Standard Specification for Chlorinated Poly(Vinyl Chloride) (CPVC) Plastic Hot- and Cold-Water Distribution Systems

ABSTRACT
This specification covers requirements, test methods, and methods of marking for chlorinated poly(vinyl chloride) plastic hot- and cold-water distribution system components made in one standard dimension ratio and intended for water service up to a certain temperature. These components comprise pipe and tubing, socket-type fittings, street fittings, plastic-to-metal transition fittings, solvent cements, and adhesives. The components are intended for use in residential and commercial, hot and cold, potable water distribution systems. The products covered by this specification are intended for use with the distribution of pressurized liquids only, which are chemically compatible with the piping materials. CPVC 4120 pipe, tubing, and fittings shall be classified by a single standard dimension ratio which shall be SDR 11, by a certain maximum continuous use temperature and by a certain diameter range for nominal pipe or tubing. CPVC plastic-to-metal transition fittings intended for use up a certain temperature are classified on the basis of resistance to failure by thermocycling. The chlorinated poly(vinyl chloride) plastics are categorized by two criteria: basic short-term properties and long-term hydrostatic strength. These short-term properties include mechanical strength, heat resistance, flammability, and chemical resistance which shall be determined after performing different tests. A test shall also be conducted in order to determine the long-term hydrostatic strength of CPVC 41 pipe, tubing, and fittings.
SCOPE
1.1 This specification covers requirements, test methods, and methods of marking for chlorinated poly(vinyl chloride) plastic hot- and cold-water distribution system components made in one standard dimension ratio and intended for water service up to and including 180F (82C). These components comprise pipe and tubing, socket-type fittings, street fittings, plastic-to-metal transition fittings, solvent cements, and adhesives. Requirements and methods of test are included for materials, workmanship, dimensions and tolerances, hydrostatic sustained pressure strength, and thermocycling resistance. The components covered by this specification are intended for use in residential and commercial, hot and cold, potable water distribution systems.
1.2 The products covered by this specification are intended for use with the distribution of pressurized liquids only, which are chemically compatible with the piping materials. Due to inherent hazards associated with testing components and systems with compressed air or other compressed gases some manufacturers do not allow pneumatic testing of their products. Consult with specific product/component manufacturers for their specific testing procedures prior to pneumatic testing.Note 1
Pressurized (compressed) air or other compressed gases contain large amounts of stored energy which present serious saftey hazards should a system fail for any reason.
1.3 The text of this specification references notes, footnotes, and appendixes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the specification.
1.4 The values stated in either inch-pound or SI units are to be regarded separately as standard. Within the text, SI units are shown in brackets. The values stated in each system are not exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in nonconformance with the specification. Suggested hydrostatic design stresses and hydrostatic pressure ratings for pipe, tubing, and fittings are listed in . Design, assembly, and installation considerations are discussed in . An optional performance qualification and an in-plant quality control program are recommended in .
1.5 The following safety hazards caveat pertains only to the test method portion, Sections and , of this specification: This stan...

General Information

Status
Historical
Publication Date
14-Mar-2006
Technical Committee
Drafting Committee
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM D2846/D2846M-06 - Standard Specification for Chlorinated Poly(Vinyl Chloride) (CPVC) Plastic Hot- and Cold-Water Distribution Systems
English language
11 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
An American National Standard
Designation: D 2846/D 2846M – 06
Standard Specification for
Chlorinated Poly(Vinyl Chloride) (CPVC) Plastic Hot- and
1
Cold-Water Distribution Systems
This standard is issued under the fixed designation D 2846/D 2846M; the number immediately following the designation indicates the
year of original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last
reapproval. A superscript epsilon (e) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the Department of Defense.
sure ratings for pipe, tubing, and fittings are listed in Appendix X1.
1. Scope
Design, assembly, and installation considerations are discussed inAppen-
1.1 This specification covers requirements, test methods,
dix X2. An optional performance qualification and an in-plant quality
and methods of marking for chlorinated poly(vinyl chloride)
control program are recommended in Appendix X3.
plastic hot- and cold-water distribution system components
1.5 The following safety hazards caveat pertains only to the
made in one standard dimension ratio and intended for water
test method portion, Sections 9 and 10, of this specification:
service up to and including 180°F (82°C). These components
This standard does not purport to address all of the safety
comprise pipe and tubing, socket-type fittings, street fittings,
concerns, if any, associated with its use. It is the responsibility
plastic-to-metal transition fittings, solvent cements, and adhe-
of the user of this standard to establish appropriate safety and
sives. Requirements and methods of test are included for
health practices and determine the applicability of regulatory
materials, workmanship, dimensions and tolerances, hydro-
limitations prior to use.
static sustained pressure strength, and thermocycling resis-
tance. The components covered by this specification are
2. Referenced Documents
intended for use in residential and commercial, hot and cold,
2
2.1 ASTM Standards:
potable water distribution systems.
D1598 Test Method for Time-to-Failure of Plastic Pipe
1.2 The products covered by this specification are intended
Under Constant Internal Pressure
for use with the distribution of pressurized liquids only, which
D1599 Test Method for Resistance to Short-Time Hydrau-
are chemically compatible with the piping materials. Due to
lic Pressure of Plastic Pipe, Tubing, and Fittings
inherent hazards associated with testing components and sys-
D1784 Specification for Rigid Poly(Vinyl Chloride) (PVC)
tems with compressed air or other compressed gases some
Compounds and Chlorinated Poly(Vinyl Chloride)
manufacturersdonotallowpneumatictestingoftheirproducts.
(CPVC) Compounds
Consult with specific product/component manufacturers for
3
D1898 Practice for Sampling of Plastics
their specific testing procedures prior to pneumatic testing.
D2122 Test Method for Determining Dimensions of Ther-
NOTE 1—Pressurized (compressed) air or other compressed gases
moplastic Pipe and Fittings
contain large amounts of stored energy which present serious saftey
D2444 Test Method for Determination of the Impact Re-
hazards should a system fail for any reason.
sistance of Thermoplastic Pipe and Fittings by Means of a
1.3 Thetextofthisspecificationreferencesnotes,footnotes,
Tup (Falling Weight)
and appendixes which provide explanatory material. These D2837 Test Method for Obtaining Hydrostatic Design
notesandfootnotes(excludingthoseintablesandfigures)shall
BasisforThermoplasticPipeMaterialsorPressureDesign
not be considered as requirements of the specification. Basis for Thermoplastic Pipe Products
1.4 The values stated in either inch-pound or SI units are to
F402 Practice for Safe Handling of Solvent Cements,
beregardedseparatelyasstandard.Withinthetext,SIunitsare Primers,andCleanersUsedforJoiningThermoplasticPipe
shown in brackets. The values stated in each system are not
and Fittings
exact equivalents; therefore, each system shall be used inde- F412 Terminology Relating to Plastic Piping Systems
pendentlyoftheother.Combiningvaluesfromthetwosystems
F493 Specification for Solvent Cements for Chlorinated
may result in nonconformance with the specification. Poly(Vinyl Chloride) (CPVC) Plastic Pipe and Fittings
NOTE 2—Suggested hydrostatic design stresses and hydrostatic pres-
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
1
This specification is under the jurisdiction ofASTM Committee F17 on Plastic contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
Piping Systems and is the direct responsibility of Subcommittee F17.61 on Water. Standards volume information, refer to the standard’s Document Summary page on
Current edition approved March 15, 2006. Published March 2006. Originally t
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.