Fixed firefighting systems - Components for gas extinguishing systems - Part 13: Requirements and test methods for check valves and non-return valves

This European standard specifies the requirements and describes test methods for check and non-return valves. This standard is applicable to check valves installed between container valve and manifold and non-return valves installed in pilot lines except those valves, which are tested in combination with non-electrical control devices. Non-return and check valves shall allow the passage in the direction of flow and they shall prevent flow in the reverse direction.

Ortsfeste Brandbekämpfungsanlagen - Bauteile für Löschanlagen mit gasförmigen Löschmitteln - Teil 13: Anforderungen und Prüfverfahren für Rückflussverhinderer und Rückschlagventile

Anwendungsbereich
Diese Europäische Norm legt Anforderungen und Prüfverfahren für Rückflussverhinderer und Rück-
schlagventile für CO 2 -Feuerlöschanlagen, Inertgas-Feuerlöschanlagen oder Feuerlöschanlagen mit
halogenierten Kohlenwasserstoffen fest.
Rückflussverhinderer und Rückschlagventile ermöglichen den Durchfluss in Flussrichtung und verhin-
dern ihn in entgegengesetzter Richtung.
Diese Europäische Norm kann angewendet werden auf Rückflussverhinderer, die zwischen Behälter-
ventil und Sammelrohr installiert sind, und auf Rückschlagventile, die in Steuerleitungen installiert sind
außer denjenigen Ventilen, die in Kombination mit nichtelektrischen Steuereinrichtungen geprüft werden.
Seite 3 EN 12094-13:2001.

Installations fixes de lutte contre l'incendie - Eléments d'installation d'extinction à gaz - Partie 13: Exigences et méthodes d'essai pour clapets anti-retour

1 Domaine d'application
La présente Norme européenne spécifie les exigences et décrit les méthodes d'essai applicables aux clapets anti-retour des systèmes d'extinction au CO2, à gaz inerte ou halogéné.
Les clapets anti-retour permettent le passage dans le sens de l'écoulement et l'empêchent en sens inverse.
La présente Norme européenne est applicable aux clapets anti-retour installés entre la vanne du réservoir et le collecteur et aux clapets anti-retour de circuit de pilotage installés dans les canalisations pilotes, à l'exception de ceux dont les essais sont effectués en les associant aux dispositifs non électriques de commande.

Vgrajeni gasilni sistemi - Sestavni deli sistemov za gašenje s plinom - 13. del: Zahteve in preskusne metode za kontrolne ventile in nepovratne ventile

General Information

Status
Published
Publication Date
20-Mar-2001
Current Stage
9093 - Decision to confirm - Review Enquiry
Start Date
30-Nov-2011
Completion Date
30-Nov-2011

Relations

Buy Standard

Standard
EN 12094-13:2001
English language
17 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Vgrajeni gasilni sistemi - Sestavni deli sistemov za gašenje s plinom - 13. del: Zahteve in preskusne metode za kontrolne ventile in nepovratne ventileOrtsfeste Brandbekämpfungsanlagen - Bauteile für Löschanlagen mit gasförmigen Löschmitteln - Teil 13: Anforderungen und Prüfverfahren für Rückflussverhinderer und RückschlagventileInstallations fixes de lutte contre l'incendie - Eléments d'installation d'extinction a gaz - Partie 13: Exigences et méthodes d'essai pour clapets anti-retourFixed firefighting systems - Components for gas extinguishing systems - Part 13: Requirements and test methods for check valves and non-return valves13.220.10Gašenje požaraFire-fightingICS:Ta slovenski standard je istoveten z:EN 12094-13:2001SIST EN 12094-13:2001en01-oktober-2001SIST EN 12094-13:2001SLOVENSKI
STANDARD
EUROPEAN STANDARDNORME EUROPÉENNEEUROPÄISCHE NORMEN 12094-13March 2001ICS 13.220.20English versionFixed firefighting systems - Components for gas extinguishingsystems - Part 13: Requirements and test methods for checkvalves and non-return valvesInstallations fixes de lutte contre l'incendie - Elémentsd'installation d'extinction à gaz - Partie 13: Exigences etméthodes d'essai pour clapets anti-retourOrtsfeste Brandbekämpfungsanlagen - Bauteile fürLöschanlagen mit gasförmigen Löschmitteln - Teil 13:Anforderungen und Prüfverfahren für Rückflussverhindererund RückschlagventileThis European Standard was approved by CEN on 4 February 2001.CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this EuropeanStandard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such nationalstandards may be obtained on application to the Management Centre or to any CEN member.This European Standard exists in three official versions (English, French, German). A version in any other language made by translationunder the responsibility of a CEN member into its own language and notified to the Management Centre has the same status as the officialversions.CEN members are the national standards bodies of Austria, Belgium, Czech Republic, Denmark, Finland, France, Germany, Greece,Iceland, Ireland, Italy, Luxembourg, Netherlands, Norway, Portugal, Spain, Sweden, Switzerland and United Kingdom.EUROPEAN COMMITTEE FOR STANDARDIZATIONCOMITÉ EUROPÉEN DE NORMALISATIONEUROPÄISCHES KOMITEE FÜR NORMUNGManagement Centre: rue de Stassart, 36
B-1050 Brussels© 2001 CENAll rights of exploitation in any form and by any means reservedworldwide for CEN national Members.Ref. No. EN 12094-13:2001 ESIST EN 12094-13:2001

Page 2EN 12094-13:2001ContentsPageForeword.3Introduction.31
Scope.42
Normative references.43
Terms and definitions.44
Requirements.54.1
General design.54.2
Connection threads.64.3
Internal pressure.64.4
Strength.64.5
Flow way.64.6
Leakage.64.7
Impact.64.8
Function and ambient temperatures.64.9
Corrosion.64.10
Stress corrosion.74.11
Vibration resistance.74.12
Documentation.75
Test methods.75.1
Test conditions.75.2
Test samples and order of tests.75.3
Compliance.85.4
Internal pressure.85.5
Strength test.85.6
Leakage test.95.7
Impact test.95.8
Function.95.9
Function at high and low temperature.95.10
Corrosion.105.11
Stress corrosion.105.12
Vibration.106
Marking.117
Evaluation of conformity.117.1
General.117.2
Initial type testing.117.3
Factory production control (FPC).11Annex A (normative) Flow characteristics.12Annex ZA (informative) Clauses of this European Standard addressing the provisions of the EU ConstructionProducts Directive.14Bibliography.17SIST EN 12094-13:2001

Page 3EN 12094-13:2001ForewordThis European Standard has been prepared by Technical Committee CEN/TC 191 "Fixed firefighting systems", thesecretariat of which is held by BSI.This European Standard shall be given the status of a national standard, either by publication of an identical text or byendorsement, at the latest by September 2001, and conflicting national standards shall be withdrawn at the latest byDecember 2002.This European Standard has been prepared under a mandate given to CEN by the European Commission and theEuropean Free Trade Association, and supports essential requirements of EU Directive(s).For relationship with EU Directive(s), see informative Annex ZA, which is an integral part of this standard.This part of EN 12094 is one of a number of European Standards prepared by CEN/TC 191 covering components forgas extinguishing systems.They are included in a series of European Standards planned to cover:- gas extinguishing systems (EN 12094)- sprinkler systems (EN 12259 and EN 12845)- powder systems (EN 12416)- explosion protection systems (EN 26184)- foam systems (EN 13565)- hose systems (EN 671)- smoke and heat control systems (EN 12101)- water spray systemsThe following parts of this European Standard are planned:- Part 1: Requirements and test methods for electrical automatic control and delay devices- Part 2: Requirements and test methods for non-electrical automatic control and delay devices- Part 3: Requirements and test methods for manual triggering and stop devices- Part 4: Requirements and test methods for high- pressure container valve assemblies and actuators- Part 5: Requirements and test methods for selector valves and actuators for CO2 systems- Part 6: Requirements and test methods for non-electrical disable devices for CO2 systems- Part 7: Requirements and test methods for nozzles for CO2 systems- Part 8: Requirements and test methods for flexible connectors for CO2 systems- Part 9: Requirements and test methods for special fire detectors- Part 10: Requirements and test methods for pressure gauges and pressure switches- Part 11: Requirements and test methods for weighing devices- Part 12: Requirements and test methods for alarm devices- Part 13: Requirements and test methods for check valves and non-return valves- Part 16: Requirements and test methods for odorizing devices for low pressure CO2 systems- Part 17: Requirements and test methods for pipe hangers- Part 20: Requirements and test methods for compatibility of componentsAccording to the CEN/CENELEC Internal Regulations, the national standards organizations of the followingcountries are bound to implement this European Standard: Austria, Belgium, Czech Republic, Denmark, Finland,France, Germany, Greece, Iceland, Ireland, Italy, Luxembourg, Netherlands, Norway, Portugal, Spain, Sweden,Switzerland and the United Kingdom.IntroductionIt has been assumed in the preparation of this European Standard that the execution of its provisions is entrusted toappropriately qualified and experienced people.All pressure data in this European Standard are given as gauge pressures in bar, unless otherwise stated.NOTE
1 bar = 105 N m-2 = 100 kPa.SIST EN 12094-13:2001

Page 4EN 12094-13:20011
ScopeThis European Standard specifies the requirements and describes test methods for check and non-return valves forCO2, inert gas or halocarbon gas fire extinguishing systems.Non-return and check valves allow the passage in the direction of flow and they prevent flow in the reverse direction.This European Standard is applicable to check valves installed between container valve and manifold and non-returnvalves installed in pilot lines, except those valves which are tested in combination with non-electrical control devices.2
Normative referencesThis European Standard incorporates by dated or undated reference, provisions from other publications. Thesenormative references are cited at the appropriate places in the text and the publications are listed hereafter. For datedreferences subsequent amendments to or revisions of any of these publications apply to this European Standard onlywhen incorporated in it by amendment or revision. For undated references the latest edition of the publication referredto applies (including amendments).EN 12094-8, Fixed firefighting systems - Components for gas extinguishing systems - Requirements and testmethods for flexible connectors for CO2 systemsISO 7-1, Pipe threads where pressure-tight joints are made on the threads - Part 1: Dimensions, tolerances anddesignationISO 228-1, Pipe threads where pressure-tight joints are not made on the threads - Part 1: Dimensions, tolerancesand designation3
Terms and definitionsFor the purposes of this European Standard the terms and definitions of EN 12094-8 and the following terms anddefinitions apply:3.1check valvecomponent intended for installation between container valve and manifold, which permits flow only in one direction3.2CO2-high-pressure installationfire extinguishing installation in which the CO2 is stored at ambient temperature, e.g. the pressure of the CO2 in storageis pabs = 58,6 bar at 21oC3.3CO2-low-pressure installationfire extinguishing installation in which the CO2 is stored at low
...