Water-tube boilers and auxiliary installations - Part 13: Requirements for flue gas cleaning systems

This European Standard applies to the design of equipment for boiler plants to reduce air pollutants in the flue gases.
NOTE   The effects of explosion are not considered in this Part of the is European Standard.

Wasserrohrkessel und Anlagenkomponenten - Teil 13: Anforderungen an Rauchgasreinigungsanlagen

Diese EN-Norm gilt für die Auslegung der Ausrüstung von Kesselanlagen zur Verminderung von luftverunreinigenden Stoffen in Rauchgasen. Die Auswirkungen einer Explosion werden in diesem Teil der Norm nicht berücksichtigt.

Chaudières à tubes d'eau et installations auxiliaires - Partie 13: Exigences pour les systèmes de traitement des fumées

La présente partie de cette Norme européenne s'applique à la conception d'un équipement de chaufferie destiné à réduire les polluants atmosphériques dans les gaz de combustion.
NOTE   Les effets d'une explosion ne sont pas pris en considération dans la présente partie de cette norme européenne.

Vodocevni kotli in pomožne napeljave - 13. del: Zahteve za čistilne naprave dimnih plinov

General Information

Status
Published
Publication Date
18-Mar-2003
Withdrawal Date
29-Sep-2003
Current Stage
9092 - Decision on results of review/2YR ENQ - revise - Review Enquiry
Completion Date
03-Jun-2021

Relations

Buy Standard

Standard
EN 12952-13:2003
English language
10 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.SOLQRYWasserrohrkessel und Anlagenkomponenten - Teil 13: Anforderungen an RauchgasreinigungsanlagenChaudieres a tubes d'eau et installations auxiliaires - Partie 13: Exigences pour les systemes de traitement des fuméesWater-tube boilers and auxiliary installations - Part 13: Requirements for flue gas cleaning systems27.060.30Grelniki vode in prenosniki toploteBoilers and heat exchangersICS:Ta slovenski standard je istoveten z:EN 12952-13:2003SIST EN 12952-13:2003en01-december-2003SIST EN 12952-13:2003SLOVENSKI
STANDARD
EUROPEAN STANDARDNORME EUROPÉENNEEUROPÄISCHE NORMEN 12952-13March 2003ICS 27.040; 27.060.30English versionWater-tube boilers and auxiliary installations - Part 13:Requirements for flue gas cleaning systemsChaudières à tubes d'eau et installations auxiliaires - Partie13: Exigences pour les systèmes de traitement des fuméesWasserrohrkessel und Anlagenkomponenten - Teil 13:Anforderungen an RauchgasreinigungsanlagenThis European Standard was approved by CEN on 27 December 2002.CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this EuropeanStandard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such nationalstandards may be obtained on application to the Management Centre or to any CEN member.This European Standard exists in three official versions (English, French, German). A version in any other language made by translationunder the responsibility of a CEN member into its own language and notified to the Management Centre has the same status as the officialversions.CEN members are the national standards bodies of Austria, Belgium, Czech Republic, Denmark, Finland, France, Germany, Greece,Hungary, Iceland, Ireland, Italy, Luxembourg, Malta, Netherlands, Norway, Portugal, Slovakia, Spain, Sweden, Switzerland and UnitedKingdom.EUROPEAN COMMITTEE FOR STANDARDIZATIONCOMITÉ EUROPÉEN DE NORMALISATIONEUROPÄISCHES KOMITEE FÜR NORMUNGManagement Centre: rue de Stassart, 36
B-1050 Brussels© 2003 CENAll rights of exploitation in any form and by any means reservedworldwide for CEN national Members.Ref. No. EN 12952-13:2003 ESIST EN 12952-13:2003

Guidance on operation matters.8Annex ZA (informative)
Clauses of this European Standard addressing essential requirements or otherprovisions of EU Directives.9Bibliography.10SIST EN 12952-13:2003

monitoredseal air;b) one shut-off device with double seal and seal-air space between the two seals supplied with reliably1) moni-tored seal air;c) two shut-off devices arranged in series with an intermediate opening to atmosphere and monitoring equipmentto detect leaking flue gas;d) readily visible, tight blanking disc;e) one shut-off device situated between the section to be inspected and the induced-draught fan withreliably1) monitored sub-atmospheric pressure between the shut-off device and the induced-draught fan. In thiscase one monitoring criteria shall become effective which directly indicates the failure of the draught, e. g. bymeans of flow or air measurements. This induced-draught fan shall not be used for boiler operation during in-spection;f) Other equivalent means.The seal air pressure shall be monitored continuously e. g. by measuring the differential pressure between seal airand flue gas. The seal air pressure shall always be higher than the respective pressure on the flue gas side.NOTEOnly the seal air pressure need be monitored if the maximum possible flue gas pressure (gauge) is known for alloperating and upset conditions2).Where the seal air pressure is less than its fixed limit value, at least one locally positioned optical and acousticalarm shall automatically be tripped. The alarm shall be tripped so as to be recognizable by all personnel working inthe respective work area.The measuring points for seal air monitoring shall be arranged so as to give representative values for the seal-airspace even under unfavourable conditions, e. g. caking, dust deposition, leaking sealing elements.The closed shut-off devices shall be safeguarded against unintentional or erroneous opening. This means mechan-ical interlocking or similar means shall be required in addition to cutting off the auxiliary energy. The interlockingdevice shall be designed so as to withstand 1.5 times the design value
...