Ventilation for buildings - Fire resisting duct sections

This European Standard applies to fire resistant duct sections, which are to be used in conjunction with partitions to maintain fire compartments in heating, ventilating and air conditioning (HVAC) installations. This standard specifies requirements and gives reference to the test methods defined for fire resistant duct sections, which are intended to be installed in heating, ventilation and air conditioning (HVAC) systems in buildings. It also provides the evaluation of conformity of the products to the requirements of this standard. Furthermore, marking and information on installation and maintenance of these products are also given in this European Standard.

Lüftung von Gebäuden - Feuerwiderstandsfähige Leitungen

Diese Europäische Norm
— legt Anforderungen an feuerwiderstandsfähige Leitungsabschnitte und deren Bauteile (z. B. Aufhängungen und andere Elemente als Brandschutzdichtungen, die sich zum Zeitpunkt der Prüfung bewährt haben), die in raumlufttechnischen Anlagen in Gebäuden eingebaut werden sollen, fest und verweist auf entsprechende Prüfverfahren, und
— legt ein Verfahren für den Nachweis der Leistungsbeständigkeit dieser Produkte in Bezug auf die Anforderungen des vorliegenden Dokuments fest, und
— legt die Kennzeichnung und Informationen zum Einbau und zur Instandhaltung dieser Produkte fest.
Dieses Dokument
— gilt für feuerwiderstandsfähige Leitungsabschnitte auf dem Markt, die in feuerwiderstandsfähigen Luftverteilungsleitungssystemen außer Entrauchungsanlagen eingesetzt werden, und
— gilt für zugehörige Bauteile, die zusammen mit den Leitungsabschnitten verwendet werden (z. B. Leitbleche, Schalldämpfer, Zugangsklappen, mit Ausnahme von z. B. Brandschutzklappen, die von anderen Normen abgedeckt werden).
Um eine Redundanz zu vermeiden, wird auf verschiedene andere Normen verwiesen. Aus diesem Grund wird empfohlen, das vorliegende Dokument in Verbindung mit EN 13501-3 für die Klassifizierung und EN 1366-1 und EN 15882-1 für Einzelheiten zur Feuerwiderstandsprüfung und zum direkten und erweiterten Anwendungsbereich zu lesen.
Dieses Dokument berücksichtigt nicht detailliert die schädlichen und/oder korrosiven Auswirkungen durch chemische Prozesse in der Atmosphäre verursacht werden können, die sich beabsichtigt oder unbeabsichtigt durch das System ziehen.

Ventilation des bâtiments - Tronçons de conduits résistants au feu

La présente Norme européenne :
 spécifie les prescriptions et fournit la référence aux méthodes d’essai définies pour les tronçons de
conduits résistants au feu et leurs composants associés (par exemple, les dispositifs de suspension
et autres éléments tels que les joints de calfeutrement éprouvés au moment de l’essai), qui sont
prévus pour être installés dans les systèmes de chauffage, ventilation et climatisation (CVAC) dans
les bâtiments ; et
 spécifie une méthode de vérification de la constance des performances de ces produits par rapport
aux prescriptions du présent document ; et
 spécifie le marquage et les informations relatives à l’installation et à la maintenance de ces
produits.
Le présent document :
 est applicable aux tronçons de conduits résistants au feu mis sur le marché et utilisés dans les
systèmes de conduits de distribution d’air résistants au feu, à l’exclusion des systèmes d’extraction
des fumées ; et
 régit les composants associés utilisés avec des tronçons de conduits (par exemple, les déflecteurs,
les silencieux, les panneaux d’accès, à l’exception, par exemple, des clapets coupe‐feu qui sont
traités dans d’autres normes).
Pour éviter toute duplication, il est fait référence à une variété d’autres normes. À cette fin, il est
recommandé de lire le présent document conjointement à l’EN 13501‐3 pour la classification et
l’EN 1366‐1 et l’EN 15882‐1 pour les détails sur les essais de résistance au feu et le champ d’application
direct et étendu.
Le présent document ne tient pas compte dans le détail des éventuels effets néfastes et/ou corrosifs des
produits chimiques présents dans l’atmosphère et véhiculés par le système, volontairement ou par
accident.

Prezračevanje stavb - Požarno odporni deli kanalov

General Information

Status
Not Published
Current Stage
3098 - Decision to reject - Consensus building
Start Date
06-Dec-2013
Completion Date
06-Dec-2013

Buy Standard

Draft
prEN 15871:2017
English language
26 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
oSIST prEN 15871:2017
01-julij-2017
3UH]UDþHYDQMHVWDYE3RåDUQRRGSRUQLGHOLNDQDORY
Ventilation for buildings - Fire resisting duct sections
Lüftung von Gebäuden - Feuerwiderstandsfähige Leitungen
Ventilation des bâtiments - Tronçons de conduits résistants au feu
Ta slovenski standard je istoveten z: prEN 15871
ICS:
13.220.50 Požarna odpornost Fire-resistance of building
gradbenih materialov in materials and elements
elementov
91.140.30 3UH]UDþHYDOQLLQNOLPDWVNL Ventilation and air-
VLVWHPL conditioning systems
oSIST prEN 15871:2017 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------
oSIST prEN 15871:2017

---------------------- Page: 2 ----------------------
oSIST prEN 15871:2017


DRAFT
EUROPEAN STANDARD
prEN 15871
NORME EUROPÉENNE

EUROPÄISCHE NORM

July 2017
ICS 13.220.99; 91.140.30
English Version

Ventilation for buildings - Fire resisting duct sections
Ventilation des bâtiments - Tronçons de conduits Lüftung von Gebäuden - Feuerwiderstandsfähige
résistants au feu Leitungen
This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee
CEN/TC 156.

If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations
which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.

This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC
Management Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and United Kingdom.

Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are
aware and to provide supporting documentation.

Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without
notice and shall not be referred to as a European Standard.


EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2017 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 15871:2017 E
worldwide for CEN national Members.

---------------------- Page: 3 ----------------------
oSIST prEN 15871:2017
prEN 15871:2017 (E)
Contents Page
European foreword . 4
1 Scope . 5
2 Normative references . 5
3 Terms and definitions . 6
4 Requirements . 7
4.1 Resistance to fire . 7
4.1.1 Performance characteristics of a duct system formed using fire resisting duct
sections . 7
4.2 Durability of resistance to fire . 7
4.3 Reaction to fire . 7
5 Testing, assessment and sampling methods . 7
5.1 Resistance to fire . 7
5.1.1 General . 7
5.1.2 Fire resistance and leakage test . 8
6 Assessment and Verification of Constancy of Performance (AVCP) . 8
6.1 General . 8
6.2 Type Testing . 8
6.2.1 General . 8
6.2.2 Test samples, testing and compliance criteria . 9
6.2.3 Test report . 10
6.2.4 Shared other party results . 10
6.2.5 Cascading determination of the product type results . 10
6.3 Factory product control (FPC) . 11
6.3.1 General . 11
6.3.2 Requirements . 12
6.3.3 Product specific requirements . 15
6.3.4 Initial inspection of factory and of FPC . 15
6.3.5 Continuous surveillance of FPC . 16
6.3.6 Procedure for modifications . 16
6.3.7 One-off products, pre-production products (e.g. prototypes) and products produced
in very low quantity . 16
7 Marking, labelling and packaging . 17
Annex A (informative) Example of inspection procedure . 18
Annex B (normative) Test plan for factory production control supplemental requirements . 19
Annex C (informative) Product, installation and maintenance information (documentation) . 20
C.1 Product specification . 20
C.2 Installation information . 20
C.3 Maintenance information. 21
Annex D (informative) Example of declaration of Performance (DoP) . 22
Annex ZA (informative) Relationship of this European Standard with Regulation (EU)
No 305/2011 . 24
2

---------------------- Page: 4 ----------------------
oSIST prEN 15871:2017
prEN 15871:2017 (E)
ZA.1 Scope and relevant characteristics . 24
ZA.2 System of Assessment and Verification of Constancy of performance (AVCP) . 24
ZA.2.1 System of AVCP . 24
ZA.2.2 Assignment of AVCP tasks . 25
Bibliography . 26
3

---------------------- Page: 5 ----------------------
oSIST prEN 15871:2017
prEN 15871:2017 (E)
European foreword
This document (prEN 15871:2017) has been prepared by Technical Committee CEN/TC 156
“Ventilation for buildings”, the secretariat of which is held by BSI.
This document is currently submitted to the CEN Enquiry.
This document has been prepared under a mandate given to CEN by the European Commission and the
European Free Trade Association, and supports essential requirements of EU Directive 89/106/EEC.
For relationship with EU Directive, see informative Annex ZA, which is an integral part of this
document.
4

---------------------- Page: 6 ----------------------
oSIST prEN 15871:2017
prEN 15871:2017 (E)
1 Scope
This European Standard:
— specifies requirements and gives reference to the test methods defined for fire resisting duct
sections and their associated components (e.g. hangers and other items as fire stopping seals
proven at the time of testing), which are intended to be installed in heating, ventilation and air
conditioning (HVAC) systems in buildings, and
— specifies a method for the verification of constancy of performance of these products to the
requirements of this document, and
— specifies the marking and information on installation and maintenance of these products.
This document:
— is applicable to fire resisting duct sections placed on the market used in fire resisting air
distribution duct systems excluding smoke extraction systems, and
— governs associated components used together with duct sections (e.g. turning vanes, silencers,
access panels, with the exceptions of, e.g. fire dampers which are covered by separate standards).
To avoid duplication, reference is made to a variety of other standards. To this end, it is advised to read
this document in conjunction with EN 13501-3 for classification and EN 1366-1 and EN 15882-1 for
details of the fire resistance testing and the direct and extended field of application.
This document does not consider in detail the detrimental and/or corrosive effects that can be caused
by chemical processes present in the atmosphere, which are drawn through the system intentionally or
inadvertently.
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application. For dated references, only the edition cited applies. For undated
references, the latest edition of the referenced document (including any amendments) applies.
EN 1363-1, Fire resistance tests ― Part 1: General Requirements
EN 1366-1, Fire resistance tests for service installations ― Part 1: Ventilation ducts
EN 1507, Ventilation for buildings ― Sheet metal air ducts with rectangular section ― Requirements for
strength and leakage
EN 12237, Ventilation for buildings ― Ductwork ― Strength and leakage of circular sheet metal ducts
EN 12792, Ventilation for buildings ― Symbols, terminology and graphical symbols
EN 13501-1, Fire classification of construction products and building elements ― Part 1: Classification
using data from reaction to fire tests
EN 13501-3, Fire classification of construction products and building elements ― Part 3: Classification
using data from fire resistance tests on products and elements used in building service installations ― Fire
resisting ducts and fire dampers
EN 15882-1, Extended application of results from fire resistance tests for service installations ― Part 1:
Ducts
5

---------------------- Page: 7 ----------------------
oSIST prEN 15871:2017
prEN 15871:2017 (E)
EN ISO 1101, Geometrical product specifications (GPS) ― Geometrical tolerancing ― Tolerances of form,
orientation, location and run-out (ISO 1101)
EN ISO 8015, Geometrical product specifications (GPS) ― Fundamentals ― Concepts, principles and rules
(ISO 8015)
EN ISO 13943, Fire safety - Vocabulary (ISO 13943)
3 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 12792, EN 1363-1 and
EN ISO 13943 and the following apply.
3.1
fire resisting duct section
length of duct without any intermediate transverse joints designed to be combined with other fire
resisting duct sections to form a fire resistant duct system; if applicable this includes e.g. access panels,
seals, flanges, connection fittings incorporated in the duct section
Note 1 to entry: The fire resisting duct sections are placed on the market by the manufacturer and sold to
another party to install in fire resisting duct systems.
3.2
fire stopping seal
product used between the fire resisting duct section and the fire compartment boundary structure to
maintain the fire resistance when tested and having met the requirements of EN 1366-1 and EN 15882-
1 as appropriate at the position where a fire resisting duct section passes through the fire compartment
boundary structure (wall or floor)
3.3
structural support
means of retaining the fire resisting duct section to the building structure
3.4
access panel
cover for an inspection opening within the duct
3.5
manufacturer
any natural or legal person who manufactures a construction product or who has such a product
designed or manufactured, and markets that product under his name or trademark
3.6
fire resistant duct system
duct system which includes all items incorporated, e.g. fire resisting duct sections, duct seals and
connections, support system and fire stopping seals, and has been classified in accordance with
EN 13501-3
6

---------------------- Page: 8 ----------------------
oSIST prEN 15871:2017
prEN 15871:2017 (E)
4 Requirements
4.1 Resistance to fire
4.1.1 Performance characteristics of a duct system formed using fire resisting duct sections
4.1.1.1 General
The performances given in 4.1.1.2 to 4.1.1.6 shall be determined.
4.1.1.2 Integrity
Integrity shall be based upon fire tests of ducts carried out in accordance with EN 1366-1 and
EN 15882-1. The integrity (E) class shall be determined in accordance with EN 13501-3 and declared by
the manufacturer.
4.1.1.3 Insulation
Insulation shall be based upon fire tests of ducts carried out in accordance with EN 1366-1 and
EN 15882-1. The insulation (I) class shall be determined in accordance with EN 13501-3 and declared
by the manufacturer.
4.1.1.4 Smoke leakage
Smoke leakage shall be based upon fire tests of ducts carried out in accordance with EN 1366-1 and
EN 15882-1. The smoke leakage (S) class shall be determined in accordance with EN 13501-3 and
declared by the manufacturer.
4.1.1.5 Mechanical stability
Mechanical stability shall be demonstrated by achieving integrity in accordance with 5.1.2.6.
4.1.1.6 Maintenance of cross section
Maintenance of cross section shall be demonstrated by achieving integrity in accordance with 5.1.2.7.
4.2 Durability of resistance to fire
Durability of fire resistance is ensured if the mounting and fixing conditions prescribed by the
manufacturer’s installation instruction are followed during the installation phase on site.
4.3 Reaction to fire
If reaction to fire is required in some member states, the components of a fire resisting duct section
shall be classified in accordance with EN 13501-1.
5 Testing, assessment and sampling methods
5.1 Resistance to fire
5.1.1 General
The test samples shall be selected in accordance with Table 1. The fire resisting duct sections shall be
installed in a furnace and subjected to the fire resistance test in accordance with EN 1366-1 and if
required as described in EN 15882-1.
7

---------------------- Page: 9 ----------------------
oSIST prEN 15871:2017
prEN 15871:2017 (E)
5.1.2 Fire resistance and leakage test
5.1.2.1 Resistance to fire
The test method and equipment shall be in accordance with EN 1366-1.
5.1.2.2 Leakage test
The test method and equipment shall be in accordance with EN 1366-1 at ambient temperature.
5.1.2.3 Fire resisting duct sections – Structural supports
Observations shall be made as to the satisfactory performance of the structural supports according to
EN 1366-1 and if required as described in EN 15882-1. The structural support method and relevant
material names and references shall be recorded.
5.1.2.4 Fire resisting duct sections – Duct sealant materials
Observations shall be made as to the satisfactory performance of the duct sealant according to
EN 1366-1. The duct sealant name and reference shall be recorded.
5.1.2.5 Penetration seals (between fire compartments)
Observations shall be made as to the satisfactory performance of the penetration seals according to
EN 1366-1. The penetration seal method and relevant material names and references shall be recorded.
5.1.2.6 Mechanical stability
Observations shall be made as to the satisfactory mechanical stability of the fire resisting duct sections
according to EN 1366-1.
5.1.2.7 Maintenance of cross section
Observations shall be made as to the satisfactory maintenance of cross section of the fire resisting duct
sections according to EN 1366-1.
6 Assessment and Verification of Constancy of Performance (AVCP)
6.1 General
The compliance of a fire resisting duct section with the requirements of this standard and with the
performances declared by the manufacturer in the DoP shall be demonstrated by:
— determination of the product type;
— factory production control by the manufacturer, including product assessment.
The manufacturer shall always retain the overall control and shall have the necessary means to take
responsibility for the conformity of the product with its declared performance(s).
Annex D gives an example of declaration of Performance (DoP).
6.2 Type Testing
6.2.1 General
All performances related to characteristics included in this standard shall be determined when the
manufacturer intends to declare the respective performances unless this standard gives provisions for
declaring them without performing tests. (e.g. use of previously existing data, classified without further
testing (CWFT) and conventionally accepted performance).
8

---------------------- Page: 10 ----------------------
oSIST prEN 15871:2017
prEN 15871:2017 (E)
Assessment previously performed in accordance with the provisions of this standard, may be taken into
account provided that they were made to the same or a more rigorous test method, under the same
AVCP system on the same product or products of similar design, construction and functionality, such
that the results are applicable to the product in question.
NOTE Same AVCP system means testing by an independent third party, under the responsibility of a notified
product certification body.
For the purposes of assessment, the manufacturer’s products may be grouped into families, where it is
considered that the results for one more characteristics from any one product within the family are
representative for those same characteristics for all products within that same family.
Products may be grouped in different families for different characteristics.
Reference to the assessment method standards should be made to allow the selection of a suitable
representative sample.
In addition, the determination of the product type shall be performed for all characteristics included in
the standard for which the manufacturer declares the performance:
— at the beginning of the production of a new or modified fire resisting duct section (unless a member
of the same family), or
— at the beginning of a new or modified method of production (where this may affect the stated
properties), or
they shall be repeated for the appropriate characteristic(s), whenever a change occurs in the fire
resisting duct section design, in the raw material or in the supplier of the components, or in the method
of production (subject to the definition of a family), which would affect significantly one or more of the
characteristics.
Where components are used whose characteristics have already been determined, by the component
manufacturer, on the basis of assessment methods of other product standards, these characteristics
need not be re-assessed. The specifications of these components shall be documented.
Products bearing regulatory marking in accordance with appropriate harmonized European
specifications may be presumed to have the performances declared in the DoP, although this does not
replace the responsibility on the fire resisting duct section manufacturer to ensure that the fire resisting
duct section as a whole is correctly manufactured and its component products have the declared
performance values.
6.2.2 Test samples, testing and compliance criteria
The number of test samples of fire resisting duct sections to be tested/assessed shall be in accordance
with Table 1.
Table 1 — Number of samples to be tested and compliance criteria
Characteristic Requirement Assessment Number of Compliance
method samples criteria
Resistance to 4.1.1 5.1.2 a 4.1.2
fire
a
Number of samples depends of the manufacturer’s decision for range of application and test standard
EN 1366–1 and EN 15882–1.
9

---------------------- Page: 11 ----------------------
oSIST prEN 15871:2017
prEN 15871:2017 (E)
6.2.3 Test report
The results of the determination of the product type shall be documented in test reports. All test reports
shall be retained by the manufacturer for at least 10 years after the last date of production of the fire
resisting duct section to which they relate.
6.2.4 Shared other party results
A manufacturer may use the results of the product type determination obtained by someone else (e.g.
by another manufacturer, as a common service to manufacturers, or by a product developer), to justify
his own declaration of performance regarding a product that is manufactured according to the same
design (e.g. dimensions) and with raw materials, constituents and manufacturing methods of the same
kind, provided that:
— the results are known to be valid for products with the same essential characteristics relevant for
the product performance;
— in addition to any information essential for confirming that the product has such same
performances related to specific essential characteristics, the other party who has carried out the
1)
determination of the product type concerned or has had it carried out, has expressly accepted to
transmit to the manufacturer the results and the test report to be used for the latter’s product type
determination, as well as information regarding production facilities and the production control
process that can be taken into account for FPC;
— the manufacturer using other party results accepts to remain responsible for the product having
the declared performances and he also:
— ensures that the product has the same characteristics relevant for performance as the one that
has been subjected to the determination of the product type, and that there are no significant
differences with regard to production facilities and the production control process compared
to that used for the product that was subjected to the determination of the product type, and
— keeps available a copy of the determination of the product type report that also contains the
information needed for verifying that the product is manufactured according to the same
design and with raw materials, constituents and manufacturing methods of the same kind.
6.2.5 Cascading determination of the product type results
For some construction products, there are companies (often called “system houses”) which supply or
2)
ensure the supply of, on the basis of an agreement, some or all of the components (e.g. in case of
3)
windows: profiles, gaskets, weather strips) to an assembler who then manufactures the finished
product (referred to below as the “assembler”) in his factory.
Provided that the activities for which such a system house is legally established include
manufacturing/assembling of products as the assembled one, the system house may take the
responsibility for the determination of the product type regarding one or several essential

1)
The formulation of such an agreement can be done by license, contract, or any other type of written consent.
2)
This can be, for instance, a contract, license or whatever kind of written agreement, which should also contain
clear provisions with regard to responsibility and liability of the component producer (system house, on the one
hand, and the assembler of the finished product, on the other hand).
3)
These companies may produce components but they are not required to do so.
10

---------------------- Page: 12 ----------------------
oSIST prEN 15871:2017
prEN 15871:2017 (E)
characteristics of an end product which is subsequently manufactured and/or assembled by other firms
in their own factory.
When doing so, the system house shall submit an “assembled product” using components manufactured
by it or by others, to the determination of the product type and then make the determination of the
product type report available to the assemblers, i.e. the actual manufacturer of the product placed on
the market.
To take into account such a situation, the concept of cascading determination of the product type might
be taken into consideration in the technical specification, provided that this concerns characteristics for
which either a notified product certification body or a notified test laboratory intervene, as presented
below.
The determination of the product type report that the system house has obtained with regard to tests
carried out by a notified body, and which is supplied to the assemblers, may be used for the regulatory
marking purposes without the assembler having to involve again a notified body to undertake the
determination of the product type of the essential characteristic(s) that were already tested, provided
that:
— the assembler manufactures a product which uses the same combination of components
(components with the same characteristics), and in the same way, as that for which the system
house has obtained the determination of the product type report. If this report is based on a
combination of components not representing the final product as to be placed on the market,
and/or is not assembled in accordance with the system house’s instruction for assembling the
components, the assembler needs to submit his finished product to the determination of the
product type;
— the system house has notified to the manufacturer the instructions for manufacturing/assembling
the product and installation guidance;
— the assembler (manufacturer) assumes the responsibility for the correct assembly of the product in
accordance with the instructions for manufacturing/assembling the product and installation
guidance notified to him by the system house;
— the instructions for manufacturing/assembling the product and installation guidance notified to the
assembler (manufacturer) by the system house are an integral part of the assembler’s Factory
Production Control system and are referred to in the determination of the product type report;
— the assembler is able to provide documented evidence that the combination of components he is
using, and his way of manufacturing, correspond to the one for which the system house has
obtained the determination of the product type report (he needs to keep a copy of the system
house’s determination of the product type report);
— regardless the possibility of referring, on the basis of the agreement signed with the system house,
to the latter’s responsibility and liability under private law, the assembler remains responsible for
the product being in compliance with the declared performances, including both the design and
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.