Fixed firefighting systems - Components for gas extinguishing systems - Part 8: Requirements and test methods for connectors

This document specifies product characteristics and describes test methods for flexible and rigid connectors intended to be used in gas extinguishing systems (i.e. CO2, Inert Gas or Halocarbon gas) installed in buildings as a part of a complete operating system.
This document is applicable to the following connectors:
-   Type 1 and Type 5: used between container valves and the manifold
-   Type 3: used in pneumatic pilot lines
-   Type 2 and Type 4: used in distribution pipework of fire extinguishing installations downstream of the manifold/selector valve.

Ortsfeste Brandbekämpfungsanlagen - Bauteile für Löschanlagen mit gasförmigen Löschmitteln - Teil 8: Anforderungen und Prüfverfahren für Verbindungen

Dieses Dokument legt Produkteigenschaften fest und beschreibt Prüfverfahren für flexible und starre Verbindungen, die in Löschanlagen mit gasförmigen Löschmitteln (d. h. CO2 , Inertgas Feuerlöschanlagen und Feuerlöschanlagen mit halogenierten Kohlenwasserstoffen) eingesetzt werden, welche in Gebäuden als Teil eines vollständigen Betriebssystems installiert sind.
Dieses Dokument gilt für die folgenden Verbindungen:
-   Typ 1 und Typ 5: verwendet zwischen Behälterventilen und dem Sammelrohr
-   Typ 3: verwendet in pneumatischen Steuerleitungen
-   Typ 2 und Typ 4: verwendet in Düsenrohrnetzen von Löschanlagen hinter dem Sammelrohr/dem Bereichsventil.

Installations fixes de lutte contre l’incendie - Éléments constitutifs des installations d’extinction à gaz - Partie 8 : Exigences et méthodes d’essai pour raccords

Le présent document spécifie les caractéristiques des produits et décrit les méthodes d’essai des raccords flexibles et rigides destinés à être utilisés dans les installations d’extinction à gaz (à savoir à CO2, à gaz inerte ou à gaz inhibiteur) équipant les bâtiments sous forme de système complet.
Le présent document est applicable aux raccords suivants :
-   type 1 et type 5 : utilisés entre les vannes du réservoir et le collecteur ;
-   type 3 : utilisés dans les lignes pilotes pneumatiques ;
-   type 2 et type 4 : utilisés dans le réseau d’alimentation des installations d’extinction incendie, en aval du collecteur/de la vanne directionnelle.

Vgrajeni gasilni sistemi - Sestavni deli sistemov za gašenje s plinom - 8. del: Zahteve in preskusne metode za spoje

General Information

Status
Not Published
Publication Date
17-Dec-2023
Withdrawal Date
20-Sep-2022
Current Stage
4599 - Dispatch of FV draft to CMC - Finalization for Vote
Start Date
21-Feb-2023
Due Date
15-Nov-2020
Completion Date
21-Feb-2023

Relations

Buy Standard

Draft
prEN 12094-8:2016
English language
19 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
oSIST prEN 12094-8:2016
01-julij-2016
Vgrajeni gasilni sistemi - Sestavni deli sistemov za gašenje s plinom - 8. del:
Zahteve in preskusne metode za spoje
Fixed firefighting systems - Components for gas extinguishing systems - Part 8:
Requirements and test methods for connectors
Ortsfeste Brandbekämpfungsanlagen - Bauteile für Löschanlagen mit gasförmigen
Löschmitteln - Teil 8: Anforderungen und Prüfverfahren für Verbindungen

Installations fixes de lutte contre l'incendie - Élements constitutifs des installations

d'extinction à gaz - Partie 8 : Exigences et méthodes d'essai pour raccords
Ta slovenski standard je istoveten z: prEN 12094-8
ICS:
13.220.10 Gašenje požara Fire-fighting
oSIST prEN 12094-8:2016 en,fr,de

2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------
oSIST prEN 12094-8:2016
---------------------- Page: 2 ----------------------
oSIST prEN 12094-8:2016
DRAFT
EUROPEAN STANDARD
prEN 12094-8
NORME EUROPÉENNE
EUROPÄISCHE NORM
May 2016
ICS 13.220.20 Will supersede EN 12094-8:2006
English Version
Fixed firefighting systems - Components for gas
extinguishing systems - Part 8: Requirements and test
methods for connectors

Installations fixes de lutte contre l'incendie - Élements Ortsfeste Brandbekämpfungsanlagen - Bauteile für

constitutifs des installations d'extinction à gaz - Partie Löschanlagen mit gasförmigen Löschmitteln - Teil 8:

8 : Exigences et méthodes d'essai pour raccords Anforderungen und Prüfverfahren für Verbindungen

This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee

CEN/TC 191.

If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations

which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.

This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other

language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC

Management Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,

Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,

Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and

United Kingdom.

Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are

aware and to provide supporting documentation.

Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without

notice and shall not be referred to as a European Standard.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels

© 2016 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 12094-8:2016 E

worldwide for CEN national Members.
---------------------- Page: 3 ----------------------
oSIST prEN 12094-8:2016
prEN 12094-8:2016 (E)
Contents Page

European Foreword ...................................................................................................................................................... 3

1 Scope .................................................................................................................................................................... 4

2 Terms and definitions ................................................................................................................................... 4

3 Product characteristics ................................................................................................................................. 5

3.1 Operational reliability and Performance under fire condition...................................................... 5

3.2 Durability of Operational reliability and Performance under fire condition ........................... 6

3.2.1 Material specification (metal parts)......................................................................................................... 6

3.2.2 Resistance to bursting (all types) .............................................................................................................. 6

3.2.3 Resistance to pressure and heat (only type 2 and 4) ......................................................................... 6

3.2.4 Resistance to heat and cold shock (only type 2 and 4 for CO ) ....................................................... 6

3.2.5 Resistance to cold (only type 1, 2, 3 and 4) ............................................................................................ 6

3.2.6 Resistance of type 2 connectors to flexing (only type 2) .................................................................. 7

4 Testing, assessment and sampling methods ......................................................................................... 7

4.1 Conditions .......................................................................................................................................................... 7

4.2 Samples ............................................................................................................................................................... 7

4.3 Compliance ........................................................................................................................................................ 8

4.4 Operational reliability and Performance under fire conditions.................................................... 8

4.5 Durability of Operational reliability and Performance under fire condition ........................... 8

4.5.1 Material specification (metal parts)......................................................................................................... 8

4.5.2 Resistance to bursting (all types) .............................................................................................................. 8

4.5.3 Resistance to pressure and heat (only type 2 and 4) ......................................................................... 8

4.5.4 Resistance to heat and cold shock (only type 2 and 4 for CO ) ....................................................... 8

4.5.5 Resistance to cold (only type 1, 2, 3 and 4) ............................................................................................ 9

4.5.6 Resistance to flexing (only type 2) ............................................................................................................ 9

5 Marking, labelling and packaging ............................................................................................................. 9

6 Assessment and verification of constancy of performance -AVCP ................................................ 9

6.1 General ................................................................................................................................................................ 9

6.2 Type testing ....................................................................................................................................................... 9

6.2.1 General ................................................................................................................................................................ 9

6.2.2 Test samples, testing and compliance criteria .................................................................................. 10

6.2.3 Test reports .................................................................................................................................................... 10

6.2.4 Shared other party results ........................................................................................................................ 10

6.3 Factory production control (FPC) .......................................................................................................... 11

6.3.1 General ............................................................................................................................................................. 11

6.3.2 Requirements ................................................................................................................................................ 11

6.3.3 Product specific requirements ................................................................................................................ 13

6.3.4 Initial inspection of factory and of FPC ................................................................................................ 14

6.3.5 Continuous surveillance of FPC ............................................................................................................... 15

6.3.6 Procedure for modifications .................................................................................................................... 15

6.3.7 Pre-production products (e.g. prototypes) ......................................................................................... 15

Annex A (informative) Documentation ............................................................................................................... 17

Annex ZA (informative) Relationship of this European Standard with Regulation (EU)

No. 305/2011 ................................................................................................................................................. 18

---------------------- Page: 4 ----------------------
oSIST prEN 12094-8:2016
prEN 12094-8:2016 (E)
European foreword

This document (prEN 12094-8:2016) has been prepared by Technical Committee CEN/TC 191 “Fixed

firefighting systems”, the secretariat of which is held by BSI.
This document is currently submitted to the CEN Enquiry.
This document will supersede EN 12094-8:2006.

This document has been prepared under a mandate given to CEN by the European Commission and the

European Free Trade Association, and supports essential requirements of Regulation (EU) 305/2011.

For relationship with Regulation (EU) 305/2011, see informative Annex ZA, which is an integral part of

this document.

EN 12094, Fixed firefighting systems - Components for gas extinguishing systems consists of the following

parts:

— Part 1: Requirements and test methods for electrical automatic control and delay devices

— Part 2: Requirements and test methods for non-electrical automatic control and delay devices

— Part 3: Requirements and test methods for manual triggering and stop devices

— Part 4: Requirements and test methods for container valve assemblies and their actuators

— Part 5: Requirements and test methods for high and low pressure selector valves and their actuators

— Part 6: Requirements and test methods for non-electrical disable devices
— Part 7: Requirements and test methods for nozzles
— Part 8: Requirements and test methods for connectors
— Part 9: Requirements and test methods for special fire detectors

— Part 10: Requirements and test methods for pressure gauges and pressure switches

— Part 11: Requirements and test methods for mechanical weighing devices
— Part 12: Requirements and test methods for pneumatic alarm devices
— Part 13: Requirements and test methods for check valves and non-return valves

— Part 16: Requirements and test methods for odorizing devices for CO low pressure systems

NOTE This list includes standards that are in preparation and other standards may be added. For current

status of published standards, refer to www.cen.eu.
---------------------- Page: 5 ----------------------
oSIST prEN 12094-8:2016
prEN 12094-8:2016 (E)
1 Scope

This European Standard specifies product characteristics and describes test methods for flexible and

rigid connectors intended to be used in gas extinguishing systems (i.e. CO , inert gas or halocarbon gas)

installed in buildings as a part of a complete operating system.
This European Standard is applicable to the following connectors:
— Type 1 and Type 5: used between container valves and the manifold;
— Type 3: used in pneumatic pilot lines;

— Type 2 and Type 4: used in distribution pipework of fire extinguishing installations downstream of

the manifold/selector valve.
2 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
2.1
CO -high-pressure installation
fire extinguishing installation in which the CO is stored at ambient temperature
EXAMPLE The pressure of the CO in storage is p = 58,6 bar at 21 °C.
2 abs
2.2
CO -low-pressure installation
fire extinguishing installation in which the CO is stored at low temperature
Note 1 to entry: Normally −19 °C to −21 °C.
2.3
fill ratio
the mass of extinguishing medium related to the net capacity of a container
Note 1 to entry: Expressed as kilogram per litre (kg/l).
2.4
flexible connector

link between two parts which are subject to relative movement or subject to tolerances

2.5
halocarbon gas

extinguishing agent that contains as primary components one or more organic compounds containing

one or more of the elements fluorine, chlorine, bromine or iodine
2.6
halocarbon gas installation

fire extinguishing installation in which the halocarbon gas is stored at ambient temperature

2.7
inert gas

non liquefied gas or mixture of gases which extinguish the fire mainly by reducing the oxygen-

concentration in the protected zone
EXAMPLE Argon, nitrogen or mixtures of these gases with CO .
---------------------- Page: 6 ----------------------
oSIST prEN 12094-8:2016
prEN 12094-8:2016 (E)
2.8
inert gas installation

fire extinguishing installation in which the inert gas is stored at ambient temperature

2.9
type 1 connector
flexible connector for connecting containers to a manifold
2.10
type 2 connector

flexible connector for use in distribution pipework downstream the manifold or selector valve for the

connection of moving parts
2.11
type 3 connector
flexible connector for use in pneumatic pilot lines
2.12
type 4 connector

flexible connector for use in distribution pipework downstream the manifold or selector valve for the

connection of non-moving parts which allow for dimensional adjustments
2.13
type 5 connector
rigid connector for connecting containers to a manifold
2.14
working pressure
pressure at which the component is used in the system
3 Product characteristics
3.1 Operational reliability and performance under fire condition

The manufacturer shall specify the type of the connector and the working pressure at least in

accordance with Table 1.
Table 1 — Working pressure
Type Working pressure
in bar
CO -high-pressure CO -low-pressure Inert gas Halocarbon gas
2 2
component component component component
Type 1 connector 140 not applicable see NOTE 1 see NOTE 1
Type 2 connector 60 25 as specified by the see NOTE 2
manufacturer
Type 3 connector As specified by the manufacturer
Type 4 connector 60 25 As specified by the see NOTE 2
manufacturer
Type 5 connector 140 not applicable see NOTE 1 see NOTE 1

NOTE 1 This value is given as the developed pressure in the container at 50 °C with the highest fill

ratio/ superpressurization, where applicable, or – for components specified for use in systems with reduced and controlled

pressure only – as specified by the manufacturer.

NOTE 2 This value is given as the developed pressure in the container at 20 °C with the highest fill

ratio/superpressurization, where applicable, or – for components specified for use in systems with reduced and controlled

pressure only – as specified by the manufacturer.
---------------------- Page: 7 ----------------------
oSIST prEN 12094-8:2016
prEN 12094-8:2016 (E)

Connectors shall not leak, and shall show no sign of damage which could impair proper function when

pressurized up to 1,5 times the working pressure according to Table 1 when tested in accordance with

4.1.
The performance shall be declared as working pressure in bar.
3.2 Durability of Operational reliability and Performance under fire condition
3.2.1 Material specification (metal parts)

Metal parts of connectors shall be made of stainless steel, copper, copper alloy or corrosion-protected

steel (e.g. galvanized) or other metal which has been proved to be equally suitable (regarding e.g.

corrosion resistance, ductile strength).
The performance shall be declared as description of the metal.
3.2.2 Resistance to bursting (all types)

Connectors shall not burst when pressurized up to 3 times the working pressure according to Table 1

when tested in accordance with 4.5.2.
The performance shall be declared as “no bursting”.
3.2.3 Resistance to pressure and heat (only type 2 and 4)

Type 2 and type 4 connectors shall show no sign of damage which could impair proper function when

tested in accordance with 4.5.3 at the pressure and temperature conditions given in Table 2 and shall

not leak when subsequently tested in accordance with 4.1.

Table 2 — Test pressure and temperature conditions for resistance of type 2 and type 4

connectors to pressure and heat
Test condition Test pressure Test temperature
in bar in °C
CO -low pressure component 25 600
CO -high pressure component 60 600
Inert gas component working pressure 600
(see Table 1)
Halocarbon gas component working pressure 600
(see Table 1)
The performance shall be declared as “no damage and no leakage”.
3.2.4 Resistance to heat and cold shock (only type 2 and 4 for CO )

Type 2 and type 4 connectors shall show no sign of damage which could impair proper function when

tested in accordance with 4.5.4 and shall not leak when subsequently tested in accordance with 4.1.

The performance shall be declared as “no damage and no leakage”.
3.2.5 Resistance to cold (only type 1, 2, 3 and 4)

Flexible connectors shall show no visible sign of damage when tested in accordance with 4.5.5.

The performance shall be declared as “no damage”.
---------------------- Page: 8 ----------------------
oSIST prEN 12094-8:2016
prEN 12094-8:2016 (E)
3.2.6 Resistance of type 2 connectors to flexing (only type 2)

Type 2 connectors shall not leak when tested in accordance with 4.1 after being tested in accordance

with 4.5.6.
The performance shall be declared as “no leakage”.
4 Testing, assessment and sampling methods
4.1 Conditions

The components shall be assembled for test according to the manufacturer instructions. The tests shall

be carried out at a temperature of (25 ± 10) °C, except when otherwise specified for a particular test.

The tolerance for all test parameters is ± 5 %, unless otherwise stated.
4.2 Samples

Test samples shall be submit for tests as follows: three samples for type 1, type 3 and type 5 connectors,

six samples for type 2 and five samples for type 4 connectors. One of these samples is needed for

reference.

If for type 2 or type 4 connectors the same materials and parts are used to provide a range of

connectors, use six samples of 350 mm to 1 000 mm long. The sequence of tests is shown in Table 3 and

is given by the numbers 1, 2, 3, etc. in the Table. A, B, etc. are the different samples.

Table 3 — Order of tests
Tests Order of tests for
type 1, type 3 and
type 2 and type 4
type 5
a b
Sample A Sample B Sample A Sample B Sample C Sample D Sample E
4.1 Working pressure - 2 and 4 - 2 and 4 3 3 3
4.5.2 Resistance to bursting
2 - 2 - - - -
(all types)
4.5.3 Resistance to pressure
- - - - 2 - -
and heat (only type 2 and 4)
4.5.4 Resistance to heat and
cold shock (only type 2 and - - - - - 2 -
4 for CO )
4.5.5 Resistance to cold
- 3 - 3 - -
(only type 1, 2, 3 and 4)
4.5.6 Resistance to flexing
- - - - - - 2
(only type 2)
Prior to the tests, all samples are checked according to 5.3.

In addition, the documentation is checked according to 5.5.1, Material specification (metal parts).

a Only for CO -components.
b Only for type 2 connectors.
c Not for type 5 connectors.
---------------------- Page: 9 ----------------------
oSIST prEN 12094-8:2016
prEN 12094-8:2016 (E)
4.3 Compliance

A visual and measurement check shall be made to determine whether the test samples correspond to

the manufacturer documentation (see Annex A).
4.4 Operational reliability and performance under fire conditions

Connect the inlet of the sample to a hydraulic pressure supply and block the outlet. Vent the system and

increase the pressure by (2 ± 1) bar/s up to the test pressure ( ) %.

Maintain this pressure for a period of (10 ) min. At the end of this period release the hydraulic

pressure and examine the sample for damage.
4.5 Durability of Operational reliability and Performance under fire condition
4.5.1 Material specification (metal parts)
The documentation shall be checked to verify compliance with 3.2.1.
4.5.2 Resistance to bursting (all types)

Connect the inlet of the sample to a hydraulic pressure supply and block the outlet. Vent the system and

increase the pressure at (5 ± 1) bar/s up to the test pressure ( ) %.

Maintain this pressure for a period of (10 ) min. At the end of this period release the hydraulic

pressure and examine the sample.
4.5.3 Resistance to pressure and heat (only type 2 and 4)

Connect the sample to a vessel delivering an absolute pressure in accordance with Table 2. Block the

outlet. Subject the sample to a temperature of (600 ± 30) °C in a furnace for a period of 10 min. Then

pressurize the heated sample for (30 ± 5) s with gaseous CO , nitrogen or air at test pressure. Remove

the sample from the furnace and allow it to cool at normal temperature.

Then examine the sample for visible evidence of damage. Subsequently test the sample in accordance

with 4.4.
4.5.4 Resistance to heat and cold shock (only type 2 and 4 for CO )

Connect the sample to a CO vessel which incorporates a diptube and is capable of delivering liquid CO

2 2

at an absolute pressure of (20 ± 1) bar. A 2 position, 3 port ball valve (by-pass-valve) shall be installed

in the pipework between the vessel and the sample which allows to control the CO -flow from the

vessel. The nominal diameter of the pipework between the vessel and the by-pass-valve shall be at least

25 mm. The nominal diameter of the by-pass-valve and the connected pipe to the sample shall be

25 mm. The length of the connected pipe shall not exceed 1,1 m.

In one position, the test position, the by-pass-valve allows the CO to pass through the sample. In the

other position, the by-pass position, the outlet to the sample is closed and the CO -flow is diverted via

an appropriate pipework, which is dimensioned to reach a stable flow of liquid CO at the by-pass-valve

within 30 s. At the outlet of the sample connect a nozzle with a 10 mm orifice.

Subject the sample to a temperature of (600 ± 30) °C in a furnace for a period of (10 ) min. Just before

completion of the heating period commence CO flow through the by-pass. Upon stabilization of liquid

+10

CO flow and completion of heating period divert flow through the sample for a period of ( ) s.

Remove the sample from the furnace and allow it to cool at normal temperature.

Then examine the sample for visible evidence of damage. Subsequently test the sample in accordance

with 4.4.
---------------------- Page: 10 ----------------------
oSIST prEN 12094-8:2016
prEN 12094-8:2016 (E)
4.5.5 Resistance to cold (only type 1, 2, 3 and 4)

Condition the sample for (4 ± 1) h at (− 20 ) °C. With the sample at – 20 °C bend to the minimum

radius and maximum angle of deflection as specified by the manufacturer. If the maximum angle of

deflection is not specified, then bend the flexible connector along the whole length to the specified

minimum radius.
Then examine the sample for visible evidence of deterioration or damage.
4.5.6 Resistance to flexing (only type 2)

Use a bending rig to bend the sample around the minimum radius specified by the manufacturer. One

bending cycle consists of bending the sample from straight to the maximum angle of deflection specified

by the manufacturer (or, if not specified, to the maximum possible angle of deflection), and back to

straight. Carry out 3 000 bending cycles.
Subsequently test the sample in accordance with 4.4.
5 Marking, labelling and packaging
Connectors shall be marked with the following:
a) manufacturer's name or trademark;
b) model designation;
c) working pressure;

d) some mark(s) or code(s) (e.g. serial number or batch code), by which, at least, the date or batch and

place of manufacture (if several places of manufacture) can be identified by the manufacturer.

The markings should be non-detachable, non-flammable (with exception of a) and c) when marked on the

flammable hose material), permanent, and legible.

Where regulatory marking provisions require information on some or all items listed in this clause, the

provisions of this clause concerning those common items are deemed to be met.
6 Assessment and verification of constancy of performance -AVCP
6.1 General

The compliance of connectors with the requirements of this standard and with the performances

declared by the manufacturer in the DoP shall be demonstrated by:
— determination of the product type;
— factory production control by the manufacturer, including product assessment.

The manufacturer shall always retain the overall control and shall have the necessary means to take

responsibility for the conformity of the product with its declared performance(s).

6.2 Type testing
6.2.1 General

All performances related to characteristics included in this standard shall be determined when the

manufacturer intends to declare the respective performances.
---------------------- Page: 11 ----------------------
oSIST prEN 12094-8:2016
prEN 12094-8:2016 (E)

Assessment previously performed in accordance with the provisions of this standard, may be taken into

account provided that they were made to the same or a more rigorous test method, under the same

AVCP system on the same product or products of similar design, construction and functionality, such

that the results are applicable to the product in question.

NOTE 1 Same AVCP system means testing by an independent third party, under the responsibility of a notified

product certification body.

For the purposes of assessment, the manufacturer's products may be grouped into families, where it is

considered that the results for one or more characteristics from any one product within the family are

representative for that same characteristics for all products within that same family

NOTE 2 Products may be grouped in different families for different characteristics.

NOTE 3 Reference to the assessment method standards should be made to allow the selection of a suitable

representative sample.

In addition, the determination of the product type shall be performed for all characteristics included in

the standard for which the manufacturer declares the performance:

— at the beginning of the production of a new or modified connector (unless a member of the same

product range); or

— at the beginning of a new or modified method of production (where this may affect the stated

properties); or

they shall be repeated for the appropriate characteristic(s), whenever a change occurs in the connector

design, in the raw material or in the supplier of the components, or in the method of production (subject

to the definition of a family), which would affect significantly one or more of the characteristics.

Where components are used whose characteristics have already been determined, by the component

manufacturer, on the basis of assessment methods of other product standards, these characteristics

need not be re-assessed. The specifications of these components shall be documented.

Products bearing regulatory marking in accordance with appropriate harmonized European

specifications may be presumed to have the performances declared in the DoP, although this does not

replace the responsibility on the connector manufacturer to ensure that the connector as a whole is

correctly manufactured and its component products have the declared performance values.

6.2.2 Test samples, testing and compliance criteria

The number of samples of connectors to be tested or assessed, the assessment methods and the

acceptance criteria shall be in accordance with 4.2.
6.2.3 Test reports

The results of the determination of the product type shall be documented in test reports. All test reports

shall be retained by the manufacturer for at least 10 years after the last date of production of the

connectors to which they relate.
6.2.4 Shared other party results

A manufacturer may use the results of the product type determination obtained by someone else (e.g.

by another manufacturer, as a common service to manufacturers, or by a product developer), to justify

his own declaration of performance regarding a product that is manufactured according to the same

design (e.g. dimensions) and with raw materials, constituents and manufacturing methods of the same

kind, provided that:
---------------------- Page: 12 ----------------------
oSIST prEN 12094-8:2016
prEN 12094-8:2016 (E)

— the results are known to be valid for products with the same essential characteristics relevant for

the product performance;
— in addition to any in
...