ASTM E1680-16(2022)
(Test Method)Standard Test Method for Rate of Air Leakage through Exterior Metal Roof Panel Systems
Standard Test Method for Rate of Air Leakage through Exterior Metal Roof Panel Systems
SIGNIFICANCE AND USE
5.1 This test method is a standard procedure for determining air leakage characteristics under specified air pressure differences.
Note 1: The air pressure differences acting across a building envelope vary greatly. The slope of the roof and other factors affecting air pressure differences and the implications of the resulting air leakage relative to the environment within buildings are discussed in the literature.4,5,6 These factors shall be considered fully when specifying the test pressure difference to be used.
Note 2: When applying the results of tests by this test method, note that the performance of a roof or its components, or both, may be a function of proper installation and adjustment. The performance in service will also depend on the rigidity of supporting construction, the presence of interior treatments, the roof slope, and the resistance of components to deterioration by various causes: corrosive atmospheres, aging, ice, vibration, thermal expansion, and contraction, etc. It is difficult to simulate the identical complex environmental conditions that can be encountered in service, including rapidly changing pressures due to wind gusting. Some designs are more sensitive than others to these environmental conditions.
5.2 Rates of air leakage are sometimes used for comparison purposes. The comparisons are not always valid unless the components being tested and compared are of essentially the same size, configuration, and design.
Note 3: The specimen construction discussed in 1.2 and required in 8.1 isolates a source of leakage. The rate of air leakage measured during the test method has units of cubic feet per minute per square foot (litres per second per square metre). Openings and details such as end laps or roof curbs are excluded since leakage is measured more appropriately in cubic feet per minute per foot (litres per second per metre) at these conditions. The test specimen area is relatively small; the inclusion of details will give unrea...
SCOPE
1.1 This test method covers the determination of the resistance of exterior metal roof panel systems to air infiltration resulting from either positive or negative air pressure differences. The test method described is for tests with constant temperature and humidity across the specimen. This test method is a specialized adaption of Test Method E283.
1.2 This test method is applicable to any roof area. This test method is intended to measure only the air leakage associated with the field of the roof, including the panel side laps and structural connections; it does not include leakage at the openings or perimeter or any other details.
1.3 The proper use of this test method requires knowledge of the principles of air flow and pressure measurements.
1.4 The text of this test method references notes and footnotes excluding tables and figures, which provide explanatory material. These notes and footnotes shall not be considered to be requirements of the test method.
1.5 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. For specific precautionary statements, see Section 7.
1.7 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
General Information
Relations
Standards Content (Sample)
This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the
Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
Designation: E1680 − 16 (Reapproved 2022)
Standard Test Method for
Rate of Air Leakage through Exterior Metal Roof Panel
Systems
This standard is issued under the fixed designation E1680; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision.Anumber in parentheses indicates the year of last reapproval.A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope 2. Referenced Documents
1.1 This test method covers the determination of the resis- 2.1 ASTM Standards:
tance of exterior metal roof panel systems to air infiltration E177Practice for Use of the Terms Precision and Bias in
resulting from either positive or negative air pressure differ- ASTM Test Methods
ences. The test method described is for tests with constant E283Test Method for Determining Rate of Air Leakage
temperature and humidity across the specimen. This test Through ExteriorWindows, Skylights, CurtainWalls, and
method is a specialized adaption of Test Method E283. Doors Under Specified Pressure Differences Across the
Specimen
1.2 This test method is applicable to any roof area.This test
E631Terminology of Building Constructions
method is intended to measure only the air leakage associated
E691Practice for Conducting an Interlaboratory Study to
with the field of the roof, including the panel side laps and
Determine the Precision of a Test Method
structural connections; it does not include leakage at the
E1592Test Method for Structural Performance of Sheet
openings or perimeter or any other details.
Metal Roof and Siding Systems by Uniform Static Air
1.3 The proper use of this test method requires knowledge
Pressure Difference
of the principles of air flow and pressure measurements.
E1646Test Method for Water Penetration of Exterior Metal
Roof Panel Systems by Uniform Static Air Pressure
1.4 The text of this test method references notes and
footnotes excluding tables and figures, which provide explana- Difference
tory material. These notes and footnotes shall not be consid-
2.2 Other Standard:
ered to be requirements of the test method.
AAMA 501Methods of Test for Metal Curtain Walls
1.5 The values stated in inch-pound units are to be regarded
3. Terminology
as standard. The values given in parentheses are mathematical
conversions to SI units that are provided for information only 3.1 Definitions—For definitions of general terms relating to
buildingconstructionusedinthistestmethod,seeTerminology
and are not considered standard.
E631.
1.6 This standard does not purport to address all of the
3.2 Definitions of Terms Specific to This Standard:
safety concerns, if any, associated with its use. It is the
3.2.1 air leakage (Q)—the volume of air flowing per unit of
responsibility of the user of this standard to establish appro-
time through the assembled specimen under a test pressure
priate safety, health, and environmental practices and deter-
difference,expressedincubicfeetperminute(cubicmetresper
mine the applicability of regulatory limitations prior to use.
second).
For specific precautionary statements, see Section 7.
1.7 This international standard was developed in accor- 3.2.2 extraneous air leakage (Q )—the difference between
L
the metered air flow (Q ) and air leakage (Q); the leakage of
dance with internationally recognized principles on standard-
m
ization established in the Decision on Principles for the the remainder of the test chamber.
Development of International Standards, Guides and Recom-
3.2.3 metered air flow (Q )—the volume of air flowing per
m
mendations issued by the World Trade Organization Technical
unitoftimethroughtheairflowmeteringsystem,expressedin
Barriers to Trade (TBT) Committee.
cubic feet per minute (cubic metres per second).
1 2
This test method is under the jurisdiction of ASTM Committee E06 on For referenced ASTM standards, visit the ASTM website, www.astm.org, or
Performance of Buildings and is the direct responsibility of Subcommittee E06.57 contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
on Performance of Metal Roof Systems. Standards volume information, refer to the standard’s Document Summary page on
Current edition approved May 1, 2022. Published May 2022. Originally the ASTM website.
approved in 1995. Last previous edition approved in 2016 as E1680–16. DOI: Available from Fenestration & Glazing IndustryAlliance (FGIA), 1900 E Golf
10.1520/E1680-16R22. Rd, Suite 1250, Schaumburg, IL 60173, https://www.fgiaonline.org/.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
E1680 − 16 (2022)
feet per minute per foot (litres per second per metre) at these conditions.
3.2.4 rate of air leakage—the air leakage per unit of
Thetestspecimenareaisrelativelysmall;theinclusionofdetailswillgive
specimen area (A), expressed in cubic feet per minute per
unrealistic import to the detail’s presence when compared to actual roof
square foot (cubic metres per second per square metre).
constructions. This test method shall not be relied on singularly to form
conclusionsaboutoverallairleakagethroughmetalroofs.Aroofcontains
3.2.5 reference standard conditions—dryairatapressureof
many details.Although prescribed modifications are outside the scope of
29.92in.Hg(101.3kPa),temperatureof69.4°F(20.8°C),and
3 3 this test method, an experienced testing engineer is able to use the
air density of 0.075 lb/ft (1.2 kg/m ).
principles presented in the test method and to generate significant data by
3.2.6 specimen—the entire assembled unit submitted for isolating specific details and measuring leakage.
Additional leakage sources are introduced if details are included. If
testing as described in Section 8.
total leakage is then measured, the results will generally be conservative
3.2.7 specimen area (A)—theareadeterminedbytheoverall
relative to tests without details. To minimize the number of tests, the
dimensions of the test specimen expressed in square feet specifier may allow details such as end laps when qualitative or general
quantitative results are desired and the isolation of sources is not required
(square metres). The dimensions used to determine area shall
for performance. Only one panel end lap shall be allowed. The user shall
not include exterior framework.
be aware of the bias when comparing alternate systems if end laps are
3.2.8 test pressure difference—the specified difference in
included.
NOTE 4—This is a test procedure. It is the responsibility of the
static air pressure across the fixed specimen, expressed in
specifying agency to determine the specimen construction, size, and test
pounds-force per square foot (pascals).
pressures after considering the test methods’ guidelines. Practical consid-
erations suggest that every combination of panel thickness, span, and
4. Summary of Test Method
design load need not be tested in order to substantiate product perfor-
4.1 The test procedure consists of sealing and fixing a test mance.
specimen into or against one face of an air chamber, supplying
6. Apparatus
airtoorexhaustingairfromthechamberattheraterequiredto
6.1 This description of the apparatus is general in nature,
maintain the specified test pressure difference across the
and any arrangement of equipment capable of performing the
specimen, and measuring the resultant air flow through the
test procedure within the allowable tolerances is permitted.
specimen.
6.2 Major Components (see Fig. 1).
5. Significance and Use
6.2.1 Test Chamber—A well-sealed chamber or box with
5.1 Thistestmethodisastandardprocedurefordetermining either an opening, a removable mounting panel, or one open
air leakage characteristics under specified air pressure differ-
face in which or against which the specimen is installed and
ences. sealed. The specimen shall be installed horizontally. At least
one static pressure tap shall be provided to measure the
NOTE 1—The air pressure differences acting across a building envelope
chamber pressure.All pressure taps shall be located so that the
vary greatly. The slope of the roof and other factors affecting air pressure
differences and the implications of the resulting air leakage relative to the reading is unaffected by the air supply either to or from the
4,5,6
environment within buildings are discussed in the literature. These
chamber. The air supply opening into the chamber shall be
factors shall be considered fully when specifying the test pressure
arranged so that air does not impinge directly on the test
difference to be used.
specimen with any significant velocity. When required, a
NOTE 2—When applying the results of tests by this test method, note
meansofaccessshallbeprovidedintothechambertofacilitate
that the performance of a roof or its components, or both, may be a
functionofproperinstallationandadjustment.Theperformanceinservice adjustments and observations after the specimen has been
willalsodependontherigidityofsupportingconstruction,thepresenceof
installed.
interior treatments, the roof slope, and the resistance of components to
6.2.2 Air System—A controllable blower, compressed air
deterioration by various causes: corrosive atmospheres, aging, ice,
supply, exhaust system, or reversible blower designed to
vibration,thermalexpansion,andcontraction,etc.Itisdifficulttosimulate
provide the required air flow at the specified test pressure
theidenticalcomplexenvironmentalconditionsthatcanbeencounteredin
service, including rapidly changing pressures due to wind gusting. Some
difference. the system shall provide constant air flow at a fixed
designs are more sensitive than others to these environmental conditions.
pressure for the period required to obtain readings of air flow
5.2 Rates of air leakage are sometimes used for comparison and pressure difference, and it shall be capable of maintaining
purposes. The comparisons are not always valid unless the positive and negative pressures.
components being tested and compared are of essentially the 6.2.3 Pressure Measuring Apparatus—Adeviceformeasur-
same size, configuration, and design. ing the test pressure difference within a tolerance of 62%,or
60.01 in. (62.5Pa), of water column, whichever is greater.
NOTE 3—The specimen construction discussed in 1.2 and required in
The device must measure positive and negative pressures.
8.1 isolates a source of leakage. The rate of air leakage measured during
6.2.4 Air-Flow Metering System—A device to measure the
thetestmethodhasunitsofcubicfeetperminutepersquarefoot(litresper
second per square metre). Openings and details such as end laps or roof
air flow within the limitations of error prescribed in 6.3. (The
5,6
curbs are excluded since leakage is measured more appropriately in cubic
publications listed in Footnotes 5 and 6 present background
information on fluid metering practices.)
ASHRAE Handbook of Fundamentals, American Society of Heating,
6.3 The air flow through the test specimen shall be deter-
Refrigeration, and Air-Conditioning Engineers, Inc., 1972, Chapter 25.
mined with an error not greater than 6 5% when this flow
Fluid Meters—Their Theory and Application, 5th edition, 1959.
6 equals or exceeds 2 ft /min (0.94 L/s) or 6 10% when the air
Chapter 4, “Flow Measurements,” ASME—Power Test Code, 2nd edition, Part
3 3
5, 1956. flow is below 2 ft /min but more than ⁄2 ft /min (0.24 L/s).
E1680 − 16 (2022)
FIG. 1 General Arrangement of Air Leakage Apparatus
NOTE 5—A greater percentage of error will usually be acceptable at
than the width of three typical units plus the side rail
lower flows. Special flow-measuring techniques are necessary if higher
supporting elements at each edge. The specimen shall contain
precision is required. The accuracy of the specimen leakage flow
at least three assembled side lap seams; this allows partial
measurement is affected by the accuracy of the flowmeter and amount of
width units. The specimen width shall be sufficient to provide
extraneousleakageoftheapparatus(seeAnnexA1ofTestMethodE283).
loading on at least one typical unit (see Fig. 1). When partial
7. Safety Precautions
width units are used at the specimen sides, the maximum
portiontobeusedincalculatingthespecimenareashallbeone
7.1 Glass breakage and specimen failure will not normally
half of the unit. The specimen shall be of sufficient length to
occur at the small pressure differences applied in this test
develop a multispan condition unless the panel is used only in
procedure. Larger or excessive pressure differences occur
single-span applications. If two spans are used, they shall be
duringpreload,duetoerrorinoperation,orwhentheapparatus
unequal, with the shorter being 75% of the longer. Building
is used for other purposes such as structural testing; therefore
perimeter details need not and interior details, other than
exercise adequate precautions to protect personnel.
typical side seams, shall not be inlcuded (see Note 3 for
8. Test Specimen
commentary and exceptions).The specimen perimeter shall be
well sealed.
8.1 The roof specimen shall be of sufficient size to deter-
mine the performance of all typical parts of the roof system.
NOTE 6—The unbalanced span criterion more closely simulates multi-
For roofs constructed with prefabricated or preformed units or
span panel deflection curvature. This works the panel sidelap while
panels, the specimen width shall be equivalent to or greater minimizing the specimen length.
E1680 − 16 (2022)
8.1.1 All parts of the roof test specimen shall be full size, 9.5 Performance of the flow measurements shall be made
using the same materials, details, and methods of construction under normal operation conditions for the laboratory being
and anchorage as those on actual buildings. calibrated. Provision must be made to account for extraneous
chamber leakage so as not to compromise the integrity of the
8.1.2 The condition of structural support shall be simulated
calibration procedure.
as accurately as possible. If the roof accommodates thermal
expansion parallel to the panel length, this detail must be
9.6 Flow readings shall be measured at each of the three
included in the test specimen, and the interior support must be
pressure differentials given in 9.2. Reverse the calibration
able to slide parallel to the panel or its attachment, or both.
orifice plate if required, reseal the plate, and measure the flow
readings at the negative value of each of the three pressure
8.2 If insulation is an optional component of
...
Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.