5.2.2 Hydrostatic Pressure Test:
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
5.2.2.1 When the pipe is subjected to an internal hydrostatic
Standards volume information, refer to the standard’s Document Summary page on
the ASTM website. pressure of 10 psi (68.9 KPa) for the elapsed time shown in the
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
C700 − 18 (2022)
TABLE 1 Minimum Strength (3-Edge Bearing)
Perforated Vitrified Clay Pipe
Extra Strength Standard Strength
Nominal
Vitrified Clay Pipe Vitrified Clay Pipe
Extra Strength Standard Strength
Size, in.
lbf/linear kN/linear lbf/linear kN/linear lbf/linear kN/linear lbf/linear kN/linear
(mm)
ft m ft m ft m ft m
3 (76) 2000 29 . . . . . .
4 (100) 2000 29 1200 18 1250 18 1000 15
5 (125) 2000 29 1200 18 1250 18 1000 15
6 (150) 2000 29 1200 18 1600 23 1000 15
8 (205) 2200 32 1400 20 1600 23 1000 15
10 (255) 2400 35 1600 23 1600 23 1100 16
12 (305) 2600 38 1800 26 1800 26 1200 18
15 (380) 2900 42 2000 29 2200 32 1400 20
18 (455) 3300 48 2200 32 2640 39 1700 25
21 (535) 3850 56 2400 35 3100 45 2000 29
24 (610) 4400 64 2600 38 3520 51 2400 35
27 (685) 4700 69 . . . . . .
30 (760) 5000 73 . . . . . .
33 (840) 5500 80 . . . . . .
36 (915) 6000 88 . . . . . .
39 (990) 6600 96 . . . . . .
42 (1065) 7000 102 . . . . . .
48 (1220) 8000 117 . . . . . .
following table, there shall be no leaking on the exterior of the 6. Allowable Limits for Dimensional Variation
pipe. Moisture appearing on the surface of the pipe in the form
6.1 Sizes and dimensions of pipe are as described in Table
of beads adhering to the surface shall not be considered
2.
leakage. However, moisture which starts to run on the pipe
6.2 The inside diameter shall not vary from a true circle by
shall be construed as leakage regardless of quantity.
more than 3 % of its nominal diameter measured at any one
Hydrostatic Pressure Test Time
location along the pipe barrel.
Thickness of Barrel
Test Time (min.)
in. (mm)
6.3 The average inside diameter shall be determined by
Up to and including 1 (25) 7
taking any two 90° (1.6-rad) opposing measurements and
Over 1 (25) including 1 ⁄2 (38) 9
Over 1 ⁄2 (38) including 2 (51) 12
averaging the readings.
Over 2 (51) including 2 ⁄2 (64) 15
Over 2 ⁄2 (64) including 3 (76) 18
7. Straightness
Over 3 (76) 21
7.1 Pipe shall not deviate from straight by more than ⁄16
5.2.2.2 If any of the test specimens fail to meet the Hydro-
in./ft (5 mm/m) of length when the maximum offset is
static Pressure Test requirements, a retest will be allowed and
measured from the concave side of the pipe.
the pipe accepted as provided in 5.1.3.
5.2.3 Absorption Test:
7.2 Measurementshallbetakenbyplacingastraightedgeon
the concave side of the full length of the pipe barrel, excluding
5.2.3.1 The absorption of vitrified clay pipe shall not exceed
8%. the spigot joint material or socket, and measuring the maxi-
mumdistancebetweenthestraightedgeandconcavesideofthe
5.2.3.2 If any of the test specimens fail to meet the absorp-
pipe.
tion requirements, a retest will be allowed and the pipe
accepted as provided in 5.1.3.
8. Blisters
5.3 Acid Resistance:
8.1 Pipe of nominal sizes from 3 in. (76 mm) to 18 in. (455
5.3.1 This test is used to determine the resistance of pipe to
mm),shallhavenoblisterwithadimensionexceeding3in.(76
the action of acids encountered in sanitary sewers. Test results
mm), and no blister or pimple shall project more than ⁄8 in.
shall be provided when requested.
(3.2 mm) above the surface of the pipe.
5.3.2 Test specimens shall be representative of the material
8.2 Pipe of nominal sizes over 18 in. (455 mm), shall have
of the pipe supplied.
no blister exceeding 2 in./ft (165 mm/m) of internal diameter,
5.3.3 The loss of material from the test specimen shall not
and no blister or pimple shall project above the surface of the
exceed 0.25%.
pipe more than ⁄8 in./ft (10 mm/m) of internal diameter.
5.
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.