Smoke and heat control systems - Part 11: Horizontal flow powered ventilation systems for enclosed car parks

This document gives minimum design, installation and commissioning requirements for powered smoke and heat control systems for enclosed car parks using horizontal flow powered ventilation, with or without sprinkler protection, on one or more levels, for cars and light commercial vehicles (max 3,5 t), to reach the design objectives outlined in this document .
This document is applicable for car parks with vehicles powered by petrol, diesel, electricity, CNG or LPG.
NOTE 1   For the purpose of this document for smoke ventilation systems, it is assumed that cars powered by electricity, CNG (compressed natural gas) or LPG (liquefied petroleum gas) will have similar HRR to vehicles powered by petrol or diesel.
NOTE 2   Cars powered by hydrogen are not covered by this document.
This document only covers traditional car parks that are with cars parked alongside each other, with common car access lanes. It does not cover other forms of car parking systems, such as stacking systems.
This document does not cover requirements for day‐to‐day ventilation.
Any other risks than fire from cars are not covered by this document.

Rauch- und Wärmefreihaltung - Teil 11: Horizontal betriebene Systeme der Rauchfreihaltung für geschlossene Parkhäuser

Dieses Dokument enthält die Mindestanforderungen an Auslegung, Installation und Inbetriebnahme für angetriebene Anlagen zur Rauch- und Wärmefreihaltung für umschlossene Parkhäuser für Autos und leichte Nutzfahrzeuge (max. 3,5 t), in denen angetriebene Belüftungssysteme mit horizontalem Luftstrom, mit oder ohne Sprinklerschutz, auf einer oder mehreren Ebenen verwendet werden, die zur Erreichung der in diesem Dokument dargelegten Entwurfsziele erforderlich sind.
Dieses Dokument ist anwendbar für Parkhäuser mit benzin-, diesel-, gasbetriebenen (CNG oder LPG) oder elektrisch betriebenen Fahrzeugen.
ANMERKUNG 1   Für die Anwendung dieses Dokuments zu Rauchschutz-Belüftungssystemen wird angenommen, dass elektrisch, mit CNG (verdichtetes Erdgas) oder LPG (Flüssiggas) angetriebene Autos eine ähnliche Wärmefreisetzungsrate aufweisen wie benzin- oder dieselbetriebene Autos.
ANMERKUNG 2   Autos mit Wasserstoffantrieb sind von diesem Dokument nicht abgedeckt.
Dieses Dokument deckt nur traditionelle Parkhäuser mit nebeneinander angeordneten Parkplätzen und gemeinsamen Zufahrtsspuren ab. Andere Parksysteme, wie Stapelparker, sind nicht abgedeckt.
Dieses Dokument deckt keine Anforderungen an die alltägliche Belüftung ab.
Jegliche anderen Risiken außer Fahrzeugbrände werden von diesem Dokument nicht abgedeckt.

Systèmes pour le contrôle des fumées et de la chaleur - Partie 11 : Systèmes de ventilation motorisée à flux horizontal pour aires de stationnement fermées

Le présent document énonce les exigences minimales de dimensionnement, d’installation et de mise en service des systèmes motorisés pour le contrôle des fumées et de la chaleur pour les aires de stationnement fermées utilisant une ventilation motorisée à flux horizontal, avec ou sans protection par sprinkleurs, sur un ou plusieurs niveaux, pour les voitures et les véhicules commerciaux légers (max. 3,5 t), afin d’atteindre les objectifs de dimensionnement décrits dans le présent document.
Le présent document est applicable aux aires de stationnement de véhicules fonctionnant à l’essence ou au diesel, à l’électricité, au GNC ou au GPL.
NOTE 1   Pour les besoins du présent document concernant les systèmes de dispositifs d’évacuation des fumées, les voitures fonctionnant à l’électricité, au GNC (gaz naturel comprimé) ou au GPL (gaz de pétrole liquéfié) sont présumées avoir un débit calorifique similaire à celui des véhicules fonctionnant à l’essence ou au diesel.
NOTE 2   Les voitures fonctionnant à l’hydrogène ne sont pas couvertes par le présent document.
Le présent document couvre uniquement les aires de stationnement conventionnelles dont les voitures sont garées côte à côte, avec des voies d’accès communes. Il ne couvre pas d’autres formes de systèmes de stationnement, tels que les systèmes d’empilage.
Le présent document ne couvre pas les exigences concernant la ventilation normale.
Les risques autres que l’incendie de voitures ne sont pas couverts par le présent document.

Sistemi za nadzor dima in toplote - 11. del: Prezračevalni sistemi z vodoravnim tokom za zaprta parkirišča

(1) Ta tehnična specifikacija določa minimalne zahteve glede zasnove, namestitve in začetka obratovanja za električne sisteme za nadzor dima in toplote na zaprtih parkiriščih, ki uporabljajo prezračevanje s horizontalnim kroženjem, z ali brez sprinklerske zaščite, na eni ali več ravneh, za avtomobile in lahka gospodarska vozila (največ 3,5 t), da se dosežejo cilji projektiranja, opisani v tej tehnični specifikaciji.
Glej cilje zasnove v določilih CEN TC191 SC1, dok. N721, 5.1 (1):
Sistem mora za vsako požarno lokacijo zagotavljati vsaj eno dostopno pot brez prevelike količine dima, ki gasilcem omogoča dostop z zunanje strani ali z zaščitene dostopne poti (npr. stopnišča) na razdalji 15 m od sprednje strani požara. Merila naj se preverijo, ko se na parkirišču vzpostavi stacionarno stanje.
OPOMBA: Meja 15 m je potrebna za doseganje ognja s curkom iz brizgalne cevi.
(2) Ta tehnična specifikacija se uporablja za goreče avtomobile na bencin, dizel ali druga goriva, ki bodo imeli podobne požarne lastnosti kot vozila na bencin ali elektriko. Ne uporablja se za druge požare na parkirišču (npr. skladišče).
OPOMBA: Predpostavlja se, da bodo imeli avtomobili na goriva, ki niso bencin ali dizel, podobne požarne lastnosti kot vozila na bencin ali dizel.
(3) Ta tehnična specifikacija zajema le tradicionalna parkirišča, kjer so avtomobili parkirani eden poleg drugega s skupnimi dovoznimi cestami/pasovi za vstop in izstop avtomobilov. Ne zajema drugih oblik sistemov za parkiranje avtomobilov, kot so sistemi za etažno parkiranje avtomobilov. Sistemi za nadzor dima in toplote za vozila, težja od 3,5 t (parkirišča za tovornjake, avtobusna parkirišča itd.), v tej tehnični specifikaciji niso zajeti.
(4) Ta tehnična specifikacija ne zajema zahtev za vsakodnevno prezračevanje.
(5) V tej tehnični specifikaciji poleg gorečih avtomobilov niso zajeta nobena druga tveganja.

General Information

Status
Published
Publication Date
19-Jul-2022
Current Stage
6060 - Definitive text made available (DAV) - Publishing
Start Date
20-Jul-2022
Due Date
07-Feb-2021
Completion Date
20-Jul-2022

Buy Standard

Technical specification
TS CEN/TS 12101-11:2022 - BARVE
English language
51 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-september-2022
Sistemi za nadzor dima in toplote - 11. del: Prezračevalni sistemi z vodoravnim
tokom za zaprta parkirišča
Smoke and heat control systems - Part 11: Horizontal flow powered ventilation systems
for enclosed car parks
Rauch- und Wärmefreihaltung - Teil 11: Rauchfreihaltung von Parkhäusern
Systèmes pour le contrôle des fumées et de la chaleur - Partie 11 : Systèmes de
ventilation motorisée à flux horizontal pour aires de stationnement fermées
Ta slovenski standard je istoveten z: CEN/TS 12101-11:2022
ICS:
13.220.20 Požarna zaščita Fire protection
91.140.30 Prezračevalni in klimatski Ventilation and air-
sistemi conditioning systems
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

CEN/TS 12101-11
TECHNICAL SPECIFICATION
SPÉCIFICATION TECHNIQUE
July 2022
TECHNISCHE SPEZIFIKATION
ICS 13.220.99
English Version
Smoke and heat control systems - Part 11: Horizontal flow
powered ventilation systems for enclosed car parks
Systèmes pour le contrôle des fumées et de la chaleur - Rauch- und Wärmefreihaltung - Teil 11:
Partie 11 : Systèmes de ventilation motorisée à flux Rauchfreihaltung von Parkhäusern
horizontal pour aires de stationnement fermées
This Technical Specification (CEN/TS) was approved by CEN on 13 June 2022 for provisional application.

The period of validity of this CEN/TS is limited initially to three years. After two years the members of CEN will be requested to
submit their comments, particularly on the question whether the CEN/TS can be converted into a European Standard.

CEN members are required to announce the existence of this CEN/TS in the same way as for an EN and to make the CEN/TS
available promptly at national level in an appropriate form. It is permissible to keep conflicting national standards in force (in
parallel to the CEN/TS) until the final decision about the possible conversion of the CEN/TS into an EN is reached.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and
United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2022 CEN All rights of exploitation in any form and by any means reserved Ref. No. CEN/TS 12101-11:2022 E
worldwide for CEN national Members.

Contents Page
European foreword . 4
Introduction . 5
1 Scope . 7
2 Normative references . 7
3 Terms and definitions . 8
3.1 Terms . 8
3.2 Symbols . 9
3.2.1 Latin upper case letters . 9
3.2.2 Latin lower case letters .10
3.2.3 Greek upper case letters .10
3.2.4 Greek lower case letters .11
4 Design fires .11
4.1 Design principle .11
4.2 Heat release rate .11
5 Normative requirements .11
5.1 Design objectives .11
5.2 Design solutions .13
5.3 Activation sequence .13
5.4 Wind effect .14
6 Installation and components .14
6.1 Fans .14
6.2 Controls .15
6.2.1 Operation of the smoke and heat control systems .15
6.2.2 Functions of the synoptic and manual control device .15
6.3 Cabling .16
6.4 Ducts (including fixings), attenuators (silencers) and grilles .16
6.5 Dampers .16
6.6 Discharge terminations .17
6.7 Air inlet and smoke extract (natural and powered) .17
6.8 Smoke discharge .17
6.9 Initiation systems: sprinklers and detection .18
6.10 Smoke barriers .18
6.11 Power supply systems .18
6.11.1 Reliability of operation .18
6.11.2 Power source .18
7 Interactions between horizontal flow powered ventilation and other systems and
functions .19
7.1 Sprinklers interaction .19
7.2 Pressure difference .19
7.3 Day to day ventilation .20
8 Commissioning .21
9 Acceptance testing of installation on site .21
10 Maintenance and periodical checking .22
11 Documentation . 22
11.1 General design documentation . 22
11.2 System design documentation . 22
11.3 Installation, maintenance and testing documentation . 23
11.4 Computer control software documentation . 23
Annex A (normative) Horizontal flow ventilation design without CFD analysis – Systems
without jet fans . 26
Annex B (normative) Horizontal flow ventilation design without CFD analysis – Systems with
jet fans. 32
Annex C (informative) Verification of horizontal ventilation design by CFD calculation
Systems with or without jet fans . 41
Annex D (informative) Commissioning. 47
Annex E (informative) Hot smoke testing . 49
Bibliography . 51

European foreword
This document (CEN/TS 12101-11:2022) has been prepared by Technical Committee CEN/TC 191 “Fixed
firefighting systems”, the secretariat of which is held by BSI.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN shall not be held responsible for identifying any or all such patent rights.
Any feedback and questions on this document should be directed to the users’ national standards body.
A complete listing of these bodies can be found on the CEN website.
According to the CEN/CENELEC Internal Regulations, the national standards organisations of the
following countries are bound to announce this Technical Specification: Austria, Belgium, Bulgaria,
Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland,
Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Republic of
North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United
Kingdom.
Introduction
0.1 General
The requirements in this document are provided for powered smoke and heat control systems installed
in car parks with or without sprinkler protection.
Modern cars are generally larger than their predecessors and contain a larger quantity of flammable
materials, in particular plastics, which results in an increase of heat and smoke output from burning cars.
Consequently, the design fires recommended in this document are larger and have a greater heat and
smoke output than those in some previous guidance.
0.2 Purposes of smoke control systems
Smoke control systems can be generally designed for one or more of three purposes in the event of a fire:
— to protect means of escape from the car park;
— to provide an access sufficiently free of smoke for fire-fighters to a point close to the seat of the fire;
— to assist fire-fighters to clear smoke from a car park.
The system requirements will differ depending upon the purpose. Not all types of ventilation systems are
suitable for all purposes.
This document only covers smoke control systems which are intended to provide an access sufficiently
free of smoke for fire-fighters.
0.3 Smoke control systems to provide an access sufficiently free of smoke for fire-fighters
This document deals only with horizontal flow powered ventilation systems.
The following systems are not covered by this document however, they are briefly discussed here:
— Horizontal natural ventilation - These systems may be suitable for open car parks, where at each
level, ventilation openings are located on at least two opposite façades. The size of the ventilation
openings will need to meet the relevant national regulations.
— SHEVS – These systems are covered by the recommendations of CEN/TR 12101-5 for steady-
state design fires or prCEN/TR 12101-12 (under development) for time-dependent design fires.
Hot smoky gases from a fire rise up to the ceiling, where it spread to form a smoke layer above
the denser cold air beneath. SHEVS, which may be natural or powered, are designed and sized to
maintain conditions beneath the smoke layer that allow evacuation and/or firefighting
operations. Such a system
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.