High-voltage switchgear and controlgear - Part 202: High-voltage/low-voltage prefabricated substation

IEC 62271-202:2014 specifies the service conditions, rated characteristics, general structural requirements and test methods of high voltage/low voltage or low voltage/high voltage prefabricated substations, which are cable-connected, to be operated from inside (walk-in type) or outside (non-walk-in type) for alternating current of rated voltages above 1 kV and up to and including 52 kV on the high voltage side, and for one or more transformers for service frequencies up to and including 60 Hz for outdoor installation at locations with public accessibility and where protection of personnel is provided. This second edition cancels and replaces the first edition published in 2006. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition: a) regarding temperature-rise test an alternative method for liquid filled transformers is (re)introduced and the temperature-rise test method for dry-type transformers is specified more precisely; b) testing procedure for short time and peak withstand current tests are specified more precisely; c) assessment of electromagnetic fields is considered including a type test (optional) according IEC/TR 62271-208:2009; d) influence of the product on the environment is considered (Clause 12); e) internal arc test requirements have been adapted to IEC 62271-200:2011 and requirements for the assessment of pressure relief volumes below the floor / ground has been assigned; f) the method for defining the load factor in an enclosure for liquid filled transformers is extended with different temperature rises for the transformer outside the enclosure (Annex DD); g) for the calculation of the load factor of dry-type transformers in an enclosure the insulation systems according to IEC 60076-1:2011, Tables B.1 and B.2 are worked out in detail.

Hochspannungs-Schaltgeräte und -Schaltanlagen - Teil 202: Fabrikfertige Stationen für Hochspannung/Niederspannung

Appareillages à haute tension - Partie 202: Postes préfabriqués haute tension/basse tension

L'IEC 62271-202:2014 spécifie les conditions de service, les caractéristiques assignées, les exigences structurelles générales et les méthodes d'essai applicables aux postes préfabriqués haute tension/basse tension ou basse tension/haute tension qui sont connectés par câble, pour être man uvrés de l'intérieur (à aire de manoeuvre) ou de l'extérieur (sans aire de manoeuvre), pour courant alternatif de tensions assignées supérieures à 1 kV et inférieures ou égales à 52 kV côté haute tension, pour un ou plusieurs transformateurs, pour des fréquences de service inférieures ou égales à 60 Hz et pour installation extérieure, dans des endroits accessibles au public et où la protection des personnes est assurée. Cette deuxième édition annule et remplace la première édition, parue en 2006. Cette édition constitue une révision technique. Cette édition inclut les modifications techniques majeures suivantes par rapport à l'édition précédente: a) eu égard à l'essai d'échauffement, une autre méthode pour les transformateurs immergés est (ré)introduite, et la méthode d'essai d'échauffement des transformateurs de type sec est spécifiée plus en détails; b) la procédure d'essai au courant de courte durée et à la valeur de crête du courant admissible est spécifiée plus en détails; c) l'évaluation des champs électromagnétiques est prise en compte, y compris un essai de type (facultatif) conforme à l'IEC/TR 62271-208:2009; d) l'influence du produit sur l'environnement est prise en compte (Article 12); e) les exigences d'essai d'arc interne ont été adaptées à l'IEC 62271-200:2011, et les exigences d'évaluation des volumes de décharge de pression sous le sol ont été attribuées; f) la méthode de définition du facteur de charge dans une enveloppe pour transformateurs immergés a été étendue aux différents échauffements, pour le transformateur placé à l'extérieur de l'enveloppe (Annexe DD); g) pour le calcul du facteur de charge des transformateurs de type sec dans une enveloppe, les systèmes d'isolation conformes au Tableaux B.1 et B.2 de l'IEC 60076-1:2011 ont été approfondis.

Visokonapetostne stikalne in krmilne naprave - 202. del: Visokonapetostna/nizkonapetostna montažna postaja (IEC 62271-202:2014)

Standard EN IEC 62271-202 določa pogoje obratovanja, naznačene karakteristike, splošne strukturne zahteve in preskusne metode visokonapetostnih/nizkonapetostnih ali nizkonapetostnih/visokonapetostnih montažnih postaj, povezanih s kabli, ki se upravljajo od znotraj (vhodni tip) ali zunaj (nevhodni tip) za izmenični tok naznačenih napetosti nad 1 kV in do vključno 52 kV na visokonapetostni strani, ter za enega ali več transformatorjev za storitvene frekvence do vključno 60 Hz za zunanjo vgradnjo na lokacijah z javno dostopnostjo in kadar se zagotovi zaščita osebja. Montažne postaje se lahko nahajajo na tleh ali delno ali popolnoma pod površjem. Na splošno montažna postaja zajema ohišje, ki vsebuje naslednje električne komponente: – elektroenergetske transformatorje; – visokonapetostne in nizkonapetostne stikalne in krmilne naprave; – visokonapetostne in nizkonapetostne povezave; – pomožno opremo in tokokroge. Vendar pa se zadevne določbe tega standarda uporabljajo za zasnove, pri katerih ne obstajajo vse te električne komponente (na primer, inštalacija, ki vključuje elektroenergetski transformator in nizkonapetostno stikalno napravo). Nemontažne postaje naj bi bile skladne z ustreznimi zahtevami standarda IEC 61936-1:2010.

General Information

Status
Published
Publication Date
05-Jun-2014
Withdrawal Date
30-Apr-2017
Current Stage
6060 - Document made available - Publishing
Start Date
06-Jun-2014
Completion Date
06-Jun-2014

Relations

Buy Standard

Standard
EN 62271-202:2014 - BARVE
English language
100 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 62271-202:2014
01-september-2014
1DGRPHãþD
SIST EN 62271-202:2007
Visokonapetostne stikalne in krmilne naprave - 202. del:
Visokonapetostna/nizkonapetostna montažna postaja (IEC 62271-202:2014)
High-voltage switchgear and controlgear - Part 202: High voltage/low voltage
prefabricated substation
Appareillages à haute tension - Partie 202: Postes préfabriqués haute tension/basse
tension
Ta slovenski standard je istoveten z: EN 62271-202:2014
ICS:
29.130.10 Visokonapetostne stikalne in High voltage switchgear and
krmilne naprave controlgear
SIST EN 62271-202:2014 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST EN 62271-202:2014

---------------------- Page: 2 ----------------------

SIST EN 62271-202:2014


EUROPEAN STANDARD EN 62271-202

NORME EUROPÉENNE

EUROPÄISCHE NORM
June 2014
ICS 29.130.10 Supersedes EN 62271-202:2007
English Version
High-voltage switchgear and controlgear - Part 202: High-
voltage/low-voltage prefabricated substation
(IEC 62271-202:2014)
Appareillages à haute tension - Partie 202: Postes Hochspannungs-Schaltgeräte und -Schaltanlagen - Teil
préfabriqués haute tension/basse tension 202: Fabrikfertige Stationen für
(CEI 62271-202:2014) Hochspannung/Niederspannung
(IEC 62271-202:2014)
This European Standard was approved by CENELEC on 2014-05-01. CENELEC members are bound to comply with the CEN/CENELEC
Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the
same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom.



European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2014 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
 Ref. No. EN 62271-202:2014 E

---------------------- Page: 3 ----------------------

SIST EN 62271-202:2014
EN 62271-202:2014 - 2 -
Foreword
The text of document 17C/595/FDIS, future edition 2 of IEC 62271-202, prepared by SC 17C
“High-voltage switchgear and controlgear assemblies” of IEC TC 17 “Switchgear and controlgear" was
submitted to the IEC-CENELEC parallel vote and approved by CENELEC as EN 62271-202:2014.

The following dates are fixed:
(dop) 2014-11-01
• latest date by which the document has to be
implemented at national level by
publication of an identical national
standard or by endorsement
• latest date by which the national (dow) 2017-05-01
standards conflicting with the
document have to be withdrawn

This document supersedes EN 62271-202:2007.

EN 62271-202:2014 includes the following significant technical changes with respect to
EN 62271-202:2007:
a) regarding temperature-rise test an alternative method for liquid filled transformers is (re)introduced
and the temperature-rise test method for dry-type transformers is specified more precisely;
b) testing procedure for short time and peak withstand current tests are specified more precisely;
c) assessment of electromagnetic fields is considered including a type test (optional) according
CLC/TR 62271-208:2010;
d) influence of the product on the environment is considered (Clause 12);
e) internal arc test requirements have been adapted to EN 62271-200:2012 and requirements for the
assessment of pressure relief volumes below the floor / ground has been assigned;
f) the method for defining the load factor in an enclosure for liquid filled transformers is extended with
different temperature rises for the transformer outside the enclosure (Annex DD);
g) for the calculation of the load factor of dry-type transformers in an enclosure the insulation systems
according to EN 60076-1:2011, Tables B.1 and B.2 are worked out in detail.

Attention is drawn to the possibility that some of the elements of this document may be the subject of
...

Questions, Comments and Discussion