Standard Specification for Flexible, Low Permeance Vapor Retarders for Thermal Insulation

SCOPE
1.1 This specification covers vapor retarders for thermal insulation, specifically, flexible materials with permeance of 0.10 perm or lower and surface burning characteristics of 25 flame spread/50 smoke or lower. These materials are intended for use at surface temperatures of -20 to 150°F (-29 to 66°C). It does not cover mastics or barrier coatings applied in liquid form, nor materials intended for use as weather barriers.
1.2 This specification provides physical requirements for vapor retarders. Practice C 755 should provide assistance in solving problems related to moisture vapor transmission through thermal insulation materials.
1.3 The values stated in inch-pound units are to be regarded as standard. The SI units given in parentheses are for information only.
1.4 The following precautionary caveat pertains to the test methods portion only, Section 10, of this specification: This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

General Information

Status
Historical
Publication Date
09-May-2003
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM C1136-03 - Standard Specification for Flexible, Low Permeance Vapor Retarders for Thermal Insulation
English language
4 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superceded and replaced by a new version or discontinued.
Contact ASTM International (www.astm.org) for the latest information.
Designation: C 1136 – 03
Standard Specification for
Flexible, Low Permeance Vapor Retarders for Thermal
1
Insulation
This standard is issued under the fixed designation C 1136; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (e) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the Department of Defense.
1. Scope D 828 Test Method for Tensile Properties of Paper and
Paperboard Using Constant-Rate-of-Elongation Appara-
1.1 This specification covers vapor retarders for thermal
3
tus
insulation, specifically, flexible materials with permeance of
D 882 Test Methods for Tensile Properties of Thin Plastic
0.10 perm or lower and surface burning characteristics of 25
4
Sheeting
flame spread/50 smoke or lower. These materials are intended
D 1204 Test Method for Linear Dimensional Changes of
for use at surface temperatures of −20 to 150°F (−29 to 66°C).
Nonrigid Thermoplastic Sheeting or Film at Elevated
It does not cover mastics or barrier coatings applied in liquid
5
Temperature
form, nor materials intended for use as weather barriers.
E 84 Test Method for Surface Burning Characteristics of
1.2 This specification provides physical requirements for
6
Building Materials
vapor retarders. Practice C 755 should provide assistance in
E 96 Test Methods for Water Vapor Transmission of Mate-
solving problems related to moisture vapor transmission
2
rials
through thermal insulation materials.
2.2 TAPPI Standards:
1.3 The values stated in inch-pound units are to be regarded
T461 Flame Resistance of Treated Paper and Paperboard
as standard. The SI units given in parentheses are for informa-
T803 Puncture Test of Containerboard
tion only.
1.4 The following precautionary caveat pertains to the test
3. Terminology
methods portion only, Section 10, of this specification: This
3.1 Definitions—Definitions in Terminology C 168 apply to
standard does not purport to address all of the safety concerns,
terms used in this specification.
if any, associated with its use. It is the responsibility of the user
of this standard to establish appropriate safety and health
4. Classification
practices and determine the applicability of regulatory limita-
4.1 Classification of vapor retarders is based on vapor
tions prior to use.
retardance and strength properties, as listed in Table 1.
2. Referenced Documents
5. Materials and Manufacture
2.1 ASTM Standards:
2 5.1 Vapor retarders may be constructed of any number of
C 168 Terminology Relating to Thermal Insulation
various films, foils, cloths, papers, and reinforcements, alone or
C 755 Practice for Selection of Vapor Retarders for Thermal
2 in combination, to achieve required performance.
Insulation
C 1258 Test Method for Elevated Temperature and Humid-
6. Physical Properties
2
ity Resistance of Vapor Retarders for Insulation
6.1 Maximum permeance for a specific type vapor retarder
C 1263 Test Method for Thermal Integrity of Flexible Water
shall be as shown in Table 1 when tested in accordance with
2
Vapor Retarders
10.1.
C 1338 Test Method for Determining Fungi Resistance of
6.2 All vapor retarders shall demonstrate a flame spread of
2
Insulation Materials and Facings
25 or less and smoke developed of 50 or less when testing the
1
This specification is under the jurisdiction of ASTM Committee C16 on
Thermal Insulation and is the direct responsibility of Subcommittee C16.33 on
3
Insulation Finishes and Moisture. Annual Book of ASTM Standards, Vol 15.09.
4
Current edition approved May 10, 2003. Published June 2003. Originally Annual Book of ASTM Standards, Vol 08.01.
5
approved in 1990. Last previous edition approved 2002 as C 1136 – 02. Annual Book of ASTM Standards, Vol 08.03.
2 6
Annual Book of ASTM Standards, Vol 04.06. Annual Book of ASTM Standards, Vol 04.07.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1

---------------------- Page: 1 ----------------------
NOTICE: This standard has either been superceded and replaced by a new version or discontinued.
Contact ASTM International (www.astm.org) for the latest information.
C1136–03
TABLE 1 Physical Property Requirements
Type
Physical Properties
I II III IV V VI
Permeance, max, Perms 0.02 (1.15) 0.02 (1.15) 0.10 (5.75) 0.10 (5.75) 0.20 (1.15) 0.03 (1.72)
−1 −1 −2
(Ng·Pa s m )
Puncture Resistance, 50 (58) 25 (29) 50 (58) 25 (29) 175 (87) 25 (29)
min, Beach units (metric
units)
Machine Direction 45 (7.9) 30 (5.3) 45 (7.9) 30 (5.3) 40 (7.0) 20 (3.5)
Tensile, min, lb/in. width
(N/mm width, min)
Cross Direction Tensile, 30 (5.3) 20 (3.5) 30 (5.3) 20 (3.5) 60 (10.6) 30 (5.3)
m
...

Questions, Comments and Discussion