EN ISO 16484-5:2008/A1:2009
(Amendment)Building automation and control systems - Part 5: Data communication protocol - Amendment 1 (ISO 16484-5:2008/Amd 1:2009)
Building automation and control systems - Part 5: Data communication protocol - Amendment 1 (ISO 16484-5:2008/Amd 1:2009)
!!MINOR AMENDMENT!! !!MINOR AMENDMENT!! !!MINOR AMENDMENT!! !!MINOR AMENDMENT!!
Systeme der Gebäudeautomation - Teil 5: Datenkommunikationsprotokoll - Änderung 1 (ISO 16484-5:2008/Amd 1:2009)
Systèmes d'automatisation et de gestion technique du bâtiment - Partie 5: Protocole de communication de données - Amendement 1 (ISO 16484-5:2008/Amd 1:2009)
Avtomatizacija stavb in sistemi za regulacijo - 5. del: Protokol izmenjave podatkov - Dodatek (ISO 16484-5:2008/Amd 1:2009)
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
01-oktober-2009
Avtomatizacija stavb in sistemi za regulacijo - 5. del: Protokol izmenjave podatkov
- Dodatek (ISO 16484-5:2008/Amd 1:2009)
Building automation and control systems - Part 5: Data communication protocol -
Amendment 1 (ISO 16484-5:2008/Amd 1:2009)
Systeme der Gebäudeautomation - Teil 5: Datenkommunikationsprotokoll - Änderung 1
(ISO 16484-5:2008/Amd 1:2009)
Systèmes d'automatisation et de gestion technique du bâtiment - Partie 5: Protocole de
communication de données - Amendement 1 (ISO 16484-5:2008/Amd 1:2009)
Ta slovenski standard je istoveten z: EN ISO 16484-5:2008/A1:2009
ICS:
35.240.99 8SRUDEQLãNHUHãLWYH,7QD IT applications in other fields
GUXJLKSRGURþMLK
97.120 Avtomatske krmilne naprave Automatic controls for
za dom household use
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
EUROPEAN STANDARD
EN ISO 16484-5:2008/A1
NORME EUROPÉENNE
EUROPÄISCHE NORM
May 2009
ICS 35.240.99; 91.040.01
English Version
Building automation and control systems - Part 5: Data
communication protocol - Amendment 1 (ISO 16484-
5:2008/Amd 1:2009)
Systèmes d'automatisation et de gestion technique du Systeme der Gebäudeautomation - Teil 5:
bâtiment - Partie 5: Protocole de communication de Datenkommunikationsprotokoll - Änderung 1 (ISO 16484-
données - Amendement 1 (ISO 16484-5:2008/Amd 1:2009) 5:2008/Amd 1:2009)
This amendment A1 modifies the European Standard EN ISO 16484-5:2008; it was approved by CEN on 20 April 2009.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for inclusion of this
amendment into the relevant national standard without any alteration. Up-to-date lists and bibliographical references concerning such
national standards may be obtained on application to the CEN Management Centre or to any CEN member.
This amendment exists in three official versions (English, French, German). A version in any other language made by translation under the
responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as the official
versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland,
France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,
Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2009 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN ISO 16484-5:2008/A1:2009: E
worldwide for CEN national Members.
Contents Page
Foreword .3
Foreword
This document (EN ISO 16484-5:2008/A1:2009) has been prepared by Technical Committee ISO/TC 205
"Building environment design" in collaboration with Technical Committee CEN/TC 247 “Building Automation,
Controls and Building Management” the secretariat of which is held by SNV.
This European Standard shall be given the status of a national standard, either by publication of an identical
text or by endorsement, at the latest by November 2009, and conflicting national standards shall be withdrawn
at the latest by November 2009.
Attention is drawn to the possibility that some of the elements of this document may be the subject of patent
rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights.
According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following
countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Cyprus, Czech
Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain,
Sweden, Switzerland and the United Kingdom.
Endorsement notice
The text of ISO 16484-5:2008/Amd 1:2009 has been approved by CEN as a EN ISO 16484-5:2008/A1:2009
without any modification.
INTERNATIONAL ISO
STANDARD 16484-5
Second edition
2007-03-15
AMENDMENT 1
2009-05-15
Building automation and control
systems —
Part 5:
Data communication protocol
AMENDMENT 1
Systèmes d'automatisation et de gestion technique du bâtiment —
Partie 5: Protocole de communication de données
AMENDEMENT 1
Reference number
ISO 16484-5:2007/Amd.1:2009(E)
©
ISO 2009
ISO 16484-5:2007/Amd.1:2009(E)
PDF disclaimer
This PDF file may contain embedded typefaces. In accordance with Adobe's licensing policy, this file may be printed or viewed but
shall not be edited unless the typefaces which are embedded are licensed to and installed on the computer performing the editing. In
downloading this file, parties accept therein the responsibility of not infringing Adobe's licensing policy. The ISO Central Secretariat
accepts no liability in this area.
Adobe is a trademark of Adobe Systems Incorporated.
Details of the software products used to create this PDF file can be found in the General Info relative to the file; the PDF-creation
parameters were optimized for printing. Every care has been taken to ensure that the file is suitable for use by ISO member bodies. In
the unlikely event that a problem relating to it is found, please inform the Central Secretariat at the address given below.
© ISO 2009
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form or by any means,
electronic or mechanical, including photocopying and microfilm, without permission in writing from either ISO at the address below or
ISO's member body in the country of the requester.
ISO copyright office
Case postale 56 • CH-1211 Geneva 20
Tel. + 41 22 749 01 11
Fax + 41 22 749 09 47
E-mail copyright@iso.org
Web www.iso.org
Published in Switzerland
ii © ISO 2009 – All rights reserved
ISO 16484-5:2007/Amd.1:2009(E)
Foreword
ISO (the International Organization for Standardization) is a worldwide federation of national standards bodies
(ISO member bodies). The work of preparing International Standards is normally carried out through ISO
technical committees. Each member body interested in a subject for which a technical committee has been
established has the right to be represented on that committee. International organizations, governmental and
non-governmental, in liaison with ISO, also take part in the work. ISO collaborates closely with the
International Electrotechnical Commission (IEC) on all matters of electrotechnical standardization.
International Standards are drafted in accordance with the rules given in the ISO/IEC Directives, Part 2.
The main task of technical committees is to prepare International Standards. Draft International Standards
adopted by the technical committees are circulated to the member bodies for voting. Publication as an
International Standard requires approval by at least 75 % of the member bodies casting a vote.
Attention is drawn to the possibility that some of the elements of this document may be the subject of patent
rights. ISO shall not be held responsible for identifying any or all such patent rights.
Amendment 1 to ISO 16484-5:2007 was prepared by Technical Committee ISO/TC 205, Building environment
design.
ISO 16484-5:2007/Amd.1:2009(E)
Introduction
The purpose of this Addendum is to add a number of independent substantive changes to the BACnet
standard. The changes are summarized below.
135-2004a-1, p. 1: Revise Life Safety Point and Life Safety Zone object types to modify their behaviour when
placed out of service.
135-2004c-1, p. 4: Add BACnet/WS Web Services Interface.
135-2004d-1, p. 39: Add a new Structured View object type.
135-2004d-2, p. 45: Allow acknowledgement of unseen TO-OFFNORMAL event notifications.
135-2004d-3, p. 46: Relax the Private Transfer and Text Message BIBB requirements.
135-2004d-4, p. 47: Exclude LIFE_SAFETY and BUFFER_READY notifications from the Alarm Notifications
BIBBs.
135-2004d-5, p. 49: Establish the minimum requirements for a BACnet device with an application layer.
135-2004d-6, p. 51: Remove the requirement for the DM-DOB-A BIBB from the B-OWS and B-BC device
profiles.
135-2004d-7, p. 52: Relax mandated values for APDU timeouts and retries when configurable, and change
default values.
135-2004d-8, p. 53: Fix EventCount handling error in MS/TP Master Node State Machine.
135-2004d-9, p. 54: Permit routers to use a local network number in Device_Address_Binding.
135-2004d-10, p. 55: Identify conditionally writable properties.
135-2004d-11, p. 56: Specify Error returns for the AcknowledgeAlarm service.
135-2004e-1, p. 58: Add a new Load Control object type.
135-2004f-1, p. 71: Add new Access Door object type.
In this Amendment, text being added to existing clauses of ISO 16484-5 is indicated through the use of italics,
while deletions are indicated by strikethrough. Plain type is used throughout where entirely new subclauses
are added.
iv
ISO 16484-5:2007/Amd.1:2009(E)
Building automation and control systems —
Part 5:
Data communication protocol
AMENDMENT 1
135-2004a-1. Revise Life Safety Point and Life Safety Zone object types for out-of-service operation.
Addendum 135-2004a-1
[Change Table 12-18, p. 194]
Table 12-18. Properties of the Life Safety Point Object Type
Property Identifier Property Datatype Conformance Code
... ... ...
Present_Value BACnetLifeSafetyState R R
Tracking_Value BACnetLifeSafetyState OR
... ... ...
[Change 12.15.4, p. 195]
12.15.4 Present_Value
This property, of type BACnetLifeSafetyState, reflects the state of the Life Safety Point object. The means of
deriving the Present_Value shall be a local matter. Present_Value may latch non-NORMAL state values until reset.
The Present_Value property shall be writable when Out_Of_Service is TRUE.
[Change 12.15.5, p. 195]
12.15.5 Tracking_Value
This optional property, of type BACnetLifeSafetyState, reflects the non-latched state of the Life Safety Point object.
The means of deriving the state shall be a local matter. Unlike Present_Value, which may latch non-NORMAL state
values until reset, Tracking_Value shall continuously track changes in the state. The Tracking_Value property shall
be writable when Out_Of_Service is TRUE.
ISO 16484-5:2007/Amd.1:2009(E)
[Change 12.15.11, p. 196]
12.15.11 Out_Of_Service
The Out_Of_Service property, of type BOOLEAN, is an indication whether (TRUE) or not (FALSE) the input(s) or
process the object represents is not in service. This means that changes to the Present_Value Tracking_Value
property are decoupled from the input(s) or process when the value of Out_Of_Service is TRUE. In addition, the
Reliability property and the corresponding state of the FAULT flag of the Status_Flags property shall be decoupled
when Out_Of_Service is TRUE. While the Out_Of_Service property is TRUE, the Present_Value Tracking_Value
and Reliability properties may be changed to any value as a means of simulating specific fixed conditions or for
testing purposes. Other functions that depend on the state of the Present_Value Tracking_Value or Reliability
properties shall respond to changes made to these properties while Out_Of_Service is TRUE, as if those changes had
occurred to the input(s) or process.
[Change Table 12-19, p. 200]
Table 12-19. Properties of the Life Safety Zone Object Type
Property Identifier Property Datatype Conformance Code
... ... ...
Present_Value BACnetLifeSafetyState R R
Tracking_Value BACnetLifeSafetyState O R
... ... ...
[Change 12.16.4, p. 201]
12.16.4 Present_Value
This property, of type BACnetLifeSafetyState, reflects the state of the Life Safety Zone object. The means of
deriving the Present_Value shall be a local matter. Present_Value may latch non-NORMAL state values until reset.
The Present_Value property shall be writable when Out_Of_Service is TRUE.
[Change 12.16.5, p. 201]
12.16.5 Tracking_Value
This optional property, of type BACnetLifeSafetyState, reflects the non-latched state of the Life Safety Zone object.
The means of deriving the state shall be a local matter. Unlike Present_Value, which may latch non-NORMAL state
values until reset, Tracking_Value shall continuously track changes in the state. The Tracking_Value property shall
be writable when Out_Of_Service is TRUE.
[Change 12.16.11, p. 202]
12.16.11 Out_Of_Service
The Out_Of_Service property, of type BOOLEAN, is an indication whether (TRUE) or not (FALSE) the input(s) or
process the object represents is not in service. This means that changes to the Present_Value Tracking_Value
property are decoupled from the input(s) or process when the value of Out_Of_Service is TRUE. In addition, the
Reliability property and the corresponding state of the FAULT flag of the Status_Flags property shall be decoupled
when Out_Of_Service is TRUE. While the Out_Of_Service property is TRUE, the Present_Value Tracking_Value
and Reliability properties may be changed to any value as a means of simulating specific fixed conditions or for
testing purposes. Other functions that depend on the state of the Present_Value Tracking_Value or Reliability
properties shall respond to changes made to
...