Safety of transformers, reactors, power supply units and combinations thereof - Part 2-15: Particular requirements and tests for isolating transformers for the supply of medical locations

IEC 61558-2-15:2011 deals with safety aspects of isolating transformers for the supply of medical locations. This second edition cancels and replaces the first edition published in 1999. It constitutes a technical revision. The main changes consist of updating this part in accordance with IEC 61558-1:2005. This part has the status of a group safety publication in accordance with IEC Guide 104:2010. The preparation of safety publications and the use of basic safety publications and group safety publications. The attention of National Committees is drawn to the fact that equipment manufacturers and testing organizations may need a transitional period following publication of a new, amended or revised IEC publication in which to make products in accordance with the new requirements and to equip themselves for conducting new or revised tests. It is the recommendation of the committee that the content of this publication be adopted for implementation nationally not earlier than 12 months from the date of publication. This publication is to be read in conjunction with IEC 61558-1:2005.

Sicherheit von Transformatoren, Drosseln, Netzgeräten und entsprechenden Kombinationen - Teil 2-15: Besondere Anforderungen und Prüfungen an Trenntransformatoren zur Versorgung medizinischer Räume

Sécurité des transformateurs, bobines d'inductance, blocs d'alimentation et des combinaisons de ces éléments - Partie 2-15: Règles particulières et essais pour les transformateurs de séparation de circuits pour locaux à usages médicaux

La CEI 61558-2-15:2011 traite des aspects de sécurité des transformateurs de séparation de circuits pour locaux à usages médicaux. Cette deuxième édition annule et remplace la première édition parue en 1999. Elle constitue une révision technique. Les principales modifications consistent en la mise à jour de la présente partie conformément à la CEI 61558-1:2005. La présente partie a le statut de publication groupée de sécurité conformément au guide CEI 104:2010. The preparation of safety publications and the use of basic safety publications and group safety publications (disponible en anglais seulement). L'attention des Comités Nationaux est attirée sur le fait que les fabricants d'appareils et les organismes d'essai peuvent avoir besoin d'une période transitoire après la publication d'une nouvelle publication CEI, ou d'une publication amendée ou révisée, pour fabriquer des produits conformes aux nouvelles exigences et pour adapter leurs équipements aux nouveaux essais ou aux essais révisés. Le comité recommande que le contenu de cette publication soit entériné au niveau national au plus tôt 12 mois après la date de publication. Cette publication doit être lue conjointement avec la CEI 61558-1:2005.

Varnost transformatorjev, dušilk, napajalnikov in njihovih kombinacij - 2-15. del: Posebne zahteve in preskusi za ločilne transformatorje v napajalnikih v medicinskih prostorih

Ta del standarda IEC 61558 obravnava varnostne vidike ločilnih transformatorjev v napajalnikih v medicinskih prostorih. Razen če ni drugače določeno, od tu naprej izraz transformator zajema ločilne transformatorje v napajalnikih v medicinskih prostorih. Ta del velja za stacionarne, enofazne ali trifazne, zračno hlajene (naravno ali umetno) samostojne suhe ločilne transformatorje v napajalnikih v medicinskih sistemih IT za medicinske lokacije iz skupine 2, ki so stalno povezani s fiksnim ožičenjem ter so del napajalnega sistema IT na sekundarni strani. Navitja so lahko enkapsulirana ali neenkapsulirana. Nazivna napajalna napetost ne presega 1000 V izmenične napetosti. Nazivna napajalna frekvenca in notranja operativna frekvenca ne presegata 500 Hz. Nazivna izhodna moč ni manjša od 0,5 kVA in ne presega 10 kVA za enofazne in trifazne transformatorje. Ta del velja za transformatorje brez omejitev nazivne izhodne moči, o čemer se dogovorita kupec in izdelovalec. Izhodna napetost brez obremenitve in nazivna (izhodna) izmenična napetost ne presegata 250 V izmenične napetosti za enofazne ali trifazne transformatorje (medfazna napetost). Ta standard ne zajema enote električnega napajalnika. Ta del ne velja za zunanje tokokroge in njihove sestavne dele, ki so namenjeni za povezavo z vhodnimi in izhodnimi terminali transformatorjev. Transformatorji, ki jih ta del obravnava, se uporabljajo v aplikacijah, v katerih pravila inštalacij ali specifikacije aplikacije zahtevajo dvojno ali ojačano izolacijo med tokokrogi. – Za transformatorje, ki so namenjeni za uporabo v vozilih, na ladjah in letalih, so morda potrebne dodatne zahteve (iz drugih veljavnih standardov, nacionalnih pravil itd.); – upoštevati je treba tudi ukrepe za zaščito ohišja in sestavnih delov v ohišju pred zunanjimi vplivi, kot so glive, mrčes, termiti, sončno sevanje in zmrzovanje; – upoštevati je treba tudi različne pogoje za transport, shranjevanje in delovanje transformatorjev; – za transformatorje, ki so namenjeni za uporabo v posebnih okoljih, lahko veljajo dodatne zahteve v skladu z drugimi ustreznimi standardi in nacionalnimi pravili.

General Information

Status
Published
Publication Date
02-Feb-2012
Withdrawal Date
26-Dec-2014
Current Stage
6060 - Document made available - Publishing
Start Date
03-Feb-2012
Completion Date
03-Feb-2012

Relations

Buy Standard

Standard
EN 61558-2-15:2012
English language
22 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Sicherheit von Transformatoren, Drosseln, Netzgeräten und entsprechenden Kombinationen - Teil 2-15: Besondere Anforderungen und Prüfungen an Trenntransformatoren zur Versorgung medizinischer RäumeSécurité des transformateurs, bobines d'inductance, blocs d'alimentation et des combinaisons de ces éléments - Partie 2-15: Règles particulières et essais pour les transformateurs de séparation de circuits pour locaux à usages médicauxSafety of
transformers, reactors, power supply units and combination thereof - Part 2-15: Particular requirements and tests for isolating transformers for the supply of medical locations29.180Transformatorji. DušilkeTransformers. ReactorsICS:Ta slovenski standard je istoveten z:EN 61558-2-15:2012SIST EN 61558-2-15:2012en01-maj-2012SIST EN 61558-2-15:2012SLOVENSKI
STANDARD



SIST EN 61558-2-15:2012



EUROPEAN STANDARD EN 61558-2-15 NORME EUROPÉENNE
EUROPÄISCHE NORM February 2012
CENELEC European Committee for Electrotechnical Standardization Comité Européen de Normalisation Electrotechnique Europäisches Komitee für Elektrotechnische Normung
Management Centre: Avenue Marnix 17, B - 1000 Brussels
© 2012 CENELEC -
All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 61558-2-15:2012 E
ICS 29.180 Supersedes EN 61558-2-15:2001 + corr. Apr.2004
English version
Safety of transformers, reactors, power supply units and combinations thereof -
Part 2-15: Particular requirements and tests for isolating transformers for the supply of medical locations (IEC 61558-2-15:2011)
Sécurité des transformateurs, bobines d'inductance, blocs d'alimentation et des combinaisons de ces éléments -
Partie 2-15: Règles particulières et essais pour les transformateurs de séparation de circuits pour locaux à usages médicaux (CEI 61558-2-15:2011)
Sicherheit von Transformatoren, Drosseln, Netzgeräten und entsprechenden Kombinationen -
Teil 2-15: Besondere Anforderungen und Prüfungen an Trenntransformatoren zur Versorgung medizinischer Räume (IEC 61558-2-15:2011)
This European Standard was approved by CENELEC on 2011-12-27. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom.
SIST EN 61558-2-15:2012



EN 61558-2-15:2012 - 2 -
Foreword The text of document 96/384/FDIS, future edition 2 of IEC 61558-2-15, prepared by IEC/TC 96, "Transformers, reactors, power supply units and combinations thereof" was submitted to the IEC-CENELEC parallel vote and approved by CENELEC as EN 61558-2-15:2012.
The following dates are fixed: • latest date by which the document has to be implemented at national level by publication of an identical national standard or by endorsement (dop) 2012-09-27 • latest date by which the national standards conflicting with the document have to be withdrawn (dow) 2014-12-27
This document supersedes EN 61558-2-15:2001 + corrigendum April 2004. The main changes consist of updating EN 61558-2-15:2012 in accordance with EN 61558-1:2005. This standard is to be used in conjunction with EN 61558-1:2005. This part supplements or modifies the corresponding clauses in EN 61558-1, so as to convert that publication into the European standard: "Particular requirements and tests for isolating transformers for the supply of medical locations". Where a particular subclause of Part 1 is not mentioned in this part, that subclause applies as far as is reasonable. Where this part states "addition", "modification" or "replacement", the relevant text of Part 1 is to be adapted accordingly. In this part, the following print types are used: – requirements proper: in roman type; – test specifications: in italic type; – explanatory matter: in smaller roman type: In the text of this part, the words in bold are defined in Clause 3. Subclauses, notes, figures and tables additional to those in Part 1 are numbered starting from 101; supplementary annexes are entitled AA, BB, etc. Attention
...