EN 54-12:2015
(Main)Fire detection and fire alarm systems - Part 12: Smoke detectors - Line detectors using an optical beam
Fire detection and fire alarm systems - Part 12: Smoke detectors - Line detectors using an optical beam
This European Standard specifies requirements, test methods and performance criteria for line detectors using an optical beam that detect smoke by utilizing the attenuation and/or changes in attenuation of an optical beam, for use in fire detection and fire alarm systems installed in buildings (see EN 54 1:2011).
This European Standard provides for the assessment and verification of constancy of performance (AVCP) of line detectors using an optical beam to this EN.
This European Standard does not cover:
- line detectors using an optical beam designed to operate with separations between opposed components of less than 1 m;
- line detectors using an optical beam whose optical path length is defined or adjusted by an integral mechanical connection;
- line detectors using an optical beam with special characteristics, which cannot be assessed by the test methods in this European Standard.
NOTE The term "optical" is used to describe that part of the electromagnetic spectrum produced by the transmitter to which the receiver is responsive; this is not restricted to visible wavelengths.
Brandmeldeanlagen - Teil 12: Rauchmelder - Linienförmiger Melder nach dem Durchlichtprinzip
Diese Europäische Norm legt Anforderungen, Prüfverfahren und Leistungsmerkmale für linienförmige Melder nach dem Durchlichtprinzip fest, die Rauch durch die Auswertung der Dämpfung und/oder der Änderungen der Dämpfung eines optischen Strahls in Brandmelde- und Feueralarmanlagen, die in Gebäuden eingebaut sind, erkennen (siehe EN 54-1:2011).
Diese Europäische Norm sieht die Bewertung und Überprüfung der Leistungsbeständigkeit (AVCP) von linienförmigen Meldern nach dem Durchlichtprinzip nach dieser EN vor.
Diese Europäische Norm behandelt nicht:
linienförmige Melder nach dem Durchlichtprinzip, die für den Betrieb zwischen gegenüberliegenden Bestandteilen mit einem Abstand kleiner als 1 m ausgelegt sind;
linienförmige Melder nach dem Durchlichtprinzip, deren optische Messstrecke mit einer inneren mechanischen Verbindung festgelegt wird oder einstellbar ist;
linienförmige Melder nach dem Durchlichtprinzip mit speziellen Kenngrößen, die durch die Prüfverfahren nach dieser Europäischen Norm nicht bewertet werden können.
ANMERKUNG Der Begriff „optisch“ wird für den Bereich des elektromagnetischen Spektrums verwendet, der vom Sender erzeugt wird und für den der Empfänger empfindlich ist; dieser Begriff ist nicht auf sichtbare Wellenlängen beschränkt.
Systèmes de détection et d'alarme incendie - Partie 12 : Détecteurs de fumée - Détecteurs linéaires fonctionnant suivant le principe de la transmission d'un faisceau d'ondes optiques rayonnées
La présente Norme européenne spécifie les exigences, les méthodes d’essai et les critères de performance des détecteurs linéaires de fumée fonctionnant suivant le principe de la transmission d'un faisceau d'ondes optiques rayonnées qui détectent la fumée par atténuation et/ou par variation de l'atténuation d’un faisceau d’ondes optiques, utilisés dans les systèmes de détection et d’alarme incendie installés dans les bâtiments (voir l’EN 54-1:2011).
La présente Norme européenne prévoit l'évaluation et la vérification de la constance des performances (EVCP) des détecteurs linéaires fonctionnant suivant le principe de la transmission d'un faisceau d'ondes optiques rayonnées, par rapport à la présente EN.
La présente Norme européenne ne couvre pas :
- les détecteurs linéaires fonctionnant suivant le principe de la transmission d'un faisceau d'ondes optiques rayonnées, conçus pour fonctionner avec des composants opposés ayant une portée inférieure à 1 m ;
- les détecteurs linéaires fonctionnant suivant le principe de la transmission d'un faisceau d'ondes optiques rayonnées dont le parcours optique est défini ou réglé par une liaison mécanique intégrée ;
- les détecteurs linéaires fonctionnant suivant le principe de la transmission d'un faisceau d'ondes optiques rayonnées possédant des caractéristiques particulières ne pouvant pas être évaluées par les méthodes d’essai de cette Norme européenne.
NOTE Le terme « ondes optiques » décrit la partie du spectre électromagnétique produite par un émetteur et à laquelle un récepteur répond ; ce terme ne se limite pas aux longueurs d'ondes visibles.
Sistemi za odkrivanje in javljanje požara ter alarmiranje - 12. del: Dimni javljalniki - Linijski javljalniki z optičnim žarkom
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
01-junij-2015
1DGRPHãþD
SIST EN 54-12:2003
6LVWHPL]DRGNULYDQMHLQMDYOMDQMHSRåDUDWHUDODUPLUDQMHGHO'LPQLMDYOMDOQLNL
/LQLMVNLMDYOMDOQLNL]RSWLþQLPåDUNRP
Fire detection and fire alarm systems - Part 12: Smoke detectors - Line detectors using
an optical beam
Brandmeldeanlagen - Teil 12: Rauchmelder - Linienförmiger Melder nach dem
Durchlichtprinzip
Systèmes de détection et d'alarme incendie - Partie 12: Détecteurs de fumée -
Détecteurs linéaires fonctionnant suivant le principe de la transmission d'un faisceau
d'ondes optiques rayonnées
Ta slovenski standard je istoveten z: EN 54-12:2015
ICS:
13.220.20 3RåDUQD]DãþLWD Fire protection
13.320 Alarmni in opozorilni sistemi Alarm and warning systems
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
EUROPEAN STANDARD
EN 54-12
NORME EUROPÉENNE
EUROPÄISCHE NORM
April 2015
ICS 13.220.20 Supersedes EN 54-12:2002
English Version
Fire detection and fire alarm systems - Part 12: Smoke detectors
- Line detectors using an optical beam
Systèmes de détection et d'alarme incendie - Partie 12: Brandmeldeanlagen - Rauchmelder - Teil 12: Linienförmiger
Détecteurs de fumée - Détecteurs linéaires fonctionnant Melder nach dem Durchlichtprinzip
suivant le principe de la transmission d'un faisceau d'ondes
optiques rayonnées
This European Standard was approved by CEN on 1 February 2015.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national
standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same
status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United
Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2015 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 54-12:2015 E
worldwide for CEN national Members.
Contents Page
Foreword .5
1 Scope .7
2 Normative references .7
3 Terms and definitions .8
4 Requirements .9
4.1 Compliance .9
4.2 Operational reliability .9
4.2.1 Individual alarm indication .9
4.2.2 Connection of ancillary devices .9
4.2.3 Manufacturer’s adjustments .9
4.2.4 On-site adjustment of response value .9
4.2.5 Protection against ingress of foreign bodies . 10
4.2.6 Monitoring of detachable detectors and connections . 10
4.2.7 Requirements for software controlled detectors (when provided) . 10
4.3 Nominal activation conditions/sensitivity . 11
4.3.1 Reproducibility . 11
4.3.2 Repeatability . 11
4.3.3 Tolerance to beam misalignment . 11
4.3.4 Rapid changes in attenuation . 12
4.3.5 Response to slowly developing fires. 12
4.3.6 Optical path length dependence . 12
4.3.7 Stray light . 12
4.4 Tolerance to supply voltage - Variation in supply parameters . 12
4.5 Performance parameters under fire conditions - Fire sensitivity . 12
4.6 Durability of nominal activation conditions/sensitivity . 12
4.6.1 Temperature resistance . 12
4.6.2 Humidity resistance . 13
4.6.3 Vibration resistance . 13
4.6.4 Electrical stability - Electromagnetic Compatibility (EMC), Immunity tests (operational) . 13
4.6.5 Corrosion resistance - Sulphur dioxide (SO ) corrosion (endurance) . 13
5 Testing, assessment and sampling methods . 13
5.1 General . 13
5.1.1 Atmospheric conditions for tests . 13
5.1.2 Operating conditions for tests . 14
5.1.3 Mounting arrangements . 14
5.1.4 Tolerances . 14
5.1.5 Measurement of response value . 14
5.1.6 Provision for tests . 15
5.1.7 Test schedule . 15
5.2 Operational reliability . 16
5.2.1 Individual alarm indication . 16
5.2.2 Connection of ancillary devices . 16
5.2.3 Manufacturer’s adjustments . 16
5.2.4 On-site adjustment of response value . 16
5.2.5 Protection against ingress of foreign bodies . 17
5.2.6 Monitoring of detachable detectors and connections . 17
5.2.7 Additional requirements for software controlled detectors . 17
5.3 Normal activation conditions/sensitivity . 17
5.3.1 Reproducibility . 17
5.3.2 Repeatability . 17
5.3.3 Tolerance to beam misalignment . 18
5.3.4 Rapid changes in attenuation . 19
5.3.5 Response to slowly developing fires . 19
5.3.6 Optical path length dependence . 19
5.3.7 Stray light . 20
5.4 Tolerance to supply voltage — Variation of supply parameters . 21
5.4.1 Object of the test . 21
5.4.2 Test procedure . 21
5.4.3 Test requirements . 21
5.5 Performance parameters under fire conditions . 21
5.5.1 Fire sensitivity . 21
5.6 Durability of nominal activation conditions/sensitivity . 23
5.6.1 Temperature resistance . 23
5.6.2 Humidity resistance . 25
5.6.3 Vibration resistance . 27
5.6.4 Electrical stability - Electromagnetic compatibility (EMC), immunity tests (operational) . 29
5.6.5 Corrosion resistance — Sulphur dioxide (SO ) corrosion (endurance) . 30
6 Assessment and verification of constancy of performance (AVCP) . 30
6.1 General . 30
6.2 Type testing . 31
6.2.1 General . 31
6.2.2 Test samples, testing and compliance criteria . 32
6.2.3 Test reports . 32
6.3 Factory production control (FPC) . 32
6.3.1 General . 32
6.3.2 Requirements . 33
6.3.3 Product specific requirements . 35
6.3.4 Initial inspection of factory and FPC . 36
6.3.5 Continuous surveillance of FPC . 36
6.3.6 Procedure for modifications. 36
...