Extended application of test results on durability of self-closing for fire resistance and/or smoke control doorsets and openable windows - Part 3: Durability of self-closing of steel sliding doorsets

This document is applicable to the following types of steel based doorsets: horizontally sliding doorsets (single and double), telescopic doorsets (single and double) and single vertically sliding doorsets as covered by EN 15269 7 or EN 15269 20.
This document prescribes the methodology for extending the application of test results obtained from durability of self-closing test(s) conducted in accordance with EN 12605:2017+A1:2020 or EN 1191.
Subject to the completion of the appropriate self-closing test(s), the extended application can cover all or some of the following non-exhaustive list:
—   door leaf;
—   pass doors;
—   wall/ceiling fixed elements (frame/suspension system);
—   ventilation grilles and/or louvres;
—   glazing for door leaf;
—   items of building hardware;
—   decorative finishes;
—   intumescent, smoke, draught or acoustic seals;
—   alternative supporting construction(s).

Erweiterter Anwendungsbereich von Prüfergebnissen zur Dauerhaftigkeit der Selbstschließung für Feuerschutz und/oder Rauchschutztüren und zu öffnende Fenster - Teil 3: Dauerhaftigkeit der Selbstschließung von Schiebetoren aus Stahl

Dieses Dokument befasst sich mit den folgenden Arten von Stahltoren: horizontal öffnende Schiebetore/ türen (ein  oder zweiflügelig), Teleskoptore/ türen (ein  oder zweiflügelig) und von einer Seite aus vertikal öffnende Schiebetore/ türen, wie in EN 15269 7 oder EN 15269 20 beschrieben.
Dieses Dokument beschreibt die Methodik zur Erweiterung der Anwendung von Ergebnissen aus Dauerfunktionsprüfung(en) des Selbstschließens, die nach EN 12605:2017+A1:2020 oder EN 1191 durchgeführt wurden.
In Abhängigkeit von der Durchführung der entsprechenden Prüfung(en) zum Selbstschließen, darf der erweiterte Anwendungsbereich einige oder alle der nachstehend aufgeführten Bereiche abdecken, wobei diese Liste als unvollständig anzusehen ist:
—   Tor /Türblatt;
—   Schlupftür;
—   Wand-/Deckenbefestigungselemente (Rahmen/Aufhängungssysteme);
—   Lüftungsgitter und/oder  lamellen;
—   Tor /Türblatt-Verglasung;
—   Baubeschläge;
—   dekorative Oberflächenbeschichtungen;
—   dämmschichtbildende Dichtungen, sowie Dichtungen zur Behinderung von Rauchdurchtritt (Rauchschutzdichtungen), Durchzug oder Schallübertragung (Schallschutzdichtungen);
—   alternative Tragkonstruktion(en).

Application étendue des résultats d’essais de durabilité de la fermeture automatique des blocs-portes et fenêtres ouvrantes résistants au feu et/ou étanches à la fumée - Partie 3 : Durabilité de la fermeture automatique des blocs-portes coulissants en acier

Le présent document s’applique aux types suivants de blocs-portes à base d’acier : blocs-portes coulissant horizontalement (simples et doubles), blocs-portes télescopiques (simples et doubles) et blocs-portes simples coulissant verticalement visés par l’EN 15269 7 ou l’EN 15269 20.
Le présent document établit la méthodologie d’extension de l’application des résultats d’essai obtenus suite aux essais de durabilité de la fermeture automatique réalisés conformément à l’EN 12605:2017+A1:2020 ou l’EN 1191.
Sous réserve de la réalisation de l’essai ou des essais appropriés de fermeture automatique, l’application étendue peut couvrir tout ou partie des éléments de la liste non exhaustive suivante :
—   vantail ;
—   portillons ;
—   éléments fixes muraux/de plafond (structure/système de suspension) ;
—   grilles de ventilation et/ou jalousies ;
—   vitrage de vantail ;
—   tout élément de quincaillerie intégré ;
—   finitions décoratives ;
—   joints intumescents, joints d’étanchéité aux fumées, joints d’étanchéité à l’air ou joints acoustiques ;
—   autres supports.

Razširjena uporaba rezultatov preskusov trajnosti samozapiranja za požarno odporna in/ali dimotesna vrata in okna, ki se odpirajo - 3. del: Trajnost samozapiranja jeklenih drsnih vrat

General Information

Status
Not Published
Current Stage
4599 - Dispatch of FV draft to CMC - Finalization for Vote
Due Date
24-Feb-2022
Completion Date
24-Feb-2022

Buy Standard

Draft
prEN 17020-3:2021
English language
64 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (sample)

SLOVENSKI STANDARD
oSIST prEN 17020-3:2021
01-junij-2021
Razširjena uporaba rezultatov preskusov trajnosti samozapiranja za požarno
odporna in/ali dimotesna vrata in okna, ki se odpirajo - 3. del: Trajnost
samozapiranja jeklenih drsnih vrat

Extended application of test results on durability of self-closing for fire resistance and/or

smoke control doorsets and openable windows - Part 3: Durability of self-closing of steel

sliding doorsets
Erweiterter Anwendungsbereich von Prüfergebnissen zur Dauerhaftigkeit der

Selbstschließung für Feuerschutz und/oder Rauchschutztüren und zu öffnende Fenster

- Teil 3: Dauerhaftigkeit der Selbstschließung von Schiebetoren aus Stahl

Application étendue des résultats d ’essais de durabilité de la fermeture automatique des

blocs-portes et fenêtres ouvrantes résistants au feu et/ou étanches à la fumée - Partie 3

: Durabilité de la fermeture automatique des blocs-portes coulissants en acier
Ta slovenski standard je istoveten z: prEN 17020-3
ICS:
13.220.50 Požarna odpornost Fire-resistance of building
gradbenih materialov in materials and elements
elementov
91.060.50 Vrata in okna Doors and windows
oSIST prEN 17020-3:2021 en,fr,de

2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------
oSIST prEN 17020-3:2021
---------------------- Page: 2 ----------------------
oSIST prEN 17020-3:2021
DRAFT
EUROPEAN STANDARD
prEN 17020-3
NORME EUROPÉENNE
EUROPÄISCHE NORM
May 2021
ICS 13.220.50; 91.060.50
English Version
Extended application of test results on durability of self-
closing for fire resistance and/or smoke control doorsets
and openable windows - Part 3: Durability of self-closing
of steel sliding doorsets
Erweiterter Anwendungsbereich von Prüfergebnissen
zur Dauerhaftigkeit der Selbstschließung für
Feuerschutz- und/oder Rauchschutztüren und zu
öffnende Fenster - Teil 3: Dauerhaftigkeit der
Selbstschließung von Schiebetoren aus Stahl

This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee

CEN/TC 127.

If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations

which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.

This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other

language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC

Management Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,

Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,

Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and

United Kingdom.

Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are

aware and to provide supporting documentation.

Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without

notice and shall not be referred to as a European Standard.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels

© 2021 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 17020-3:2021 E

worldwide for CEN national Members.
---------------------- Page: 3 ----------------------
oSIST prEN 17020-3:2021
prEN 17020-3:2021 (E)
Contents Page

European foreword ....................................................................................................................................................... 3

Introduction .................................................................................................................................................................... 4

1 Scope .................................................................................................................................................................... 5

2 Normative references .................................................................................................................................... 5

3 Terms and definitions ................................................................................................................................... 6

4 Determination of the field of extended application ........................................................................... 7

4.1 General ................................................................................................................................................................ 7

4.2 Procedure for evaluation ............................................................................................................................. 8

4.3 Procedure for maximum field of extended application .................................................................... 8

4.4 Interpretation of test results ...................................................................................................................... 9

5 Extended application report ....................................................................................................................... 9

6 Classification report ....................................................................................................................................... 9

Annex A (normative) Construction parameter variations ........................................................................ 10

Annex B (normative) Construction parameter variation simulation by applying additional

weights ............................................................................................................................................................. 63

Bibliography ................................................................................................................................................................. 64

---------------------- Page: 4 ----------------------
oSIST prEN 17020-3:2021
prEN 17020-3:2021 (E)
European foreword

This document (prEN 17020-3:2021) has been prepared by Technical Committee CEN/TC 127 “Fire

safety in buildings”, the secretariat of which is held by BSI.
This document is currently submitted to the CEN Enquiry.

This document has been prepared under a mandate given to CEN by the European Commission and the

European Free Trade Association.
A list of all parts in the EN 17020 series can be found on the CEN website.
---------------------- Page: 5 ----------------------
oSIST prEN 17020-3:2021
prEN 17020-3:2021 (E)
Introduction

The EN 15269 series of standards covering extended application of test results for fire resistance and/or

smoke control for door, shutter and openable window assemblies, including their elements of building

hardware, does not include the durability of self-closing of the doorsets following an extended application

process. This document is one of the EN 17020 series of standards intended to be used for the purpose of

producing an extended application report based on the evaluation of one or more durability of self-

closing tests. These European Standards may also be used to identify the best selection of test specimens

required to cover a wide range of product variations.

Before there can be any consideration for extended application, the doorset should have been tested in

accordance with EN 12605:2017+A1:2020 or EN 1191 to achieve a test result which could generate a

classification in accordance with EN 13501-2 and EN 16034 at least equal to the classification

subsequently required from extended application considerations.
---------------------- Page: 6 ----------------------
oSIST prEN 17020-3:2021
prEN 17020-3:2021 (E)
1 Scope

This document is applicable to the following types of steel based doorsets: horizontally sliding doorsets

(single and double), telescopic doorsets (single and double) and single vertically sliding doorsets as

covered by EN 15269-7 or EN 15269-20.

This document prescribes the methodology for extending the application of test results obtained from

durability of self-closing test(s) conducted in accordance with EN 12605:2017+A1:2020 or EN 1191.

Subject to the completion of the appropriate self-closing test(s), the extended application can cover all or

some of the following non-exhaustive list:
— door leaf;
— pass doors;
— wall/ceiling fixed elements (frame/suspension system);
— ventilation grilles and/or louvres;
— glazing for door leaf;
— items of building hardware;
— decorative finishes;
— intumescent, smoke, draught or acoustic seals;
— alternative supporting construction(s).
2 Normative references

The following documents, in whole or in part, are normatively referenced in this document and are

indispensable for its application. For dated references, only the edition cited applies. For undated

references, the latest edition of the referenced document (including any amendments) applies.

EN 1191, Windows and doors - Resistance to repeated opening and closing - Test method

EN 1363-1, Fire resistance tests - Part 1: General requirements
EN 1363-2, Fire resistance tests - Part 2: Alternative and additional procedures

EN 1634-1, Fire resistance and smoke control tests for door and shutter assemblies, openable windows and

elements of building hardware - Part 1: Fire resistance test for door and shutter assemblies and openable

windows

EN 1634-3, Fire resistance and smoke control tests for door and shutter assemblies, openable windows and

elements of building hardware - Part 3: Smoke control test for door and shutter assemblies

EN 12209, Building hardware - Mechanically operated locks and locking plates - Requirements and test

methods

EN 12433-1, Industrial, commercial and garage doors and gates - Terminology - Part 1: Types of doors

EN 12433-2, Industrial, commercial and garage doors and gates - Terminology - Part 2: Parts of doors

---------------------- Page: 7 ----------------------
oSIST prEN 17020-3:2021
prEN 17020-3:2021 (E)

EN 12605:2017+A1:2020, Industrial, commercial and garage doors and gates - Mechanical aspects - Test

methods

EN 13501-2, Fire classification of construction products and building elements - Part 2: Classification using

data from fire resistance tests, excluding ventilation services

EN 14846, Building hardware - Locks and latches - Electromechanically operated locks and striking plates

- Requirements and test methods

EN 15269-1, Extended application of test results for fire resistance and/or smoke control for door, shutter

and openable window assemblies, including their elements of building hardware - Part 1: General

requirements

EN 15269-7, Extended application of test results for fire resistance and/or smoke control for door, shutter

and openable window assemblies, including their elements of building hardware - Part 7: Fire resistance for

steel sliding doorsets

EN 15685:2015, Building hardware – Multipoint locks, latches and locking plates - Requirements and test

methods
EN ISO 13943, Fire safety - Vocabulary (ISO 13943)
3 Terms and definitions

For the purposes of this document, the terms and definitions given in EN 1191, EN 1363-1,

EN 1363-2, EN 1634-1, EN 1634-3, EN 15269-1, EN 15269-7, EN 12433-1, EN 12433-2 and

EN ISO 13943 and the following apply.

ISO and IEC maintain terminological databases for use in standardization at the following addresses:

— ISO Online browsing platform: available at https://www.iso.org/obp/ui
— IEC Electropedia: available at http://www.electropedia.org/
3.1
full scale test
test of a full size doorset in accordance with EN 12605:2017+A1:2020 or EN 1191
3.2
panel
part of a leaf or element of a doorset indicated as 1 in Figures 1 and 2
---------------------- Page: 8 ----------------------
oSIST prEN 17020-3:2021
prEN 17020-3:2021 (E)
Key
1 panel
2 leaf
3 element
Figure 1 — Double leaf telescopic door
Key
1 panel
2 leaf
Figure 2 — Double leaf sliding door
3.3
leaf
part of a doorset indicated as 2 in Figures 1 and 2
3.4
element
part of a leaf indicated as 3 in Figure 1
4 Determination of the field of extended application
4.1 General

4.1.1 Before there can be any consideration for extended application, the doorset shall have been tested

in accordance with EN 12605:2017+A1:2020 or EN 1191 to achieve a test result which could generate a

classification in accordance with EN 13501-2 and/or correspond to a use category according to

EN 16034.

4.1.2 A review of the doorset construction parameters can indicate, that one or more characteristics

can be improved by a particular parameter variation. All evaluations shall be made on the basis of

retaining the classifications obtainable from testing to EN 12605:2017+A1:2020 and/or EN 1191,

including those with a lower number of opening and closing cycles. However, this shall never lead to an

increased classification for any specific parameter beyond that achieved during any one test unless

specifically identified in the relevant Construction Parameter Variation tables.
---------------------- Page: 9 ----------------------
oSIST prEN 17020-3:2021
prEN 17020-3:2021 (E)

4.1.3 If, when following the extended application procedure, any part of the classified product cannot

be achieved by extended application rules, that part shall be omitted from the subsequent extended

application report and classification report.
4.2 Procedure for evaluation

4.2.1 Identify the variations from the original test specimen(s) which are required to be covered by an

extended application report.

4.2.2 Locate the variations in the appropriate parameter variation by reference to columns (1) and (2)

of Annex A, Table A.1.

4.2.3 Establish from the contents of column (3) of Annex A, Table A.1 whether any extended application

is available without the need for further testing.

4.2.4 Where this is deemed to be possible, this can be recorded in the extended application report

together with any appropriate restrictions and the stated rules from column (3) in Annex A, Table A.1.

4.2.5 Where the variations required can only be achieved from additional testing according to

column (4), the additional test can be made on a similar specimen type to the original test against which

the extended application is sought. Alternatively, column (4) in Table A.1 identifies an option for

alternative testing and relevant test parameters.
4.3 Procedure for maximum field of extended application

4.3.1 It is possible to provide a limited field of extended application from the results of a single test.

However, where a manufacturer intends to produce a range of sliding doors incorporating single leaf

door assemblies and also double leaf door assemblies, with or without pass doors, with or without

glazing, with alternative items of building hardware, etc., it is recommended that careful consideration is

given to the complete range of doorset designs and options in order to minimize the testing required

before testing commences.

4.3.2 Establish all the parameter variations, which are required to be part of the product range.

4.3.3 Determine which are the most important specification requirements and incorporate as many as

possible into the specimen(s) for the first tests in the series.

4.3.4 Conduct the first durability test or a series of tests and then establish, which of the original desired

parameter variations have not been covered by this test(s).

4.3.5 Identify these parameter variations in Annex A, Table A.1 and establish if any extended

application is possible without further testing.

4.3.6 Record this for the extended application report together with any restrictions and rules given in

column (3) in Annex A, Table A.1.

4.3.7 Evaluate which, if any, of the desired parameter variations have not been covered by the initial

field of extended application derived from 4.3.6 above.

4.3.8 Determine if the product range is to include only single leaf doorsets or if the range is to also

include double leaf configurations. Where only single doorsets are to be part of the product range, the

outstanding construction parameter variations shall only be incorporated into specimens for the single

leaf doorsets. Where single leaf and double leaf doorsets are to be included in the product range, the

outstanding construction parameter variations for the extended application of single leaf doorsets may

---------------------- Page: 10 ----------------------
oSIST prEN 17020-3:2021
prEN 17020-3:2021 (E)

be incorporated into either repeated single leaf doorset tests or, in the weakest option, as defined in

column (4) of the table in Annex A, Table A.1, double leaf doorset configurations.

4.3.9 Select the required outstanding parameter variations from column (1) and column (2) of Annex A,

Table A.1 and observe from column (4) of Annex A, Table A.1 which are the most appropriate weakest

specimen options for further testing.

4.3.10 If the complete selection of required parameter variations has not been covered by the tests

completed in accordance with 4.3.8 and 4.3.9 above, then an appropriate test or tests may be carried out

with the additional product variations incorporated.
4.4 Interpretation of test results

4.4.1 In order to maximize the field of extended application, it is important that the test reports shall

record details of any failures occurred throughout the test duration.

4.4.2 Where a series of tests have been conducted, the field of extended application shall be based on

the lowest performance achieved from the complete series of tests unless premature failure has been

attributed to one or more specific construction parameter variations.

4.4.3 Where it has been possible, to identify specific parameter failures, the extended application for

all other construction parameter variations can be based on the performance achieved after isolating the

premature failure(s).
5 Extended application report

Prepare an extended application report in accordance with the requirements of EN 15269-1 based on the

results of evaluations in accordance with the above.
6 Classification report

The classification report shall be determined from the results of the extended application report and shall

be presented in accordance with EN 13501-2:2016, Annex A.
---------------------- Page: 11 ----------------------
oSIST prEN 17020-3:2021
prEN 17020-3:2021 (E)
Annex A
(normative)
Construction parameter variations

Table A.1 below is designed to be used by experts competent in the field of fire resistance and self-closing

durability testing of steel sliding doorsets.

The table shall only be used to assess a field of extended application when at least one positive self-closing

durability test to EN 12605:2017+A1:2020 or EN 1191 has generated a classification according to

EN 13501-2 and EN 16034.

The first two columns identify possible variations to the construction details of the specimen tested. It is

presupposed that the variation does not restrain the door closing.

Column (3) leads to the judgement of the possibility of extending the field of application.

Where additional tests are deemed to be necessary, the type of specimen approved for incorporation of

the changed parameter is defined in column (4). Where it is possible to use information from tests

performed on one configuration for evidence on a different configuration, this allowance has been made

in order to reduce the overall number of tests required for extended application evaluation e.g. single leaf

doorsets to double leaf doorsets.

Where an additional test is required in column (4), the test is a full scale test unless otherwise specified.

In order to maximize the possible field of application from a minimum number of tests, the parameter

changes have been spread over a series of test specimens. Where more than a single parameter variation

is required, the influence on other variations shall also be taken into account.
---------------------- Page: 12 ----------------------
oSIST prEN 17020-3:2021
prEN 17020-3:2021 (E)
Table A.1 — Construction parameter variations

Construction Parameter Variation Possibility of extension Additional Evidence Required

(1) (2) (3) (4)
A Door leaf
A.1 General
Possible providing the overlap of the single leaf
door is similar to the overlap of the double door
(meeting edge) and all the constructional details
A.1.1 Number of leaves (not
Single leaf from double
have been tested (in the double door), otherwise
applicable for vertically Additional test single leaf doorset
leaf door test
not possible without an additional test.
sliding doors)
Any size variations of door leaf shall be in line
with A.2.1 to A.2.4 incl.
A.1.2 Number of leaves (not
Double leaf from single Additional test double leaf doorset
applicable for vertically Not possible without an additional test
leaf door test or double leaf telescopic
sliding doors)
A.1.3 Number of elements of Possible providing all constructional details have
Additional test single or double
telescopic doors, single Decrease been tested, otherwise not possible without an
leaf telescopic
leaf additional test
A.1.4 Number of elements of
Additional test single or double
telescopic doors, single Increase Not possible without an additional test
leaf telescopic
leaf
Possible providing all constructional details have
A.1.5 Number of elements of
been tested and the reduction of elements is the Additional test double leaf
telescopic doors, double Decrease
same for both leaves, otherwise not possible telescopic
leaf — See Figure A.1
without an additional test
A.1.6 Number of elements of
telescopic doors, double Additional test double leaf
Increase Not possible without an additional test
leaf (not applicable for telescopic
vertically sliding doors)
---------------------- Page: 13 ----------------------
oSIST prEN 17020-3:2021
prEN 17020-3:2021 (E)

Construction Parameter Variation Possibility of extension Additional Evidence Required

(1) (2) (3) (4)
Possible if tested at least one leaf (single, primary
or secondary) with the minimum of two panels
A.1.7 Number of panels per
Additional test single or double
and the intended jointing technique centrally
leaf/element- See Add
leaf doorset
located in the door leaf.
Figure A.2
Otherwise not possible without an additional test
A.1.8 Number of panels per
leaf/element- See Reduce Possible -
Figure A.3
A.1.9 Ventilation grilles Possible providing the requirements of Annex B
Additional test single or double
(louvres) in door leaf Add are fulfilled, otherwise not possible without an
leaf doorset
tested without ventilation additional test
A.1.10 Ventilation grilles
Remove Possible -
(louvres) in door leaf
A.1.11 Ventilation grilles
(louvres) in door leaf
Change of Location Possible -
tested with ventilation
grille
Smaller size/Larger size Smaller size: Possible
A.1.12 Ventilation grilles
(louvres) in door leaf Additional test single or double
Larger size: possible providing the requirements
tested with ventilation leaf doorset
of Annex B are fulfilled, otherwise not possible
grille
without an additional test
A.2 Size variations/single or multiple panel construction
A.2.1 Size (area, width, height)
Decrease Possible -
of door leaf
Possible providing the requirements of Annex B Additional test double for single
A.2.2 Width of door leaf — See

Increase are fulfilled, otherwise not possible without an and double leaf door sets or single

Figure A.4
additional test for single leaf door sets
---------------------- Page: 14 ----------------------
oSIST prEN 17020-3:2021
prEN 17020-3:2021 (E)

Construction Parameter Variation Possibility of extension Additional Evidence Required

(1) (2) (3) (4)
Possible providing the requirements of Annex B Additional test double for single
A.2.3 Height of door leaf — See

Increase are fulfilled, otherwise not possible without an and double leaf door sets or single

Figure A.5
additional test for single leaf door sets
Possible providing the requirements of Annex B Additional test double for single

A.2.4 Area of door leaf Increase are fulfilled, otherwise not possible without an and double leaf door sets or single

additional test for single leaf door sets
A.2.5 Width of vertical door leaf
panel for a sliding door Decrease Possible -
with more than one panel
Possible providing the requirements of Annex B Additional test double for single
A.2.6 Height of vertical door

Increase are fulfilled, otherwise not possible without an and double leaf door sets or single

leaf panel
additional test for single leaf door sets
A.2.7 Height of vertical door
Decrease Possible -
leaf panel
Possible providing the requirements of Annex B Additional test double for single
A.2.8 Width of vertical door leaf

Increase are fulfilled, otherwise not possible without an and double leaf door sets or single

panel
additional test for single leaf door sets
Possible providing the requirements of Annex B Additional test double for single
A.2.9 Area of vertical door leaf

Increase are fulfilled, otherwise not possible without an and double leaf door sets or single

panel
additional test for single leaf door sets
A.2.10 Number of horizontal
Increase Possible -
joints between panels
Possible
A.2.11 Number of horizontal
decrease -
joints between panels
---------------------- Page: 15 ----------------------
oSIST prEN 17020-3:2021
prEN 17020-3:2021 (E)

Construction Parameter Variation Possibility of extension Additional Evidence Required

(1) (2) (3) (4)
Additional test double for single
Possible providing the requirements of Annex B
and double leaf door sets or single
are fulfilled and by a maximum of 25 %,
A.2.12 Thickness of the door leaf increase
for single leaf door sets
otherwise not possible without an additional test
Additional test double for single
Possible by a maximum of 25 %,
A.2.13 Thickness of the door leaf Decrease and double leaf door sets or single
otherwise not possible without an additional test
for single leaf door sets
A.3 Materials and constructions
Possible providing the requirements of Annex B Additional test double for single

A.3.1 Density of core material Increase are fulfilled, otherwise not possible without an and double leaf door sets or single

additional test for single leaf door sets
A.3.2 Density of core material Decrease Possible -
Possible providing the requirements of Annex B Additional test double for single
A.3.3 Thickness of core

Increase are fulfilled, otherwise not possible without an and double leaf door sets or single

material
additional test for single leaf door sets
A.3.4 Thickness of core
Decrease Possible -
material
A.3.5 Pattern of core material Increase number of
Possible -
— See Figure A.6 pieces
A.3.6 Pattern of core material Decrease number of
Possible -
— See Figure A.7 pieces
A.3.7 Number of layers of
identical core material — Increase Possible -
See Figure A.8
---------------------- Page: 16 ----------------------
oSIST prEN 17020-3:2021
prEN 17020-3:2021 (E)

Construction Parameter Variation Possibility of extension Additional Evidence Required

(1) (2) (3) (4)
A.3.8 Number of layers of
identical core material — Decrease Possible -
See Figure A.9
A.3.9 Number of layers of
different materials — See Increase Possible -
Figure A.10
A.3.10 Number of layers of
different materials — See Decrease Possible -
Figure A.11
Change of
A.3.11 Core material (single
supplier/manufacturer of
thickness or in
identical material with Possible -
combination of different
identical composition
layers)
and properties
A.3.12 Type of core material
(single thickness or in
Alternative composition Possible -
combination of different
layers)
A.3.13 Amount of adhesives/m
– Products < Euroclass Increase Possible -
A.3.14 Amount of adhesives/m
Possible by a maximum of 50 %
Additional test single or double
– Products < Euroclass Decrease
leaf doorset
otherwise not possible without an additional test

The term "Euroclass A1" stands for the reaction to fire class "A1" according to EN 13501-1.

---------------------- Page: 17 ----------------------
oSIST prEN 17020-3:2021
prEN 17020-3:2021 (E)

Construction Parameter Variation Possibility of extension Additional Evidence Required

(1) (2) (3) (4)
A.3.15 Amount of adhesives/m
– Products of Euroclass Increase Possible -
A.3.16 Amount of adhesives/m
Possible by a maximum of 50 %
Additional test single or double
– Products of Euroclass Decrease
leaf doorset
otherwise not possible without an additional test
Change of
supplier/manufacturer of
A.3.17 Type of adhesives identical material with Possible -
identical composition
and properties
A.3.18 Type of adhesives Alternative composition Possible -
A.3.19 Metal armour sheet
Possible providing the requirements of Annex B Additional test double for single
(internally or externally

Add are fulfilled, otherwise not possible without an and double leaf door sets or single

mounted) — See
additional test for single leaf door sets
Figure A.12
A.3.20 Metal armour sheet
(internally or externally
Remove Possib
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.