EN 54-26:2015
(Main)Fire detection and fire alarm systems - Part 26: Carbon monoxide detectors - Point detectors
Fire detection and fire alarm systems - Part 26: Carbon monoxide detectors - Point detectors
This European Standard specifies requirements, test methods and performance criteria for point detectors using carbon monoxide sensing for use in fire detection and fire alarm systems in and around buildings (see EN 54 1:2011).
This European Standard provides for the assessment and verification of consistency of performance (AVCP) of carbon monoxide point detectors to this EN.
This European Standard does not cover fire detectors incorporating at least one CO sensing element in combination with other elements sensing different fire phenomena.
CO detectors having special characteristics suitable for the detection of specific fire risks are not covered by this European Standard. The performance requirements for any additional functions are beyond the scope of this European Standard (e.g. additional features or enhanced functionality for which this standard does not define a test or assessment method).
Brandmeldeanlagen - Teil 26: Kohlenmonoxidmelder - Punktförmige Melder
Diese Europäische Norm legt Anforderungen, Prüfverfahren und Leistungsmerkmale für punktförmige Melder fest, die Kohlenmonoxid erkennen und die in Brandmelde- und Feueralarmanlagen in und um Gebäude eingesetzt werden (siehe EN 54 1:2011).
Diese Europäische Norm sieht die Bewertung und Überprüfung der Leistungsbeständigkeit (AVCP, en: assessment and verification of consistency of performance ) von punktförmigen Kohlenmonoxidmeldern nach dieser EN vor.
Nicht Gegenstand dieser Europäischen Norm sind Brandmelder, die neben mindestens einem CO-Sensor in Kombination andere Sensoren zum Erkennen unterschiedlicher Brandkenngrößen enthalten.
CO-Brandmelder mit speziellen Merkmalen, die zur Erkennung besonderer Brandgefahren geeignet sind, sind nicht Gegenstand dieser Europäischen Norm. Die Leistungsanforderungen an zusätzliche Funktionen liegen nicht im Anwendungsbereich dieser Europäischen Norm (z. B. zusätzliche Merkmale oder erweiterter Funktionsumfang, für den die vorliegende Norm keine Prüf- oder Bewertungsverfahren festlegt).
Système de détection et d'alarme incendie - Partie 26: Détecteurs de monoxide de carbone - Détecteurs ponctuels
La présente Norme européenne spécifie les exigences, les méthodes d'essais et les critères de performance des détecteurs ponctuels fonctionnant suivant le principe de la détection de monoxyde de carbone, utilisés dans les systèmes de détection et d'alarme incendie installés dans et autour des bâtiments (voir l'EN 54 1:2011).
La présente Norme européenne prévoit l'évaluation et la vérification de la constance des performances (EVCP) des détecteurs ponctuels de monoxyde de carbone par rapport à la présente EN.
La présente Norme européenne ne prend pas en compte les détecteurs d'incendie qui combinent au moins un élément de détection de CO avec d'autres éléments de détection de différents phénomènes d'incendie.
Les détecteurs de CO possédant des caractéristiques particulières adaptées à la détection des risques d'incendie spécifiques ne sont pas pris en compte par la présente Norme européenne. Les exigences de performance relatives à toute autre fonction supplémentaire ne relèvent pas du domaine d'application de la présente Norme européenne (par exemple, caractéristiques supplémentaires ou fonctionnalité améliorée pour lesquelles la présente norme ne définit pas de méthode d'essai ou d'évaluation).
Sistemi za odkrivanje in javljanje požara ter alarmiranje - 26. del: Javljalniki ogljikovega monoksida - Točkovni javljalniki
General Information
Standards Content (Sample)
SLOVENSKI STANDARD
01-junij-2015
6LVWHPL]DRGNULYDQMHLQMDYOMDQMHSRåDUDWHUDODUPLUDQMHGHO-DYOMDOQLNL
RJOMLNRYHJDPRQRNVLGD7RþNRYQLMDYOMDOQLNL
Fire detection and fire alarm systems - Part 26: Carbon monoxide detectors - Point
detectors
Brandmeldeanlagen - Teil 26: Kohlenmonoxidmelder - Punktfoermige Melder
Système de détection et d'alarme incendie - Partie 26: Détecteurs de monoxide de
carbone - Détecteurs ponctuels
Ta slovenski standard je istoveten z: EN 54-26:2015
ICS:
13.220.20 3RåDUQD]DãþLWD Fire protection
13.320 Alarmni in opozorilni sistemi Alarm and warning systems
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
EUROPEAN STANDARD
EN 54-26
NORME EUROPÉENNE
EUROPÄISCHE NORM
April 2015
ICS 13.220.20
English Version
Fire detection and fire alarm systems - Part 26: Carbon
monoxide detectors - Point detectors
Système de détection et d'alarme incendie - Partie 26: Brandmeldeanlagen - Teil 26: Kohlenmonoxidmelder -
Détecteurs de monoxide de carbone - Détecteurs ponctuels Punktfoermige Melder
This European Standard was approved by CEN on 25 January 2015.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national
standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same
status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United
Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2015 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 54-26:2015 E
worldwide for CEN national Members.
Contents Page
Foreword .5
Introduction .7
1 Scope .8
2 Normative references .8
3 Terms, definitions and abbreviations .9
3.1 Terms and definitions .9
3.2 Abbreviations .9
4 Requirements .9
4.1 General .9
4.2 Nominal activation conditions/sensitivity .9
4.2.1 Individual alarm indication .9
4.2.2 Rate sensitive CO response .9
4.2.3 Response to slowly developing fires.9
4.2.4 Repeatability . 10
4.2.5 Directional dependence . 10
4.2.6 Reproducibility . 10
4.2.7 Air movement . 10
4.3 Operational reliability . 10
4.3.1 Connection of ancillary devices . 10
4.3.2 Monitoring of detachable detectors . 10
4.3.3 Manufacturer's adjustments . 10
4.3.4 On-site adjustment of behaviour . 10
4.3.5 Software controlled detectors . 11
4.3.6 Long term stability . 12
4.4 Tolerance to supply voltage — Variation in supply parameters . 12
4.5 Performance parameters under fire conditions — Fire sensitivity . 12
4.6 Durability of nominal activation conditions/sensitivity . 12
4.6.1 Temperature resistance . 12
4.6.2 Humidity resistance . 12
4.6.3 Corrosion resistance — SO corrosion (endurance) . 13
4.6.4 Shock and vibration resistance . 13
4.6.5 Electrical stability — EMC, immunity (operational) . 13
4.6.6 Resistance to chemical agents . 13
5 Test and assessment methods . 14
5.1 General . 14
5.1.1 Atmospheric conditions for tests . 14
5.1.2 Operating conditions for tests . 14
5.1.3 Mounting arrangements . 14
5.1.4 Tolerances . 14
5.1.5 Measurement of CO response value. 14
5.1.6 Provision for tests . 15
5.1.7 Test schedule . 15
5.2 Nominal activation conditions/sensitivity . 16
5.2.1 Individual alarm indication . 16
5.2.2 Rate sensitive CO response . 17
5.2.3 Response to slowly developing fires. 17
5.2.4 Repeatability . 17
5.2.5 Directional dependence . 18
5.2.6 Reproducibility . 18
5.2.7 Air movement . 19
5.3 Operational reliability . 19
5.3.1 Connection of ancillary devices . 19
5.3.2 Monitoring of detachable detectors . 19
5.3.3 Manufacturer's adjustments . 19
5.3.4 On-site adjustment of behaviour . 19
5.3.5 Software controlled detectors . 19
5.3.6 Long term stability . 19
5.4 Tolerance to supply voltage . 20
5.4.1 Variation in supply parameters . 20
5.5 Performance parameters under fire conditions . 21
5.5.1 Fire sensitivity . 21
5.6 Durability of nominal activation conditions/sensitivity . 23
5.6.1 Temperature resistance . 23
5.6.2 Humidity resistance . 25
5.6.3 Corrosion resistance — SO corrosion (endurance) . 29
5.6.4 Shock and vibration resistance . 30
5.6.5 Electrical stability . 34
5.6.6 Resistance to chemical agents . 35
6 Assessment and verification of constancy of performance (AVCP) . 37
6.1 General . 37
6.2 Type testing . 37
6.2.1 General . 37
6.2.2 Test samples, testing and compliance criteria . 38
6.2.3 Test reports . 39
6.3 Factory production control (FPC) . 39
6.3.1 General . 39
6.3.2 Requirements . 40
6.3.3 Product specific requirements . 42
6.3.4 Initial inspection of factory and FPC . 42
6.3.5 Continuous surveillance of FPC . 43
6.3.6 Procedure for modifications.
...
Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.