EN 50399:2011/A1:2016
(Amendment)Common test methods for cables under fire conditions - Heat release and smoke production measurement on cables during flame spread test - Test apparatus, procedures, results
Common test methods for cables under fire conditions - Heat release and smoke production measurement on cables during flame spread test - Test apparatus, procedures, results
This amendment consists of a modification to Subclauses 6.4 and 6.5 to cover the testing of non circular cables and to improve the repeatability and reproducibility of testing of bundles (for cables with a diameter less than or equal to 5,0 mm) and some further improvements based on wider operating experience.
Allgemeine Prüfverfahren für das Verhalten von Kabeln und isolierten Leitungen im Brandfall - Messung der Wärmefreisetzung und Raucherzeugung während der Prüfung der Flammenausbreitung - Prüfeinrichtung, Prüfverfahren und Prüfergebnis
Méthodes d'essai communes aux câbles soumis au feu - Mesure de la chaleur et de la fumée dégagées par les câbles au cours de l'essai de propagation de la flamme - Appareillage d'essai, procédure et résultats
Skupne preskusne metode za ognjevzdržnost kablov - Meritve oddajanja toplote in nastajanja dima na kablih med preskusom z razpršenim plamenom - Preskusna naprava, postopki, rezultati - Dopolnilo A1
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
01-september-2016
Skupne preskusne metode za ognjevzdržnost kablov - Meritve oddajanja toplote in
nastajanja dima na kablih med preskusom z razpršenim plamenom - Preskusna
naprava, postopki, rezultati - Dopolnilo A1
Common test methods for cables under fire conditions - Heat release and smoke
production measurement on cables during flame spread test - Test apparatus,
procedures, results
Allgemeine Prüfverfahren für das Verhalten von Kabeln und isolierten Leitungen im
Brandfall - Messung der Wärmefreisetzung und Raucherzeugung während der Prüfung
der Flammenausbreitung - Prüfeinrichtung, Prüfverfahren und Prüfergebnis
Méthodes d'essai communes aux câbles soumis au feu - Mesure de la chaleur et de la
fumée dégagées par les câbles au cours de l'essai de propagation de la flamme -
Appareillage d'essai, procédure et résultats
Ta slovenski standard je istoveten z: EN 50399:2011/A1:2016
ICS:
13.220.40 Sposobnost vžiga in Ignitability and burning
obnašanje materialov in behaviour of materials and
proizvodov pri gorenju products
29.060.20 Kabli Cables
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
EUROPEAN STANDARD EN 50399:2011/A1
NORME EUROPÉENNE
EUROPÄISCHE NORM
June 2016
ICS 13.220.40; 29.060.20
English Version
Common test methods for cables under fire conditions - Heat
release and smoke production measurement on cables during
flame spread test - Test apparatus, procedures, results
Méthodes d'essai communes aux câbles soumis au feu - Allgemeine Prüfverfahren für das Verhalten von Kabeln und
Mesure de la chaleur et de la fumée dégagées par les isolierten Leitungen im Brandfall - Messung der
câbles au cours de l'essai de propagation de la flamme - Wärmefreisetzung und Raucherzeugung während der
Appareillage d'essai, procédure et résultats Prüfung der Flammenausbreitung - Prüfeinrichtung,
Prüfverfahren und Prüfergebnis
This amendment A1 modifies the European Standard EN 50399:2011; it was approved by CENELEC on 2016-04-18. CENELEC members
are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this amendment the status of a
national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This amendment exists in three official versions (English, French, German). A version in any other language made by translation under the
responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the same status as
the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom.
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2016 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Ref. No. EN 50399:2011/A1:2016 E
Contents Page
European foreword .3
1 Modification to Clause 2, Normative references .4
2 Modification to 6.4, Determination of the number of test pieces .4
3 Modification to 6.5.1, Mounting of the test sample for all classes .6
4 Modification to 6.5.2, Special mounting requirements for class B1 .7
ca
5 Modifications to the figures after 8.2.5 .7
6 Modification to E.4.1, General .8
7 Modifications to E.4.3, Optical filter check for white light systems .9
8 Modification to F.2.1, Oxygen analyser adjustment .9
9 Modification to F.4.2, Actions .9
10 Modification to F.4.3, Criterion .9
11 Addition of a new Annex J (normative), Rounding of numbers .9
European foreword
This document (EN 50399:2011/A1:2016) has been prepared by CLC/TC 20 “Electric cables”.
The following dates are fixed:
• latest date by which this document has to be (dop) 2017-04-18
implemented at national level by publication of an
identical national standard or by endorsement
• latest date by which the national standards conflicting (dow) 2019-04-18
with this document have to be withdrawn
Attention is drawn to the possibility that some of the elements of this document may be the
subject of patent rights. CENELEC [and/or CEN] shall not be held responsible for identifying any
or all such patent rights.
1 Modification to Clause 2, Normative references
Replace the whole reference to EN 60332-3-10 with the following one:
"EN 60332-3-10:2009, Tests on electric and optical fibre cables under fire conditions – Part 3-10:
Test for vertical flame spread of vertically-mounted bunched wires or cables – Apparatus
(IEC 60332-3-10:2000)".
2 Modification to 6.4, Determination of the number of test pieces
Replace the whole subclause with the following one:
"
6.4 Determination of the number of test pieces
6.4.1 General
The following formulae shall be used to determine the number of test pieces (N) for the test.
6.4.2 Circular cables with a diameter greater than or equal to 20,0 mm
The number of test pieces, N, is given by:
300+ 20
N= int (1)
d + 20
c
where
d is the measured diameter of the cable (in millimetres, measured to one
c
decimal place of a millimetre and rounded to the nearest millimetre according
to Annex J);
int function the integer part of the result (i.e. the value rounded down).
6.4.3 Circular cables with a diameter greater than 5,0 mm but less than 20,0 mm
The number of test pieces, N, is given by
300+d
c
N= int (2)
2d
c
where
d is the measured diameter of the cable (in millimetres, measured to one
c
decimal place of a millimetre and rounded to the nearest millimetre according
to Annex J);
int function the integer part of the result (i.e. the value rounded down).
6.4.4 Circular cables with a diameter less than or equal to 5,0 mm
A number of approximately 10 mm diameter bundles (N ) shall be mounted where:
bu
300+10
N = int =15 (3)
bu
Thus 15 bundles shall be mounted.
The number of test pieces in each bundle (n) is:
100
n= int (4)
d
c
where
d is the measured diameter of the cable (in millimetres, measured to two
c
decimal places of a millimetre and rounded to one decimal place according to
Annex J);
int function the integer part of the result (i.e. the value rounded down).
The total number of test pieces (N) will thus be:
N=n×15 (5)
6.4.5 Non-circular cables with a major axis dimension greater than or equal to 20,0 mm,
a minor axis dimension greater than 4,0 mm and a major to minor axis ratio less
than or equal to 5
...
Questions, Comments and Discussion