EN 50085-2-2:2008
(Main)Cable trunking systems and cable ducting systems for electrical installations - Part 2-2: Particular requirements for cable trunking systems and cable ducting systems intended for mounting underfloor, flushfloor, or onfloor
Cable trunking systems and cable ducting systems for electrical installations - Part 2-2: Particular requirements for cable trunking systems and cable ducting systems intended for mounting underfloor, flushfloor, or onfloor
Replacement: This European Standard specifies requirements and tests for cable trunking systems (CTS) and cable ducting systems (CDS) intended for the accommodation, and where necessary for the electrically protective separation, of insulated conductors, cables and possibly other electrical equipment in electrical and/or communication systems installations. The maximum voltage of these installations is 1 000 V a.c. and 1 500 V d.c. These systems are intended for mounting underfloor, flushfloor or onfloor. This standard does not apply to CTS/CDS which are intended to be fixed to the wall and supported by the floor. This standard does not apply to conduit systems, cable tray systems, cable ladder systems, power track systems or equipment covered by other standards. This standard shall be used in conjunction with EN 50085-1:2005, Cable trunking systems and cable ducting systems for electrical installations – Part 1: General requirements, which is referred to in this document as Part 1.
Elektroinstallationskanalsysteme für elektrische Installationen - Teil 2-2: Besondere Anforderungen für Elektroinstallationskanalsysteme für die Montage unterboden, bodenbündig, oder aufboden
Ersatz: Diese Europäische Norm legt Anforderungen und Prüfungen für Elektroinstallationskanalsysteme, die für die Aufnahme und, wo erforderlich, für die elektrische Trennung von isolierten Leitern, Kabeln, Leitungen und möglichen anderen elektrischen Betriebsmitteln in elektrischen Installationen oder Kommunikationssystemen fest. Die maximale Spannung dieser Installationen ist 1 000 V Wechselspannung und 1 500 V Gleichspannung. Die Systeme sind für die Montage unterboden, bodenbündig oder aufboden vorgesehen. Diese Norm gilt nicht für Elektroinstallationskanalsysteme, die zur Wandmontage, unterstützt durch den Fußboden, vorgesehen sind. Diese Norm gilt nicht für Elektroinstallationsrohrsysteme, Kabelträgersysteme, Stromschienensysteme oder Einrichtungen, die von anderen Normen abgedeckt sind. Diese Norm muss zusammen mit EN 50085-1:2005 „Elektroinstallationssysteme für elektrische Installationen – Teil 1: Allgemeine Anforderungen“ benutzt werden, auf welche in dieser Norm als Teil 1 Bezug genommen wird.
Systèmes de goulottes et systèmes de conduits-profilés pour installations électriques - Partie 2-2: Règles particulières pour les systèmes de goulottes et systèmes de conduits-profilés prévus pour être montés en sous-sol, encastrés dans le sol, ou sur le sol
Remplacement: La présente Norme Européenne spécifie les règles et les essais pour les systèmes de goulotte (SG) et les systèmes de conduits-profilés (SCP) destinés au logement de conducteurs isolés, câbles et éventuels autres équipements électriques et si nécessaire à leur séparation de protection électrique, dans des installations électriques et/ou de systèmes de communication. La tension maximale de ces installations est de 1 000 V en courant alternatif et 1 500 V en courant continu. Ces systèmes sont prévus pour être montés sous le sol, encastrés dans le sol, ou sur le sol. La présente norme ne s'applique pas aux SG/SCP prévus pour être fixés à un mur et soutenus par le sol. La présente norme ne s'applique pas aux systèmes de conduit, systèmes de chemin de câble, systèmes d'échelle à câble, systèmes de canalisation préfabriquée ou aux équipements couverts par d’autres normes. La présente norme doit être utilisée conjointement avec la EN 50085-1:2005, Systèmes de goulottes et systèmes de conduits-profilés pour installations électriques - Partie 1: Règles générales, à laquelle il est fait référence dans ce document comme Partie 1.
Sistemi kabelskih korit in sistemi kabelskih cevi za električne inštalacije - 2-2. del: Posebne zahteve za sisteme kabelskih korit in sisteme kabelskih cevi, namenjene za montažo pod tlemi, po golih tleh ali po tleh
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
01-januar-2009
6LVWHPLNDEHOVNLKNRULWLQVLVWHPLNDEHOVNLKFHYL]DHOHNWULþQHLQãWDODFLMHGHO
3RVHEQH]DKWHYH]DVLVWHPHNDEHOVNLKNRULWLQVLVWHPHNDEHOVNLKFHYLQDPHQMHQH
]DPRQWDåRSRGWOHPLSRJROLKWOHKDOLSRWOHK
Cable trunking systems and cable ducting systems for electrical installations - Part 2-2:
Particular requirements for cable trunking systems and cable ducting systems intended
for mounting underfloor, flushfloor, or onfloor
Elektroinstallationskanalsysteme für elektrische Installationen - Teil 2-2: Besondere
Anforderungen für Elektroinstallationskanalsysteme für die Montage unterboden,
bodenbündig, oder aufboden
Systèmes de goulottes et systèmes de conduits-profilés pour installations électriques -
Partie 2-2: Systèmes de goulottes et systèmes de conduits-profilés prévus pour être
montés en sous-sol, encastrés dans le sol, ou sur le sol
Ta slovenski standard je istoveten z: EN 50085-2-2:2008
ICS:
29.120.10 ,QãWDODFLMVNHFHYL]D Conduits for electrical
HOHNWULþQHQDPHQH purposes
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
EUROPEAN STANDARD
EN 50085-2-2
NORME EUROPÉENNE
November 2008
EUROPÄISCHE NORM
ICS 29.120.10
English version
Cable trunking systems and cable ducting systems
for electrical installations -
Part 2-2: Particular requirements for cable trunking systems
and cable ducting systems intended for mounting underfloor,
flushfloor, or onfloor
Systèmes de goulottes Elektroinstallationskanalsysteme
et systèmes de conduits-profilés für elektrische Installationen -
pour installations électriques - Teil 2-2: Besondere Anforderungen
Partie 2-2: Règles particulières für Elektroinstallationskanalsysteme
pour les systèmes de goulottes für die Montage unterboden,
et systèmes de conduits-profilés bodenbündig, oder aufboden
prévus pour être montés en sous-sol,
encastrés dans le sol, ou sur le sol
This European Standard was approved by CENELEC on 2008-10-01. CENELEC members are bound to comply
with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard
the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and notified
to the Central Secretariat has the same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Cyprus, the
Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain,
Sweden, Switzerland and the United Kingdom.
CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
Central Secretariat: rue de Stassart 35, B - 1050 Brussels
© 2008 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 50085-2-2:2008 E
Foreword
This European Standard was prepared by the Technical Committee CENELEC TC 213, Cable
Management Systems.
The text of the draft was submitted to the formal vote and was approved by CENELEC as EN 50085-2-2
on 2008-10-01.
The following dates were fixed:
– latest date by which the EN has to be implemented
at national level by publication of an identical
national standard or by endorsement (dop) 2009-10-01
– latest date by which the national standards conflicting
with the EN have to be withdrawn (dow) 2011-10-01
This European Standard is a system standard for cable management products used for electro-
technical purposes. It relates to the Council Directives on the approximation of laws, regulations
and administrative provisions of the Member States relating to Low Voltage Directive 2006/95/EC
through consideration of the essential requirements of this directive.
This European Standard is supported by separate standards to which references are made.
This Part 2-2 is to be used in conjunction with EN 50085-1:2005 “Cable trunking systems and
cable ducting systems for electrical installations - Part 1: General requirements”.
This Part 2-2 supplements or modifies the corresponding clauses of EN 50085-1:2005. Where a
particular clause or subclause of Part 1 is not mentioned in this Part 2, that clause or subclause of
Part 1 applies as far as it is reasonable. Where this Part 2 states “addition” or “replacement”, the
relevant text of Part 1 is to be adapted accordingly.
NOTE The following numbering system is used:
– subclauses, tables and figures that are additional to those in Part 1 are numbered starting from 101;
– additional annexes are lettered AA, BB, etc.
__________
– 3 – EN 50085-2-2:2008
Contents
Page
1 Scope . 4
2 Normative references . 4
3 Definitions . 4
4 General requirements . 5
5 General conditions for tests . 5
6 Classification . 5
7 Marking and documentation . 6
8 Dimensions . 6
9 Construction . 6
10 Mechanical properties . 8
11 Electrical properties . 12
12 Thermal properties . 12
13 Fire hazard . 12
14 External influences . 12
15 Electromagnetic compatibility . 13
Annex A (informative) Types of Cable Trunking Systems (CTS) and Cable Ducting Systems (CDS) . 27
Annex B (informative) A-deviations . 28
Annex C (normative) CTS/CDS IK code . 28
Annex AA (normative) Mechanical load tests . 29
Bibliography . 31
Figures
Figure 101 – Types and application of CTS/CDS for underfloor, flushfloor or onfloor installations . 14
Figure 102 – Examples of trunking and ducting installations . 15
Figure 103 – Example of underfloor embedded CDS according to 3.101 . 16
Figure 104 – Example of flushfloor CTS according to 3.102 . 17
Figure 105 – Example of onfloor CTS according to 3.103. 18
Figure 106 – Principles for arrangement . 19
Figure 107 – Examples for arrangement . 19
Figure 108 – Load test set-up for CTS/CDS in accordance with 10.5.103 . 23
Figure 109 – Load test set-up for CTS/CDS in accordance with 10.5.104 . 26
Table
Table AA.1 – Mechanical load tests . 29
1 Scope
Replacement:
This European Standard specifies requirements and tests for cable trunking systems (CTS) and
cable ducting systems (CDS) intended for the accommodation, and where necessary for the
electrically protective separation, of insulated conductors, cables and possibly other electrical
equipment in electrical and/or communication systems installations. The maximum voltage of
these installations is 1 000 V a.c. and 1 500 V d.c.
These systems are intended for mounting underfloor, flushfloor or onfloor.
This standard does not apply to CTS/CDS which are intended to be fixed to the wall and
supported by the floor.
This standard does not apply to conduit systems, cable tray systems, cable ladder systems, power
track systems or equipment covered by other standards.
This standard shall be used in conjunction with EN 50085-1:2005, Cable trunking systems and
cable ducting systems for electrical installations – Part 1: General requirements, which is referred
to in this document as Part 1.
2 Normative references
This clause of Part 1 is applicable except as follows:
Add the following normative references:
EN 60068-2-60 1996 Environmental testing – Part 2: Tests - Test Ke: Flowing mixed
gas corrosion test (IEC 60068-2-60:1995)
EN 60068-2-75 1997 Environmental testing – Part 2-75: Tests - Test Eh: Hammer
tests (IEC 60068-2-75:1997)
3 Definitions
This clause of Part 1 is applicable except as follows:
3.1 Replace the note by:
NOTE Different types of CTS are shown in Figure 101 and explained in Clause A.2.
3.2 Replace the note by:
NOTE Different types of CDS are shown in Figure 101 and explained in Clause A.2.
3.3 Add:
f) service unit
Replace the note by:
NOTE A system does not necessarily include all system components a) to f). Different combinations of system components may
be used.
– 5 – EN 50085-2-2:2008
Additional subclauses:
3.101
underfloor CTS/CDS
CTS/CDS whose components, except access units and service units, are intended to be mounted within
or under a floor and in normal use are not exposed to traffic loads (Figures 102a), 102c) and 103)
3.102
flushfloor CTS/CDS
CTS/CDS whose components, except access units and service units, are intended to be mounted flush
such that the height above the upper level of the floor covering is not more than 4 mm. The upper surface
is considered to be exposed to traffic loads (Figures 102b) and 104)
3.103
onfloor CTS/CDS
CTS/CDS whose components are intended to be mounted on a floor such that the height above the upper
level of the floor covering is greater than 4 mm. The upper surface is considered to be exposed to traffic
loads (Figures 102d) and 105)
3.104
access unit
system component intended to provide access to insulated conductors or cables
3.105
service unit
system component intended for incorporation of one or more apparatus either directly or by means of one
or more apparatus mounting devices
3.106
service unit, when not in use
service unit which has no cables connected to electrical equipments
3.107
service unit, when in use
service unit which has cables connected to electrical equipments
4 General requirements
This clause of Part 1 is applicable.
5 General conditions for tests
This clause of Part 1 is applicable.
6 Classification
This clause of Part 1 is applicable except as follows:
Additional subclauses:
6.101 According to floor treatment
6.101.1 CTS/CDS for dry-treatment of floor
6.101.2 CTS/CDS for wet-treatment of floor when the service unit is not in use
6.101.3 CTS/CDS for wet-treatment of floor when the service unit is in use
6.102 According to resistance to vertical load applied through small surface area
6.102.1 CTS/CDS for 500 N
6.102.2 CTS/CDS for 750 N
6.102.3 CTS/CDS for 1 000 N
6.102.4 CTS/CDS for 1 500 N
6.102.5 CTS/CDS for 2 000 N
6.102.6 CTS/CDS for 2 500 N
6.102.7 CTS/CDS for 3 000 N
6.103 Optional classification according to resistance to vertical load applied through
large surface area
6.103.1 CTS/CDS for 2 000 N
6.103.2 CTS/CDS for 3 000 N
6.103.3 CTS/CDS for 5 000 N
6.103.4 CTS/CDS for 10 000 N
6.103.5 CTS/CDS for 15 000 N
7 Marking and documentation
This clause of Part 1 is applicable except as follows:
Additional subclauses:
7.101 Access units and service units of systems classified according to 6.101.1 shall be marked
that they are suitable for dry treatment of floor only. The marking shall be visible by the user which
may be achieved by opening the cover.
NOTE This marking may be in the form of text or graphic.
7.102 Service units shall be marke
...