EN 50264-2-2:2008
(Main)Railway applications - Railway rolling stock power and control cables having special fire performance - Part 2-2: Cables with crosslinked elastomeric insulation - Multicore cables
Railway applications - Railway rolling stock power and control cables having special fire performance - Part 2-2: Cables with crosslinked elastomeric insulation - Multicore cables
EN 50264-2-2 specifies requirements for, and constructions and dimensions of, multicore cables of the following types and voltage ratings: • 300/500 V screened or unscreened (1 mm², 1,5 mm² and 2,5 mm², number of cores from 2 to 40); • 0,6/1 kV screened or unscreened (1,5 mm² to 50 mm², 2, 3 and 4 cores). NOTE Not all conductor sizes or number of cores are specified for every type. All cables have class 5 tinned copper conductors to EN 60228, halogen-free insulation and halogen-free sheath. They are for use in railway rolling stock as fixed wiring, or wiring where limited flexing in operation is encountered. The requirements provide for a continuous conductor temperature not exceeding 90 °C and a maximum temperature for short circuit conditions of 200 °C based on a duration of 5 s. Under fire conditions the cables exhibit special performance characteristics in respect of maximum permissible flame propagation (flame spread) and maximum permissible emission of smoke and toxic gases. EN 50264-2-2 should be read in conjunction with Part 1 “General requirements”.
Bahnanwendungen - Starkstrom- und Steuerleitungen für Schienenfahrzeuge mit verbessertem Verhalten im Brandfall - Teil 2-2: Leitungen mit vernetzter elastomerer Isolierung - Mehr- und vieladrige Leitungen
EN 50264-2-2 legt Anforderungen an und Aufbauten und Abmessungen von mehr- und vieladrigen Leitungen für folgende Bauarten und Nennspannungen fest: • 300 V/500 V mit oder ohne Schirm (1 mm², 1,5 mm² und 2,5 mm², Aderzahlen von 2 bis 40); • 0,6 kV/1 kV mit oder ohne Schirm (1,5 mm² bis 50 mm², 2, 3 und 4 Adern). ANMERKUNG Nicht alle Leiterquerschnitte oder Aderzahlen sind für jede Bauart festgelegt. Alle Leitungen haben einen verzinnten Kupferleiter Klasse 5 nach EN 60228, eine halogenfreie Isolierung und gegebenenfalls einen halogenfreien Mantel. Sie sind für feste Verlegung im Schienenfahrzeug bestimmt oder für Verdrahtungen, bei denen im Betrieb begrenzt mit Bewegungen gerechnet werden muss. Die Anforderungen berücksichtigen eine dauernde Leitertemperatur von nicht mehr als 90 °C und eine maximale Kurzschlusstemperatur von 200 °C bei einer Dauer von 5 Sekunden. Unter Brandbedingungen zeigen die Leitungen besondere Leistungsmerkmale hinsichtlich der maximal zulässigen Weiterleitung der Flammen (Ausbreitung der Flammen) und der höchsten zulässigen Emission von Rauch und giftigen Gasen. EN 50264-2-2 sollte in Verbindung mit Teil 1 „Allgemeine Anforderungen“ gelesen werden.
Applications ferroviaires - Câbles de puissance et de contrôle à comportement au feu spécifié pour matériel roulant ferroviaire - Partie 2-2: Câbles à enveloppe isolante réticulée - Câbles multiconducteurs
La EN 50264-2-2 spécifie les prescriptions, la construction et les dimensions des câbles multiconducteurs des types et tensions assignées suivants: • 300/500 V avec ou sans blindage (de 1 mm², 1,5 mm² et 2,5 mm²; de 2 à 40 conducteurs); • 0,6/1 kV avec ou sans blindage (de 1,5 mm² à 50 mm²; de 2, 3 et 4 conducteurs). NOTE Les combinaisons des sections et des nombres de conducteurs ne sont pas toutes spécifiées pour chaque type. Tous les câbles possèdent une âme en cuivre étamé de classe 5 selon la EN 60228, une enveloppe isolante et une gaine sans halogènes. Ils sont destinés aux installations fixes ou soumis à de faibles flexions en service des matériels roulants ferroviaires. Les prescriptions sont basées pour une température permanente de l’âme ne dépassant pas 90 °C et à une température maximale de 200 °C pour une durée de 5 s en cas de court-circuit. Les câbles présentent, en cas d’incendie, des performances particulières de propagation maximale admissible de la flamme (longueur brûlée) et d’émission de fumées et de gaz toxiques. Il est recommandé de lire la EN 50264-2-2 conjointement avec la Partie 1 "Prescriptions générales".
Železniške naprave - Energetski in krmilni kabli za železniška vozna sredstva, ki imajo posebne ognjevarne lastnosti - 2-2. del: Kabli z zamreženo elastomerno izolacijo - Večžilni kabli
General Information
Relations
Overview
EN 50264-2-2:2008 (CLC) specifies requirements, constructions and dimensions for multicore railway rolling stock power and control cables with crosslinked elastomeric insulation and special fire performance. It covers screened and unscreened types for two voltage ranges:
- 300/500 V control cables (1 mm², 1.5 mm², 2.5 mm²; 2 to 40 cores)
- 0.6/1 kV power cables (1.5 mm² to 50 mm²; 2, 3 and 4 cores)
All cables use class 5 tinned copper conductors (EN 60228) and halogen‑free insulation and sheath, intended for fixed wiring or applications with limited flexing in railway vehicles.
Key topics and technical requirements
- Rated voltages and conductor sizes: Defined sets for 300/500 V and 0.6/1 kV multicore cables (specific tables list dimensions).
- Construction elements: Conductor, insulation system (crosslinked elastomeric), core laying, fillers, metallic screens (where applicable) and sheath (normally black).
- Thermal ratings: Continuous conductor temperature ≤ 90 °C; short‑circuit peak ≤ 200 °C for 5 s.
- Fire performance: Limits on flame propagation (flame spread), smoke density and toxic gas emissions under fire conditions; cables are halogen‑free to reduce corrosive/toxic by‑products.
- Identification & marking: Manufacturer, EN reference, voltage rating, number/size of cores and code designation (Annex A); core identification by numbers or colours to HD 308 / EN 50334.
- Mechanical & environmental tests: Conductor resistance, voltage, insulation resistance, dielectric strength, spark test, ageing, hot set, ozone, mineral oil/fuel/acid/alkali resistance, low temperature bending/impact, compatibility and water absorption.
- Fire test references: Linked test standards (e.g., EN 60332‑1‑2, EN 61034‑2, EN 50266 series, EN 50305) and Part 1 “General requirements”.
Applications and who uses it
- Designers and engineers of railway rolling stock specifying onboard power and control cabling.
- Cable manufacturers developing multicore, halogen‑free, crosslinked elastomeric insulated products to meet railway fire safety.
- Procurement specialists and compliance teams selecting cables for passenger and freight vehicles where fire performance and smoke/toxicity limits are critical.
- Test laboratories and certification bodies performing the specified electrical, mechanical and fire tests.
- Installation and maintenance teams needing guidance for fixed or limited‑flex wiring in trains, trams and metros.
Related standards
- EN 50264-1:2008 - Part 1: General requirements (to be read together with Part 2‑2)
- EN 50264 series (other parts for single core and reduced-dimension cables)
- Test and identification standards referenced in EN 50264‑2‑2 (e.g., EN 60228, EN 60332‑1‑2, EN 61034‑2, EN 50305)
Keywords: EN 50264-2-2, railway cables, multicore cables, crosslinked elastomeric insulation, halogen-free, fire performance, 0.6/1 kV, 300/500 V, CENELEC, cable testing.
Standards Content (Sample)
SLOVENSKI STANDARD
01-september-2008
1DGRPHãþD
SIST EN 50264-3:2003
äHOH]QLãNHQDSUDYH(QHUJHWVNLLQNUPLOQLNDEOL]DåHOH]QLãNDYR]QDVUHGVWYDNL
LPDMRSRVHEQHRJQMHYDUQHODVWQRVWLGHO.DEOL]]DPUHåHQRHODVWRPHUQR
L]RODFLMR9HþåLOQLNDEOL
Railway applications - Railway rolling stock power and control cables having special fire
performance -- Part 2-2: Cables with crosslinked elastomeric insulation - Multicore cables
Bahnanwendungen - Starkstrom- und Steuerleitungen für Schienenfahrzeuge mit
verbessertem Verhalten im Brandfall -- Teil 2-2: Leitungen mit vernetzter elastomerer
Isolierung - Mehr- und vieladrige Leitungen
Applications ferroviaires - Câbles de puissance et de contrôle à comportement au feu
spécifié pour matériel roulant ferroviaire -- Partie 2-2: Câbles à enveloppe isolante
réticulée - Câbles multiconducteurs
Ta slovenski standard je istoveten z: EN 50264-2-2:2008
ICS:
13.220.20 3RåDUQD]DãþLWD Fire protection
29.060.20 Kabli Cables
45.060.01 Železniška vozila na splošno Railway rolling stock in
general
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
EUROPEAN STANDARD
EN 50264-2-2
NORME EUROPÉENNE
June 2008
EUROPÄISCHE NORM
ICS 13.220.20; 29.060.20; 45.060.01 Supersedes EN 50264-3:2002
English version
Railway applications -
Railway rolling stock power and control cables
having special fire performance -
Part 2-2: Cables with crosslinked elastomeric insulation -
Multicore cables
Applications ferroviaires - Bahnanwendungen -
Câbles de puissance et de contrôle Starkstrom- und Steuerleitungen
à comportement au feu spécifié für Schienenfahrzeuge mit verbessertem
pour matériel roulant ferroviaire - Verhalten im Brandfall -
Partie 2-2: Câbles à enveloppe Teil 2-2: Leitungen mit vernetzter
isolante réticulée - elastomerer Isolierung -
Câbles multiconducteurs Mehr- und vieladrige Leitungen
This European Standard was approved by CENELEC on 2008-03-01. CENELEC members are bound to comply
with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard
the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and notified
to the Central Secretariat has the same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Cyprus, the
Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain,
Sweden, Switzerland and the United Kingdom.
CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
Central Secretariat: rue de Stassart 35, B - 1050 Brussels
© 2008 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 50264-2-2:2008 E
Foreword
This European Standard was prepared by Working Group 12, Railway cables, of the Technical Committee
CENELEC TC 20, Electric cables, as part of the overall programme of work in the Technical Committee
CENELEC TC 9X, Electrical and electronic applications for railways.
The text of the draft was submitted to the formal vote and was approved by CENELEC as EN 50264-2-2 on
2008-03-01.
This European Standard supersedes EN 50264-3:2002.
The following dates were fixed:
– latest date by which the EN has to be implemented
at national level by publication of an identical
national standard or by endorsement (dop) 2009-03-01
– latest date by which the national standards conflicting
with the EN have to be withdrawn (dow) 2011-03-01
__________
– 3 – EN 50264-2-2:2008
Contents
Page
Introduction . 5
1 Scope . 6
2 Normative references . 6
3 Definitions . 7
4 Rated voltage . 7
5 Marking and identification . 7
5.1 Marking of cable . 7
5.2 Core identification. 8
5.3 Sheath . 8
6 Construction of cables . 8
6.1 General . 8
6.2 Conductor . 8
6.3 Insulation system. 9
6.4 Laying up of cores and fillers . 9
6.5 Metallic screen . 9
6.6 Sheath . 9
6.7 Construction . 10
7 Tests . 18
7.1 Definitions relating to tests . 18
7.2 Conductor resistance. . 18
7.3 Voltage test . 18
7.4 Insulation resistance . 19
7.5 Dielectric strength on sample . 19
7.6 Spark test . 19
7.7 Surface resistance. 20
7.8 Ageing test . 20
7.9 Hot set test . 20
7.10 Compatibility . 20
7.11 Water absorption of sheath . 21
7.12 Ozone resistance . 21
7.13 Mineral oil resistance . 21
7.14 Fuel resistance . 22
7.15 Acid and alkali resistance . 22
7.16 Bending test at low temperature (cores or cables with OD ≤ 12,5 mm) . 23
7.17 Cold elongation test (cores or cables with OD > 12,5 mm) . 23
7.18 Impact test at low temperature . 23
7.19 Reaction to fire – Cable . 23
7.20 Reaction to fire – Components . 23
Annex A (normative) Code designation . 27
Bibliography . 28
Tables
Table 1 – Multicore cables – unscreened (300/500 V) . 11
Table 2 – Multicore cables – screened (300/500 V) . 13
Table 3 – Dimensions of core (0,6/1 kV) . 15
Table 4 – Two cores – (0,6/1 kV) unscreened. 15
Table 5 – Two cores – (0,6/1 kV) screened. 16
Table 6 – Three cores – (0,6/1 kV) unscreened . 16
Table 7 – Three cores – (0,6/1 kV) screened . 17
Table 8 – Four cores – (0,6/1 kV) unscreened . 17
Table 9 – Four cores – (0,6/1 kV) screened . 18
Table 10 – Schedule of tests for cables . 24
– 5 – EN 50264-2-2:2008
Introduction
The EN 50264 series covers a range of cables, based upon halogen free materials, for use in railway rolling
stock. It is divided into 5 parts under the generic title “Railway applications - Railway rolling stock power and
control cables having special fire performance”:
– Part 1 General requirements;
– Part 2-1 Cables with crosslinked elastomeric insulation – Single core cables;
– Part 2-2 Cables with crosslinked elastomeric insulation – Multicore cables;
– Part 3-1 Cables with crosslinked elastomeric insulation with reduced dimensions – Single core
cables;
– Part 3-2 Cables with crosslinked elastomeric insulation with reduced dimensions – Multicore cables.
Information regarding selection and installation of cables, including current ratings can be found in EN 50355
and EN 50343. The procedure for selection of cable cross-sectional area, including reduction factors for
ambient temperature and installation type, is described in EN 50343.
Special test methods referred to in EN 50264 are given in EN 50305.
Part 1, “General requirements”, contains a more extensive introduction to EN 50264, and should be read in
conjunction with this Part 2-2.
1 Scope
EN 50264-2-2 specifies requirements for, and constructions and dimensions of, multicore cables of the
following types and voltage ratings:
• 300/500 V screened or unscreened (1 mm², 1,5 mm² and 2,5 mm², number of cores from 2 to 40);
• 0,6/1 kV screened or unscreened (1,5 mm² to 50 mm², 2, 3 and 4 cores).
NOTE Not all conductor sizes or number of cores are specified for every type.
All cables have class 5 tinned copper conductors to EN 60228, halogen-free insulation and halogen-free
sheath. They are for use in railway rolling stock as fixed wiring, or wiring where limited flexing in operation is
encountered. The requirements provide for a continuous conductor temperature not exceeding 90 °C and a
maximum temperature for short circuit conditions of 200 °C based on a duration of 5 s.
Under fire conditions the cables exhibit special performance characteristics in respect of maximum
permissible flame propagation (flame spread) and maximum permissible emission of smoke and toxic gases.
EN 50264-2-2 should be read in conjunction with Part 1 “General requirements”.
2 Normative references
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
EN 10002-1 Metallic materials – Tensile testing – Methods of test at ambient temperature
EN 50264-1:2008 Railway applications – Railway rolling stock power and control cables having
special fire performance – Part 1: General requirements
EN 50266-2-4 Common test methods for cables under fire conditions – Test for vertical flame
spread of vertically-mounted bunched wires or cables –
Part 2-4: Procedures – Category C
EN 50266-2-5 Common test methods for cables under fire conditions – Test for vertical flame
spread of vertically-mounted bunched wires or cables –
Part 2-5: Procedures – Small cables – Category D
EN 50305:2002 Railway applications – Railway rolling stock cables having special fire performance
– Test methods
EN 50334 Marking by inscription for the identification of cores of electric cables
EN 60228 Conductors of insulated cables (IEC 60228)
EN 60332-1-2 Tests on electric and optical fibre cables under fire conditions –
Part 1-2: Test for vertical flame propagation for a single insulated wire or cable –
Procedure for 1 kW pre-mixed flame (IEC 60332-1-2)
EN 60811-1-1:1995 Insulating and sheathing materials of electric and optical cables – Common test
methods – Part 1-1: General application – Measurement of thickness and overall
dimensions – Tests for determining the mechanical properties
(IEC 60811-1-1:1993)
– 7 – EN 50264-2-2:2008
EN 60811-1-2:1995 Insulating and sheathing materials of electric cables – Common test methods –
Part 1-2: General application – Thermal ageing methods
(IEC 60811-1-2:1985 + A1:1989 + corr. May 1986)
EN 60811-1-3:1995 Insulating and sheathing materials of electric and optical cables – Common test
methods – Part 1-3: General application – Methods for determining the density –
Water absorption tests – Shrinkage test (IEC 60811-1-3:1993)
EN 60811-1-4:1995 Insulating and sheathing materials of electric and optical cables – Common test
methods – Part 1-4: General application – Tests at low temperature
(IEC 60811-1-4:1985 + A1:1993 + corr. May 1986)
EN 60811-2-1:1998 Insulating and sheathing materials of electric and optical cables – Common test
methods – Part 2-1: Methods specific to elastomeric compounds – Ozone
resistance, hot set and mineral oil immersion tests
(IEC 60811-2-1:1998)
EN 61034-2 Measurement of smoke density of cables burning under defined conditions –
Part 2: Procedure and requirements (IEC 61034-2)
HD 308 Identification of cores in cables and flexible cords
3 Definitions
For the purposes of this document, the terms and definitions given in EN 50264-1 apply.
4 Rated voltage
The rated voltage for multicore cables shall be as follows:
a) 300/500 V (1 mm² to 2,5 mm²) control cables;
b) 0,6/1 kV (1,5 mm² to 50 mm²) power cables.
5 Marking and identification
5.1 Marking of cable
Cables shall be marked with the following:
• manufacturer’s name;
• EN reference;
• voltage rating (U );
o
• number of cores and conductor size;
• a code designation according to Annex A.
If a cable is screened, an additional letter, S, shall be added.
An example of a complete mark is:
XYZ EN 50264-2-2 300 V 37 x 1,5 FF S
The marking shall conform to the requirements of EN 50264-1, Clause 5.
5.2 Core identification
The cores of all cables, except the earthing conductor, shall be black unless otherwise specified.
The identification of the individual core in a cable, except the earthing conductor, shall be by printed number
or colour. The number shall be printed in a colour which contrasts with the core colour. If a colour other than
black is specified it shall be a clearly identifiable colour in accordance with HD 308 and shall be durable. The
colour shall be throughout the whole of the insulation or on its surface. Durability shall be checked by the test
given in EN 50305, 10.1.
The marking by numbers shall conform to EN 50334, unless otherwise specified, and conformity shall be
checked by visual examination and measurement.
5.3 Sheath
The sheath shall be black unless otherwise agreed between the manufacturer and purchaser.
6 Construction of cables
6.1 General
Cores complying with this part or EN 50264-2-1 may be used as components of multicore cables.
The control cable dimensions shall be as given in Tables 1 or 2 as appropriate to the cable type.
The power cable core dimensions shall be as given in Table 3 and cable dimensions as given in Tables 4
to 9 as appropriate to the cable type (see Clause 4).
If agreed between the purchaser and manufacturer, cables may be made with the number of cores not
specified in Tables 1 and 2. In such cases the thickness of the sheath and diameter of the braid wire (if any)
shall be those specified in the relevant table for the cable containing the next higher number of cores.
6.2 Conductor
Conductors shall be tin-coated annealed copper, class 5, according to EN 60228.
When tested in accordance with EN 10002-1 the minimum average elongation of the wires from the
conductor shall be 15 %, with a minimum value of 10 % for any individual wire.
NOTE It is not necessary to test all individual wires. 5 % of wires or 10 wires, whichever is the least number, should be selected at
random.
– 9 – EN 50264-2-2:2008
6.3 Insulation system
Insulation shall be one or more extruded materials as defined in EN 50264-1 applied so as to meet the
requirements of EI 101 to EI 105:
EI 101 low temperature resistant, oil resistant;
EI 102 extra low temperature resistant, oil resistant;
EI 103 low temperature resistant, extra oil and fuel resistant;
EI 104 extra low temperature resistant, extra oil and fuel resistant;
EI 105 extra low temperature resistant, non oil resistant.
To claim extra low temperature performance both insulation and sheath shall be extra low temperature
resistant.
The insulation shall be applied to meet the requirements of EN 50264-1, 6.2.
The insulation thickness shall conform to the specified value given in Tables 1 to 3.
6.4 Laying up of cores and fillers
The cores shall be twisted together with either a continuous right or left-hand direction of lay.
The pitch or lay for primary cores shall not be greater than 20 times the diameter of the bunch of cores in the
cable.
NOTE Non-hygroscopic fillers may be applied as given in EN 50264-1, 6.3. A synthetic binder tape may be used over the laid-up
assembly at the manufacturer’s discretion.
6.5 Metallic screen
Where screens are applied over cores a tape shall be used between cores and screens. The metallic
screening braid shall meet the requirements of EN 50264-1, 6.4.
6.6 Sheath
Sheath shall be an extruded material as defined in EN 50264-1 applied so as to meet the requirements of
compound type EM 101 to EM 104:
EM 101 low temperature resistant, oil resistant;
EM 102 extra low temperature resistant, oil resistant;
EM 103 low temperature resistant, extra oil and fuel resistant;
EM 104 extra low temperature resistant, extra oil and fuel resistant.
The sheath shall consist of one or more extruded layers of the same type.
The sheath shall be applied to meet the requirements of EN 50264-1, 6.6.
The sheath thickness shall conform to the specified value given in Tables 1, 2 or 4 to 9 as appropriate.
6.7 Construction
Power and control cables of all types shall be composed of the following components in the order given:
• conductor flexible tin coated annealed copper, class 5;
• separator optional;
• insulation compound as given in 6.3;
• laying up and fillers as given in 6.4;
• metallic screen (where required) as given in 6.5 and specified in Tables 2, 5, 7, 9;
• separator optional;
• sheath compound as given in 6.6.
– 11 – EN 50264-2-2:2008
Table 1 – Multicore cables – unscreened (300/500 V)
1 2 3 45 6 7 8 9 10 11 1
Number and Conductor Mean Core Mean Overall diameter Conductor Insulation Insulation Number and
nominal cross- diameter thickness of diameter thickness of resistance resistance resistance nominal cross-
a b a
sectional area d insulation sheath D at 20 °
...
Frequently Asked Questions
EN 50264-2-2:2008 is a standard published by CLC. Its full title is "Railway applications - Railway rolling stock power and control cables having special fire performance - Part 2-2: Cables with crosslinked elastomeric insulation - Multicore cables". This standard covers: EN 50264-2-2 specifies requirements for, and constructions and dimensions of, multicore cables of the following types and voltage ratings: • 300/500 V screened or unscreened (1 mm², 1,5 mm² and 2,5 mm², number of cores from 2 to 40); • 0,6/1 kV screened or unscreened (1,5 mm² to 50 mm², 2, 3 and 4 cores). NOTE Not all conductor sizes or number of cores are specified for every type. All cables have class 5 tinned copper conductors to EN 60228, halogen-free insulation and halogen-free sheath. They are for use in railway rolling stock as fixed wiring, or wiring where limited flexing in operation is encountered. The requirements provide for a continuous conductor temperature not exceeding 90 °C and a maximum temperature for short circuit conditions of 200 °C based on a duration of 5 s. Under fire conditions the cables exhibit special performance characteristics in respect of maximum permissible flame propagation (flame spread) and maximum permissible emission of smoke and toxic gases. EN 50264-2-2 should be read in conjunction with Part 1 “General requirements”.
EN 50264-2-2 specifies requirements for, and constructions and dimensions of, multicore cables of the following types and voltage ratings: • 300/500 V screened or unscreened (1 mm², 1,5 mm² and 2,5 mm², number of cores from 2 to 40); • 0,6/1 kV screened or unscreened (1,5 mm² to 50 mm², 2, 3 and 4 cores). NOTE Not all conductor sizes or number of cores are specified for every type. All cables have class 5 tinned copper conductors to EN 60228, halogen-free insulation and halogen-free sheath. They are for use in railway rolling stock as fixed wiring, or wiring where limited flexing in operation is encountered. The requirements provide for a continuous conductor temperature not exceeding 90 °C and a maximum temperature for short circuit conditions of 200 °C based on a duration of 5 s. Under fire conditions the cables exhibit special performance characteristics in respect of maximum permissible flame propagation (flame spread) and maximum permissible emission of smoke and toxic gases. EN 50264-2-2 should be read in conjunction with Part 1 “General requirements”.
EN 50264-2-2:2008 is classified under the following ICS (International Classification for Standards) categories: 13.220.20 - Fire protection; 29.060.20 - Cables; 45.060.01 - Railway rolling stock in general. The ICS classification helps identify the subject area and facilitates finding related standards.
EN 50264-2-2:2008 has the following relationships with other standards: It is inter standard links to EN 50264-3:2002. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
You can purchase EN 50264-2-2:2008 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of CLC standards.
La norme EN 50264-2-2:2008 traite des câbles d'alimentation et de contrôle pour le matériel roulant ferroviaire ayant des performances spéciales en matière de feu. Son champ d'application est clairement défini, spécifiant les exigences, les constructions et les dimensions des câbles multicœurs, notamment pour les tensions de 300/500 V et de 0,6/1 kV. Les types de câbles concernés varient en fonction de la section des conducteurs, allant de 1 mm² à 50 mm², et comprenant entre 2 et 40 conducteurs. Une mention particulière est faite concernant la taille des conducteurs et le nombre de cœurs, qui ne sont pas spécifiés pour toutes les catégories. Un des points forts de cette norme est l'exigence relative à des conducteurs en cuivre étamé de classe 5, conformément à la norme EN 60228, ainsi que l'utilisation d'une isolation et d'une gaine sans halogène. Ces spécifications assurent non seulement la sécurité et la durabilité des câbles dans le milieu ferroviaire, mais contribuent également à la réduction des risques liés à l'incendie. En matière de performance thermique, la norme stipule que la température continue des conducteurs ne doit pas dépasser 90°C, avec une température maximale en cas de court-circuit de 200°C sur une durée limitée à 5 secondes. Ceci reflète une préoccupation essentielle pour la sécurité dans les applications ferroviaires, où les conditions d'exploitation peuvent être particulièrement exigeantes. De plus, EN 50264-2-2 se distingue par ses performances en cas d'incendie, mettant en avant des caractéristiques telles que la propagation des flammes et l’émission maximale de fumée et de gaz toxiques. Ces exigences sont critiques pour garantir la sécurité des passagers et du personnel à bord des véhicules ferroviaires. Enfin, il est à noter que EN 50264-2-2 doit être interprétée en relation avec la Partie 1, qui traite des exigences générales, ce qui renforce sa pertinence en tant que document de référence pour les professionnels du secteur ferroviaire. En conclusion, cette norme constitue une base solide pour la conception et l'utilisation de câbles multicœurs, en répondant à des enjeux de sécurité essentiels dans le domaine des applications ferroviaires.
EN 50264-2-2:2008 serves as a critical standard within the railway applications sector, specifically focusing on railway rolling stock power and control cables that are endowed with special fire performance features. This standard delineates comprehensive requirements, including constructions and dimensions for multicore cables, ensuring that they comply with essential safety and functional specifications required for railway environments. The scope of EN 50264-2-2 is clearly defined, covering various cable types and voltage ratings, including 300/500 V and 0.6/1 kV configurations. By specifying conductor sizes from 1 mm² to 50 mm² and allowing for configurations with 2 to 40 cores, the standard ensures versatility and compatibility in electrical systems used in railway rolling stock. The use of class 5 tinned copper conductors and halogen-free insulation and sheath materials reflects a commitment to safety and environmental considerations, which is paramount in public transportation systems. Strengths of EN 50264-2-2 include its detailed specification of temperature ratings, which stipulate a continuous conductor temperature limit of 90 °C and a short circuit maximum of 200 °C with a clear duration specification, enhancing the robustness of cables under different operational scenarios. The focus on fire performance characteristics is another significant strength; it addresses critical factors such as flame propagation and smoke and toxic gas emissions, ensuring that cables not only perform well electrically but also uphold safety standards in emergency situations. The relevance of EN 50264-2-2 cannot be overstated in the context of modern railways, where safety and reliability are paramount. The inclusion of halogen-free materials further aligns with the industry's increasing emphasis on sustainable practices and environmental responsibility. This standard is essential for manufacturers, maintenance personnel, and safety regulators to ensure that the cables used in railway rolling stock meet rigorous performance and safety standards. Proper adherence to EN 50264-2-2 guarantees a higher level of protection and performance in railway electrical systems, making it an indispensable reference for professionals in the railway sector.
EN 50264-2-2:2008は、鉄道応用における特別な火災性能を持つ鉄道車両の電源および制御ケーブルに関する重要な標準です。この標準は、耐火性が要求される多芯ケーブルの使用要件を詳述しており、特に300/500 Vおよび0,6/1 kVの電圧範囲で、さまざまな太さとコア数のケーブルに適用されます。具体的には、1 mm²、1.5 mm²、2.5 mm²のコアから2~40本のコアを有するケーブルや、1.5 mm²から50 mm²の範囲のコア数2、3、4のケーブルが含まれています。 この標準の強みは、火災条件下での特別な性能特性を持つケーブルの要件を詳しく定義している点です。最大許容炎拡散速度や煙および有毒ガスの排出量に関する基準が設けられており、鉄道車両における安全性を高めるための重要な指針となっています。また、すべてのケーブルは、EN 60228に準拠したクラス5の錫メッキ銅導体を使用しており、ハロゲンフリーの絶縁体およびシースを採用しています。これにより、環境への配慮もなされていることが特徴です。 さらに、連続的な導体温度が90°Cを超えないこと、短絡条件での最大温度が200°C(5秒間の持続時間に基づく)であることも明記されており、これにより高温環境下での使用にも耐えうる設計がされています。EN 50264-2-2は、標準の一般要求事項に関する第1部と併せて読むことが推奨されており、これにより鉄道車両の固定配線や限られた屈曲に対応した配線の安全性と信頼性を確保するための包括的な基準を提供します。 この標準は、鉄道産業における規制遵守や安全向上の観点から非常に重要であり、業界における信頼性の高い施工が求められる場面で、欠かせない資源となっています。鉄道の発展と共に、EN 50264-2-2の重要性はますます増しており、現在および将来の鉄道車両において、安心して使用できる基盤を提供しています。
Die Norm EN 50264-2-2:2008 legt die Anforderungen und Konstruktionen von Mehrbereichskabeln mit querschnittsvernetzten elastomeren Isolierungen fest, die speziell für den Einsatz im Schienenfahrzeugbereich konzipiert sind. Der Anwendungsbereich dieser Norm ist klar umrissen und umfasst Kabel mit einer Nennspannung von 300/500 V und 0,6/1 kV, die sowohl geschirmt als auch ungeschirmt erhältlich sind. Die definierten Querschnittsgrößen reichen von 1 mm² bis 50 mm², und die Anzahl der Adern variiert von 2 bis 40. Diese Flexibilität in den Konfigurationen ermöglicht eine breite Einsatzmöglichkeit in unterschiedlichen Anwendungen der Bahntechnik. Eine der größten Stärken der EN 50264-2-2 liegt in den spezifischen Anforderungen an die Feuerbeständigkeit der Kabel. Die Norm garantiert, dass die Kabel unter Brandbedingungen besondere Leistungsmerkmale aufweisen, einschließlich einer maximal zulässigen Flammenausbreitung und einer reduzierten Emission von Rauch und toxischen Gasen. Dies ist besonders relevant für die Sicherheit im Schienenverkehr, wo Brandschutz von höchster Priorität ist. Darüber hinaus sind alle Kabel mit klassifizierten, verzinnten Kupferleitern gemäß EN 60228 ausgestattet und verfügen über halogenfreie Isolierungen und Umhüllungen, was deren Umweltverträglichkeit erhöht. Die Definition von Temperaturgrenzwerten, mit einem maximalen kontinuierlichen Leiterbetriebstemperatur von 90 °C und einer Höchsttemperatur für Kurzschlussbedingungen von 200 °C für eine Dauer von 5 Sekunden, zeigt die herausragende thermische Stabilität dieser Kabel auf und trägt zur Zuverlässigkeit in verschiedenen Betriebsbedingungen bei. Insgesamt ist die Norm EN 50264-2-2:2008 von erheblicher Relevanz für die Konstruktion und Anwendung von Kabeln im Schienenfahrzeugbereich, da sie nicht nur technische Anforderungen formuliert, sondern auch Sicherheitsaspekte in Bezug auf Feuerfestigkeit und Schadstoffemission berücksichtigt. Die enge Zusammenarbeit mit der allgemeinen Norm EN 50264-1 zur Sicherstellung der Gesamtanforderungen verdeutlicht die umfassende Herangehensweise dieser Norm und unterstreicht ihre Bedeutung für die Qualität und Sicherheit im Bereich der Bahnanwendungen.
표준 EN 50264-2-2:2008은 특수 화재 성능을 갖춘 철도 차량의 전력 및 제어 케이블에 대한 요구 사항을 구체적으로 규명하고 있습니다. 이 문서는 다중 코어 케이블의 구조 및 치수를 정의하며, 300/500 V 및 0,6/1 kV의 다양한 전압 등급을 포함합니다. 이 표준의 주요 강점은 전선이 90 °C의 지속적인 도체 온도를 견딜 수 있도록 설계되어 있다는 점이며, 단락 조건에서 최대 200 °C의 온도를 허용함으로써 안전성을 높이는 데 기여합니다. 또한, EN 50264-2-2는 할로겐이 없는 절연체와 할로겐이 없는 피복을 적용하여 화재 발생 시 화재 확산 및 연기와 독성 가스의 배출 특성에서 우수한 성능을 발휘하도록 설계되었습니다. 이러한 특성은 특히 철도 차량이 안전하게 운영될 수 있도록 하는 데 필수적인 요소로 작용합니다. 따라서 이 표준은 철도 차량의 설계 및 운행에 있어 매우 중요한 참고 자료입니다. 추가로, 이 문서는 Part 1 "일반 요구 사항"과 함께 읽어야 하며, 이는 표준의 전체적인 이해를 돕고, 다중 코어 케이블에 대한 포괄적인 안전 및 성능 기준을 제공합니다. EN 50264-2-2는 철도 분야에서의 안전과 성능을 극대화하는 데 중요한 역할을 하고 있으며, 이에 따라 철도 Rolling stock의 요구 사항을 충족하는 데 필수적인 표준으로 평가됩니다.








Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.
Loading comments...