EN 13341:2005
(Main)Thermoplastics static tanks for above ground storage of domestic heating oils, kerosene and diesel fuels - Blow moulded polyethylene, rotationally moulded polyethylene and polyamide 6 by anionic polymerization tanks - Requirements and test methods
Thermoplastics static tanks for above ground storage of domestic heating oils, kerosene and diesel fuels - Blow moulded polyethylene, rotationally moulded polyethylene and polyamide 6 by anionic polymerization tanks - Requirements and test methods
This document specifies requirements for materials, physical properties and performance of single blow moulded and rotationally moulded polyethylene tanks or polyamide 6 (by anionic polymerisation) tanks, with or without reinforcements, for above ground storage of domestic heating oil, kerosene and diesel fuels.
It is only applicable to static blow moulded and rotationally moulded polyethylene tanks and polyamide 6 (by anionic polymerisation) tanks that are subject to atmospheric pressure and have a capacity from 450 l up to 10 000 l.
This document does not consider the consequences of wind or snow loading which is considered to be an installation issue.
Ortsfeste Tanks aus Thermoplasten für die oberirdische Lagerung von Heizölen, Kerosin und Dieselkraftstoffen - Tanks, die aus blasgeformtem Polyethylen, rotationsgeformtem Polyethylen und durch anionische Polymerisation von Polyamid 6 hergestellt wurden - Anforderungen und Prüfverfahren
Dieses Dokument legt Anforderungen an die Werkstoffe, die physikalischen Eigenschaften und die Leistung von einzelnen Tanks aus blas und rotationsgeformtem Polyethylen oder Polyamid 6 (durch anionische Polymerisation) - mit oder ohne Verstärkungen - für die oberirdische Lagerung von Haushalts Heizöl, Kerosin und Dieselölen fest.
Es gilt nur für aus blas und rotationsgeformtem Polyethylen und Polyamid 6 (durch anionische Polymerisation) hergestellte ortsfeste Tanks, die dem atmosphärischem Druck ausgesetzt sind und ein Füllvolumen von 450 l bis 10 000 l aufweisen.
Dieses Dokument berücksichtigt nicht die Auswirkungen von Wind oder Schneelasten, die als Aspekte der Aufstellung angesehen werden.
Réservoirs statiques en thermoplastiques destinés au stockage non enterré de fioul domestique, combustible liquide pour appareil mobile de chauffage/pétrole lampant et gazole - Réservoirs en polyéthylène moulés par soufflage, en polyéthylène moulés par rotation et en polyamide 6 par polymérisation anionique - Exigences et méthodes d'essai
Le présent document spécifie les exigences pour les matières, les propriétés physiques et les performances des réservoirs simples en polyéthylène moulés par soufflage et moulés par rotation, ou des réservoirs simples en polyamide 6 (par polymérisation anionique), avec ou sans renforts, pour le stockage non enterré de fioul domestique, combustible liquide pour appareil mobile de chauffage/pétrole lampant et gazole.
Il ne s'applique qu'aux réservoirs statiques moulés par soufflage et moulés par rotation et aux réservoirs statiques en polyamide 6 (par polymérisation anionique), qui sont soumis à la pression atmosphérique et d'une capacité comprise entre 450 l et 10 000 l.
Le présent document ne considère pas les conséquences du vent ou des charges dues à la neige qui sont considérées être une question d'installation.
Plastomerne stabilne posode za nadzemno skladiščenje kurilnega olja, kerozina in dizelskih pogonskih goriv - Posode iz pihanega polietilena, rotacijsko oblikovanega polietilena in iz poliamida 6, proizvedenega z anionsko polimerizacijo - Zahteve in preskusne metode
General Information
Relations
Standards Content (Sample)
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Thermoplastics static tanks for above ground storage of domestic heating oils, kerosene and diesel fuels - Blow moulded polyethylene, rotationally moulded polyethylene and polyamide 6 by anionic polymerization tanks - Requirements and test methodsLMVNRVNRRéservoirs statiques en thermoplastiques destinés au stockage non enterré de fioul domestique, combustible liquide pour appareil mobile de chauffage/pétrole lampant et gazole - Réservoirs en polyéthylene moulés par soufflage, en polyéthylene moulés par rotation et en polyamide 6 par polymérisation anionique - Exigences et méthodes d'essaiOrtsfeste Tanks aus Thermoplasten für die oberirdische Lagerung von Heizölen, Kerosin und Dieselkraftstoffen - Tanks, die aus blasgeformtem Polyethylen, rotationsgeformtem Polyethylen und durch anionische Polymerisation von Polyamid 6 hergestellt wurden - Anforderungen und PrüfverfahrenTa slovenski standard je istoveten z:EN 13341:2005SIST EN 13341:2005en23.020.10ICS:SLOVENSKI
STANDARDSIST EN 13341:200501-junij-2005
EUROPEAN STANDARDNORME EUROPÉENNEEUROPÄISCHE NORMEN 13341March 2005ICS 23.020.10English versionThermoplastics static tanks for above ground storage ofdomestic heating oils, kerosene and diesel fuels - Blow mouldedpolyethylene, rotationally moulded polyethylene and polyamide 6by anionic polymerization tanks - Requirements and testmethodsRéservoirs statiques en thermoplastiques destinés austockage non enterré de fioul domestique, combustibleliquide pour appareil mobile de chauffage/pétrole lampantet gazole - Réservoirs en polyéthylène moulés parsoufflage, en polyéthylène moulés par rotation et enpolyamide 6 par polymérisation anionique - Exigences etméthodes d'essaiOrtsfeste Tanks aus Thermoplasten für die oberirdischeLagerung von Heizölen, Kerosin und Dieselkraftstoffen -Tanks, die aus blasgeformtem Polyethylen,rotationsgeformtem Polyethylen und durch anionischePolymerisation von Polyamid 6 hergestellt wurden -Anforderungen und PrüfverfahrenThis European Standard was approved by CEN on 3 February 2005.CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this EuropeanStandard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such nationalstandards may be obtained on application to the Central Secretariat or to any CEN member.This European Standard exists in three official versions (English, French, German). A version in any other language made by translationunder the responsibility of a CEN member into its own language and notified to the Central Secretariat has the same status as the officialversions.CEN members are the national standards bodies of Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France,Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia,Slovenia, Spain, Sweden, Switzerland and United Kingdom.EUROPEAN COMMITTEE FOR STANDARDIZATIONCOMITÉ EUROPÉEN DE NORMALISATIONEUROPÄISCHES KOMITEE FÜR NORMUNGManagement Centre: rue de Stassart, 36
B-1050 Brussels© 2005 CENAll rights of exploitation in any form and by any means reservedworldwide for CEN national Members.Ref. No. EN 13341:2005: E
Test methods for determination of material characteristics.18 Annex B (normative)
Test methods for determination of tank characteristics.22 Bibliography.33
1 Scope This document specifies requirements for materials, physical properties and performance of single blow moulded and rotationally moulded polyethylene tanks or polyamide 6 (by anionic polymerisation) tanks, with or without reinforcements, for above ground storage of domestic heating oil, kerosene and diesel fuels. It is only applicable to static blow moulded and rotationally moulded polyethylene tanks and polyamide 6 (by anionic polymerisation) tanks that are subject to atmospheric pressure and have a capacity from 450 l up to 10 000 l. This document does not consider the consequences of wind or snow loading which is considered to be an installation issue. 2 Normative references The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 13160-1, Leak detection systems — Part 1: General principles EN 13160-2, Leak detection systems — Part 2: Pressure and vacuum systems EN 13160-3, Leak detection systems — Part 3: Liquid systems for tanks EN 13160-4, Leak detection systems — Part 4: Liquid and/or vapour sensor systems for use in leakage containments or interstitial spaces EN 13160-5, Leak detection systems — Part 5: Tank gauge leak detection systems EN 13160-6, Leak detection systems — Part 6: Sensors in monitoring wells EN 13160-7, Leak detection systems — Part 7: General requirements and test methods for interstitial spaces, leak protecting linings and leak protecting jackets EN 13501-1, Fire classification of construction products and building elements — Part 1. Classification using test data from reaction to fire tests EN 13616, Overfill prevention devices for static tanks for liquid petroleum fuels EN ISO 175, Plastics — Methods of test for the determination of the effects of immersion in liquid chemicals (ISO 175:1999) EN ISO 527-3:1995, Plastics — Determination of tensile properties — Part 3: Test conditions for films and sheets (ISO 527-3:1995) EN ISO 960, Plastics — Polyamides (PA) — Determination of water content (ISO 960:1998) EN ISO 1133:1999, Plastics — Determination of the melt mass-flow rate (MFR) and the melt volume-flow rate (MVR) of thermoplastics (ISO 1133:1997) EN ISO 1183-1, Plastics - Methods for determining the density of non-cellular plastics - Part 1: Immersion method, liquid pyknometer method and titration method (ISO 1183-1:2004)
— Code of practice for the avoidance of hazards due to static electricity 3 Terms and definitions For the purposes of this document, the following terms and definitions apply. 3.1 tank container for the storage of domestic heating, kerosene and diesel fuels at atmospheric pressure which retains its designed shape without any reinforcements when empty 3.2 brimful capacity (of a tank) volume of water held by the tank filled through the filling orifice to the point of overflowing 3.3 maximum filling capacity (of a tank) value of 95 % of the brimful capacity 4 Requirements 4.1 Materials 4.1.1 General Raw materials and samples taken from tanks shall be tested and fulfil the requirements according to Table 1. The proportion of regrind from the same material shall not exceed 50 % for blow-moulded tanks. Regrind shall not be used for rotationally moulded tanks. Tanks for external installation shall be sufficiently opaque so as to protect the contents from degradation by ultra violet light. The manufacturer may use visual or prescriptive means to demonstrate compliance with this requirement. 4.1.2 Reaction to fire Where the product is subject to regulatory requirements, tanks made from polyethylene and polyamide 6 may be declared as Class F without further testing (CWFT) or the material shall be classified according to EN 13501-1, mounted and tested in conditions representative of the product’s intended use.
A.2.2 Tensile strength c
Tensile strength at yield shall not be less than 15 MPa. Elongation at yield shall not be more than 25 %. The elongation at break shall not be less than 200 %. A.2.3 Rotationally moulded polyethylene
Resistance to oil c Mass alteration shall be less than 10 %. Variation in tensile strength at yield shall not exceed 20 % of that measured in A.2.3. Change in elongation at break shall be less than 150 % of that measured in A.2.3. A.2.4 Tensile strength c Tensile strength shall not be less than 30 MPa at yield. Elongation shall be more than 20 % at break. A.3.1 Resistance to oil c Mass alteration shall be less than 0,4 %. Variation in tensile strength shall not exceed 5 % of that measured in A.3.1. Elongation at break shall be more than 20 %. A.3.2
Polyamide 6 (by anionic polymerization) Colour bleed c The bleed time of any sample shall not be less than 5,5 h. A.3.3 Blow moulded polyethylene
Rotationally moulded polyethylene Polyamide 6 (by anionic polymerisation) Resistance to weathering c
For external installations after exposure to total irradiance of 34 GJ/m2, the elongation at break shall be greater than 50 % of the ini
...
Questions, Comments and Discussion