EN 54-23:2010
(Main)Fire detection and fire alarm systems - Part 23: Fire alarm devices - Visual alarm devices
Fire detection and fire alarm systems - Part 23: Fire alarm devices - Visual alarm devices
This European Standard specifies the requirements, test methods and performance criteria for visual alarm devices in a fixed installation intended to signal a visual warning of a fire between the fire detection and fire alarm system and the occupants of a building. It is intended to cover only those devices which derive their operating power by means of a physical electrical connection to an external source such as a fire alarm system.
This European Standard specifies the evaluation of conformity and the marking of the visual alarm devices.
This European Standard applies to visual alarm devices that rely on software for their operation and to those that do not.
This European Standard applies only to pulsing or flashing visual alarm devices, for example xenon beacons or rotating beacons. Devices giving continuous light output are excluded from this European Standard.
This European Standard is not intended to cover visual indicators, for example those on detectors or on the control and indicating equipment.
Brandmeldeanlagen - Teil 23: Feueralarmeinrichtungen - Optische Signalgeber
Diese Europäische Norm legt Anforderungen, Prüfverfahren und Leistungsmerkmale für fest eingebaute optische Signalgeber fest, die zu dem Zweck vorgesehen sind, das von der Brandmeldeanlage veranlasste optische Warnsignal an Personen in einem Gebäude auszusenden (siehe Bestandteil C in Bild 1 der
EN 54-1:1996). Sie gilt nur für die Einrichtungen, die ihre Betriebsenergie durch eine körperliche elektrische Verbindung von einer äußeren Energiequelle beziehen, z. B. von einer Brandmeldeanlage.
Diese Europäische Norm legt Anforderungen an die Bewertung der Konformität und an die Kennzeichnung von optischen Signalgebern fest.
Diese Europäische Norm gilt für softwaregesteuerte und nicht-softwaregesteuerte optische Signalgeber.
Diese Europäische Norm gilt nur für pulsierende oder blinkende optische Signalgeber, zum Beispiel für Xenon-Blitz- oder Rundumleuchten. Sie gilt nicht für Einrichtungen, bei denen die Lichtabstrahlung kontinuierlich erfolgt.
Diese Europäische Norm gilt nicht für optische Anzeigeelemente, zum Beispiel bei Brandmeldern oder bei Brandmelderzentralen.
Systèmes de détection et d'alarme incendie - Partie 23 : Dispositifs d'alarme feu - Dispositifs visuels d'alarme feu
La présente Norme européenne spécifie les exigences, les méthodes d'essai et les critères de performance pour les dispositifs visuels d'alarme feu dans une installation fixe destinés à donner un avertissement visuel de feu entre un système de détection d’incendie et d'alarme feu et les occupants d'un bâtiment (Voir élément C de la Figure 1 de l'EN 54-1:1996). Elle est destinée à couvrir uniquement les dispositifs qui tirent leur puissance de fonctionnement au moyen d'un raccordement électrique physique à une source externe tel qu'un système de détection incendie et d’alarme feu.
La présente Norme européenne spécifie l'évaluation de conformité et le marquage des dispositifs visuels d'alarme feu.
La présente Norme européenne s'applique aux dispositifs visuels d’alarme feu dont le fonctionnement repose sur un logiciel et aux dispositifs pour lesquels ce n'est pas le cas.
La présente Norme européenne s'applique uniquement aux dispositifs visuels d'alarme feu à clignotement ou à impulsions, par exemple flashes au xénon ou gyrophares. Sont exclus de la présente Norme européenne les dispositifs à émission lumineuse continue.
La présente Norme européenne n'est pas destinée à couvrir les indicateurs visuels, par exemple sur les détecteurs ou sur l'équipement de contrôle et de signalisation.
Sistemi za odkrivanje in javljanje požara ter alarmiranje - 23. del: Naprave za alarmiranje - Vizualne alarmne naprave
Ta evropski standard opredeljuje zahteve, preskusne metode in merila za zmogljivost za vizualne alarmne naprave v fiksni namestitvi, namenjeni signaliziranju vizualnega opozorila na ogenj med sistemom za odkrivanje in javljanje požara ter alarmiranje in stanovalci stavbe (glej točko C Slike 1 iz EN 54-1:1996). Namenjen je temu, da zajame le tiste naprave, ki pridobivajo svojo obratovalno moč s pomočjo fizične električne povezave z zunanjim virom, kot je sistem za javljanje požara in alarmiranje. Ta evropski standard opredeljuje vrednotenje skladnosti in označevanje vizualnih alarmnih naprav. Ta evropski standard velja za vizualne alarmne naprave, ki se pri svojem delovanju opirajo na programsko opremo in tudi tiste, ki se ne. Ta evropski standard velja le za utripajoče in svetlikajoče vizualne alarmne naprave, na primer za ksenonske signalne luči ali vrteče se signalne luči. Iz tega evropskega standarda so izvzete naprave, ki dajejo nepretrgano svetlobo. Ta evropski standard ne pokriva vizualnih indikatorjev, na primer indikatorjev na detektorjih ali na nadzorni in indikacijski opremi.
General Information
Standards Content (Sample)
SLOVENSKI STANDARD
01-junij-2010
Sistemi za odkrivanje in javljanje požara ter alarmiranje - 23. del: Naprave za
alarmiranje - Vizualne alarmne naprave
Fire detection and fire alarm systems - Part 23: Fire alarm devices - Visual alarm devices
Brandmeldeanlagen - Teil 23: Feueralarmeinrichtungen - Optische Signalgeber
Systemes d'alarme feu et de détection d'incendie - Partie 23: Dispositifs d'alarme feu -
Alarmes visuelles
Ta slovenski standard je istoveten z: EN 54-23:2010
ICS:
13.220.20 3RåDUQD]DãþLWD Fire protection
13.320 Alarmni in opozorilni sistemi Alarm and warning systems
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
EUROPEAN STANDARD
EN 54-23
NORME EUROPÉENNE
EUROPÄISCHE NORM
March 2010
ICS 13.220.20
English Version
Fire detection and fire alarm systems - Part 23: Fire alarm
devices - Visual alarm devices
Systèmes d'alarme feu et de détection d'incendie - Partie Brandmeldeanlagen - Teil 23: Feueralarmeinrichtungen -
23: Dispositifs d'alarme feu - Alarmes visuelles Optische Signalgeber
This European Standard was approved by CEN on 23 January 2010.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national
standards may be obtained on application to the CEN Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as the
official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland,
Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2010 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 54-23:2010: E
worldwide for CEN national Members.
Contents Page
Foreword .5
Introduction .7
1 Scope .8
2 Normative references .8
3 Terms, definitions and abbreviations .9
3.1 Definitions .9
3.2 Abbreviations . 10
4 Requirements . 10
4.1 General . 10
4.2 Operational reliability . 10
4.2.1 Duration of operation . 10
4.2.2 Provision for external conductors . 10
4.2.3 Flammability of materials . 11
4.2.4 Enclosure protection . 11
4.2.5 Access . 11
4.2.6 Manufacturer's adjustments . 11
4.2.7 On site adjustments of behaviour . 11
4.2.8 Requirements for software controlled devices . 11
4.3 Performance parameters under fire conditions . 13
4.3.1 Coverage volume . 13
4.3.2 Variation of light output . 13
4.3.3 Minimum and maximum effective luminous intensity . 13
4.3.4 Light colour . 13
4.3.5 Light temporal pattern and frequency of flashing . 14
4.3.6 Marking and data . 14
4.3.7 Synchronization (option with requirements) . 15
4.4 Durability . 16
4.4.1 Temperature resistance . 16
4.4.2 Humidity resistance . 16
4.4.3 Shock and vibration resistance . 16
4.4.4 Corrosion resistance − Sulphur dioxide (SO ) corrosion (endurance) . 16
4.4.5 Electrical stability − EMC, immunity (operational) . 17
5 Tests and evaluation methods . 17
5.1 General . 17
5.1.1 Atmospheric conditions for tests . 17
5.1.2 Operating conditions for tests . 17
5.1.3 Mounting arrangements . 17
5.1.4 Tolerances . 18
5.1.5 Provision for tests . 18
5.1.6 Test schedule . 18
5.1.7 Reproducibility . 20
5.2 Operational reliability . 20
5.2.1 Duration of operation . 20
5.2.2 Provision for external conductors . 21
5.2.3 Flammability of materials . 21
5.2.4 Enclosure protection . 21
5.2.5 Access . 22
5.2.6 Manufacturer's adjustments . 23
5.2.7 On site adjustments of behaviour . 23
5.2.8 Requirements for software controlled devices . 23
5.3 Performance parameters under fire conditions . 23
5.3.1 Coverage volume . 23
5.3.2 Variation of luminous intensity . 23
5.3.3 Minimum and maximum light intensity . 24
5.3.4 Light colour . 24
5.3.5 Light pattern and frequency of flashing . 24
5.3.6 Marking and data . 24
5.3.7 Synchronization (option with requirements) . 24
5.4 Durability . 26
5.4.1 Temperature resistance . 26
5.4.2 Humidity resistance . 29
5.4.3 Shock and vibration resistance . 33
5.4.4 Corrosion resistance − Sulphur dioxide (SO ) corrosion (endurance) . 37
5.4.5 Electrical stability − Electromagnetic compatibility (EMC), immunity . 38
6 Evaluation of conformity . 39
6.1 General . 39
6.2 Initial type testing . 40
6.2.1 General . 40
6.2.2 Test samples . 40
6.2.3 Test reports . 40
6.3 Factory production control. 41
6.3.1 General . 41
6.3.2 General requirements . 41
6.3.3 Product specific requirements . 42
6.3.4 Initial inspection of factory and FPC . 43
6.3.5 Surveillance of FPC . 43
6.4 Procedure for modifications. 44
6.5 One-off products, pre-production products (e.g. prototypes) and products produced in
very low quantities . 44
Annex A (normative) Method for measuring the light distribution from a VAD . 46
A.1 General . 46
A.2 Test apparatus . 46
A.3 Instrumentation . 46
A.4 Test room . 46
A.5 Arrangement for measuring the effective luminous intensity . 48
A.6 Calculation of I (av). 52
eff
A.7 Calculation of coverage distance . 52
Annex B (normative) Comparative light output level measurement for VADs . 53
B.1 General . 53
B.2 Light test chamber . 53
B.3 Calibration of the light test chamber . 53
B.4 Mounting arrangements . 54
B.5 Measurement of effective average illumination . 54
Annex C (informative) Construction of the light test chamber and associated equipment for
comparative measurements . 55
C.1 Light test chamber . 55
C.2 Surface finishes . 55
Annex D (informative) Comparison of flammability test requirements in various standards . 57
D.1 Introduction . 57
D.2 Relevant standards . 57
D.3 Vertical burning tests . 57
D.4 Horizontal burning tests . 58
D.4.1 IEC 60695-11-10 and UL 94 . 58
D.4.2 IEC 60695-11-20 and UL 94 . 59
Annex ZA (informative) Clauses of this European Standard addressing the provisions of the EU
Construction Products Directive (89/106/EEC) . 60
ZA.1 Scope and relevant characteristics . 60
ZA.2 Procedures for the attestation of conformity of VADs . 62
ZA.2.1 System of attestation of conformity . 62
ZA.2.2 EC Certificate of conformity . 63
ZA.3 CE marking and labelling . 63
Bibliography . 66
Foreword
This document (EN 54-23:2010) has been prepared by Technical Committee CEN/TC 72 “Fire detection and
fire alarm systems”, the secretariat of which is held by BSI.
This European Standard shall be given the status of a national standard, either by publication of an identical
text or by endorsement, at the latest by September 2010, and conflicting national standards shall be
withdrawn at the latest by March 2013.
Attention is drawn to the possibility that some of the elements of this document may be the subject of patent
rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights.
This document has been prepared under a mandate given to CEN by the European Commission and the
European Free Trade Association, and supports essential requirements of EU Directive(s).
For relationship with EU Directive(s), see informative Annex ZA, which is an integral part of this document.
EN 54, Fire detection and fire alarm systems, consists of the following parts:
Part 1: Introduction
Part 2: Control and indicating equipment
Part 3: Fire alarm devices ― Sounders
Part 4: Power supply equipment
Part 5: Heat detectors ― Point detectors
Part 7: Smoke detectors ― Point detectors using scattered light, transmitted light or ionization
Part 10: Flame detectors ― Point detectors
Part 11: Manual call points
Part 12: Smoke detectors ― Line detectors using an optical light beam
Part 13: Compatibility assessment of system components
Part 14: Guidelines for planning, design, installation, commissioning, use and maintenance (in
preparation)
Part 16: Voice alarm control and indicating equipment
Part 17: Short-circuit isolators
Part 18: Input/output devices
Part 20: Aspirating smoke detectors
Part 21: Alarm transmission and fault warning routing equipment
Part 22: Resettable line-type heat detectors (in preparation)
Part 23: Fire alarm devices ― VADs
Part 24: Components of voice alarm systems ― Loudspeakers
Part 25: Components using radio links
Part 26: Point fire detectors ― Carbon monoxide fire detectors (in preparation)
Part 27: Duct smoke detectors (in preparation)
Part 28: Non-resettable (digital) line-type heat detectors (in preparation)
Part 29: Multi-sensor fire detectors ― Point detectors using a combination of smoke and heat
sensors (in preparation)
Part 30: Multi-sensor fire detectors ― Point detectors using a combination of carbon monoxide and
heat sensors (in preparation)
According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following
countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech
Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain,
Sweden, Switzerland and the United Kingdom.
Introduction
The purpose of a visual fire alarm device (VAD) is to warn person(s) within, or in the vicinity of, a building of
the occurrence of a fire emergency in order to enable such person(s) to take appropriate measures.
This European Standard allows manufacturers to specify VADs in terms of the range at which the required
illumination is met. Three categories of device are defined, one for ceiling mounted devices, one for wall
mounted devices and an open category. The maximum range of the VAD is tested by measuring the light
output in a hemisphere surrounding it to determine its light distribution. As the light output of some VADs can
change over time due, for example, to the effect of self-heating, a test has been introduced to check that the
variation of light output over time is within an acceptable limit.
This European Standard gives common requirements for the construction and robustness of VADs as well as
for their performance under climatic, mechanical and electrical interference conditions which are likely to occur
in the service environment. VADs are classified in one of two application environment types, i.e. Type A and
Type B. More severe climatic conditions are applied to devices that are primarily intended for outdoor
applications (Type B) than those primarily intended for indoor applications (Type A).
1 Scope
This European Standard specifies the requirements, test methods and performance criteria for visual alarm
devices in a fixed installation intended to signal a visual warning of a fire between the fire detection and fire
alarm system and the occupants of a building (see item C of Figure 1 of EN 54-1:1996). It is intended to cover
only those devices which derive their operating power by means of a physical electrical connection to an
external source such as a fire alarm system.
This European Standard specifies the evaluation of conformity and the marking of the visual alarm devices.
This European Standard applies to visual alarm devices that rely on software for their operation and to those
that do not.
This European Standard applies only to pulsing or flashing visual alarm devices, for example xenon beacons
or rotating beacons. Devices giving continuous light output are excluded from this European Standard.
This European Standard is not intended to cover visual indicators, for example those on detectors or on the
control and indicating equipment.
2 Normative references
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
EN 54-1:1996, Fire detection and fire alarm systems — Part 1: Introduction
EN 50130-4:1995, Alarm systems — Part 4: Electromagnetic compatibility — Product family standard:
Immunity requirements for components of fire, intruder and social alarm systems (including
EN 50130-4:1995/A1:1998 and EN 50130-4:1995/A2:2003)
EN 60068-1:1994, Environmental testing — Part 1: General and guidance (IEC 60068-1:1988 +
Corrigendum 1988 +A1:1992)
EN 60068-2-1:2007, Environmental testing — Part 2-1: Tests — Tests A: Cold (IEC 60068-2-1:2007)
EN 60068-2-2:2007, Environmental testing — Part 2-2: Tests — Test B: Dry heat (IEC 60068-2-2:2007)
EN 60068-2-6:2008, Environmental testing — Part 2-6: Tests — Tests Fc: Vibration, (sinusoidal)
(IEC 60068-2-6:2007)
EN 60068-2-27:2009, Environmental testing — Part 2-27: Tests — Test Ea and guidance: Shock
(IEC 60068-2-27:2008)
EN 60068-2-30:2005, Environmental testing — Part 2-30: Tests — Test Db: Damp heat, cyclic (12 h + 12 h
cycle) (IEC 60068-2-30:2005)
EN 60068-2-42:2003, Environmental testing — Part 2-42: Tests; Test Kc: Sulphur dioxide test for contacts
and connections (IEC 60068-2-42:2003)
EN 60068-2-75:1997, Environmental testing — Part 2-75: Tests — Test Eh: Hammer tests
(IEC 60068-2-75:1997)
EN 60068-2-78:2001, Environmental testing — Part 2-78: Tests; Test Cab: Damp heat, steady state
(IEC 60068-2-78:2001)
EN 60529:1991, Degrees of protection provided by enclosures (IP code) (IEC 60529:1989) (including
EN 60529:1991/A1:2000)
EN 60695-11-10:1999, Fire hazard testing — Part 11-10: Test flames — 50 W horizontal and vertical flame
test methods (IEC 60695-11-10:1999) (including EN 60695-11-10:1999/A1:2003)
EN 60695-11-20:1999, Fire hazard testing — Part 11-20: Test flames — 500 W flame test methods
(IEC 60695-11-20:1999) (including EN 60695-11-20:1999/A1:2003)
EN ISO 9001:2008, Quality management systems — Requirements (ISO 9001:2008)
ISO 23539:2005, Photometry — The CIE system of physical photometry
3 Terms, definitions and abbreviations
3.1 Definitions
For the purposes of this document, the terms and definitions given in EN 54-1:1996 and the following apply.
3.1.1
coverage volume
volume within which the required illumination is achieved
3.1.2
normal axis
axis normal to the mounting plane which passes through the reference point
3.1.3
effective luminous intensity
measurement corresponding to the light output of the visual alarm device measured using the equipment and
method detailed in Annex A
3.1.4
light output level
measurement corresponding to the light output of the visual alarm device measured using the equipment and
method detailed in Annex B
3.1.5
mode (of operation)
one of a possible number of pre-defined light outputs of the visual alarm device which can be selected by
means specified by the manufacturer
3.1.6
reference point
point representing the optical centre within or on the surface of the visual alarm device specified by the
manufacturer
3.1.7
required illumination
illumination of 0,4 lm/m on a surface perpendicular to the direction of the light emitted from the device
3.1.8
Type A visual alarm device
device primarily intended for indoor applications
NOTE Type A visual alarm devices may be suitable for some protected outdoor situations.
3.1.9
Type B visual alarm device
device primarily intended for outdoor applications
NOTE Type B visual alarm devices may be more suitable than Type A visual alarm devices for some indoor
situations where high temperature and/or humidity are present.
3.1.10
visual alarm device
VAD
device which generates a flashing light to signal to the occupants of a building that a fire condition exists
3.2 Abbreviations
AC Alternating current
DC Direct current
EMC Electromagnetic compatibility
RMS Root mean square
VAD Visual alarm device
4 Requirements
4.1 General
In order to comply with this standard, VADs shall meet the requirements of Clause 4, which shall be verified
by visual inspection or engineering assessment, shall be tested as described in Clause 5 and shall meet the
requirements of the tests.
4.2 Operational reliability
4.2.1 Duration of operation
The VAD shall be rated for at least 100 h operation. No limitation on duty factor or maximum on-time shall
prevent the device from operating the 1 h 'on' 1 h 'off' cycle required by the test procedure described in 5.2.
NOTE This requirement does not apply to the capacity of batteries which may be used within VADs as a means of
local storage of operating power. The capacity and charging requirements of such batteries should meet the requirement
of the system.
4.2.2 Provision for external conductors
The VAD shall provide space within its enclosure for external conductors to be brought in and terminated.
Entry holes for conductors or cables shall be provided or the location where such holes are to be made shall
be indicated by providing a template or some other suitable means.
Terminals for connecting external conductors shall be designed so that the conductors are clamped between
metal surfaces without being damaged. Each terminal shall be capable of allowing the connection of any
2 2
conductor having a cross-sectional area between 0,28 mm and 1,5 mm inclusive.
4.2.3 Flammability of materials
The VAD shall be constructed of material(s) capable of withstanding the tests specified in Clause 5. In
addition, the material(s) of plastic enclosures shall meet the following flammability requirements:
a) EN 60695-11-10:1999 as amended by EN 60695-11-10:1999/A1:2003 Class V-2 or HB75 for devices
operating from a voltage source less than or equal to 30 V RMS or 42,4 V DC and consuming less than
15 W of power;
b) EN 60695-11-20:1999 as amended by EN 60695-11-20:1999/A1:2003 Class 5VB for devices operating
from a voltage source greater than 30 V RMS or 42,4 V DC and consuming more than 15 W of power.
NOTE Annex D gives information on the test requirements and classification given in the IEC standards and
equivalent flammability ratings in UL 94.
4.2.4 Enclosure protection
The degree of protection provided by the enclosure of VADs shall meet the following requirements:
a) for Type A VAD: Code IP21C of EN 60529:1991;
b) for Type B VAD: Code IP33C of EN 60529:1991.
4.2.5 Access
Means shall be provided to limit access for removal of parts or the whole device, e.g. special tool, codes,
hidden screws, seals, etc.
4.2.6 Manufacturer's adjustments
It shall not be possible to change the manufacturer's settings except by special means (e.g. the use of a
special code or tool) or by breaking or removing a seal.
4.2.7 On site adjustments of behaviour
If there is provision for on-site adjustment of the behaviour of the VAD:
a) for each setting at which compliance with this standard is claimed, the VAD shall comply with the
requirements of this standard and access to the adjustment means shall only be possible by the use of a
code or special tool or by removing the VAD from its base or mounting; and
b) any setting(s) at which compliance with this European Standard is not claimed, shall only be accessible by
the use of a code or special tool and it shall be clearly marked on the VAD or in the associated data that
when these setting(s) are used, the VAD does not comply with the standard.
NOTE These adjustments may be carried out, for example, at the VAD or at the control and indicating equipment.
4.2.8 Requirements for software controlled devices
4.2.8.1 General
For VADs which rely on software control in order to fulfil the requirements of this European Standard, the
requirements of 4.2.8.2, 4.2.8.3 and 4.2.8.4 shall be met.
4.2.8.2 Software documentation
4.2.8.2.1 Documentation which gives an overview of the software design shall be submitted. This
documentation shall be in sufficient detail for the design to be inspected for compliance with this European
Standard and shall include at least the following:
a) a functional description of the main program flow (e.g. as a flow diagram or structogram) including:
1) a brief description of the modules and the functions that they perform;
2) the way in which the modules interact;
3) the overall hierarchy of the program;
4) the way in which the software interacts with the hardware of the VAD;
5) the way in which the modules are called, including any interrupt processing;
b) a description of which areas of memory are used for the various purposes (e.g. the program, site specific
data and running data);
c) a designation, by which the software and its version can be uniquely identified.
4.2.8.2.2 Detailed design documentation, which only needs to be provided if required for assessment
purposes, shall comprise at least the following:
a) an overview of the whole system configuration, including all software and hardware components;
b) a description of each module of the program, containing at least:
1) the name of the module;
2) a description of the tasks performed;
3) a description of the interfaces, including the type of data transfer, the valid data range and the
checking for valid data;
c) full source code listings, as hard copy or in machine-readable form (e.g. ASCII-code), including all global
and local variables, constants and labels used, and sufficient comment for the program flow to be
recognized;
d) details of any software tools used in the design and implementation phase (e.g. CASE-tools, compilers).
4.2.8.3 Software design
In order to ensure the reliability of the VAD, the following requirements for the software design shall apply:
a) the software shall have a modular structure;
b) the design of the interfaces for manually and automatically generated data shall not permit invalid data to
cause error in the program operation;
c) the software shall be designed to avoid the occurrence of deadlock of the program flow.
4.2.8.4 Storage of program and data
The program necessary to comply with this European Standard and any preset data, such as manufacturer's
settings, shall be held in non-volatile memory. Writing to areas of memory containing this program and data
shall only be possible by the use of some special tool or code and shall not be possible during normal
operation of the VAD.
Site-specific data shall be held in memory which will retain data for at least two weeks without external power
to the VAD, unless provision is made for the automatic renewal of such data, following loss of power, within 1
h of power being restored.
4.3 Performance parameters under fire conditions
4.3.1 Coverage volume
4.3.1.1 VADs shall meet the requirement for coverage volume of at least one of the following three
categories:
a) 'C', ceiling mounted devices;
b) 'W', wall mounted devices;
c) 'O', open class devices.
4.3.1.2 Category C devices shall be further specified as C-x-y (see 4.3.6.2, d), 1)), where:
x is either 3, 6 or 9, representing the maximum height, in metres (m), at which the device may be
mounted; and
y is the diameter, in metres (m), of the coverage cylindrical volume when the device is mounted at the
ceiling height.
EXAMPLE C-3-12 corresponds to a ceiling mounted device giving a coverage cylindrical volume of 12 m diameter at
3 m height.
4.3.1.3 Category W devices shall be further specified as W-x-y (see 4.3.6.2, d), 2)), where:
x is the maximum height of the devices on the wall, in metres (m), with a minimum value of 2,4 m; and
y is the width of a square room, in metres (m), covered by the device.
EXAMPLE W-2,4-6 corresponds to a wall mounted device giving a coverage cuboid volume of 2,4 m × 6 m × 6 m
when mounted at a height of 2,4 m.
4.3.1.4 For category O devices the coverage volume in which the required illumination is achieved shall
be specified (see 4.3.6.2, d), 3)).
4.3.2 Variation of light output
When tested in accordance with 5.3.2, the variation in effective luminous intensity of the VAD, over 30 min,
shall be less than 25 %.
4.3.3 Minimum and maximum effective luminous intensity
When tested in accordance with 5.3.3, the VAD shall produce an effective luminous intensity of at least 1 cd
for 70 % of all measurement points and shall not exceed 500 cd for any measurement points.
4.3.4 Light colour
The VAD shall emit a white or red flashing light.
4.3.5 Light temporal pattern and frequency of flashing
The flash rate of the VAD shall be between 0,5 Hz and 2 Hz measured at 10 % of the peak values of
consecutive leading edges of the first pulse of each flash (P ).
10L
NOTE The light temporal pattern and frequency of flashing may vary in different countries. Reference needs to be
made to local regulations.
The maximum on time, measured between the 10 % of peak value of the leading edge (P ) and the 10 %
10L
value of the trailing edge (P ) of the last pulse of the flash shall not exceed 0,2 s.
10T
If the light emitted consists of groups of several pulses and the time between the P of one pulse and the
10T
P of the next pulse is less than 0,04 s then the pulses shall be considered as a single event. Any set of
10L
multiple pulses shall not exceed 0,2 s between the P for of the first peak to the P of the last peak.
10L 10T
A set of pulses where the minimum value does not drop below 10 % of the peak value is considered as a
single pulse and shall not exceed 0,2 s between P and P .
10L 10T
4.3.6 Marking and data
4.3.6.1 Marking
Each VAD shall be clearly marked with the following information:
a) number of this standard (i.e. EN 54-23);
b) environment type (i.e. Type A or B (see 3.1.8 and 3.1.9));
c) device category (see 4.3.1);
d) name or trademark of the manufacturer or supplier;
e) manufacturer or supplier model designation (type or number of the VAD);
f) terminal designations;
g) a mark(s) or code(s) (e.g. serial number or batch code), by which the manufacturer can identify, at least,
the date or batch and place of manufacture and the version number(s) of any software contained within
the device.
For detachable VADs, the detachable part shall be marked with a), b), c), d), e) and g), and the base shall be
marked with, at least, e) (i.e. its own model designation) and f).
Where any marking on the device uses symbols or abbreviations not in common use then these shall be
explained in the data supplied with the device.
The marking need not be discernible when the device is installed and ready for use but shall be visible during
installation and shall be accessible during maintenance.
The markings shall not be placed on screws or other easily removable parts of the device.
NOTE Where ZA.3 covers the same information as this clause, the requirements of this clause are met.
4.3.6.2 Data
The information required in 4.3.6.1, together with the following, shall be supplied with the device, or shall be
given in a data sheet or technical manual identified on, or with each device:
a) rated supply voltages or voltage ranges (AC or DC);
b) power and current consumption;
c) supply frequency ranges, where relevant;
d) the coverage characteristics:
1) for category C devices, the information shall clearly show or state:
i) the maximum allowable height of the device above the floor level, given in metres (m), i.e.
parameter x in the category specification as described in 4.3.1.2;
ii) the cylindrical volume with its central axis extending vertically downwards from the device;
iii) the diameter of the above cylindrical volume, given in metres (m), i.e. parameter y in the
category specification as described in 4.3.1.2;
2) for category W devices, the information shall clearly show or state:
i) the device correct orientation;
ii) features of the device used to align the device to the orientation given in 4.3.6.2, d), 2), i);
iii) the maximum allowable mounted height of the device, given in metres (m), i.e. parameter x in
the category specification as described in 4.3.1.3;
iv) the cuboid volume with its vertical side equal to the height at which the device is mounted and
with the device in the centre of one top edge;
v) the length of the other two sides of the cuboid, given in metres (m), i.e. parameter y in the
category specification as described in 4.3.1.3;
3) for category O devices, the information shall clearly show or state:
i) the mounting position of the device;
ii) any specific requirement for mounting the device in a particular orientation, and how this
orientation can be identified on the device;
iii) any restrictions on the minimum and maximum allowable mounted height;
iv) the volumetric shape, its dimensions and how it is related to the device;
e) the light temporal pattern and frequency of flashing;
f) IP Code to EN 60529:1991 as amended by EN 60529:1991/A1:2000;
g) any other information necessary to allow correct installation, operation and maintenance of the device.
4.3.7 Synchronization (option with requirements)
VADs may include a synchronization function to eliminate the possibility of a flash frequency/temporal pattern
that could result in adverse effects, such as inducing epileptic fits, when devices are in close proximity. In such
cases, VADs shall meet the requirements of the test described in 5.3.7.
NOTE This synchronization can be achieved by internal circuitry, the addition of a trigger wire connected between
devices or by other means defined by the manufacturer.
4.4 Durability
4.4.1 Temperature resistance
4.4.1.1 Dry heat (operational)
Type A and Type B VADs shall function correctly at high ambient temperatures as specified in 5.4.1.1.
4.4.1.2 Dry heat (endurance)
Type B VADs shall be capable of withstanding long term exposure to high temperature as specified in 5.4.1.2.
4.4.1.3 Cold (operational)
Type A and Type B VADs shall function correctly at low ambient temperatures as specified in 5.4.1.3.
4.4.2 Humidity resistance
4.4.2.1 Damp heat, cyclic (operational)
Type A and Type B VADs shall function correctly at a high level of humidity as specified in 5.4.2.1.
4.4.2.2 Damp heat, steady state (endurance)
Type A and Type B VADs shall be capable of withstanding long term exposure to a high level of continuous
humidity as specified in 5.4.2.2.
4.4.2.3 Damp heat, cyclic (endurance)
Type B VADs shall be capable of withstanding the effect of cyclic humidity levels as specified in 5.4.2.3.
4.4.3 Shock and vibration resistance
4.4.3.1 Shock (operational)
Type A and Type B VADs shall operate correctly when submitte
...








Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.
Loading comments...