Fixed firefighting systems - Components for sprinkler and water spray systems - Part 14: Sprinklers for residential applications

This document specifies requirements for the construction and performance of residential sprinklers as well as test methods for their type approval, which are operated by a change of state of an element or bursting of a glass bulb under the influence of heat, for use only in automatic sprinkler systems for domestic and residential applications as defined in EN 16925:− .
This standard does not cover representative fire and other tests for special sprinklers that are intended to provide for specific fire hazards, nor does it cover fire and other tests for sprinklers for commercial and industrial sprinkler systems as in EN 12845. Those test requirements are covered by EN 12259-1.
NOTE 1   All pressure data in this European Standard are given as gauge pressures in bar.
NOTE 2    Sprinklers according to EN12259-1 can also be used in residential and domestic applications if the system is designed according to EN 12845.

Ortsfeste Brandbekämpfungsanlagen - Bauteile für Sprinkler- und Sprühwasseranlagen - Teil 14: Sprinkler für die Anwendung im Wohnbereich

Dieses Dokument legt Anforderungen an die Konstruktion und Leistung von Wohnraumsprinklern für die ausschließliche Verwendung in automatischen Sprinkleranlagen für den Wohn- und Hausgebrauch, wie in EN 16925 festgelegt, die dadurch öffnen, dass sich bei Erwärmung der Zustand eines Elements ändert oder ein Glasfass zerspringt, sowie Prüfverfahren für deren Bauartzulassung fest.
Dieses Dokument deckt weder repräsentative Brand- und andere Prüfungen für spezielle Sprinkler, die für besondere Brandgefahren vorgesehen sind, noch Brand- und andere Prüfungen für Sprinkler für handelsübliche und industrielle Sprinkleranlagen nach EN 12845 ab. Diese Prüfanforderungen sind durch EN 12259 1 abgedeckt.
ANMERKUNG 1 Alle Drücke in diesem Dokument werden als Überdrücke in Bar angegeben.
ANMERKUNG 2 Sprinkler nach EN 12259 1 können auch für den Wohn- und Hausgebrauch eingesetzt werden, wenn die Anlage nach EN 12845 ausgelegt ist.

Installations fixes de lutte contre l’incendie - Composants des systèmes d’extinction du type sprinkleur et à pulvérisation d’eau - Partie 14: Sprinkleurs pour applications résidentielles

Le présent document spécifie les exigences relatives à la construction et aux performances des sprinkleurs résidentiels, ainsi que les méthodes d’essai en vue de leur homologation de type, ces sprinkleurs étant déclenchés par un changement d’état d’un élément ou l’éclatement d’une ampoule de verre sous l’effet de la chaleur. Ces exigences et méthodes d’essai s’appliquent uniquement aux systèmes d’extinction automatique de type sprinkleurs à usage domestique et résidentiel, tels que définis dans l’EN 16925 ).
La présente norme ne couvre ni les essais au feu et autres essais représentatifs des sprinkleurs spéciaux destinés à prévenir des risques d’incendie particuliers, ni les essais au feu et autres essais des sprinkleurs des systèmes d’extinction de type sprinkleurs à usages commerciaux et industriels spécifiés dans l’EN 12845. Ces exigences d’essai sont traitées dans l’EN 12259-1.
NOTE 1   Toutes les valeurs de pression manométrique figurant dans la présente Norme européenne sont exprimées en bar.
NOTE 2    Les sprinkleurs conformes à l’EN 12259-1 peuvent également être utilisés dans les applications résidentielles et domestiques, à condition que le système soit conçu conformément à l’EN 12845.

Vgrajene naprave za gašenje - Sestavni deli sprinklerskih sistemov in sistemov s pršečo vodo - 14. del: Sprinklerji za uporabo v stanovanjih

Ta dokument določa zahteve za konstrukcijo in izvedbo ter preskusne metode za tipsko odobritev sprinklerjev za uporabo v stanovanjih, ki delujejo po načelu spremembe stanja elementa oziroma razbitja steklenega mehurčka pod vplivom toplote. Sprinklerji so namenjeni za uporabo samo v avtomatskih sprinklerskih sistemih za bivalne površine, kot je opredeljeno v standardu EN 16925.
Standard ne zajema reprezentativnih protipožarnih in drugih preskusov za posebne sprinklerje, namenjene preprečevanju določenih nevarnosti požara, niti požarnih in drugih preskusov za sprinklerje za uporabo v komercialnih in industrijskih sprinklerskih sistemih, kot je opredeljeno v standardu EN 12845. Ti preskusi so zajeti v standardu EN 12259-1.
OPOMBA 1: Vsi podatki o tlaku v tem evropskem standardu so podani kot tlačne vrednosti merilnika v barih.
OPOMBA 2: Sprinklerje iz standarda EN 12259-1 je mogoče za bivalne površine uporabljati tudi, če je sistem zasnovan v skladu s standardom EN 12845.

General Information

Status
Withdrawn
Publication Date
21-Jan-2020
Withdrawal Date
13-Apr-2025
Current Stage
9960 - Withdrawal effective - Withdrawal
Start Date
25-May-2022
Completion Date
14-Apr-2025

Relations

Standard
EN 12259-14:2020
English language
64 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-marec-2020
Vgrajene naprave za gašenje - Sestavni deli sprinklerskih sistemov in sistemov s
pršečo vodo - 14. del: Sprinklerji za uporabo v stanovanjih
Fixed firefighting systems - Components for sprinkler and water spray systems - Part 14:
Sprinklers for residential applications
Ortsfeste Löschanlagen - Bauteile für Sprinkler- und Sprühwasseranlagen - Teil 14:
Sprinkler für die Anwendung im Wohnbereich
Installations fixes de lutte contre l’incendie - Composants des systèmes d’extinction du
type sprinkleur et à pulvérisation d’eau - Partie 14: Sprinkleurs pour applications
résidentielles
Ta slovenski standard je istoveten z: EN 12259-14:2020
ICS:
13.220.10 Gašenje požara Fire-fighting
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EN 12259-14
EUROPEAN STANDARD
NORME EUROPÉENNE
January 2020
EUROPÄISCHE NORM
ICS 13.220.20
English Version
Fixed firefighting systems - Components for sprinkler and
water spray systems - Part 14: Sprinklers for residential
applications
Installations fixes de lutte contre l'incendie - Ortsfeste Brandbekämpfungsanlagen - Bauteile für
Composants des systèmes d'extinction du type Sprinkler- und Sprühwasseranlagen - Teil 14: Sprinkler
sprinkleur et à pulvérisation d'eau - Partie 14: für die Anwendung im Wohnbereich
Sprinkleurs pour applications résidentielles
This European Standard was approved by CEN on 4 November 2019.

CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this
European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references
concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN
member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by
translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and
United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2020 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 12259-14:2020 E
worldwide for CEN national Members.

Contents Page
European foreword . 6
1 Scope . 7
2 Normative references . 7
3 Terms and definitions . 7
4 Construction and performance . 10
4.1 General . 10
4.2 Dimensions and pressure rating . 10
4.3 Nominal operating temperature . 11
4.4 Operating temperatures . 11
4.5 Water flow and distribution . 12
4.6 Function . 13
4.7 Fire Test . 13
4.8 Strength of sprinkler body and deflector . 13
4.9 Strength of release element. 14
Figure 1 — Graph of service load and bulb strength distribution curves . 14
4.10 Leak resistance and hydrostatic strength . 15
4.11 Heat exposure . 15
4.12 Corrosion . 15
4.13 Water hammer . 16
4.14 Thermal response . 16
4.15 Resistance to vibration . 16
4.16 Resistance to impact . 16
4.17 Resistance to low temperature . 16
4.18 Resistance to heat . 16
4.19 Test conditions . 16
5 Marking . 17
5.1 General . 17
5.2 Identification number . 17
5.3 Nominal operating temperature and year of manufacture . 17
5.4 Manufacturing location . 17
5.5 Heat sensitive element supplier . 17
5.6 Protective covers . 17
5.7 Sidewall sprinklers . 18
5.8 Concealed sprinklers . 18
5.9 Removable recessed housing . 18
6 Instruction charts. 18
6.1 General . 18
6.2 Installation Instructions . 18
Annex A (normative) Conditions for tests . 20
Annex B (normative) Water flow test . 21
Figure B.1— Water flow test apparatus . 22
Annex C (normative) Water distribution test . 23
C.1 Water distribution test – Horizontal surface . 23
C.1.1 General . 23
C.1.2 Upright, pendant, flush, recessed and concealed sprinklers . 23
Figure C.1 — Horizontal surface water collection for upright and pendant sprinklers . 24
C.1.3 Sidewall Sprinklers . 24
Figure C.2 — Horizontal surface water collection for sidewall sprinklers . 25
C.2 Water distribution test – vertical surface . 26
C.2.1 Test method . 26
Figure C.3 — Vertical water collection . 27
C.3 Water impingement test . 28
Annex D (normative) Fire test . 29
D.1 Extent of testing . 29
Figure D.1 — Fire test arrangement – pendant, upright, flush, recessed pendant, and
concealed sprinklers . 30
Figure D.2 — Fire test arrangement – sidewall sprinklers, test arrangement No. 1 . 31
Figure D.3 — Fire test arrangement – sidewall sprinklers, test arrangement No. 2 . 32
D.2 Test arrangement . 33
D.2.1 Test room . 33
Figure D.4 — Corner fire test ignition and fuel package . 34
Table D.1 — Plywood burning characteristics . 35
D.2.2 Fire source . 35
Table D.2 — Polyether foam burning characteristics . 36
D.2.3 Sprinkler installation . 36
D.3 Test method . 37
D.4 Supplementary test . 38
Annex E (normative) Function test . 39
E.1 Function test . 39
E.2 Verification function test . 39
Figure E.1 — Example of functional test oven . 40
Annex F (normative) Strength of sprinkler body and deflector . 41
F.1 Strength of sprinkler bod. 41
Figure F.1 — Example of a tensile/compression test machine . 41
F.2 Flow endurance test . 42
F.3 Deflector strength test . 42
Annex G (normative) Strength of release elements test . 43
G.1 Glass bulbs . 43
G.2 Fusible links . 45
Annex H (normative) Leak resistance tests . 46
H.1 Leak Test . 46
H.2 Hydrostatic Strength Test . 46
Table H.1 — Test pressures for the leakage and hydrostatic tests . 46
Annex I (normative) Heat exposure . 47
I.1 High temperature test . 47
Table I.1 — High temperature test conditions. 47
I.2 Additional testing of glass bulb sprinklers . 47
I.3 Additional testing of residential sprinklers using o-rings . 48
Annex J (normative) Glass bulb sprinkler thermal shock test . 49
Annex K (normative) Exposure and corrosion tests. 50
K.1 Stress corrosion . 50
K.1.1 Sample preparation . 50
K.1.2 Apparatus . 50
K.1.3 Procedure. 50
K.2 Sulphur dioxide corrosion . 50
K.2.1 Reagents for apparatus of 5 l volume . 50
K.2.2 Apparatus . 51
K.2.3 Procedure. 51
Figure K.1 — Typical vessel for sulphur dioxide corrosion test . 52
K.3 Salt mist corrosion . 52
K.3.1 Reagents . 52
K.3.2 Apparatus . 52
K.3.3 Procedure. 52
K.4 Moist Air . 53
K.4.1 Performance criteria . 53
K.4.2 Procedure. 53
Annex L (normative) Water hammer test . 54
Annex M (normative) Thermal response test . 55
M.1 Oven heat test . 55
M.2 Room heat test . 56
M.2.1 Flush, recessed or concealed sprinklers . 56
M.2.2 Sprinkler location and orientation . 56
M.2.3 Room dimensions and water supply . 57
M.2.4 Fire source and distance to sprinkler . 57
Figure M.1 — Typical sand burner apparatus . 58
Figure M.2 — Plan view of room heat test for residential sprinklers . 59
Annex N (normative) Vibration test . 60
N.1 Sample preparation and performance criteria . 60
N.2 Procedure . 60
Table N.1 — Vibration test . 60
Annex O (normative) Impact test . 61
Annex P (normative) Resistance to low temperature test . 62
Annex Q (normative) Resistance to high temperature test . 63
Bibliography . 64

European foreword
This document (EN 12259-14:2020) has been prepared by Technical Committee CEN/TC 191 “Fixed
firefighting systems”, the secretariat of which is held by BSI.
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by July 2020, and conflicting national standards shall be
withdrawn at the latest by July 2020.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN shall not be held responsible for identifying any or all such patent rights.
It is included in a series of European Standards planned to cover:
— automatic sprinkler systems (EN 12259 and EN 12845);
— gas extinguishing systems (EN 12094);
— powder systems (EN 12416);
— foam systems (EN 13565);
— hydrant and hose reel systems (EN 671);
— smoke and heat control systems (EN 12101).
According to the CEN-CENELEC Internal Regulations, the national standards organisations of the
following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria,
Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland,
Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Republic of
North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the
United Kingdom.
1 Scope
This document specifies requirements for the construction and performance of residential sprinklers as
well as test methods for their type approval, which are operated by a change of state of an element or
bursting of a glass bulb under the influence of heat, for use only in automatic sprinkler systems for
domestic and residential applications as defined in EN 16925.
This document does not cover representative fire and other tests for special sprinklers that are
intended to provide for specific fire hazards, nor does it cover fire and other tests for sprinklers for
commercial and industrial sprinkler systems as in EN 12845. Those test requirements are covered by
EN 12259-1.
NOTE 1 All pressure data in this document are given as gauge pressures in bar.
NOTE 2 Sprinklers according to EN 12259-1 can also be used in residential and domestic applications if the
system is designed according to EN 12845.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments) applies.
EN 12259-1:1999+A1:2001, Fixed firefighting systems — Components for sprinkler and water spray
systems — Part 1: Sprinklers
EN 13501-1, Fire classification of construction products and building elements - Part 1: Classification
using data from reaction to fire tests
EN 16925, Fixed firefighting systems - Automatic residential sprinkler systems - Design, installation and
maintenance
ISO 7-1, Pipe threads where pressure-tight joints are made on the threads — Part 1: Dimensions,
tolerances and designation
ISO 49, Malleable cast iron fittings threaded to ISO 7-1
ISO 65, Carbon steel tubes suitable for screwing in accordance with ISO 7-1
ISO 5658-2:2006, Reaction to fire tests — Spread of flame — Part 2: Lateral spread on building and
transport products in vertical configuration
ISO 5660-1:2015, Reaction-to-fire tests — Heat release, smoke production and mass loss rate — Part 1:
Heat release rate (cone calorimeter method) and smoke production rate (dynamic measurement)
UL 723, Standard for test for surface burning characteristics of building materials
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
ISO and IEC maintain terminological databases for use in standardization at the following addresses:
— IEC Electropedia: available at http://www.electropedia.org/
— ISO Online browsing platform: available at http://www.iso.org/obp
3.1
concealed sprinkler
unit (pre-assembled or assembled on site) consisting of a nozzle with a thermally sensitive sealing
device, a housing and a cover plate, that ensures that the sprinkler will be installed with all or part of
the thermally sensitive element behind the plane of the ceiling
3.2
recessed sprinkler
unit (pre-assembled or assembled on site) consisting of a nozzle with a thermally sensitive sealing
device and a housing, that ensures that the sprinkler will be installed with all or part of the thermally
sensitive element above the plane of the ceiling
3.3
discharge coefficient
known as K-factor
coefficient of discharge in the formula,
Q = K √ p (1)
where
Q is the flow in litres per minute, and
p is the pressure in bar
3.4
dry-type sprinkler
nozzle with a thermally sensitive sealing device secured in an extension nipple that has a seal at the
inlet end to prevent water from entering the nipple until the sprinkler operates
3.5
flush sprinkler
unit consisting of a nozzle with a thermally sensitive sealing device and housing, that ensures that the
sprinkler will be installed partly behind, but with the temperature sensitive element before, the finished
plane of the ceiling or wall
3.6
heat responsive element
portion of a sprinkler that breaks, melts, or otherwise functions to initiate the automatic operation of
the sprinkler when exposed to sufficient heat
3.7
heptane
commercial grade heptane having the following characteristics:
a) minimum Initial Boiling Point of 88 °C;
b) maximum Dry Point of 100 °C; and
c) specific Gravity (15,6 °C/15,6 °C) of 0,68 - 0,73.
3.8
orifice
opening that controls the amount of water discharged from a sprinkler at a given pressure
3.9
pendent sprinkler
nozzle with a thermally sensitive sealing device intended to be installed so that its deflector is located
below the orifice and the water flows downward through the orifice
3.10
residential sprinkler
nozzle with a thermally sensitive sealing device intended to be installed only in residential occupancies
as defined in EN 16925
3.11
sidewall sprinkler
nozzle with a thermally sensitive sealing device intended for installation on or near the wall
3.12
upright sprinkler
nozzle with a thermally sensitive sealing device intended to be installed so that its deflector is located
above the orifice
3.13
response time index
RTI
½ ½
measure of the thermal sensitivity of the sprinkler expressed in (meters.seconds) (m×s)
Note 1 to entry: Unlike in EN12259–1, the RTI value is calculated without considering the conductivity factor
3.14
design lower tolerance limit
DLTL
glass bulb supplier’s specified and assured lowest lower tolerance limit
3.15
design upper tolerance limit
DUTL
sprinkler supplier’s specified and assured highest upper tolerance limit
3.16
fusible link sprinkler
nozzle with a thermally sensitive sealing device which opens when an element provided for that
purpose melts
3.17
glass bulb sprinkler
nozzle with a thermally sensitive sealing device which opens when a liquid-filled glass bulb bursts
3.18
mean design service load
sprinkler supplier’s specified and assured highest mean service load for any batch of 10 or more
sprinklers
3.19
mean design strength
glass bulb supplier’s specified and assured lowest mean bulb strength for any batch of 55 or more bulbs
3.20
horizontal sprinkler
nozzle with a thermally sensitive sealing device in which the nozzle directs the water horizontally
3.21
lower tolerance limit
LTL
glass bulb lowest strength determined by test and statistical analysis of a batch of 55 or more bulbs
3.22
supplier
company responsible for the design, manufacture and quality assurance of a product
3.23
upper tolerance limit
UTL
highest service load determined by test and statistical analysis of a batch of 20 or more sprinklers
3.24
frame arms
part of a sprinkler that maintains the thermally sensitive element in load bearing contact with the
sprinkler head valve
4 Construction and performance
4.1 General
Sprinklers shall only be assembled in such a way that adjustment or dismantling will result in
destruction of an element of construction.
It shall be possible to remove the cover of a concealed sprinkler without having to use special tools, e.g.
for visual inspections.
4.2 Dimensions and pressure rating
4.2.1 Dimensions
Nominal thread sizes shall be suitable for fittings threaded in accordance with ISO 7-1.
It shall be possible for a sphere of (5,0 +0,01/-0) mm diameter to pass through the orifice of the
sprinkler.
4.2.2 Pressure ratings
A residential sprinkler shall have a maximum operating pressure of at least 12 bar.
4.3 Nominal operating temperature
When tested in accordance with “Test to determine operating temperatures of fusible link sprinklers
and glass bulb sprinklers” of EN 12259-1:1999, sprinklers shall operate at a temperature within the
range:
o
T = [t ± (0,035 t +0,62)] C
test
where
t is the nominal operating temperature.
When cover plates are tested in accordance with the “Test to determine operating temperatures of
fusible link sprinklers and glass bulb sprinklers” of EN 12259-1:1999, cover plates shall operate at a
temperature within the range:
o
T = [t ± (0,035 t +0,62)] C
test cover
where
t is the nominal operating temperature of the cover.
cover
This temperature t shall be 8 °C to 20 °C lower than the nominal operating temperature of its
cover
sprinkler head.
4.4 Operating temperatures
The temperature classification, temperature rating, and colour coding of a residential sprinkler shall be
as specified in Table 1.
Table 1 — Nominal operating temperatures and colour codes
Glass bulb sprinklers Fusible link sprinklers
Nominal operating Liquid Nominal operating Frame arms
temperature colour code temperature within colour code
°C range
°C
57 Orange 57 to 77 uncoloured
68 Red 80 to 107 white
79 Yellow
93 Green
100 Green
4.5 Water flow and distribution
4.5.1 K-factor
The nominal K-factor shall be specified by the supplier. The K-factor of the sprinklers shall be within the
nominal value ± 5 % for other than dry sprinklers and ± 8 % for dry sprinklers, when determined in
accordance with Annex B.
4.5.2 Water distribution
4.5.2.1 Water distribution test – Horizontal surface
When installed in accordance with the installation instructions and tested as described in C.1 a
residential sprinkler shall distribute water over a horizontal surface so that the discharge density for
any pan within the design area (the maximum area the sprinkler is intended to protect) shall be at least
0,8 mm/min except that:
a) no more than 2 pans (0,5 m × 0,5 m) or not more than 4 pans (0,3m × 0,3m) for each quadrant shall
be allowed to be at least 0,6 mm/min for upright and pendant sprinklers; and
b) no more than 8 pans (0,3 m × 0,3 m) or 3 pans (0,5 m × 0,5 m) shall be allowed to be at least
0,6 mm/min for each half (split along the sprinkler centreline) of the maximum area a sidewall
sprinkler is intended to protect
4.5.2.2 Water distribution test – Vertical surface
When installed in accordance with the installation instructions and tested as described in C.2, a
residential sprinkler shall distribute water in a uniform manner over vertical surfaces as follows:
a) walls within the coverage area shall be completely wetted to at least within 711 mm of the ceiling
with one sprinkler discharging water at the specified design flow rate;
b) for square coverage areas, each wall within the coverage area shall be wetted with at least 5 % of
the sprinkler flow; for rectangular coverage areas, each wall within the coverage area shall be
wetted with a proportional water amount based on 20 % of the total sprinkler discharge in
accordance with the following formula

WW – 20 % (D / P) (2)
where
WW is required amount of water collected on a wall, in %;
D is wall length, in m;
P is total perimeter of coverage area, in m.
4.5.3 Water Impingement Test
When tested in accordance with Annex C and while discharging water at a service pressure of 5,2 bar
less than the maximum operating pressure, a residential sprinkler shall not prevent the operation of an
adjacent residential sprinkler.
4.6 Function
When tested in accordance with Annex E each of the residential sprinklers shall operate at service
pressures of 0,5 bar to the maximum operating pressure. The sprinkler shall open and within 5 s of
release of the thermally sensitive element shall operate satisfactorily. Any lodgement of released parts
shall be cleared within 60 s of the release of the thermally sensitive element. After testing in accordance
with Annex E the sprinkler shall conform to the requirements of 4.5.2.
NOTE In most instances visual examination of the equipment will be sufficient to establish conformity with the
requirements of 4.5.2.
4.7 Fire Test
When fire tested as described in Annex D a residential sprinkler shall limit temperatures as specified
below when tested at each spacing referenced in the installation instructions. Additionally, a maximum
of two residential sprinklers shall operate and the third sprinkler, located near the 1 000 mm wide
doorway, shall not operate. The sprinklers shall limit temperatures as follows:
a) The maximum temperature measured 76 mm below the ceiling at locations 4 and 5 as illustrated in
Figure D.1, Figure D.2 and Figure D.3 shall not exceed 316 °C.
b) The maximum temperature measured 1,6 m above the floor at location 4 shall not exceed 93 °C.
c) The temperature at the location described in (b) shall not exceed 54 °C for more than any
continuous 2 min period.
d) The maximum ceiling material temperature measured 6 mm behind the finished ceiling surface
shall not exceed 260 °C.
NOTE The thermocouple 76 mm below the ceiling, located above the fire source, is for reference purposes
only.
See Figure D.1, (pendant, upright, flush, recessed pendant, and concealed sprinklers) or Figure D.2 and
Figure D.3 (sidewall sprinklers) for temperature measuring locations.
4.8 Strength of sprinkler body and deflector
4.8.1 Strength of frame
The sprinkler body shall not show permanent elongation of more than 0,2 % between the load-bearing
parts when subjected to twice the average service load when tested in accordance with F.1.
4.8.2 Flow endurance
A residential sprinkler shall withstand for 30 min, without evidence of cracking, deformation, or
separation of any part when tested in accordance with F.2.
4.8.3 Strength of deflector
The sprinkler deflector and its supporting parts shall withstand an applied force of 70 N without
permanent deformation when tested in accordance with F.3.
4.9 Strength of release element
4.9.1 Glass bulb sprinklers
When evaluated and tested in accordance with Annex G, glass bulb sprinklers shall have:
a) a mean design bulb strength of at least six times the mean design service load;
b) a mean bulb strength not less than the mean design bulb strength;
c) a mean service load not more than the mean design service load;
d) a design lower tolerance limit (DLTL) on the distribution curve of at least two times the design
upper tolerance limit (DUTL) of the service load distribution curve;
e) an upper tolerance limit (UTL) less than or equal to the design upper tolerance limit (DUTL);
f) a lower tolerance limit (LTL) greater than or equal to the design lower tolerance limit (DLTL) see
Figure 1.
Key
1 service load distribution curve
2 bulb strength distribution curve
3 mean service load
4 mean bulb strength
5 upper tolerance limit (UTL)
6 lower tolerance limit (LTL)
A number of samples
B strength (N)
Figure 1 — Graph of service load and bulb strength distribution curves
4.9.2 Fusible link sprinklers
It shall be determined that:
a) the temperature sensitive elements withstand a load of 15 times the maximum design load for a
period of 100 h, without failure; or
b) the estimated time to failure of temperature sensitive elements is not less than 876 600 h at the
design load, when tested in accordance with Annex G.
4.10 Leak resistance and hydrostatic strength
Twenty residential sprinklers shall be tested and not leak when tested in accordance with H.1 and,
subsequently, shall not rupture, operate or release, when tested in accordance with H.2.
4.11 Heat exposure
4.11.1 General
A residential sprinkler shall withstand for 90 days, without evidence of weakness or malfunction, an
exposure to the high-ambient temperature in accordance with I.1.
After the exposure period four sprinklers shall be tested in accordance with E.2; the sprinklers shall
operate such that the waterway is cleared. Any lodgements shall be disregarded. Four sprinklers shall
be leak tested in accordance with H.1. Four sprinklers shall be tested in accordance with “Test to
determine operating temperatures of fusible link sprinklers and glass bulb sprinklers” of
EN 12259-1:1999.
Additionally, after the exposure period four recessed, concealed and flush sprinklers shall be tested in
accordance with M.2. Their mean operating time shall be equal to or less than a 1,30 multiple of the
mean operating time of the sprinkler tested in accordance with M.2 for compliance with 4.14.2.
4.11.2 Additional heat exposure of glass bulb sprinklers
There shall be no damage to the glass bulb when sprinklers are tested in accordance with I.2.
4.11.3 Additional heat exposure of sprinklers using o-rings
After the exposure period as defined in I.3 four sprinklers shall be tested in accordance with E.2; the
sprinklers shall operate such that the waterway is fully cleared. Any lodgements shall be disregarded.
4.11.4 Thermal shock
When glass bulb sprinklers are tested in accordance with Annex J, the glass bulbs shall either:
— break correctly on cooling such that the waterway is cleared; or
— remain intact. After immersion when subjected to a function test in accordance with E.2, the
sprinkler shall operate in such way that the waterway is cleared; any lodgements shall be
disregarded.
4.12 Corrosion
4.12.1 Stress corrosion
After being subjected for 10 days to a moist ammonia exposure as described in K.1 a residential
sprinkler having copper alloy parts shall:
a) show no evidence of cracking, delamination, or degradation; and
b) perform as intended when tested as described in K.1.
If the application of a 12 bar water pressure to the inlet of the sprinkler increases the assembly load by
more than 10 %, the additional load is to be applied during the moist ammonia-air mixture exposure
specified in K.1.
4.12.2 Sulphur dioxide corrosion
Residential sprinklers shall be subjected to a sulphur dioxide corrosion test in accordance with K.2.
After exposure, when subjected to a function test in accordance with E.2 the sprinkler shall operate
such that the waterway is cleared; any lodgements shall be disregarded.
4.12.3 Salt mist corrosion
Residential sprinklers shall be subjected to a salt mist corrosion test in accordance with K.3. After
exposure, when subjected to a function test in accordance with E.2, the sprinkler shall operate such that
the waterway is cleared; any lodgements shall be disregarded.
4.12.4 Moist air
Residential sprinklers shall withstand an exposure to moist air atmospheres when tested in accordance
with K.4.
4.13 Water hammer
Sprinklers shall not leak when subjected to pressure surges in accordance with Annex L. After the test,
when subjected to a function test in accordance with E.2, the sprinkler shall operate such that the
waterway is cleared; any lodgements shall be disregarded.
4.14 Thermal response
4.14.1 Oven test
When tested in accordance with M.1, upright, pendent and horizontal sprinklers, other than flush,
recessed and concealed sprinklers, shall release within a maximum time which is to be calculated from
the formula in M.1, based on a response time index (RTI) 50.
4.14.2 Room response test
When tested in accordance with M.2, flush, recessed and concealed sprinklers shall release within 75 s.
4.15 Resistance to vibration
A residential sprinkler shall withstand the effects of vibration without deterioration of its performance
characteristics when tested in accordance with Annex N.
4.16 Resistance to impact
A residential sprinkler, except for dry-type sprinklers, shall be tested as described in Annex O and shall
not be damaged or leak.
4.17 Resistance to low temperature
The sprinkler shall not operate before the function test, when tested in accordance with Annex P. After
the low temperature exposure it shall show no visible evidence of damage. Following examination,
when subjected to a function test in accordance with E.2, the sprinkler shall operate such that the
waterway is cleared; any lodgements shall be disregarded.
4.18 Resistance to heat
When tested in accordance with Annex Q, the sprinkler body, deflector and its supporting parts shall
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.

Loading comments...

Frequently Asked Questions

EN 12259-14:2020 is a standard published by the European Committee for Standardization (CEN). Its full title is "Fixed firefighting systems - Components for sprinkler and water spray systems - Part 14: Sprinklers for residential applications". This standard covers: This document specifies requirements for the construction and performance of residential sprinklers as well as test methods for their type approval, which are operated by a change of state of an element or bursting of a glass bulb under the influence of heat, for use only in automatic sprinkler systems for domestic and residential applications as defined in EN 16925:− . This standard does not cover representative fire and other tests for special sprinklers that are intended to provide for specific fire hazards, nor does it cover fire and other tests for sprinklers for commercial and industrial sprinkler systems as in EN 12845. Those test requirements are covered by EN 12259-1. NOTE 1 All pressure data in this European Standard are given as gauge pressures in bar. NOTE 2 Sprinklers according to EN12259-1 can also be used in residential and domestic applications if the system is designed according to EN 12845.

This document specifies requirements for the construction and performance of residential sprinklers as well as test methods for their type approval, which are operated by a change of state of an element or bursting of a glass bulb under the influence of heat, for use only in automatic sprinkler systems for domestic and residential applications as defined in EN 16925:− . This standard does not cover representative fire and other tests for special sprinklers that are intended to provide for specific fire hazards, nor does it cover fire and other tests for sprinklers for commercial and industrial sprinkler systems as in EN 12845. Those test requirements are covered by EN 12259-1. NOTE 1 All pressure data in this European Standard are given as gauge pressures in bar. NOTE 2 Sprinklers according to EN12259-1 can also be used in residential and domestic applications if the system is designed according to EN 12845.

EN 12259-14:2020 is classified under the following ICS (International Classification for Standards) categories: 13.220.20 - Fire protection. The ICS classification helps identify the subject area and facilitates finding related standards.

EN 12259-14:2020 has the following relationships with other standards: It is inter standard links to EN 12259-14:2020+A1:2022, EN 12259-14:2020/FprA1. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

EN 12259-14:2020 is associated with the following European legislation: Standardization Mandates: M/109. When a standard is cited in the Official Journal of the European Union, products manufactured in conformity with it benefit from a presumption of conformity with the essential requirements of the corresponding EU directive or regulation.

You can purchase EN 12259-14:2020 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of CEN standards.

EN 12259-14:2020は、固定消防システムにおける住宅用スプリンクラーの構成要素に関する基準であり、住宅アプリケーションのためのスプリンクラーの製造と性能に関する要件を明確に定義しています。この基準の範囲は、自動スプリンクラーシステムとして使用されるスプリンクラーの動作原理に基づいており、熱の影響を受けた要素の状態変化またはガラス球の破裂によって作動します。特に、家庭や居住用の用途に特化しており、EN 16925で定義された基準を踏まえた内容です。 この標準の強みは、住宅用スプリンクラーの試験方法とタイプ承認のための具体的な指針を提供している点です。これにより、製品の設計者や製造者が高い安全基準を維持しつつ、効率的にスプリンクラーを開発できる環境が整います。また、データの圧力測定がすべてバールのゲージ圧として示されていることから、設計者は実際の運用条件に基づいた正確な計算を行うことが可能です。 ただし、本標準は特定の火災危険に対処するための特殊スプリンクラーに関する試験や、商業用および産業用スプリンクラーシステムに関する試験はカバーしていないため、注意が必要です。これらの要件は、EN 12259-1において別途定義されています。 総じて、EN 12259-14:2020は住宅用スプリンクラーシステムの設計と実施において非常に重要な標準であり、信頼性の高い消防システムの構築に寄与します。住宅や居住用アプリケーションに特化した内容であるため、関連する分野での実用性は高いといえます。

La norme EN 12259-14:2020 se concentre sur les systèmes d'extinction incendie fixes, spécifiquement sur les composants destinés aux systèmes de gicleurs et de pulvérisation d'eau, en mettant l'accent sur les gicleurs pour applications résidentielles. Cette norme définit les exigences de construction et de performance des gicleurs résidentiels et les méthodes d'essai pour leur approbation de type. L'un des points forts de cette norme est sa clarté dans la définition des exigences techniques à respecter pour garantir la sécurité dans les applications domestiques. En se basant sur un changement d'état d'un élément ou la rupture d'une ampoule en verre sous l'effet de la chaleur, elle assure que les dispositifs de sprinklage fonctionnent de manière efficace et rapide en cas d'incendie. De plus, la norme précise qu'elle s'applique uniquement aux systèmes automatiques de gicleurs pour les applications domestiques, évitant ainsi les ambiguïtés liées à d'autres types de systèmes. La pertinence de la norme EN 12259-14:2020 est renforcée par son lien avec d'autres normes, telles que EN 16925 et EN 12845, offrant ainsi une approche harmonisée de la sécurité incendie dans les contextes résidentiels. Il est également à noter que les données de pression sont spécifiées en tant que pressions manométriques en bar, ce qui facilite la compréhension et l'application des exigences techniques pour les fabricants et les installateurs de systèmes de sprinklage. Cependant, il est important de souligner que la norme ne couvre pas certains tests représentatifs pour des gicleurs spéciaux destinés à des risques d'incendie spécifiques, ni les gicleurs pour systèmes commerciaux et industriels, ce qui pourrait limiter son application dans des contextes variés. Cela est compensé par la référence à EN 12259-1 pour les exigences concernant les tests de ces autres types de systèmes. En résumé, la norme SIST EN 12259-14:2020 se révèle être un document fondamental pour les fabricants et les professionnels de la sécurité incendie, consolidant ainsi les bases de la sécurité dans les installations domestiques grâce à des critères bien définis de performance et de construction des gicleurs.

Die Norm EN 12259-14:2020 legt spezifische Anforderungen an die Konstruktion und Leistung von Sprinklern für Wohnanwendungen fest, sowie die Prüfmethoden für deren Typgenehmigung. Diese Norm bezieht sich ausschließlich auf automatisierte Sprinklersysteme, die in häuslichen und wohnlichen Anwendungen eingesetzt werden, und definiert die grundlegenden Merkmale, die diese Sicherheitssysteme erfüllen müssen. Ein zentraler Stärke der EN 12259-14:2020 ist die detaillierte Beschreibung der Wirkungsweise von Sprinklern, die durch einen Zustandswechsel eines Elements oder das Zerbrechen einer Glasbirne unter dem Einfluss von Hitze aktiviert werden. Dadurch wird sichergestellt, dass die Sprinkler in der Lage sind, in kritischen Situationen effektiv zu reagieren, was die Sicherheit in Wohngebäuden erheblich erhöht. Die Dokumentation bietet auch klar angegebene Prüfmethoden zur Typgenehmigung, die es Herstellern ermöglichen, ihre Produkte nach einheitlichen Standards zu testen. Dies fördert nicht nur die Qualität und Zuverlässigkeit der Sprinkler, sondern bietet auch den Anwendern Sicherheit bei der Wahl des richtigen Produkts für ihre Bedürfnisse. Es ist wichtig zu beachten, dass diese Norm nicht für spezielle Sprinkler konzipiert ist, die für spezifische Brandgefahren bestimmt sind, noch umfasst sie Prüfungen für Sprinkler in kommerziellen oder industriellen Anwendungen, welche unter EN 12845 behandelt werden. Diese Abgrenzung macht die Norm besonders relevant für den Wohnbereich und stellt sicher, dass sie spezifisch auf die Anforderungen des häuslichen Feuerschutzes abgestimmt ist. Zusammenfassend lässt sich sagen, dass die EN 12259-14:2020 eine bedeutende Ressource im Bereich der festen Feuerlöschsysteme darstellt, da sie klare Richtlinien für die Implementierung von Sprinklersystemen in Wohnanwendungen bietet und somit einen wertvollen Beitrag zur Sicherheit von Wohngebäuden leistet. Die Einhaltung dieser Norm kann als Bestätigung für die Qualität und Zuverlässigkeit der eingesetzten Sprinkler angesehen werden.

SIST EN 12259-14:2020 표준은 주거용 스프링클러 및 물 분사 시스템의 구성 요소에 관한 중요한 요구 사항을 명시하고 있습니다. 이 표준의 주요 범위는 주거용 스프링클러의 구조와 성능, 그리고 해당 스프링클러의 유형 승인을 위한 시험 방법을 포함하여, 특정 온도에서 상태 변화를 통해 작동되거나 유리구슬의 파열로 작동되는 스프링클러에 대한 상세한 규정을 제공합니다. 이 표준의 강점 중 하나는 주거 및 국내 용도로 정의된 자동 스프링클러 시스템에 대한 명확한 지침을 제시한다는 점입니다. 특히, EN 16925에서 정의한 바와 같이 가정에서의 화재를 예방하고 안전성을 높이기 위한 목표를 가지고 있습니다. 그러므로, 주거용 애플리케이션에 특히 적합한 구성 요소를 보장하며, 기술적으로 신뢰할 수 있는 스프링클러 시스템의 설치를 촉진합니다. 또한, SIST EN 12259-14:2020은 특별한 화재 위험에 대응하기 위한 스프링클러에 대한 대표적인 화재 및 기타 시험을 다루고 있지 않으며, 상업 및 산업 스프링클러 시스템을 위한 시험 요구 사항은 EN 12845에 의해 규제됩니다. 이러한 명료한 구분은 사용자가 자신의 요구에 맞는 시스템을 선택할 수 있도록 돕고, 스프링클러 시스템의 성능을 향상시키는 데 기여합니다. 마지막으로, 이 표준은 주거용 스프링클러 시스템을 설계할 때 EN 12845에 따라 설계된 스프링클러를 사용할 수도 있음을 언급함으로써, 전반적인 설계 유연성을 제공하고 있습니다. 따라서, SIST EN 12259-14:2020은 주거용 스프링클러 시스템의 안전성, 효과성 및 신뢰성을 보장하는 데 있어 필수적인 표준으로 자리잡고 있습니다.

The EN 12259-14:2020 standard is a significant document in the realm of fire safety, specifically designed for fixed firefighting systems utilized in residential applications. The scope of this standard is clearly defined, establishing essential requirements for the construction and performance of residential sprinklers. This focus on sprinklers ensures that these critical components of fire safety are effectively evaluated and operated in environments typical of domestic and residential settings. One of the primary strengths of EN 12259-14:2020 is its specification of test methods for type approval, which are crucial for ensuring that residential sprinklers respond properly to heat stimuli. The document emphasizes the importance of the construction quality and performance standards necessary for sprinklers, thus enhancing their reliability in real-world scenarios. By focusing only on automatic sprinkler systems for residential applications, this standard provides targeted guidelines that meet the unique challenges faced in domestic environments. Furthermore, while EN 12259-14:2020 establishes comprehensive guidelines for residential sprinklers, it importantly distinguishes itself by not covering special fire hazard tests or sprinklers intended for commercial and industrial systems. Instead, those requirements are addressed in EN 12259-1 and EN 12845, allowing users to easily identify which standards apply to specific scenarios. This separation of standards aids in clarity and helps manufacturers and safety professionals ensure compliance with the correct regulations for their respective applications. The standard also includes valuable notes clarifying that all pressure data is presented as gauge pressures in bar, and highlights that sprinklers according to EN 12259-1 can also be utilized for residential purposes, provided the overall system is designed according to EN 12845. This flexibility enhances the applicability of the guidelines to a broader range of systems while still maintaining a specific focus on residential safety. In summary, the EN 12259-14:2020 standard is vital for establishing effective safety measures in residential firefighting systems. By setting clear expectations for sprinkler construction, performance, and testing, it directly contributes to improved fire safety in domestic settings, offering peace of mind to homeowners and fire safety professionals alike.