Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling - Part 2: Test conditions

1.1   The scope of EN 14511-1 is applicable.
1.2   This European Standard specifies the test conditions for the rating of air conditioners, liquid chilling packages and heat pumps, using either, air, water or brine as heat transfer media, with electrically driven compressors when used for space heating and/or cooling. It also specifies test conditions for heat recovery operation of multisplit systems.
1.3   This European Standard specifies the conditions for which performance data shall be declared for single duct and double duct units for compliance to the Ecodesign regulation 206/2012 and Energy labelling regulation 626/2011.

Luftkonditionierer, Flüssigkeitskühlsätze und Wärmepumpen mit elektrisch angetriebenen Verdichtern für die Raumbeheizung und -kühlung - Teil 2: Prüfbedingungen

1.1   Es gilt der Anwendungsbereich von EN 14511 1.
1.2   Diese Europäische Norm legt die Bedingungen für die Leistungsprüfung von Luftkonditionierern, Flüssigkeitskühlsätzen und Wärmepumpen, die Luft, Wasser oder Sole als Wärmeträger nutzen, mit elektrisch angetriebenen Verdichtern für die Raumbeheizung und/oder -kühlung fest.
1.3   Die vorliegende Europäische Norm legt die Bedingungen fest, für die die leistungsbezogenen Daten zu Einkanal- und Zweikanal-Geräten zum Zwecke der Übereinstimmung mit der Ökodesign-Verordnung 206/2012 und der Energiekennzeichnungs-Verordnung 626/2011 anzugeben sind.

Climatiseurs, groupes refroidisseurs de liquide et pompes à chaleur avec compresseur entraîné par moteur électrique pour le chauffage et la réfrigération des locaux - Partie 2: Conditions d'essai

1.1   Le domaine d'application de l’EN 14511-1 est applicable.
1.2   La présente Norme européenne spécifie les conditions d'essai pour la détermination des caractéristiques de performance des climatiseurs, groupe refroidisseurs de liquide et pompes à chaleur utilisant l’air, l’eau ou l’eau glycolée comme fluide caloporteur avec compresseur entraîné par moteur électrique, lorsqu'ils sont utilisés pour le chauffage et/ou le refroidissement des locaux.
1.3   La présente Norme européenne spécifie les conditions pour lesquelles les données de performance doivent être déclarées pour les appareils à simple ou double raccordement pour la conformité au règlement d’écoconception 206/2012 et du Règlement Etiquetage énergétique 626/2011

Klimatske naprave, enote za tekočinsko hlajenje in toplotne črpalke z električnimi kompresorji za segrevanje in hlajenje prostora - 2. del: Preskusni pogoji

Ta evropski standard določa preskusne pogoje za ocenjevanje klimatskih naprav, enot za tekočinsko hlajenje in toplotnih črpalk, ki uporabljajo zrak, vodo ali slanico kot medij za prenos toplote, z električnimi kompresorji, kadar se uporabljajo za segrevanje in/ali hlajenje prostora. Ta evropski standard določa pogoje, za katere se navedejo podatki o delovanju za enote z enojnim in dvojnim jaškom v zvezi s skladnostjo z uredbo o okoljski primerni zasnovi št. 206/2012 in uredbo o energijskem označevanju št. 626/2011.

General Information

Status
Withdrawn
Publication Date
06-Aug-2013
Withdrawal Date
13-Mar-2018
Current Stage
9960 - Withdrawal effective - Withdrawal
Completion Date
14-Mar-2018

Relations

Buy Standard

Standard
EN 14511-2:2013
English language
19 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Luftkonditionierer, Flüssigkeitskühlsätze und Wärmepumpen mit elektrisch angetriebenen Verdichtern für die Raumbeheizung und -kühlung - Teil 2: PrüfbedingungenClimatiseurs, groupes refroidisseurs de liquide et pompes à chaleur avec compresseur entraîné par moteur électrique pour le chauffage et la réfrigération des locaux - Partie 2: Conditions d'essaiAir conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling - Part 2: Test conditions91.140.30VLVWHPLVentilation and air-conditioning27.080Heat pumps23.120QDSUDYHVentilators. Fans. Air-conditionersICS:Ta slovenski standard je istoveten z:EN 14511-2:2013SIST EN 14511-2:2013en,fr,de01-december-2013SIST EN 14511-2:2013SLOVENSKI
STANDARDSIST EN 14511-2:20121DGRPHãþD

EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM
EN 14511-2
August 2013 ICS 27.080; 91.140.30 Supersedes EN 14511-2:2011English Version
Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling - Part 2: Test conditions
Climatiseurs, groupes refroidisseurs de liquide et pompes à chaleur avec compresseur entraîné par moteur électrique pour le chauffage et la réfrigération des locaux - Partie 2: Conditions d'essai
Luftkonditionierer, Flüssigkeitskühlsätze und Wärmepumpen mit elektrisch angetriebenen Verdichtern für die Raumbeheizung und -kühlung - Teil 2: Prüfbedingungen This European Standard was approved by CEN on 30 May 2013.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre:
Avenue Marnix 17,
B-1000 Brussels © 2013 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 14511-2:2013: ESIST EN 14511-2:2013

Relationship between this European Standard and the requirements of Commission Regulation (EC) No 206/2012 . 18 Bibliography . 19
1.3 This European Standard specifies the conditions for which performance data shall be declared for single duct and double duct units for compliance to the Ecodesign regulation 206/2012 and Energy labelling regulation 626/2011. 2 Normative references The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its application. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 14511-1:2013, Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling  Part 1: Terms, definitions and classification EN 14511-4:2013, Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling  Part 4: Operating requirements, marking and instructions 3 Terms and definitions For the purposes of this document, the terms and definitions given in EN 14511-1:2013 apply. 4 Test conditions 4.1 Environmental conditions and electrical power supply requirements The tests shall be carried out under the environmental conditions specified in Table 1 or Table 2 depending on the location of the unit. For all units, electrical power voltage and frequency shall be given by the manufacturer. SIST EN 14511-2:2013

15 °C to 30 °C Water-to-air and brine-to-air units with duct connection on the air inlet and outlet side Dry bulb temperature 15 °C to 30 °C Water-to-air and brine-to-air units without duct connection on the air inlet and outlet side Dry bulb temperature Wet bulb temperature
Inlet temperature (see Table 5 or Table 6) Air-to-air units with duct connection
on the outdoor air inlet and outlet side Dry bulb temperature 15 °C to 30 °C Air-to-air units without duct connection
on the outdoor air inlet and outlet side Dry bulb temperature Wet bulb temperature
As inlet temperature see Table 3 or Table 4
Table 2 — Environmental conditions for units designed for installation outdoors Type Measured quantities Rating test Air-to-water units
Dry bulb temperature Wet bulb temperature Inlet temperature (see Tables 12 to 15 and Table 16) Water-to-air and brine-to-air units without duct connection on the air inlet side Dry bulb temperature Wet bulb temperature
Inlet temperature (see Table 5 and Table 6) Water-to-water and brine-to-water operating in cooling mode Dry bulb temperature 15 °C to 30 °C Water-to-water and brine-to-water operating in heating mode Dry bulb temperature 0 °C to 7 °C Air-to-air units with duct connection on the indoor air inlet and outlet side Dry bulb temperature Wet bulb temperature
Inlet temperature (see Table 3 and Table 4)
4.2 Rating conditions For the rating tests, the appropriate test conditions shall be applied in accordance with:  Table 3 for air-to-air units in heating mode;  Table 4 for air-to-air units in cooling mode;  Table 5 for water-to-air and brine-to-air units in heating mode;  Table 6 for water-to-air and brine-to-air units in cooling mode;  Tables 7 to 10 for water-to-water and brine-to-water units in heating mode, depending on the temperature applications; SIST EN 14511-2:2013

Outdoor heat exchanger Indoor heat exchanger Inlet dry bulb temperature °C Inlet wet bulb temperature °C Inlet dry bulb temperature °C Inlet wet bulb temperature °C Standard rating
conditions Outdoor air / recycled air (e.g. window, double duct, split units) 7 6 20 15 max Exhaust air / recycled air (e.g. single duct heat pump) 20 12 20 12 Exhaust air / outdoor air 20 12 7 6 Application rating
conditions Outdoor air / recycled air (e.g. window, double duct, split units) 2 1 20 15 max. Outdoor air / recycled air (e.g. window, double duct, split units) - 7 - 8 20 15 max. Outdoor air / recycled air (e.g. window, double duct, split units) - 15 - 20 15 max. Outdoor air / recycled air (e.g. window, double duct, split units) 12 11 20 15 max. Exhaust air / outdoor air 20 12 2 1 Exhaust air / outdoor air 20 12 - 7 - 8
Outdoor heat exchanger Indoor heat exchanger Inlet dry bulb temperature °C Inlet wet bulb temperature °C Inlet dry bulb temperature °C Inlet wet bulb temperature °C Standard rating
conditions Comfort (outdoor air / recycled air) (e.g. window, double duct, split units)
35 24 a 27 19 Comfort (exhaust air / recycled air) 27 19 27 19 Comfort (exhaust air / outdoor air) 27 19 35 24 Single duct b, c 35 24 35 24 Control cabinet 35 24 35 24 Close control 35 24 24 17 Application rating
conditions Comfort (outdoor air / recycled air) (e.g. window, double duct, split units)
27 19 a 21 15 Single duct b, c
27 19 27 19 Comfort (outdoor air / recycled air) (e.g. window, double duct, split units)
46 24 a
29 19 Control cabinet 50 30 35 24 Close control 27 19 21 15 a The wet bulb temperature condition is not required when testing units which do not evaporate condensate. b When using the calorimeter room method, pressure equilibrium between indoor and outdoor compartments shall be obtained by introducing into indoor compartment, air at the same rating temperature conditions. c The pressure difference between the two compartme
...