Gas safety shut-off devices for inlet pressure up to 10 MPa (100 bar)

This document specifies constructional, functional, testing marking and sizing requirements and documentation of gas safety shut-off devices:
-   for inlet pressures up to 100 bar and nominal diameters up to DN 400;
-   for an operating temperature range from -20 °C to +60 °C;
which operate with fuel gases of the 1st and 2nd family as defined in EN 437, used in the pressure regulating stations in accordance with EN 12186 or EN 12279, in transmission and distribution networks and also in commercial and industrial installations.
"Gas safety shut-off devices" will hereafter be called "SSDs" except in titles.
For standard safety shut-off devices when used in pressure regulating stations complying with EN 12186 or EN 12279, Annex ZA lists all applicable Essential Safety Requirements of Directive 2014/68/EU (PED).
This document considers the following temperature classes/types of SSDs:
-   temperature class 1: operating temperature range from -10 °C to 60 °C;
-   temperature class 2: operating temperature range from -20 °C to 60 °C;
-   functional class A: SSDs that close when damage to the pressure detecting element occurs or when external power fails and whose re-opening, is possible only manually;
-   functional class B: SSDs that do not close when damage to the pressure detecting element occurs but provide suitable and reliable protection and whose re-opening, is possible only manually;
-   type IS: (integral strength type);
-   type DS: (differential strength type).
SSDs complying with the requirements of this document may be declared as "in conformity with EN 14382" and bear the mark "EN 14382".
The material and functional requirements specified in this document may be applied to SSDs which use thermal energy or the effects of electrical energy to trip the operation of the closing member. For these SSDs the operational parameters are not specified in this document.
The SSD may incorporate a vent limiter, complying with the requirements in Annex J.
This standard for some paragraphs and sub clauses makes full reference to prEN 334:2016.
This document does not apply to:
-   SSDs upstream from/on/in domestic gas-consuming appliances which are installed downstream of domestic gas meters;
-   SSDs designed to be incorporated into pressure-regulating devices used in service lines  with volumetric flow rate ≤ 200 m3/h at normal conditions and inlet pressure ≤ 5 bar.
Continued integrity of safety shut-off devices is ensured by periodic functional checks. For periodic functional checks it is common to refer to national regulations/standards where existing or users/manufacturers practices.
This document considers the reaction of the SSDs functional class A to the specified reasonable expected failures in terms of "fail close" behaviour, but it should be consider that there are other types of failures whose consequences cannot bring to the same reactions (these risks are covered via redundancy as per EN 12186) and that residual hazards should be reduced by a suitable surveillance in use / maintenance.
In this document, both safety shut-off devices that can be classified as "safety accessories" by themselves according the Pressure Equipment Directive (2014/68/EU) as well as safety shut-off devices that can be used to provide the necessary pressure protection through redundancy (e.g. shutoff device integrated in a pressure regulator, shut-off device with a second shut-off device) are considered. Addition of environmental considerations;
The provisions in this document are in line with the state of art at the moment of writing.
This document does not intend to limit the improvement of actual provisions (materials, requirements, test methods, acceptance criteria, etc.) or the developing of new provisions for SSDs where they are suitable to ensure an equivalent level of reliability.

Gas-Sicherheitsabsperreinrichtungen für Eingangsdrücke bis 10 MPa (100 bar)

No scope available

Dispositifs de sécurité pour postes et installations de détente-régulation de pression de gaz - Clapets de sécurité pour pressions amont jusqu'à 100 bar

No scope available

Plinske varnostne zaporne naprave za vstopne tlake do 10 MPa (100 bar) - Dopolnilo A1

General Information

Status
Not Published
Publication Date
21-Jan-2025
Current Stage
4599 - Dispatch of FV draft to CMC - Finalization for Vote
Start Date
01-Jun-2023
Due Date
21-Jan-2024
Completion Date
01-Jun-2023

Relations

Buy Standard

Draft
EN 14382:2019/oprA1:2022
English language
5 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 14382:2019/oprA1:2022
01-oktober-2022
Plinske varnostne zaporne naprave za vstopne tlake do 10 MPa (100 bar) -
Dopolnilo A1
Gas safety shut-off devices for inlet pressure up to 10 MPa (100 bar)
Gas-Sicherheitsabsperreinrichtungen für Eingangsdrücke bis 10 MPa (100 bar)
Clapets de sécurité pour pressions amont jusqu'à 10 MPa (100 bar)
Ta slovenski standard je istoveten z: EN 14382:2019/prA1
ICS:
23.060.40 Tlačni regulatorji Pressure regulators
SIST EN 14382:2019/oprA1:2022 en,fr,de

2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------
SIST EN 14382:2019/oprA1:2022
---------------------- Page: 2 ----------------------
SIST EN 14382:2019/oprA1:2022
DRAFT
EUROPEAN STANDARD
EN 14382:2019
NORME EUROPÉENNE
EUROPÄISCHE NORM
prA1
September 2022
ICS
English Version
Gas safety shut-off devices for inlet pressure up to 10 MPa
(100 bar)

Clapets de sécurité pour pressions amont jusqu'à 10 Gas-Sicherheitsabsperreinrichtungen für

MPa (100 bar) Eingangsdrücke bis 10 MPa (100 bar)

This draft amendment is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee CEN/TC 235.

This draft amendment A1, if approved, will modify the European Standard EN 14382:2019. If this draft becomes an amendment,

CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for inclusion of

this amendment into the relevant national standard without any alteration.

This draft amendment was established by CEN in three official versions (English, French, German). A version in any other

language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC

Management Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,

Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,

Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and

United Kingdom.

Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are

aware and to provide supporting documentation.

Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without

notice and shall not be referred to as a European Standard.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels

© 2022 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 14382:2019/prA1:2022 E

worldwide for CEN national Members.
----------------------
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.