EN 17020-5:2023
(Main)Extended application of test results on durability of self-closing for fire resistance and/or smoke control doorsets and openable windows - Part 5: Durability of self-closing of hinged and pivoted timber doorsets
Extended application of test results on durability of self-closing for fire resistance and/or smoke control doorsets and openable windows - Part 5: Durability of self-closing of hinged and pivoted timber doorsets
This document is applicable to single and double leaf, hinged and pivoted doorsets with timber-based leaves or timber framed glazed door leaves, covered by EN 15269-3 and / or EN 15269-20.
This document prescribes the methodology for extending the application of test results obtained from durability of self-closing test(s) conducted in accordance with EN 1191 and or EN 12605:2000, as appropriate.
Subject to the completion of the appropriate self-closing test(s), the extended application can cover all or some of the following examples:
- door leaf; pass doors;
- glazed doorsets including vision panels and framed glazed doorsets;
- side, transom and/or overpanels;
- ventilation grilles and/or louvres;
- wall or ceiling fixed elements (door frame/suspension system);
- glazing for door leaf, side, transom and flush over panels;
- items of building hardware;
- decorative finishes;
- intumescent, strips, smoke, draught or acoustic seals;
- alternative supporting construction(s).
Erweiterte Anwendung von Prüfergebnissen zur Dauerhaftigkeit der Selbstschließung für Feuerschutz- und/oder Rauchschutztüren und zu öffnende Fenster - Teil 5: Dauerhaftigkeit der Selbstschließung von Drehflügeltüren aus Holz
Dieses Dokument ist anwendbar für ein- und zweiflügelige Drehflügeltüren mit Türflügeln aus Holz oder verglasten Türflügeln mit Holzrahmen, wie in EN 15269 3 und/oder EN 15269 20 beschrieben.
Dieses Dokument schreibt die Methodik zur Erweiterung der Anwendung von Prüfergebnissen zur Dauerhaftigkeit der Selbstschließung vor, die nach EN 1191 bzw. nach EN 12605:2000 durchgeführt wurden.
In Abhängigkeit von der Durchführung der entsprechenden Prüfung(en) zur Dauerhaftigkeit der Selbstschließung kann die erweiterte Anwendung die nachfolgende nicht-abschließende Auflistung ganz oder auch nur teilweise abdecken:
Türflügel; Schlupftüren;
verglaste Türelemente einschließlich Sichtfenster und verglaste Rahmentürelemente;
Seitenteile, Oberblenden und/oder Oberteile mit Kämpfern;
Lüftungsgitter und/oder lamellen;
an der Wand/oder Decke befestigte Elemente (Türzarge/Aufhängungssystem);
Verglasung für Türflügel, Seitenteile, Oberteile mit Kämpfern und bündige Oberblenden;
Baubeschläge;
dekorative Beschichtungen;
dämmschichtbildende Streifen, Dichtungen zur Behinderung von Rauchdurchtritt (Rauchschutzdichtungen), Durchzug oder Schallübertragung (Schallschutzdichtungen);
alternative Tragkonstruktion(en).
Application étendue des résultats d’essai de durabilité de fermeture automatique pour les blocs-portes coupe-feu et/ou pare-fumée et les fenêtres ouvrantes - Partie 5 : Durabilité de la fermeture automatique des blocs-portes battants et pivotants en bois
Le présent document s’applique aux blocs-portes battants et pivotants à vantaux en bois ou vitrés à ossature bois, à un ou deux vantaux, visés par l’EN 15269-3 et/ou l’EN 15269-20.
Le présent document établit la méthodologie d’extension de l’application des résultats d’essai obtenus à la suite d’essais de durabilité de la fermeture automatique réalisés conformément à l’EN 1191 et/ou l’EN 12605:2000, suivant le cas.
Sous réserve de la réalisation de l’essai ou des essais de fermeture automatique appropriés, l’application étendue peut couvrir tout ou partie des exemples suivants :
- vantail ; portes de passage ;
- blocs-portes vitrés dont les regards vitrés et les blocs-portes vitrés à ossature ;
- panneaux latéraux, supérieurs et/ou d’imposte ;
- grilles de ventilation et/ou jalousies ;
- éléments fixes muraux ou de plafond (dormant/système de suspension) ;
- vitrage pour vantail ou panneaux latéraux, supérieurs affleurants et d’imposte ;
- tout élément de quincaillerie de bâtiment ;
- finitions décoratives ;
- garnitures d’étanchéité intumescentes, bandes, garnitures d’étanchéité aux fumées, garnitures d’étanchéité à l’air ou calfeutrements acoustiques ;
- autre(s) support(s).
Razširjena uporaba rezultatov preskusov trajnosti samozapiranja za požarno odporna in/ali dimotesna vrata in okna, ki se odpirajo - 5. del: Trajnost samozapiranja lesenih vrat na tečajih z vrtljivim krilom
Ta dokument se uporablja za enokrilna in dvokrilna vrata s tečajnim ali vrtljivim lesenim krilom ali zastekljena vrata z lesenim okvirom, obravnavana v standardu EN 15269-3 oziroma EN 15269-20.
Ta dokument predpisuje metodologijo za razširitev uporabe rezultatov, pridobljenih iz preskusov trajnosti samozapiranja, izvedenih v skladu s standardom EN 1191.
Razširjena uporaba lahko (glede na opravljene ustrezne preskuse samozapiranja) zajema vse ali nekatere primere:
– – vratno krilo; prehodna vrata;
– stekleni elementi, vključno z zastekljenimi ploščami in steklenimi vrati;
– stranice, tramovi in/ali podboji;
– prezračevalne rešetke in/ali žaluzijske lopute;
– stensko/stropno okovje (okvir/sistem vzmetenja);
– steklo za vratno krilo, stranice, tramove in poravnane podboje;
– elementi stavbnega okovja;
– okrasni zaključki;
– intumescentna, dimna, akustična tesnila in tesnila za preprečevanje prepiha;
– alternativne podporne konstrukcije.
General Information
Standards Content (Sample)
SLOVENSKI STANDARD
01-junij-2023
Razširjena uporaba rezultatov preskusov trajnosti samozapiranja za požarno
odporna in/ali dimotesna vrata in okna, ki se odpirajo - 5. del: Trajnost
samozapiranja lesenih vrat na tečajih z vrtljivim krilom
Extended application of test results on durability of self-closing for fire resistance and/or
smoke control doorsets and openable windows - Part 5: Durability of self-closing of
hinged and pivoted timber doorsets
Erweiterter Anwendungsbereich von Prüfergebnissen zur Dauerhaftigkeit des
Selbstschließens für Feuerschutz- und/oder Rauchschutztüren und zu öffnende Fenster
- Teil 5: Dauerhaftigkeit der Selbstschließung von Drehflügeltüren und zu öffnenden
Fenstern aus Holz
Application étendue des résultats d’essai de durabilité de fermeture automatique pour
les blocs portes coupe feu et/ou pare fumée et les fenêtres ouvrantes - Partie 5 :
Durabilité de la fermeture automatique des blocs portes battants et pivotants en bois
Ta slovenski standard je istoveten z: EN 17020-5:2023
ICS:
13.220.50 Požarna odpornost Fire-resistance of building
gradbenih materialov in materials and elements
elementov
91.060.50 Vrata in okna Doors and windows
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
EN 17020-5
EUROPEAN STANDARD
NORME EUROPÉENNE
March 2023
EUROPÄISCHE NORM
ICS 13.220.50; 91.060.50
English Version
Extended application of test results on durability of self-
closing for fire resistance and/or smoke control doorsets
and openable windows - Part 5: Durability of self-closing
of hinged and pivoted timber doorsets
Application étendue des résultats d'essai de durabilité Erweiterter Anwendungsbereich von Prüfergebnissen
de fermeture automatique pour les blocs-portes coupe- zur Dauerhaftigkeit des Selbstschließens für
feu et/ou pare-fumée et les fenêtres ouvrantes - Partie Feuerschutz- und/oder Rauchschutztüren und zu
5 : Durabilité de la fermeture automatique des blocs- öffnende Fenster - Teil 5: Dauerhaftigkeit der
portes battants et pivotants en bois Selbstschließung von Drehflügeltüren und zu
öffnenden Fenstern aus Holz
This European Standard was approved by CEN on 6 February 2023.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this
European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references
concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN
member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by
translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Türkiye and
United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2023 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 17020-5:2023 E
worldwide for CEN national Members.
Contents Page
European foreword . 3
Introduction . 4
1 Scope . 5
2 Normative references . 5
3 Terms and definitions . 7
4 Determination of the field of extended application . 9
4.1 General . 9
4.2 Procedure for evaluation . 9
4.3 Procedure for maximum field of extended application . 9
4.4 Interpretation of test results . 10
5 Extended application report . 10
6 Classification report . 10
Annex A (normative) Construction parameter variations . 11
Annex B (normative) Arrangements for hinged and pivoted doorsets incorporating side
and/or flush over panels . 69
Annex C (normative) Construction parameter variations . 77
Bibliography . 78
European foreword
This document (EN 17020-5:2023) has been prepared by Technical Committee CEN/TC 127 “Fire safety
in buildings”, the secretariat of which is held by BSI.
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by September 2023, and conflicting national standards shall
be withdrawn at the latest by September 2023.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN shall not be held responsible for identifying any or all such patent rights.
A list of all parts in the EN 17020 series and the EN 15269 series can be found on the CEN website.
Any feedback and questions on this document should be directed to the users’ national standards body.
A complete listing of these bodies can be found on the CEN website.
According to the CEN-CENELEC Internal Regulations, the national standards organisations of the
following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia,
Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland,
Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Republic of North
Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Türkiye and the United
Kingdom.
Introduction
The EN 15269 series of standards covering extended application of test results for fire resistance and/or
smoke control for doorsets, openable window and shutter assemblies, including their items of building
hardware, does not yet include the durability of self-closing following an extended application process.
This document is one of the EN 17020 series of standards intended to be used for the purpose of
producing an extended application report based on the evaluation of one or more durability of self-
closing tests. These European standards may also be used to identify the best selection of test specimens
required to cover a wide range of product variations.
1 Scope
This document is applicable to single and double leaf, hinged and pivoted doorsets with timber-based
leaves or timber framed glazed door leaves, covered by EN 15269-3 and / or EN 15269-20.
This document prescribes the methodology for extending the application of test results obtained from
durability of self-closing test(s) conducted in accordance with EN 1191 and or EN 12605:2000, as
appropriate.
Subject to the completion of the appropriate self-closing test(s), the extended application can cover all or
some of the following examples:
— door leaf; pass doors;
— glazed doorsets including vision panels and framed glazed doorsets;
— side, transom and/or overpanels;
— ventilation grilles and/or louvres;
— wall or ceiling fixed elements (door frame/suspension system);
— glazing for door leaf, side, transom and flush over panels;
— items of building hardware;
— decorative finishes;
— intumescent, strips, smoke, draught or acoustic seals;
— alternative supporting construction(s).
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments) applies.
EN 179, Building hardware - Emergency exit devices operated by a lever handle or push pad, for use on
escape routes - Requirements and test methods
EN 1125, Building hardware - Panic exit devices operated by a horizontal bar, for use on escape routes -
Requirements and test methods
EN 1154, Building hardware - Controlled door closing devices - Requirements and test methods
EN 1155, Building hardware - Electrically powered hold-open devices for swing doors - Requirements and
test methods
EN 1158, Building hardware - Door coordinator devices - Requirements and test methods
EN 1191, Windows and doors - Resistance to repeated opening and closing - Test method
EN 1363-1, Fire resistance tests - Part 1: General requirements
EN 1634-1, Fire resistance and smoke control tests for door and shutter assemblies, openable windows and
elements of building hardware - Part 1: Fire resistance test for door and shutter assemblies and openable
windows
EN 1634-3, Fire resistance and smoke control tests for door and shutter assemblies, openable windows and
elements of building hardware - Part 3: Smoke control test for door and shutter assemblies
EN 1935:2002, Building hardware - Single-axis hinges - Requirements and test methods
EN 12209, Building hardware - Mechanically operated locks and locking plates - Requirements and test
methods
EN 12519, Windows and pedestrian doors - Terminology
EN 12605:2000, Industrial, commercial and garage doors and gates - Mechanical aspects - Test Methods
EN 13501-1, Fire classification of construction products and building elements - Part 1: Classification using
data from reaction to fire tests
EN 13501-2, Fire classification of construction products and building elements - Part 2: Classification using
data from fire resistance tests, excluding ventilation services
EN 13637, Building hardware - Electrically controlled exit systems for use on escape routes - Requirements
and test methods
EN 14846, Building hardware - Locks and latches - Electromechanically operated locks and striking plates
- Requirements and test methods
EN 15269-1, Extended application of test results for fire resistance and/or smoke control for door, shutter
and openable window assemblies, including their elements of building hardware - Part 1: General
requirements
EN 15269-3, Extended application of test results for fire resistance and/or smoke control for doorsets,
shutter and openable window assemblies, including their elements of building hardware - Part 3: Fire
resistance of hinged and pivoted timber doorsets and openable timber framed windows
EN 15269-20, Extended application of test results for fire resistance and/or smoke control for door, shutter
and openable window assemblies, including their elements of building hardware - Part 20: Smoke control
for doors, shutters, operable fabric curtains and openable windows
EN 15685 , Building hardware - Requirements and test methods - Multipoint locks, latches and locking
plates
EN 16034, Pedestrian doorsets, industrial, commercial, garage doors and openable windows - Product
standard, performance characteristics - Fire resisting and/or smoke control characteristics
EN 16035, Hardware performance sheet (HPS) - Identification and summary of test evidence to facilitate
the inter-changeability of building hardware for application to fire resisting and/or smoke control doorsets
and/or openable windows
EN ISO 13943, Fire safety - Vocabulary (ISO 13943)
Under preparation. Stage at the time of publication: prEN 15685:2023.
3 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 1191, EN 1363-1, EN ISO 13943,
EN 1634-1, EN 1634-3, EN 12519, EN 15269-1, EN 15269-3 and EN 15269-20 and the following apply.
ISO and IEC maintain terminology databases for use in standardization at the following addresses:
— IEC Electropedia: available at https://www.electropedia.org/
— ISO Online browsing platform: available at https://www.iso.org/obp/ui
3.1
full scale test
test of a full size doorset in accordance with EN 1191
3.2
core
material fitted centrally within the thickness of a door leaf which may consist of a single sheet of material
or a combination either of sheets of the same material or layers of different materials
3.3
effective rebate depth
dimension of the door leaf thickness of overlapping adjacent edges of door leaf relative to the door frame,
transom or side panel or flush overpanel
3.4
panel
component of a door leaf separated from other elements by joints which break through the total door
thickness
Note 1 to entry: A door leaf can consist of one or more panels.
3.5
exposed intumescent seal
intumescent seal which is fitted in the perimeter of the leaf or in the door frame rebate and is visible when
the leaf is in the open position
3.6
concealed intumescent seal
intumescent seal which is fitted in the perimeter of the leaf or in the door frame rebate and is not visible
when the leaf is in the open position, including seals behind veneers and laminates
3.7
facing
decorative facing
outer layer of material on the leaf or panel normally only used for decorative, not for structural, purposes
3.8
subfacing
layer (or layers) of material between the core and the facing in the leaf or panel normally used for
structural purposes
3.9
add
to put an additional component to the doorset which has not been tested as a part of the original doorset
3.10
remove
to take a component away which has been tested as a part of the original doorset
3.11
alternative
variation intended by the application of EXAP rules where the original construction parameter tested
shall be substituted by another one either by change, interchange or exchange
Note 1 to entry: Finally, the alternatives are those variations that are permitted by the EXAP report.
3.12
faces and sides of a door leaf
the faces and sides of a door leaf as shown in Figure 1
Key
1 opening face
2 closing face
3 lock side
4 hinge side
5 top side
6 bottom side
Figure 1 — Faces and sides of a door leaf
4 Determination of the field of extended application
4.1 General
4.1.1 Before there can be any consideration for extended application, the doorset shall have been tested
in accordance with EN 1191 and/or EN 12605:2000 to achieve a test result which could generate a
classification for the durability of self-closing in accordance with EN 13501-2 and / or correspond to a
use category according to EN 16034.
4.1.2 A review of the doorset construction parameters can indicate that one or more characteristics can
be improved by a particular parameter variation. All evaluations shall be made on the basis of retaining
the classifications for the durability of self-closing obtainable from testing to EN 1191 and/or
EN 12605:2000, including those with a lower number of opening and closing cycles. However, this shall
never lead to an increased classification for the durability of self-closing for any specific parameter
beyond that achieved during any one test unless specifically identified in the relevant Construction
Parameter Variation tables.
4.1.3 If, when following the extended application procedure, any part of the classified product cannot
be covered by the extended application rules, that part shall be omitted from the subsequent extended
application report and classification report.
4.2 Procedure for evaluation
4.2.1 Identify the variations from the original test specimen(s) which are required to be covered by an
extended application report. Ensure that the variation(s) do/does not prevent the doorset from self-
closing.
4.2.2 Locate the variations in the appropriate parameter variation by reference to columns (1) and (2)
of Table A.1.
4.2.3 Establish from the contents of column (3) of Table A.1 whether any extended application is
available beyond the direct application rules in EN 1191 and/or EN 12605:2000 without the need for
further testing.
4.2.4 Where this is deemed to be possible this can be recorded in the extended application report
together with any appropriate restrictions and the stated rules from column (3) in Table A.1.
4.2.5 Where the variations required can only be achieved from additional testing according to column
(4), the additional test can be made on a similar specimen type to the original test against which the
extended application is sought. Alternatively, column (4) in Table A.1 identifies an option for alternative
testing and relevant test parameters.
4.3 Procedure for maximum field of extended application
4.3.1 It is possible to provide a limited field of extended application from the results of a single test.
However, where a manufacturer intends to produce a range of doorsets incorporating single leaf doorsets
and also double leaf doorsets with or without glazing, with alternative items of building hardware, etc., it
is recommended that careful consideration is given to the complete range of doorset designs and options
in order to minimize the testing required before testing commences.
4.3.2 Establish all the parameter variations which are required to be part of the product range.
4.3.3 Determine which are the most important specification requirements and incorporate as many as
possible into the specimen(s) for the first tests in the series.
4.3.4 Conduct the first durability of self-closing test or a series of tests and then establish which of the
original desired parameter variations have not been covered by this test(s), including direct application
possibilities.
4.3.5 Identify these parameter variations in Table A.1 and establish if any extended application is
possible without further testing.
4.3.6 Record this for the extended application report together with any restrictions and rules given in
column (3) in Table A.1.
4.3.7 Evaluate which, if any, of the desired parameter variations have not been covered by the initial
field of extended application derived from 4.3.6 above.
4.3.8 Determine if the product range is to include only single leaf doorsets or if the range is to also
include double leaf configurations. Where only single leaf doorsets are to be part of the product range,
the outstanding construction parameter variations shall only be incorporated into specimens for the
single leaf doorsets. Where single leaf and double leaf doorsets are to be included in the product range,
the outstanding construction parameter variations for the extended application of single leaf doorsets
may be incorporated into either repeated single leaf doorset tests or, in the weakest option, as defined in
column (4) of the table in Table A.1, double leaf doorset configurations.
4.3.9 Select the required outstanding parameter variations from column (1) and column (2) of
Table A.1 and observe from column (4) in Table A.1 which are the most appropriate weakest specimen
options for further testing.
4.3.10 If the complete selection of required parameter variations has not been covered by the tests
completed in accordance with 4.3.8 and 4.3.9 above, then an appropriate test or tests may be carried out
with the additional product variations incorporated.
4.4 Interpretation of test results
4.4.1 In order to maximize the extended field of application, it is important that the test reports shall
record details of any failures occurred throughout the test duration.
4.4.2 Where a series of tests have been conducted, the field of extended application shall be based on
the lowest performance achieved from the complete series of tests unless premature failure has been
attributed to one or more specific construction parameter variations.
4.4.3 Where it has been possible to identify specific parameter failures, the extended application for all
other construction parameter variations can be based on the performance achieved after isolating the
premature failure(s). This means that the failed parameters have to be excluded from the classification /
EXAP report.
5 Extended application report
Prepare an extended application report in accordance with the requirements of EN 15269-1, based on
the results of evaluations in accordance with the above.
6 Classification report
The classification report shall be determined from the results of the extended application report and shall
be presented in accordance with EN 13501-2.
Annex A
(normative)
Construction parameter variations
Table A.1 below is designed to be used by experts competent in the field of fire resistance and smoke
control and durability of self-closing testing of hinged or pivoted doorsets with timber based door leaves.
This table shall only be used to assess a field of extended application when at least one positive durability
of self-closing test to EN 1191 and/or EN 12605:2000, as appropriate has generated a classification
according to EN 13501-2 and /or correspond to a use category according to EN 16034.
The first two columns identify possible variations to the construction details of the specimen tested. It is
presupposed that the variations do not restrain the doorset from closing.
Column (3) leads to the judgement of the possibility of extending the field of application.
Where additional tests are deemed to be necessary, the type of specimen approved for incorporation of
the changed parameter is defined in column (4). Where it is possible to use information from tests
performed on one configuration for evidence on a different configuration, this allowance has been made
in order to reduce the overall number of tests required for extended application evaluation e.g. single
action doorsets to double action doorsets.
Where an additional test is required in column (4), the test is a full scale test unless otherwise specified.
In order to maximize the possible field of extended application from a minimum number of tests, the
parameter changes have been spread over a series of test specimens. Where more than a single parameter
variation is required, the influence on other variations shall also be taken into account.
Construction parameters tested on the inactive door leaf of a double leaf doorset can only be transferred
to the active door leaf, when both door leaves have been tested with the same number of cycles.
Solid timber can be replaced by any other solid timber of equal or higher density.
Table A.1 — Construction parameter variations
Construction parameter Variation Possibility of extension Additional evidence required
(1) (2) (3) (4)
A Door leaf
In certain cases, the rules given in Section A are also appropriate to side, transom and flush over panels or the door frame; where this is the case it is clearly indicated at the
beginning of the relevant section. For double leaf doorsets: both leaves shall be of the same basic construction.
A.1 General
A.1.1 Number of door leaves
Single leaf doorset from
only applicable to doorsets tested
Possible –
double leaf doorset test
without transom and/or flush over
panels
A.1.2 Number of leaves
Double leaf doorset from
only applicable to doorsets tested
Not possible without additional test Additional test double leaf doorset
single leaf doorset test
without transom and/or flush over
panels
A.1.3 Intumescent strips (fitted at door leaf
Location towards the
to door frame interface). See Possible –
door frame rebate
Figure A.1
A.1.4 Intumescent strips (fitted at door leaf
Location away from the
to door frame interface). See Possible –
door frame rebate
Figure A.2
A.1.5 Intumescent strips (fitted in meeting
Change Possible –
edges) – location
A.1.6 Intumescent seals – location (from
Change Possible –
door leaf to door frame and vice versa)
Construction parameter Variation Possibility of extension Additional evidence required
(1) (2) (3) (4)
A.1.7 Non intumescent seals
Possible providing the deformation of the seal will not
(draught/smoke/acoustic etc.) –
Additional test double for single and
increase during movement of the door leaf/leaves
Reaction to Fire class A1 or A2
Change double leaf doorsets or single for single
otherwise
according to EN 13501-1, (fitted in
leaf doorsets
door leaf or door frame including
not possible without an additional test
threshold) – location
A.1.8 Non-intumescent seals
Possible providing the deformation of the seal will not
(draught/smoke/acoustic etc.) – Additional test double for single and
increase during movement of the door leaf/leaves
Reaction to Fire class B-F according to Change double leaf doorsets or single for single
otherwise
EN 13501-1 (fitted in door leaf or door leaf doorsets
not possible without an additional test
frame or threshold) – location
A.1.9 Non-intumescent seals
(draught/smoke/acoustic etc.) - Additional test double for single and
Reaction to Fire class A1 or A2 Add Not possible without an additional test double leaf doorsets or single for single
according to EN 13501-1, (fitted in leaf doorsets
door leaf or door frame or threshold)
A.1.10 Non intumescent seals (draught /
smoke / acoustic etc.) - Reaction to
Fire class A1 or A2 according to Remove Possible –
EN 13501-1, (fitted in door leaf or
door frame or threshold)
A.1.11 Non-intumescent seals
(draught/smoke/acoustic etc.) – Additional test double for single and
Reaction to Fire class B-F according to Add Not possible without an additional test double leaf doorsets or single for single
EN 13501-1 (fitted in door leaf or door leaf doorsets
frame or threshold)
Construction parameter Variation Possibility of extension Additional evidence required
(1) (2) (3) (4)
A.1.12 Non-intumescent seals
(draught/smoke/acoustic etc.) –
Reaction to Fire class B-F according to Remove Possible –
EN 13501-1 (fitted in door leaf or door
frame or threshold)
Possible providing the louvre is placed in the area of
the core material and not in the area of the perimeter
Additional test single or double leaf
framing of the door leaf and providing the
A.1.13 Louvres in door leaf or panel Add
doorset
requirements of Annex C are fulfilled,
otherwise not possible without an additional test
A.1.14 Louvres in door leaf or panel Remove Possible –
Possible providing the louvre is moved inside the area
A.1.15 Louvres in door leaf or panel tested
of the core material and not in the area of the
Additional test single or double leaf
with louvre – Location in vertical Change
perimeter framing of the door leaf,
doorset
direction
otherwise not possible without an additional test
Possible providing the louvre is moved inside the area
A.1.16 Louvres in door leaf or panel tested
of the core material and not in the area of the
Additional test single or double leaf
with louvre – Location in horizontal Change
perimeter framing of the door leaf otherwise,
doorset
direction
not possible without an additional test
A.1.17 Louvres in door leaf or panel tested
with louvre – size (for area or Decrease Possible –
dimensions) – See Figure A.3
Construction parameter Variation Possibility of extension Additional evidence required
(1) (2) (3) (4)
Possible providing the louvre is placed in the area of
the core material and not in the area of the perimeter
A.1.18 Louvres in door leaf or panel tested
Additional test single or double leaf
framing of the door leaf and providing the
with louvre – size (for area or Increase
doorset
requirements of Annex C are fulfilled,
dimensions)
otherwise not possible without an additional test
A.1.19 Leaf rebate (edge of door leaf to door
Additional test double for single and
Possible in line with Figure A.4 a, b and c,
frame - not at the meeting edges. See
Add double leaf doorsets or single for single
Section A.2 for meeting edge
otherwise not possible without an additional test
leaf doorsets
parameters) - See Figure A.4
A.1.20 Leaf rebate (edge of door leaf to door
Additional test double for single and
Possible in line with Figure A.4 d, e and f,
frame - not at the meeting edges. See
Remove double leaf doorsets or single for single
Section A.2 for meeting edge
otherwise not possible without an additional test
leaf doorsets
parameters) - See Figure A.4
A.1.21 Change in mode of operation (double
Additional test single or double leaf
action from single action and vice Alternative Not possible without an additional test
doorset
versa)
A.1.22 Latching condition for single leaf
doorsets (See also Section C of this Change See rule A.1.23 See rule A.1.23
table for building hardware variation)
Construction parameter Variation Possibility of extension Additional evidence required
(1) (2) (3) (4)
Possible in line with the following relationship:
tested tested
tested
with a with a
without
latch/lock latch/
a latch/
but lock
lock
unlatched latched
A.1.23 Latching condition for single and
Additional test double for single and
double leaf doorsets (See also Section extension to:
Change – Possible Possible double leaf doorsets or single for single
C of this table for building hardware without a lock/latch
leaf doorsets
variation) – see Figure A.5.
extension to: with
lock/latch but
Possible – Possible
unlocked/unlatched
(disengaged)
extension to: with a Not Not
–
lock/latch, latched possible possible
A.1.24 Latching/locking device(s) – doorset
Remove Possible –
tested with latching/ locking device(s)
A.2 Meeting edge detail
Possible to change from rebated to unrebated meeting
edges providing the locking/latching devices
A.2.1 Rebated or plain unrebated meeting
(including strike plates) and the seals
edge detail – meeting edge detail – see Change Additional test double leaf doorset
(draught/smoke/acoustic etc.) remain unchanged,
Figure A.6.
otherwise not possible without an additional test
Possible providing the locking/latching devices
A.2.2 Unrebated meeting edge detail – see
(including strike plates) and the seals
Figure A.6 c), d) and e) – between Change Additional test double leaf doorset
(draught/smoke/acoustic etc.) remain unchanged,
unrebated edge details
otherwise not possible without an additional test
Construction parameter Variation Possibility of extension Additional evidence required
(1) (2) (3) (4)
Possible providing the requirements of Annex C are
fulfilled,
A.2.3 Astragal detail – see Figure A.6 f) Increase Additional test double leaf doorset
otherwise not possible without an additional test
A.2.4 Astragal detail – see Figure A.6 f) Remove Possible –
Possible providing primary gaps remain within the
A.2.5 Dimensions of gaps between door
Additional test double for single and
tolerances given in EN 1634-1,
frame and door leaf or panel and
Increase / Decrease double leaf doorsets or single for single
between the meeting edges for double
beyond the field of direct application rules not possible
leaf doorsets
leaf doorsets or panel
without additional test
A.3 Size variations
A.3.1 Size of door leaf or panel (area, width,
Decrease Possible –
height)
Possible by a maximum of 25 % providing the
Additional test double for single and
requirements of Annex C are fulfilled,
A.3.2 Height of door leaf or panel Increase double leaf doorsets or single for single
leaf doorsets
otherwise not possible without an additional test
Possible by a maximum of 25 % providing that the
Additional test double for single and
requirements of Annex C are fulfilled,
A.3.3 Width of door leaf or panel Increase double leaf doorsets or single for single
leaf doorsets
otherwise not possible without an additional test
Possible in line with A.3.2 and A.3.3, which can be
Additional test double for single and
combined,
A.3.4 Area of door leaf or panel Increase double leaf doorsets or single for single
leaf doorsets
otherwise not possible without an additional test
Possible providing the requirements of Annex C are
Additional test single or double leaf
fulfilled,
A.3.5 Thickness of door leaf or panel Increase
doorset
otherwise not possible without an additional test
Construction parameter Variation Possibility of extension Additional evidence required
(1) (2) (3) (4)
Additional test double for single and
Possible by a maximum of 10 %,
A.3.6 Thickness of door leaf or panel Decrease double leaf doorsets or single for single
otherwise not possible without an additional test
leaf doorsets
A.4 Materials and constructions
Possible providing the requirements of Annex C are
A.4.1 Density of core material of door leaf or Additional test single or double leaf
fulfilled,
Increase
panel doorset
otherwise not possible without an additional test
Possible providing a maximum reduction of 25 %,
A.4.2 Density of core material of door leaf or Additional test single or double leaf
Decrease
panel doorset
otherwise not possible without an additional test
possible providing the requirements of Annex C are
A.4.3 Thickness of core material or
Additional test single or double leaf
fulfilled,
individual layers of core material in Increase
doorset
door leaf or panel
otherwise not possible without an additional test
A.4.4 Thickness of core material or Additional test double for single and
Possible by a maximum of 10 %,
individual layers of core material in Decrease double leaf doorsets or single for single
otherwise not possible without an additional test
door leaf or panel leaf doorsets
A.4.5 Pieces of core material of door leaf or
panel – number of pieces – See Increase Possible –
Figure A.7
A.4.6 Pieces of core material of door leaf or
panel – number of pieces – See Decrease Possible –
Figure A.7
A.4.7 Number of layers of identical core
Decrease Possible –
material of door leaf or panel
Construction parameter Variation Possibility of extension Additional evidence required
(1) (2) (3) (4)
Possible providing the test included more than one
joint and the fixing technique to the top layer and/ or
A.4.8 Number of layers of identical core Additional test single or double leaf
Increase
cover plate is unchanged,
material of door leaf or panel doorset
otherwise not possible without additional test
A.4.9 Number of layers of core material of
different materials in door leaf or Decrease Possible –
panel
Possible providing the test included more than one
A.4.10 Number of layers of core material of
joint and the fixing technique to the top layer and/or
Additional test single or double leaf
different materials in door leaf or Increase
cover plate is unchanged,
doorset
panel
otherwise not possible without additional test
A.4.11 Type of core material in door leaf or Change
panel (single thickness or in
Possible –
combination of different layers) –
manufacturer
A.4.12 Type of core material in door leaf or Alternative
panel (single thickness or in
combination of different layers) – Possible –
composition of same basic product
type
Possible to change timber-based types providing the
alternative timber is of the same or higher density and
Additional test single or double leaf
the same or greater thickness (subject to A.4.14) and
A.4.13 Structural subfacing – type Alternative
doorset
providing the requirements of Annex C are fulfilled,
otherwise not possible without additional test
Construction parameter Variation Possibility of extension Additional evidence required
(1) (2) (3) (4)
Possible providing the requirements of Annex C are
Additional test single or double leaf
fulfilled,
A.4.14 Structural subfacing –thickness Increase
doorset
otherwise not possible without an additional test
A.4.15 Amount of adhesive g/m Increase Possible –
Possible by a maximum of 25 %,
Additional test single or double leaf
A.4.16 Amount of adhesive g/m Decrease
doorset
otherwise not possible without an additional test
A.4.17 Type of adhesive used in door leaf or
panel – manufacturer for identical Change Possible –
composition
A.4.18 Type of adhesive used in door leaf or
Alternative Possible –
panel – composition
Possible providing the requirements of Annex C are
A.4.19 Metal protective sheet used in door Additional test single or double leaf
fulfilled,
Add
leaf or panel doorset
otherwise not possible without an additional test
A.4.20 Metal protective sheet used in door
Remove Possible –
leaf or panel
Possible providing the requirements of Annex C are
A.4.21 Electronic security mesh in door leaf Additional test single or double leaf
fulfilled,
Add
or panel doorset
otherwise not possible without an additional test
A.4.22 Electronic security mesh in door leaf
Remove Possible –
or panel
Possible providing the requirements of Annex C are
A.4.23 Cross-section dimension of perimeter Additional test single or double leaf
fulfilled,
Increase
framing elements in door leaf or panel doorset
otherwise not possible without an additional test
Construction parameter Variation Possibility of extension Additional evidence required
(1) (2) (3) (4)
Possible to change species for other solid timber or
possible to change from finger joint timber to solid
timber and vice versa providing the alternative is of
A.4.24 Change of species of perimeter framing Additional test single or double leaf
Solid timber
the same or higher density and providing the
elements in door leaf or panel doorset
requirements of Annex C are fulfilled,
otherwise not possible without additional test
Possible to change from wood composite materials
(e.g. chip board) to solid timber with a density of at
A.4.25 Change of species of perimeter framing
Additional test single or double leaf
least 450 kg/m and providing the requirements of
elements in door leaf or panel – Change
doorset
Annex C are fulfilled,
material
otherwise not possible without additional test
Possible by a maximum of 10 %,
A.4.26 Cross-section dimension of perimeter Additional test single or double leaf
Decrease
framing elements in door leaf or panel doorset
otherwise not possible without an additional test
A.4.27 Decorative edge (sides and rebates)
detail of door leaf or panel – See Change Possible –
Figure A.8 – Shape
Possible providing the alternative jointing technique
can be demonstrated not to reduce the mechanical
A.4.28 Jointing technique of internal door leaf Additional test single or double leaf
Alternative
strength of the framing member,
or panel framing doorset
otherwise not possible without additional test
A.4.29 Dimension of intumescent strips
(fitted in door leaf, panel or door Increase Possible –
frame)
A.4.30 Dimension of intumescent strips
(fitted in door leaf, panel or door Decrease Possible –
frame)
Construction parameter Variation Possibility of extension Additional evidence required
(1) (2) (3) (4)
A.4.31 Exposed intumescent strips (fitted
within door leaf, panel or door frame) Change Possible –
– Exposed to concealed
Possible providing primary gaps remain within the
A.4.32 Concealed intumescent strips (fitted
Additional test single or double leaf
tolerances given in EN 1634-1,
within door leaf, panel or door frame) Change
doorset
– concealed to exposed
otherwise not possible without additional test
A.4.33 Type of intumescent strips (fitted
within door leaf, panel or door frame)
Change Possible –
– supplier/manufacturer for identical
composition
A.4.34 Type of intumescent strips (fitted
within door leaf, panel or door frame) Alternative Possible –
– material
A.4.35 Dimension/cross-section of draught /
Possible by a maximum of 15 % in any cross sectional
smoke seals (Reaction to fire class A1
Additional test single or double leaf
dimension and by a maximum of 10 % mass,
or A2 according to EN 13501-1); e.g. Increase
doorset
ceramic products (fitted in door leaf,
otherwise not possible without an additional test
panel or door frame)
A.4.36 Dimension/cross-section of draught /
smoke seals (Reaction to fire class A1
or A2 according to EN 13501-1); e.g. Decrease Possible –
ceramic products (fitted in door leaf,
panel or door frame)
A.4.37 Dimension/cross-section of draught /
Possible by a maximum of 15 % in any cross sectional
smoke seals (Reaction to fire class B-F Additional test single or double leaf
dimension and by a maximum of 10 % mass,
Increase
according to EN 13501-1) (fitted in doorset
otherwise not possible without an additional test
door leaf, panel or door frame)
Construction parameter Variation Possibility of extension Additional evidence required
(1) (2) (3) (4)
A.4.38 Dimension/cross-section of draught /
smoke seals (Reaction to fire class B-F
Decrease Possible –
according to EN 13501-1) (fitted in
door leaf, panel or door fram
...