Electromagnetic compatibility (EMC) - Part 4-11: Testing and measurement techniques - Voltage dips, short interruptions and voltage variations immunity tests for equipment with input current up to 16 A per phase

IEC 61000-4-11:2020 is available as IEC 61000-4-11:2020 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.IEC 61000-4-11:2020 defines the immunity test methods and range of preferred test levels for electrical and electronic equipment connected to low-voltage power supply networks for voltage dips, short interruptions, and voltage variations. This document applies to electrical and electronic equipment having a rated input current not exceeding 16 A per phase, for connection to 50 Hz or 60 Hz AC networks. It does not apply to electrical and electronic equipment for connection to 400 Hz AC networks. Tests for these networks will be covered by future IEC documents. The object of this document is to establish a common reference for evaluating the immunity of electrical and electronic equipment when subjected to voltage dips, short interruptions and voltage variations. NOTE 1 Voltage fluctuation immunity tests are covered by IEC 61000-4-14. The test method documented in this document describes a consistent method to assess the immunity of equipment or a system against a defined phenomenon. NOTE 2 As described in IEC Guide 107, this is a basic EMC publication for use by product committees of the IEC. As also stated in Guide 107, the IEC product committees are responsible for determining whether this immunity test standard should be applied or not, and, if applied, they are responsible for defining the appropriate test levels. Technical committee 77 and its sub-committees are prepared to co-operate with product committees in the evaluation of the value of particular immunity tests for their products. This third edition cancels and replaces the second edition published in 2004 and Amendment 1:2017. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition: - rise time and fall time of transients are now defined terms in Clause 3; - the origin of voltage dips and short interruptions is now stated in Clause 4. Keywords: immunity test methods, low-voltage power supply networks

Elektromagnetische Verträglichkeit (EMV) - Teil 4-11: Prüf- und Messverfahren - Prüfungen der Störfestigkeit gegen Spannungseinbrüche, Kurzzeitunterbrechungen und Spannungsschwankungen für Geräte mit einem Eingangsstrom bis zu und einschließlich 16 A je Leiter

Compatibilité électromagnétique (CEM) - Partie 4-11: Techniques d'essai et de mesure - Essais d'immunité aux creux de tension, coupures brèves et variations de tension pour les appareils à courant d’entrée inférieur ou égal à 16 A par phase

IEC 61000-4-11:2020 est disponible sous forme de IEC 61000-4-11:2020 RLV qui contient la Norme internationale et sa version Redline, illustrant les modifications du contenu technique depuis l'édition précédente.L'IEC 61000-4-11:2020 définit les méthodes d'essai d'immunité ainsi que la plage des niveaux d'essais préférentiels pour les matériels électriques et électroniques connectés à des réseaux d'alimentation à basse tension pour les creux de tension, les coupures brèves et les variations de tension. Le présent document s’applique aux matériels électriques et électroniques dont le courant assigné d’entrée ne dépasse pas 16 A par phase et destinés à être reliés à des réseaux électriques à courant alternatif de 50 Hz ou 60 Hz. Il ne s'applique pas aux matériels électriques et électroniques destinés à être reliés à des réseaux électriques à courant alternatif de 400 Hz. Les essais pour ces réseaux seront traités dans des documents IEC à venir. Le but du présent document est d'établir une référence commune pour l'évaluation de l'immunité des matériels électriques et électroniques soumis à des creux de tension, à des coupures brèves et à des variations de tension. NOTE 1 Les essais d’immunité aux fluctuations de tension sont traités dans l’IEC 61000-4-14. La méthode d’essai décrite dans le présent document détaille une méthode sans faille pour évaluer l’immunité d’un matériel ou d’un système à un phénomène prédéfini. NOTE 2 Comme cela est décrit dans le Guide 107 de l’IEC, ce document est une publication fondamentale en CEM destinée à l’usage des comités de produits de l’IEC. Comme cela est également mentionné dans le Guide 107, les comités de produits de l’IEC sont chargés de décider s’il convient d’utiliser ou non cette norme d’essai d’immunité et, si elle est utilisée, les comités sont responsables de la définition des niveaux d’essai appropriés. Le comité d’études 77 et ses sous-comités sont prêts à coopérer avec les comités de produits pour l’évaluation de la pertinence des essais particuliers d’immunité pour leurs produits. Cette troisième édition annule et remplace la deuxième édition parue en 2004 et l'Amendement 1:2017. Cette édition constitue une révision technique. Cette édition inclut les modifications techniques majeures suivantes par rapport à l'édition précédente: - le temps de montée et le temps de descente sont désormais des termes définis à l’Article 3; - l’origine des creux de tension et des coupures brèves est désormais décrite à l’Article 4. Mots-clés : méthodes d'essai d'immunité, réseaux d'alimentation à basse tension

Elektromagnetna združljivost (EMC) - 4-11. del: Preskusne in merilne tehnike - Preskusi odpornosti proti upadom napetosti, kratkotrajnim prekinitvam in odklonom napetosti za opremo z vhodnim tokom do 16 A na fazo

Ta del standarda IEC 61000 določa metode preskušanja odpornosti in obseg najprimernejših preskusnih nivojev za električno in elektronsko opremo, ki je priključena na nizkonapetostna električna omrežja za upade napetosti, kratkotrajne prekinitve in napetostna kolebanja.
Ta dokument se uporablja za električno in elektronsko opremo z nazivnim vhodnim tokom, ki ne presega 16 A na fazo, za priključitev na omrežja z izmeničnim napajanjem 50 Hz ali 60 Hz.
Ne uporablja se za električno in elektronsko opremo za priključitev na omrežja z izmeničnim tokom 400 Hz.
Preskusi za ta omrežja bodo zajeti v prihodnjih dokumentih Mednarodne elektrotehniške komisije (IEC).
Namen tega dokumenta je določiti skupno referenco za vrednotenje odpornosti električne in elektronske opreme na upade napetosti, kratkotrajne prekinitve ter napetostna kolebanja.
OPOMBA 1: Preskusi odpornosti pri spremembi napetosti so zajeti v standardu IEC 61000-4-14.
Preskusna metoda, dokumentirana v tem dokumentu, opisuje skladno metodo za oceno odpornosti opreme ali sistema proti opredeljenemu pojavu.
OPOMBA 2: To je osnovna objava o elektromagnetni združljivosti, ki jo uporabljajo tehnični odbori v okviru Mednarodne elektrotehniške komisije (IEC), kot je opisano v vodilu 107 Mednarodne elektrotehniške komisije. Poleg tega je v vodilu 107 navedeno, da so tehnični odbori v okviru Mednarodne elektrotehniške komisije odgovorni za določitev morebitne uporabe tega standarda s preskusom odpornosti, v primeru uporabe pa so odgovorni za določitev ustreznih preskusnih ravni. Tehnični odbor 77 in njegovi pododbori so pripravljeni za sodelovanje s tehničnimi odbori pri vrednotenju posameznih preskusov odpornosti za ustrezne izdelke.

General Information

Status
Published
Publication Date
26-Mar-2020
Current Stage
6060 - Document made available - Publishing
Start Date
27-Mar-2020
Completion Date
27-Mar-2020

Relations

Standard
EN IEC 61000-4-11:2020 - BARVE
English language
33 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day
Standard
EN IEC 61000-4-11:2020 - BARVE
English language
33 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-maj-2020
Nadomešča:
SIST EN 61000-4-11:2005
SIST EN 61000-4-11:2005/A1:2017
Elektromagnetna združljivost (EMC) - 4-11. del: Preskusne in merilne tehnike -
Preskusi odpornosti proti upadom napetosti, kratkotrajnim prekinitvam in
napetostnim kolebanjem za opremo z vhodnim tokom do 16 A na fazo
Electromagnetic compatibility (EMC) - Part 4-11: Testing and measurement techniques -
Voltage dips, short interruptions and voltage variations immunity tests for equipment with
input current up to 16 A per phase
Compatibilité électromagnétique (CEM) - Partie 4-11: Techniques d'essai et de mesure -
Essais d'immunité aux creux de tension, coupures brèves et variations de tension pour
les appareils à courant d’entrée inférieur ou égal à 16 A par phase
Ta slovenski standard je istoveten z: EN IEC 61000-4-11:2020
ICS:
33.100.20 Imunost Immunity
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EUROPEAN STANDARD EN IEC 61000-4-11

NORME EUROPÉENNE
EUROPÄISCHE NORM
March 2020
ICS 33.100.20 Supersedes EN 61000-4-11:2004 and all of its
amendments and corrigenda (if any)
English Version
Electromagnetic compatibility (EMC) - Part 4-11: Testing and
measurement techniques - Voltage dips, short interruptions and
voltage variations immunity tests for equipment with input current
up to 16 A per phase
(IEC 61000-4-11:2020)
Compatibilité électromagnétique (CEM) - Partie 4-11: Elektromagnetische Verträglichkeit (EMV) - Teil 4-11: Prüf-
Techniques d'essai et de mesure - Essais d'immunité aux und Messverfahren - Prüfungen der Störfestigkeit gegen
creux de tension, coupures brèves et variations de tension Spannungseinbrüche, Kurzzeitunterbrechungen und
pour les appareils à courant d'entrée inférieur ou égal à 16 Spannungsschwankungen für Geräte mit einem
A par phase Eingangsstrom bis zu und einschließlich 16 A je Leiter
(IEC 61000-4-11:2020) (IEC 61000-4-11:2020)
This European Standard was approved by CENELEC on 2020-03-03. CENELEC members are bound to comply with the CEN/CENELEC
Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the
same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the
Netherlands, Norway, Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom.

European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2020 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Ref. No. EN IEC 61000-4-11:2020 E

European foreword
The text of document 77A/1039/FDIS, future edition 3 of IEC 61000-4-11, prepared by SC 77A "EMC -
Low frequency phenomena" of IEC/TC 77 "Electromagnetic compatibility" was submitted to the IEC-
CENELEC parallel vote and approved by CENELEC as EN IEC 61000-4-11:2020.
The following dates are fixed:
• latest date by which the document has to be implemented at national (dop) 2020-12-03
level by publication of an identical national standard or by endorsement
• latest date by which the national standards conflicting with the (dow) 2023-03-03
document have to be withdrawn
This document supersedes EN 61000-4-11:2004 and all of its amendments and corrigenda (if any).
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC shall not be held responsible for identifying any or all such patent rights.
This document has been prepared under a mandate given to CENELEC by the European Commission
and the European Free Trade Association.

Endorsement notice
The text of the International Standard IEC 61000-4-11:2020 was approved by CENELEC as a
European Standard without any modification.
In the official version, for Bibliography, the following notes have to be added for the standards
indicated:
IEC 61000-2 (series) NOTE Harmonized as EN 61000-2 (series)
IEC 61000-2-4 NOTE Harmonized as EN 61000-2-4
IEC 61000-4-11:2004 NOTE Harmonized as EN 61000-4-11:2004 (not modified)
IEC 61000-4-14 NOTE Harmonized as EN 61000-4-14

Annex ZA
(normative)
Normative references to international publications
with their corresponding European publications
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments)
applies.
NOTE 1  Where an International Publication has been modified by common modifications, indicated by (mod), the relevant
EN/HD applies.
NOTE 2  Up-to-date information on the latest versions of the European Standards listed in this annex is available here:
www.cenelec.eu.
Publication Year Title EN/HD Year
IEC TR 61000-2-8 - Electromagnetic compatibility (EMC) − Part 2-8: - -
Environment – Voltage dips and short interruptions
on public electric power supply systems with
statistical measurement results

IEC 61000-4-11 ®
Edition 3.0 2020-01
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
colour
inside
BASIC EMC PUBLICATION
PUBLICATION FONDAMENTALE EN CEM

Electromagnetic compatibility (EMC) –

Part 4-11: Testing and measurement techniques – Voltage dips, short

interruptions and voltage variations immunity tests for equipment with input

current up to 16 A per phase
Compatibilité électromagnétique (CEM) –

Partie 4-11: Techniques d'essai et de mesure – Essais d'immunité aux creux

de tension, coupures brèves et variations de tension pour les appareils

à courant d’entrée inférieur ou égal à 16 A par phase

INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE
ICS 33.100.20 ISBN 978-2-8322-7546-7

– 2 – IEC 61000-4-11:2020 © IEC 2020
CONTENTS
FOREWORD . 4
INTRODUCTION . 6
1 Scope . 7
2 Normative references . 7
3 Terms and definitions . 7
4 General . 9
5 Test levels . 9
5.1 General . 9
5.2 Voltage dips and short interruptions . 9
5.3 Voltage variations . 11
6 Test instrumentation . 14
6.1 Test generator . 14
6.1.1 General. 14
6.1.2 Characteristics and performance of the generator . 15
6.1.3 Verification of the characteristics of the voltage dips, short
interruptions generators . 15
6.2 Power source . 16
7 Test set-up . 16
8 Test procedures . 17
8.1 General . 17
8.2 Laboratory reference conditions . 17
8.2.1 Climatic conditions . 17
8.2.2 Electromagnetic conditions . 18
8.3 Execution of the test . 18
8.3.1 General. 18
8.3.2 Voltage dips and short interruptions . 18
8.3.3 Voltage variations . 19
9 Evaluation of test results . 19
10 Test report . 20
Annex A (normative) Test circuit details . 21
A.1 Test generator peak inrush current drive capability . 21
A.2 Current monitor's characteristics for measuring peak inrush current
capability . 21
A.3 EUT peak inrush current requirement . 21
Annex B (informative) Electromagnetic environment classes . 23
Annex C (informative) Test instrumentation. 24
Annex D (informative) Rationale for generator specification regarding voltage, rise-
time and fall-time, and inrush current capability . 27
D.1 Concept of basic standard . 27
D.2 IEC 61000-4-11:1994 (first edition) . 27
D.3 Rationale for the need of rapid fall-times . 27
D.4 Interpretation of the rise-time and fall-time requirements during EUT testing . 28
D.5 Main conclusions . 28
D.6 Rationale for inrush current capability . 28
Bibliography . 30

IEC 61000-4-11:2020 © IEC 2020 – 3 –

Figure 1 – Voltage dip – Examples . 12
Figure 2 – Short interruption . 13
Figure 3 – Detailed view of rise and fall time . 13
Figure 4 – Voltage variation . 14
Figure 5 – Phase-to-neutral and phase-to-phase testing on three-phase systems . 19
Figure A.1 – Circuit for determining the inrush current drive capability of the short
interruptions generator . 22
Figure A.2 – Circuit for determining the peak inrush current requirement of an EUT . 22
Figure C.1 – Schematics of test instrumentation for voltage dips, short interruptions

and voltage variations . 25
Figure C.2 – Schematic of test instrumentation for three-phase voltage dips, short
interruptions and voltage variations using a power amplifier . 26

Table 1 – Preferred test levels and durations for voltage dips . 10
Table 2 – Preferred test levels and durations for short interruptions . 11
Table 3 – Timing of short-term supply voltage variations . 11
Table 4 – Generator specifications . 15

– 4 – IEC 61000-4-11:2020 © IEC 2020
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
ELECTROMAGNETIC COMPATIBILITY (EMC) –

Part 4-11: Testing and measurement techniques –
Voltage dips, short interruptions and voltage variations immunity
tests for equipment with input current up to 16 A per phase

FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 61000-4-11 has been prepared by subcommittee 77A: EMC – Low
frequency phenomena, of IEC technical committee 77: Electromagnetic compatibility.
It forms Part 4-11 of IEC 61000. It has the status of a basic EMC publication in accordance
with IEC Guide 107.
This third edition cancels and replaces the second edition published in 2004 and
Amendment 1:2017. This edition constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous
edition:
a) rise time and fall time of transients are now defined terms in Clause 3;
b) the origin of voltage dips and short interruptions is now stated in Clause 4.

IEC 61000-4-11:2020 © IEC 2020 – 5 –

The text of this International Standard is based on the following documents:
FDIS Report on voting
77A/1039/FDIS 77A/1056/RVD
Full information on the voting for the approval of this International Standard can be found in
the report on voting indicated in the above table.
This document has been drafted in accordance with the ISO/IEC Directives, Part 2.
A list of all parts in the IEC 61000 series, published under the general title Electromagnetic
compatibility (EMC), can be found on the IEC website.
The committee has decided that the contents of this document will remain unchanged until the
stability date indicated on the IEC website under "http://webstore.iec.ch" in the data related to
the specific document. At this date, the document will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
IMPORTANT – The 'colour inside' logo on the cover page of this publication indicates
that it contains colours which are considered to be useful for the correct
understanding of its contents. Users should therefore print this document using a
colour printer.
– 6 – IEC 61000-4-11:2020 © IEC 2020
INTRODUCTION
IEC 61000 is published in separate parts according to the following structure:
Part 1: General
General considerations (introduction, fundamental principles)
Definitions, terminology
Part 2: Environment
Description of the environment
Classification of the environment
Compatibility levels
Part 3: Limits
Emission limits
Immunity limits (in so far as they do not fall under the responsibility of the product
committees)
Part 4: Testing and measurement techniques
Measurement techniques
Testing techniques
Part 5: Installation and mitigation guidelines
Installation guidelines
Mitigation methods and devices
Part 6: Generic standards
Part 9: Miscellaneous
Each part is further subdivided into several parts, published either as International Standards
or as technical specifications or technical reports, some of which have already been published
as sections. Others will be published with the part number followed by a dash and a second
number identifying the subdivision (example: IEC 61000-6-1).

IEC 61000-4-11:2020 © IEC 2020 – 7 –

ELECTROMAGNETIC COMPATIBILITY (EMC) –

Part 4-11: Testing and measurement techniques –
Voltage dips, short interruptions and voltage variations immunity
tests for equipment with input current up to 16 A per phase

1 Scope
This part of IEC 61000 defines the immunity test methods and range of preferred test levels
for electrical and electronic equipment connected to low-voltage power supply networks for
voltage dips, short interruptions, and voltage variations.
This document applies to electrical and electronic equipment having a rated input current not
exceeding 16 A per phase, for connection to 50 Hz or 60 Hz AC networks.
It does not apply to electrical and electronic equipment for connection to 400 Hz AC networks.
Tests for these networks will be covered by future IEC documents.
The object of this document is to establish a common reference for evaluating the immunity of
electrical and electronic equipment when subjected to voltage dips, short interruptions and
voltage variations.
NOTE 1 Voltage fluctuation immunity tests are covered by IEC 61000-4-14.
The test method documented in this document describes a consistent method to assess the
immunity of equipment or a system against a defined phenomenon.
NOTE 2 As described in IEC Guide 107, this is a basic EMC publication for use by product committees of the
IEC. As also stated in Guide 107, the IEC product committees are responsible for determining whether this
immunity test standard should be applied or not, and, if applied, they are responsible for defining the appropriate
test levels. Technical committee 77 and its sub-committees are prepared to co-operate with product committees in
the evaluation of the value of particular immunity tests for their products.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their
content constitutes requirements of this document. For dated references, only the edition
cited applies. For undated references, the latest edition of the referenced document (including
any amendments) applies.
IEC TR 61000-2-8, Electromagnetic compatibility (EMC) − Part 2-8: Environment − Voltage
dips and short interruptions on public electric power supply systems with statistical
measurement results
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
ISO and IEC maintain terminological databases for use in standardization at the following
addresses:
• IEC Electropedia: available at http://www.electropedia.org/
• ISO Online browsing platform: available at http://www.iso.org/obp

– 8 – IEC 61000-4-11:2020 © IEC 2020
3.1
immunity (to a disturbance)
ability of a device, equipment or system to perform without degradation in the presence of an
electromagnetic disturbance
[SOURCE: IEC 60050-161:1990, 161-01-20]
3.2
voltage dip
sudden reduction of the voltage at a particular point of an electricity supply system below a
specified dip threshold followed by its recovery after a brief interval
Note 1 to entry: Typically, a dip is associated with the occurrence and termination of a short circuit or other
extreme current increase on the system or installations connected to it.
Note 2 to entry: A voltage dip is a two-dimensional electromagnetic disturbance, the level of which is determined
by both voltage and time (duration).
3.3
short interruption
sudden reduction of the voltage on all phases at a particular point of an electric supply system
below a specified interruption threshold followed by its restoration after a brief interval
Note 1 to entry: Short interruptions are typically associated with switchgear operations related to the occurrence
and termination of short circuits on the system or on installations connected to it.
3.4
residual voltage
minimum value of RMS voltage recorded during a voltage dip or short
interruption
Note 1 to entry: The residual voltage can be expressed as a value in volts or as a percentage or per unit value
relative to the reference voltage.
3.5
malfunction
breakdown of the ability of equipment to carry out intended functions or the execution of
unintended functions by the equipment
3.6
calibration
method to prove that the measurement equipment is in compliance with its specifications
Note 1 to entry: For the purposes of this document, calibration is applied to the test generator.
3.7
verification
set of operations which are used to check the test equipment system (e.g. the test generator
and the interconnecting cables) to demonstrate that the test system is functioning within the
specifications given in Clause 6
Note 1 to entry: The methods used for verification can be different from those used for calibration.
Note 2 to entry: The verification procedure of 6.1.3 is meant as a guide to ensure the correct operation of the test
generator and other items making up the test set-up so that the intended waveform is delivered to the EUT.
3.8
rise time
interval of time between the instants at which the instantaneous value of a transition first
reaches a specified lower value and then a specified upper value
Note 1 to entry: The lower and upper values are fixed at 10 % and 90 % of the transition magnitude.

IEC 61000-4-11:2020 © IEC 2020 – 9 –

[SOURCE: IEC 60050-161:1990, 161-02-05]
3.9
fall time
interval of time between the instants at which the instantaneous value of a transition first
reaches a specified upper value and then a specified lower value
Note 1 to entry: The lower and upper values are fixed at 10 % and 90 % of the transition magnitude.
Note 2 to entry: This definition is derived from IEC 60050-161:1990, 161-02-05.
4 General
Electrical and electronic equipment can be affected by voltage dips, short interruptions or
voltage variations of the power supply.
Voltage dips and short interruptions occur due to faults in a (public or non-public) network or
in installations by sudden changes of large loads. In certain cases, two or more consecutive
dips or interruptions can occur. Voltage variations are caused by continuously varying loads
connected to the network.
These phenomena are random in nature and can be minimally characterized for the purpose
of laboratory simulation in terms of the deviation from the rated voltage and duration.
Consequently, different types of tests are specified in this document to simulate the effects of
abrupt voltage change. These tests are to be used only for particular and justified cases,
under the responsibility of product specification or product committees.
It is the responsibility of the product committees to establish which phenomena among the
ones considered in this document are relevant and to decide on the applicability of the test.
5 Test levels
5.1 General
The voltages in this document use the rated voltage for the equipment (U ) as a basis for the
T
voltage test level specification.
Where the equipment has a rated voltage range the following shall apply:
• if the voltage range does not exceed 20 % of the lower voltage specified for the rated
voltage range, a single voltage within that range may be specified as a basis for the test
level specification (U );
T
• in all other cases, the test procedure shall be applied for both the lowest and highest
voltages declared in the voltage range;
• guidance for the selection of test levels and durations is given in IEC TR 61000-2-8.
5.2 Voltage dips and short interruptions
The change between U and the changed voltage is abrupt. The step can start and stop
T
at any phase angle on the mains voltage. The following test voltage levels (in % U )
T
are used: 0 %, 40 %, 70 % and 80 %, corresponding to dips with residual voltages of 0 %,
40 %, 70 % and 80 %.
For voltage dips, the preferred test levels and durations are given in Table 1, and an example
is shown in Figure 1a) and Figure 1b).

– 10 – IEC 61000-4-11:2020 © IEC 2020
For short interruptions, the preferred test levels and durations are given in Table 2, and an
example is shown in Figure 2.
The rise and fall time are detailed in Figure 3.
The preferred test levels and durations given in Table 1 and Table 2 take into account the
information given in IEC TR 61000-2-8.
The preferred test levels in Table 1 are reasonably severe, and are representative of many
real world dips, but are not intended to guarantee immunity to all voltage dips. More severe
dips, for example 0 % for 1 s and balanced three-phase dips, may be considered by product
committees.
The generator specification for voltage rise time, t , and voltage fall time, t , during abrupt
r f
changes is indicated in Table 4.
The levels and durations shall be given in the product specification. A test level of 0 %
corresponds to a total supply voltage interruption. In practice, a test voltage level from 0 % to
20 % of the rated voltage may be considered as a total interruption.
Shorter durations in Table 1, in particular the half-cycle, should be tested to ensure that the
equipment under test (EUT) operates within the performance limits specified for it.
When setting performance criteria for disturbances of a half-period duration for products with
a mains transformer, product committees should pay particular attention to effects which can
result from inrush currents. For such products, these can reach 10 times to 40 times the rated
current because of the magnetic flux saturation of the transformer core after the voltage dip.
High inrush currents can also occur in products with capacitors (e.g. EMC filters, bridge
rectifiers connected to DC capacitors).
Table 1 – Preferred test levels and durations for voltage dips
a
Class Test levels and durations for voltage dips (t ) (50 Hz/60 Hz)
s
Class 1 Case-by-case according to the equipment requirements
c
Class 2 0 % during 0 % during 70 % during 25/30 cycles
½ cycle 1 cycle
Class 3 0 % during 0 % during 40 % during
70 % during 80 % during
c c c
½ cycle 1 cycle 10/12 cycles 25/30 cycles 250/300 cycles
b
Class X X X X X X
a
Classes as per IEC 61000-2-4; see Annex B.
b
To be defined by product committee. For equipment connected directly or indirectly to the public network, the
levels shall not be less severe than class 2.
c
"25/30 cycles" means "25 cycles for 50 Hz test" and "30 cycles for 60 Hz test".

IEC 61000-4-11:2020 © IEC 2020 – 11 –

Table 2 – Preferred test levels and durations for short interruptions
a
Class Test levels and durations for short interruptions (t ) (50 Hz/60 Hz)
s
Class 1 Case-by-case according to the equipment requirements
c
Class 2 0 % during 250/300 cycles
c
Class 3 0 % during 250/300 cycles
b
Class X X
a
Classes as per IEC 61000-2-4; see Annex B.
b
To be defined by product committee. For equipment connected directly or indirectly to the public network, the
levels shall not be less severe than class 2.
c
"250/300 cycles" means "250 cycles for 50 Hz test" and "300 cycles for 60 Hz test".

5.3 Voltage variations
This test considers a defined transition between the rated voltage U and the changed
T
voltage.
NOTE The voltage change takes place over a short period, and can occur due to a change of load.
The preferred duration of the voltage changes and the time for which the reduced voltages are
to be maintained are given in Table 3. The rate of change should be constant; however, the
voltage may be stepped. The steps should be positioned at zero crossings, and should be no
larger than 10 % of U . Steps under 1 % of U are considered as constant rates of change of
T T
voltage.
Table 3 – Timing of short-term supply voltage variations
Voltage test level Time for decreasing Time at reduced Time for increasing
voltage (t ) voltage(t ) voltage (t ) (50 Hz/60 Hz)
d s i
b
70 % Abrupt 1 cycle 25/30 cycles
a a a a
X X X X
a
To be defined by product committee.
b
"25/30 cycles" means "25 cycles for 50 Hz test" and "30 cycles for 60 Hz test".

This shape is the typical shape of a motor starting.

– 12 – IEC 61000-4-11:2020 © IEC 2020

NOTE The voltage decreases to 70 % for 25 periods. Step at zero crossing.
a) Voltage dip: 70 % voltage dip sine wave graph at 0°

Key
t fall time
f
t rise time
r
t duration of reduced voltage
s
b) Voltage dip: 40 % voltage dip sine wave graph at 90°
Figure 1 – Voltage dip – Examples

IEC 61000-4-11:2020 © IEC 2020 – 13 –

Key
t fall time
f
t rise time
r
t duration of reduced voltage
s
Figure 2 – Short interruption
Figure 3 – Detailed view of rise and fall time
Figure 4 shows the RMS voltage as a function of time. Other values may be taken in justified
cases and shall be specified by the product committee.

– 14 – IEC 61000-4-11:2020 © IEC 2020

Key
t Time for decreasing voltage
d
t Time for increasing voltage
i
t Time at reduced voltage
s
Figure 4 – Voltage variation
6 Test instrumentation
6.1 Test generator
6.1.1 General
The following features are common to the generator for voltage dips, short interruptions and
voltage variations, except as indicated.
Examples of generators are given in Annex C.
The generator shall have provisions to prevent the emission of heavy disturbances, which, if
injected in the power supply network, can influence the test results.
Any generator creating a voltage dip of equal or more severe characteristics (amplitude and
duration) than that specified by the present document is permitted.

IEC 61000-4-11:2020 © IEC 2020 – 15 –

6.1.2 Characteristics and performance of the generator
Table 4 – Generator specifications
Output voltage at no load As required in Table 1, ±5 % of residual voltage value
Voltage change with load at the output of the generator
100 % output, 0 A to 16 A less than 5 % of U
T
80 % output, 0 A to 20 A less than 5 % of U
T
70 % output, 0 A to 23 A less than 5 % of U
T
40 % output, 0 A to 40 A less than 5 % of U
T
Output current capability 16 A RMS per phase at rated voltage. The generator
shall be capable of carrying 20 A at 80 % of rated value
for a duration of 5 s. It shall be capable of carrying 23 A
at 70 % of rated voltage and 40 A at 40 % of rated
voltage for a duration of 3 s. (This requirement may be
reduced according to the EUT's rated steady-state
supply current, see Clause A.3.)
Peak inrush current capability (no requirement for Not to be limited by the generator. However, the
voltage variation tests) maximum peak capability of the generator need not
exceed 1 000 A for 250 V to 600 V mains, 500 A for
200 V to 240 V mains, or 250 A for 100 V to 120 V
mains.
Instantaneous peak overshoot/undershoot of the Less than 5 % of U
T
actual voltage, generator loaded with 100 Ω resistive
load
Voltage rise (and fall) time t (and t ), see Figures 1b)
Between 1 µs and 5 µs
r f
and 2, during abrupt change, generator loaded with
100 Ω resistive load
Phase shifting (if necessary) 0° to 360°
Phase relationship of voltage dips and interruptions Less than +10 °
with the power frequency
Zero crossing control of the generators ±10°

The output impedance shall be predominantly resistive.
The output impedance of the test voltage generator shall be low enough even during
transitions.
The 100 Ω resistive load used to test the generator should not have additional inductivity.
To test equipment which regenerates energy, an external resistor connected in parallel to the
load can be added. The test result should not be influenced by this load.
6.1.3 Verification of the characteristics of the voltage dips, short interruptions
generators
In order to compare the test results obtained from different test generators, the generator
characteristics shall be verified according to the following:
• the 100 %, 80 %, 70 % and 40 % RMS output voltages of the generator shall conform to
the percentages of the selected operating voltage: 230 V, 120 V, etc.;
• the 100 %, 80 %, 70 % and 40 % RMS output voltages of the generator shall be measured
at no load, and shall be maintained within a specified percentage of the U ;
T
• load regulation shall be verified at nominal load current at each of the output voltages and
the variation shall not exceed 5 % of the nominal power supply voltage at 100 %, 80 %,
70 % and 40 % of the nominal power supply voltage.

– 16 – IEC 61000-4-11:2020 © IEC 2020
For output voltage of 80 % of the nominal value, the above requirements need only be verified
for a maximum of 5 s duration.
For output voltages of 70 % and 40 % of the nominal value, the above requirements need only
be verified for a maximum of 3 s duration.
For output voltages of 40% of the nominal value it is acceptable to verify the load regulation
requirements either at 200 V to 240 V nominal voltage or at 100 V to 120 V nominal voltage.
If it is necessary to verify the peak inrush drive current capability, the generator shall be
switched from 0 % to 100 % of full output, when driving a load consisting of a suitable rectifier
with an uncharged capacitor whose value is 1 700 µF on the DC side. The test shall be
carried out at phase angles of both 90° and 270°. The circuit required to measure the
generator inrush current drive capability is given in Figure A.1.
When it is believed that a generator with less than the specified standard generator peak
inrush current can be used because the EUT can draw less than the specified standard
generator peak inrush current (e.g., 500 A for 220 V to 240 V mains), this shall first be
confirmed by measuring the EUT peak inrush current. When power is applied from the test
generator, the measured EUT peak inrush current shall be less than 70 % of the peak current
drive capability of the generator, as already verified according to Annex A. The actual EUT
inrush current shall be measured both from a cold start and after a 5 s turn-off, using the
procedure of Clause A.3.
Generator switching characteristics shall be measured with a 100 Ω load of suitable power-
dissipation rating.
The 100 Ω resistive load used to test the generator should not have additional inductivity.
Rise and fall time, as well as overshoot and undershoot, shall be verified for switching at both
90° and 270°, from 0 % to 100 %, 100 % to 80 %, 100 % to 70 %, 100 % to 40 %, and 100 %
to 0 %.
Phase angle accuracy shall be verified for switching from 0 % to 100 % and 100 % to 0 %,
at nine phase angles from 0° to 360° in 45° increments. It shall also be verified for switching
from 100 % to 80 % and 80 % to 100 %, 100 % to 70 % and 70 % to 100 %, as well as from
100 % to 40 % and 40 % to 100 %, at 90° and 180°.
The voltage generators shall, preferably, be recalibrated at defined time periods in
accordance with a recognized quality assurance system.
Annex D provides the rationale for generator specification regarding the voltage rise and fall
time and the inrush current capability.
6.2 Power source
The frequency of the test voltage shall be within ±2 % of rated frequency.
7 Test set-up
The test shall be performed with the EUT connected to the test generator with the shortest
power supply cable as specified by the EUT manufacturer. If no cable length is specified, it
shall be the shortest possible length suitable to the application of the EUT.
The test set-ups for the three types of phenomena described in this document are:
• voltage dips;
IEC 61000-4-11:2020 © IEC 2020 – 17 –

• short interruptions;
• voltage variations with gradual transition between the rated voltage and the changed
voltage (option).
Examples of test set-ups are given in Annex C.
Figure C.1a) shows a schematic for the generation of voltage dips, short interruptions and
voltage variations with gradual transition between rated and changed voltage using a
generator with internal switching. In Figure C.1b) a generator and a power amplifier are used.
Figure C.2 shows a schematic for the generation of voltage dips, short interruptions and
voltage variations using a generator and a power amplifier for three-phase equipment.
8 Test procedures
8.1 General
Before starting the test of a given EUT, a test plan shall be prepared.
The test plan should be representative of the way the system is actually used.
Systems can require a precise pre-analysis to define which system configurations shall be
tested to reproduce field situations.
Test cases shall be explained and indicated in the test report.
It is recommended that the test plan include the following items:
• the type designation of the EUT;
• information on possible connections (plugs, terminals, etc.) and corresponding cables, and
peripherals;
• input power port of equipment to be tested;
• representative operational modes of the EUT for the test;
• performance criteria used and defined in the technical specifications;
• operational mode(s) of equipment;
• description of the test set-up.
If the actual operating signal sources are not available to the EUT, they can be simulated.
For each test, any degradation of performance shall be recorded. The monitoring equipment
should be capable of displaying the status of the operational mode of the EUT during and
after the tests. After each group of tests, a full functional check shall be performed.
8.2 Laboratory reference conditions
8.2.1 Climatic conditions
Unless otherwise specified by the committee responsible for the generic or product standard,
the climatic conditions in the laboratory shall be within any limits specified for the operation of
the EUT and the test equipment by their respective manufacturers.
Tests shall not be performed if the relative humidity is so high as to cause condensation on
the EUT or the test equipment.

– 18 – IEC 61000-4-11:2020 © IEC 2020
NOTE Whe
...


SLOVENSKI STANDARD
01-maj-2020
Nadomešča:
SIST EN 61000-4-11:2005
SIST EN 61000-4-11:2005/A1:2017
Elektromagnetna združljivost (EMC) - 4-11. del: Preskusne in merilne tehnike -
Preskusi odpornosti proti upadom napetosti, kratkotrajnim prekinitvam in
odklonom napetosti za opremo z vhodnim tokom do 16 A na fazo
Electromagnetic compatibility (EMC) - Part 4-11: Testing and measurement techniques -
Voltage dips, short interruptions and voltage variations immunity tests for equipment with
input current up to 16 A per phase
Elektromagnetische Verträglichkeit (EMV) - Teil 4-11: Prüf- und Messverfahren -
Prüfungen der Störfestigkeit gegen Spannungseinbrüche, Kurzzeitunterbrechungen und
Spannungsschwankungen für Geräte mit einem Eingangsstrom bis zu und einschließlich
16 A je Leiter
Compatibilité électromagnétique (CEM) - Partie 4-11: Techniques d'essai et de mesure -
Essais d'immunité aux creux de tension, coupures brèves et variations de tension pour
les appareils à courant d’entrée inférieur ou égal à 16 A par phase
Ta slovenski standard je istoveten z: EN IEC 61000-4-11:2020
ICS:
33.100.20 Imunost Immunity
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EUROPEAN STANDARD EN IEC 61000-4-11

NORME EUROPÉENNE
EUROPÄISCHE NORM
March 2020
ICS 33.100.20 Supersedes EN 61000-4-11:2004 and all of its
amendments and corrigenda (if any)
English Version
Electromagnetic compatibility (EMC) - Part 4-11: Testing and
measurement techniques - Voltage dips, short interruptions and
voltage variations immunity tests for equipment with input current
up to 16 A per phase
(IEC 61000-4-11:2020)
Compatibilité électromagnétique (CEM) - Partie 4-11: Elektromagnetische Verträglichkeit (EMV) - Teil 4-11: Prüf-
Techniques d'essai et de mesure - Essais d'immunité aux und Messverfahren - Prüfungen der Störfestigkeit gegen
creux de tension, coupures brèves et variations de tension Spannungseinbrüche, Kurzzeitunterbrechungen und
pour les appareils à courant d'entrée inférieur ou égal à 16 Spannungsschwankungen für Geräte mit einem
A par phase Eingangsstrom bis zu und einschließlich 16 A je Leiter
(IEC 61000-4-11:2020) (IEC 61000-4-11:2020)
This European Standard was approved by CENELEC on 2020-03-03. CENELEC members are bound to comply with the CEN/CENELEC
Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the
same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the
Netherlands, Norway, Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom.

European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2020 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Ref. No. EN IEC 61000-4-11:2020 E

European foreword
The text of document 77A/1039/FDIS, future edition 3 of IEC 61000-4-11, prepared by SC 77A "EMC -
Low frequency phenomena" of IEC/TC 77 "Electromagnetic compatibility" was submitted to the IEC-
CENELEC parallel vote and approved by CENELEC as EN IEC 61000-4-11:2020.
The following dates are fixed:
• latest date by which the document has to be implemented at national (dop) 2020-12-03
level by publication of an identical national standard or by endorsement
• latest date by which the national standards conflicting with the (dow) 2023-03-03
document have to be withdrawn
This document supersedes EN 61000-4-11:2004 and all of its amendments and corrigenda (if any).
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC shall not be held responsible for identifying any or all such patent rights.
This document has been prepared under a mandate given to CENELEC by the European Commission
and the European Free Trade Association.

Endorsement notice
The text of the International Standard IEC 61000-4-11:2020 was approved by CENELEC as a
European Standard without any modification.
In the official version, for Bibliography, the following notes have to be added for the standards
indicated:
IEC 61000-2 (series) NOTE Harmonized as EN 61000-2 (series)
IEC 61000-2-4 NOTE Harmonized as EN 61000-2-4
IEC 61000-4-11:2004 NOTE Harmonized as EN 61000-4-11:2004 (not modified)
IEC 61000-4-14 NOTE Harmonized as EN 61000-4-14

Annex ZA
(normative)
Normative references to international publications
with their corresponding European publications
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments)
applies.
NOTE 1  Where an International Publication has been modified by common modifications, indicated by (mod), the relevant
EN/HD applies.
NOTE 2  Up-to-date information on the latest versions of the European Standards listed in this annex is available here:
www.cenelec.eu.
Publication Year Title EN/HD Year
IEC TR 61000-2-8 - Electromagnetic compatibility (EMC) − Part 2-8: - -
Environment – Voltage dips and short interruptions
on public electric power supply systems with
statistical measurement results

IEC 61000-4-11 ®
Edition 3.0 2020-01
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
colour
inside
BASIC EMC PUBLICATION
PUBLICATION FONDAMENTALE EN CEM

Electromagnetic compatibility (EMC) –

Part 4-11: Testing and measurement techniques – Voltage dips, short

interruptions and voltage variations immunity tests for equipment with input

current up to 16 A per phase
Compatibilité électromagnétique (CEM) –

Partie 4-11: Techniques d'essai et de mesure – Essais d'immunité aux creux

de tension, coupures brèves et variations de tension pour les appareils

à courant d’entrée inférieur ou égal à 16 A par phase

INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE
ICS 33.100.20 ISBN 978-2-8322-7546-7

– 2 – IEC 61000-4-11:2020 © IEC 2020
CONTENTS
FOREWORD . 4
INTRODUCTION . 6
1 Scope . 7
2 Normative references . 7
3 Terms and definitions . 7
4 General . 9
5 Test levels . 9
5.1 General . 9
5.2 Voltage dips and short interruptions . 9
5.3 Voltage variations . 11
6 Test instrumentation . 14
6.1 Test generator . 14
6.1.1 General. 14
6.1.2 Characteristics and performance of the generator . 15
6.1.3 Verification of the characteristics of the voltage dips, short
interruptions generators . 15
6.2 Power source . 16
7 Test set-up . 16
8 Test procedures . 17
8.1 General . 17
8.2 Laboratory reference conditions . 17
8.2.1 Climatic conditions . 17
8.2.2 Electromagnetic conditions . 18
8.3 Execution of the test . 18
8.3.1 General. 18
8.3.2 Voltage dips and short interruptions . 18
8.3.3 Voltage variations . 19
9 Evaluation of test results . 19
10 Test report . 20
Annex A (normative) Test circuit details . 21
A.1 Test generator peak inrush current drive capability . 21
A.2 Current monitor's characteristics for measuring peak inrush current
capability . 21
A.3 EUT peak inrush current requirement . 21
Annex B (informative) Electromagnetic environment classes . 23
Annex C (informative) Test instrumentation. 24
Annex D (informative) Rationale for generator specification regarding voltage, rise-
time and fall-time, and inrush current capability . 27
D.1 Concept of basic standard . 27
D.2 IEC 61000-4-11:1994 (first edition) . 27
D.3 Rationale for the need of rapid fall-times . 27
D.4 Interpretation of the rise-time and fall-time requirements during EUT testing . 28
D.5 Main conclusions . 28
D.6 Rationale for inrush current capability . 28
Bibliography . 30

IEC 61000-4-11:2020 © IEC 2020 – 3 –

Figure 1 – Voltage dip – Examples . 12
Figure 2 – Short interruption . 13
Figure 3 – Detailed view of rise and fall time . 13
Figure 4 – Voltage variation . 14
Figure 5 – Phase-to-neutral and phase-to-phase testing on three-phase systems . 19
Figure A.1 – Circuit for determining the inrush current drive capability of the short
interruptions generator . 22
Figure A.2 – Circuit for determining the peak inrush current requirement of an EUT . 22
Figure C.1 – Schematics of test instrumentation for voltage dips, short interruptions

and voltage variations . 25
Figure C.2 – Schematic of test instrumentation for three-phase voltage dips, short
interruptions and voltage variations using a power amplifier . 26

Table 1 – Preferred test levels and durations for voltage dips . 10
Table 2 – Preferred test levels and durations for short interruptions . 11
Table 3 – Timing of short-term supply voltage variations . 11
Table 4 – Generator specifications . 15

– 4 – IEC 61000-4-11:2020 © IEC 2020
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
ELECTROMAGNETIC COMPATIBILITY (EMC) –

Part 4-11: Testing and measurement techniques –
Voltage dips, short interruptions and voltage variations immunity
tests for equipment with input current up to 16 A per phase

FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 61000-4-11 has been prepared by subcommittee 77A: EMC – Low
frequency phenomena, of IEC technical committee 77: Electromagnetic compatibility.
It forms Part 4-11 of IEC 61000. It has the status of a basic EMC publication in accordance
with IEC Guide 107.
This third edition cancels and replaces the second edition published in 2004 and
Amendment 1:2017. This edition constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous
edition:
a) rise time and fall time of transients are now defined terms in Clause 3;
b) the origin of voltage dips and short interruptions is now stated in Clause 4.

IEC 61000-4-11:2020 © IEC 2020 – 5 –

The text of this International Standard is based on the following documents:
FDIS Report on voting
77A/1039/FDIS 77A/1056/RVD
Full information on the voting for the approval of this International Standard can be found in
the report on voting indicated in the above table.
This document has been drafted in accordance with the ISO/IEC Directives, Part 2.
A list of all parts in the IEC 61000 series, published under the general title Electromagnetic
compatibility (EMC), can be found on the IEC website.
The committee has decided that the contents of this document will remain unchanged until the
stability date indicated on the IEC website under "http://webstore.iec.ch" in the data related to
the specific document. At this date, the document will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
IMPORTANT – The 'colour inside' logo on the cover page of this publication indicates
that it contains colours which are considered to be useful for the correct
understanding of its contents. Users should therefore print this document using a
colour printer.
– 6 – IEC 61000-4-11:2020 © IEC 2020
INTRODUCTION
IEC 61000 is published in separate parts according to the following structure:
Part 1: General
General considerations (introduction, fundamental principles)
Definitions, terminology
Part 2: Environment
Description of the environment
Classification of the environment
Compatibility levels
Part 3: Limits
Emission limits
Immunity limits (in so far as they do not fall under the responsibility of the product
committees)
Part 4: Testing and measurement techniques
Measurement techniques
Testing techniques
Part 5: Installation and mitigation guidelines
Installation guidelines
Mitigation methods and devices
Part 6: Generic standards
Part 9: Miscellaneous
Each part is further subdivided into several parts, published either as International Standards
or as technical specifications or technical reports, some of which have already been published
as sections. Others will be published with the part number followed by a dash and a second
number identifying the subdivision (example: IEC 61000-6-1).

IEC 61000-4-11:2020 © IEC 2020 – 7 –

ELECTROMAGNETIC COMPATIBILITY (EMC) –

Part 4-11: Testing and measurement techniques –
Voltage dips, short interruptions and voltage variations immunity
tests for equipment with input current up to 16 A per phase

1 Scope
This part of IEC 61000 defines the immunity test methods and range of preferred test levels
for electrical and electronic equipment connected to low-voltage power supply networks for
voltage dips, short interruptions, and voltage variations.
This document applies to electrical and electronic equipment having a rated input current not
exceeding 16 A per phase, for connection to 50 Hz or 60 Hz AC networks.
It does not apply to electrical and electronic equipment for connection to 400 Hz AC networks.
Tests for these networks will be covered by future IEC documents.
The object of this document is to establish a common reference for evaluating the immunity of
electrical and electronic equipment when subjected to voltage dips, short interruptions and
voltage variations.
NOTE 1 Voltage fluctuation immunity tests are covered by IEC 61000-4-14.
The test method documented in this document describes a consistent method to assess the
immunity of equipment or a system against a defined phenomenon.
NOTE 2 As described in IEC Guide 107, this is a basic EMC publication for use by product committees of the
IEC. As also stated in Guide 107, the IEC product committees are responsible for determining whether this
immunity test standard should be applied or not, and, if applied, they are responsible for defining the appropriate
test levels. Technical committee 77 and its sub-committees are prepared to co-operate with product committees in
the evaluation of the value of particular immunity tests for their products.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their
content constitutes requirements of this document. For dated references, only the edition
cited applies. For undated references, the latest edition of the referenced document (including
any amendments) applies.
IEC TR 61000-2-8, Electromagnetic compatibility (EMC) − Part 2-8: Environment − Voltage
dips and short interruptions on public electric power supply systems with statistical
measurement results
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
ISO and IEC maintain terminological databases for use in standardization at the following
addresses:
• IEC Electropedia: available at http://www.electropedia.org/
• ISO Online browsing platform: available at http://www.iso.org/obp

– 8 – IEC 61000-4-11:2020 © IEC 2020
3.1
immunity (to a disturbance)
ability of a device, equipment or system to perform without degradation in the presence of an
electromagnetic disturbance
[SOURCE: IEC 60050-161:1990, 161-01-20]
3.2
voltage dip
sudden reduction of the voltage at a particular point of an electricity supply system below a
specified dip threshold followed by its recovery after a brief interval
Note 1 to entry: Typically, a dip is associated with the occurrence and termination of a short circuit or other
extreme current increase on the system or installations connected to it.
Note 2 to entry: A voltage dip is a two-dimensional electromagnetic disturbance, the level of which is determined
by both voltage and time (duration).
3.3
short interruption
sudden reduction of the voltage on all phases at a particular point of an electric supply system
below a specified interruption threshold followed by its restoration after a brief interval
Note 1 to entry: Short interruptions are typically associated with switchgear operations related to the occurrence
and termination of short circuits on the system or on installations connected to it.
3.4
residual voltage
minimum value of RMS voltage recorded during a voltage dip or short
interruption
Note 1 to entry: The residual voltage can be expressed as a value in volts or as a percentage or per unit value
relative to the reference voltage.
3.5
malfunction
breakdown of the ability of equipment to carry out intended functions or the execution of
unintended functions by the equipment
3.6
calibration
method to prove that the measurement equipment is in compliance with its specifications
Note 1 to entry: For the purposes of this document, calibration is applied to the test generator.
3.7
verification
set of operations which are used to check the test equipment system (e.g. the test generator
and the interconnecting cables) to demonstrate that the test system is functioning within the
specifications given in Clause 6
Note 1 to entry: The methods used for verification can be different from those used for calibration.
Note 2 to entry: The verification procedure of 6.1.3 is meant as a guide to ensure the correct operation of the test
generator and other items making up the test set-up so that the intended waveform is delivered to the EUT.
3.8
rise time
interval of time between the instants at which the instantaneous value of a transition first
reaches a specified lower value and then a specified upper value
Note 1 to entry: The lower and upper values are fixed at 10 % and 90 % of the transition magnitude.

IEC 61000-4-11:2020 © IEC 2020 – 9 –

[SOURCE: IEC 60050-161:1990, 161-02-05]
3.9
fall time
interval of time between the instants at which the instantaneous value of a transition first
reaches a specified upper value and then a specified lower value
Note 1 to entry: The lower and upper values are fixed at 10 % and 90 % of the transition magnitude.
Note 2 to entry: This definition is derived from IEC 60050-161:1990, 161-02-05.
4 General
Electrical and electronic equipment can be affected by voltage dips, short interruptions or
voltage variations of the power supply.
Voltage dips and short interruptions occur due to faults in a (public or non-public) network or
in installations by sudden changes of large loads. In certain cases, two or more consecutive
dips or interruptions can occur. Voltage variations are caused by continuously varying loads
connected to the network.
These phenomena are random in nature and can be minimally characterized for the purpose
of laboratory simulation in terms of the deviation from the rated voltage and duration.
Consequently, different types of tests are specified in this document to simulate the effects of
abrupt voltage change. These tests are to be used only for particular and justified cases,
under the responsibility of product specification or product committees.
It is the responsibility of the product committees to establish which phenomena among the
ones considered in this document are relevant and to decide on the applicability of the test.
5 Test levels
5.1 General
The voltages in this document use the rated voltage for the equipment (U ) as a basis for the
T
voltage test level specification.
Where the equipment has a rated voltage range the following shall apply:
• if the voltage range does not exceed 20 % of the lower voltage specified for the rated
voltage range, a single voltage within that range may be specified as a basis for the test
level specification (U );
T
• in all other cases, the test procedure shall be applied for both the lowest and highest
voltages declared in the voltage range;
• guidance for the selection of test levels and durations is given in IEC TR 61000-2-8.
5.2 Voltage dips and short interruptions
The change between U and the changed voltage is abrupt. The step can start and stop
T
at any phase angle on the mains voltage. The following test voltage levels (in % U )
T
are used: 0 %, 40 %, 70 % and 80 %, corresponding to dips with residual voltages of 0 %,
40 %, 70 % and 80 %.
For voltage dips, the preferred test levels and durations are given in Table 1, and an example
is shown in Figure 1a) and Figure 1b).

– 10 – IEC 61000-4-11:2020 © IEC 2020
For short interruptions, the preferred test levels and durations are given in Table 2, and an
example is shown in Figure 2.
The rise and fall time are detailed in Figure 3.
The preferred test levels and durations given in Table 1 and Table 2 take into account the
information given in IEC TR 61000-2-8.
The preferred test levels in Table 1 are reasonably severe, and are representative of many
real world dips, but are not intended to guarantee immunity to all voltage dips. More severe
dips, for example 0 % for 1 s and balanced three-phase dips, may be considered by product
committees.
The generator specification for voltage rise time, t , and voltage fall time, t , during abrupt
r f
changes is indicated in Table 4.
The levels and durations shall be given in the product specification. A test level of 0 %
corresponds to a total supply voltage interruption. In practice, a test voltage level from 0 % to
20 % of the rated voltage may be considered as a total interruption.
Shorter durations in Table 1, in particular the half-cycle, should be tested to ensure that the
equipment under test (EUT) operates within the performance limits specified for it.
When setting performance criteria for disturbances of a half-period duration for products with
a mains transformer, product committees should pay particular attention to effects which can
result from inrush currents. For such products, these can reach 10 times to 40 times the rated
current because of the magnetic flux saturation of the transformer core after the voltage dip.
High inrush currents can also occur in products with capacitors (e.g. EMC filters, bridge
rectifiers connected to DC capacitors).
Table 1 – Preferred test levels and durations for voltage dips
a
Class Test levels and durations for voltage dips (t ) (50 Hz/60 Hz)
s
Class 1 Case-by-case according to the equipment requirements
c
Class 2 0 % during 0 % during 70 % during 25/30 cycles
½ cycle 1 cycle
Class 3 0 % during 0 % during 40 % during
70 % during 80 % during
c c c
½ cycle 1 cycle 10/12 cycles 25/30 cycles 250/300 cycles
b
Class X X X X X X
a
Classes as per IEC 61000-2-4; see Annex B.
b
To be defined by product committee. For equipment connected directly or indirectly to the public network, the
levels shall not be less severe than class 2.
c
"25/30 cycles" means "25 cycles for 50 Hz test" and "30 cycles for 60 Hz test".

IEC 61000-4-11:2020 © IEC 2020 – 11 –

Table 2 – Preferred test levels and durations for short interruptions
a
Class Test levels and durations for short interruptions (t ) (50 Hz/60 Hz)
s
Class 1 Case-by-case according to the equipment requirements
c
Class 2 0 % during 250/300 cycles
c
Class 3 0 % during 250/300 cycles
b
Class X X
a
Classes as per IEC 61000-2-4; see Annex B.
b
To be defined by product committee. For equipment connected directly or indirectly to the public network, the
levels shall not be less severe than class 2.
c
"250/300 cycles" means "250 cycles for 50 Hz test" and "300 cycles for 60 Hz test".

5.3 Voltage variations
This test considers a defined transition between the rated voltage U and the changed
T
voltage.
NOTE The voltage change takes place over a short period, and can occur due to a change of load.
The preferred duration of the voltage changes and the time for which the reduced voltages are
to be maintained are given in Table 3. The rate of change should be constant; however, the
voltage may be stepped. The steps should be positioned at zero crossings, and should be no
larger than 10 % of U . Steps under 1 % of U are considered as constant rates of change of
T T
voltage.
Table 3 – Timing of short-term supply voltage variations
Voltage test level Time for decreasing Time at reduced Time for increasing
voltage (t ) voltage(t ) voltage (t ) (50 Hz/60 Hz)
d s i
b
70 % Abrupt 1 cycle 25/30 cycles
a a a a
X X X X
a
To be defined by product committee.
b
"25/30 cycles" means "25 cycles for 50 Hz test" and "30 cycles for 60 Hz test".

This shape is the typical shape of a motor starting.

– 12 – IEC 61000-4-11:2020 © IEC 2020

NOTE The voltage decreases to 70 % for 25 periods. Step at zero crossing.
a) Voltage dip: 70 % voltage dip sine wave graph at 0°

Key
t fall time
f
t rise time
r
t duration of reduced voltage
s
b) Voltage dip: 40 % voltage dip sine wave graph at 90°
Figure 1 – Voltage dip – Examples

IEC 61000-4-11:2020 © IEC 2020 – 13 –

Key
t fall time
f
t rise time
r
t duration of reduced voltage
s
Figure 2 – Short interruption
Figure 3 – Detailed view of rise and fall time
Figure 4 shows the RMS voltage as a function of time. Other values may be taken in justified
cases and shall be specified by the product committee.

– 14 – IEC 61000-4-11:2020 © IEC 2020

Key
t Time for decreasing voltage
d
t Time for increasing voltage
i
t Time at reduced voltage
s
Figure 4 – Voltage variation
6 Test instrumentation
6.1 Test generator
6.1.1 General
The following features are common to the generator for voltage dips, short interruptions and
voltage variations, except as indicated.
Examples of generators are given in Annex C.
The generator shall have provisions to prevent the emission of heavy disturbances, which, if
injected in the power supply network, can influence the test results.
Any generator creating a voltage dip of equal or more severe characteristics (amplitude and
duration) than that specified by the present document is permitted.

IEC 61000-4-11:2020 © IEC 2020 – 15 –

6.1.2 Characteristics and performance of the generator
Table 4 – Generator specifications
Output voltage at no load As required in Table 1, ±5 % of residual voltage value
Voltage change with load at the output of the generator
100 % output, 0 A to 16 A less than 5 % of U
T
80 % output, 0 A to 20 A less than 5 % of U
T
70 % output, 0 A to 23 A less than 5 % of U
T
40 % output, 0 A to 40 A less than 5 % of U
T
Output current capability 16 A RMS per phase at rated voltage. The generator
shall be capable of carrying 20 A at 80 % of rated value
for a duration of 5 s. It shall be capable of carrying 23 A
at 70 % of rated voltage and 40 A at 40 % of rated
voltage for a duration of 3 s. (This requirement may be
reduced according to the EUT's rated steady-state
supply current, see Clause A.3.)
Peak inrush current capability (no requirement for Not to be limited by the generator. However, the
voltage variation tests) maximum peak capability of the generator need not
exceed 1 000 A for 250 V to 600 V mains, 500 A for
200 V to 240 V mains, or 250 A for 100 V to 120 V
mains.
Instantaneous peak overshoot/undershoot of the Less than 5 % of U
T
actual voltage, generator loaded with 100 Ω resistive
load
Voltage rise (and fall) time t (and t ), see Figures 1b)
Between 1 µs and 5 µs
r f
and 2, during abrupt change, generator loaded with
100 Ω resistive load
Phase shifting (if necessary) 0° to 360°
Phase relationship of voltage dips and interruptions Less than +10 °
with the power frequency
Zero crossing control of the generators ±10°

The output impedance shall be predominantly resistive.
The output impedance of the test voltage generator shall be low enough even during
transitions.
The 100 Ω resistive load used to test the generator should not have additional inductivity.
To test equipment which regenerates energy, an external resistor connected in parallel to the
load can be added. The test result should not be influenced by this load.
6.1.3 Verification of the characteristics of the voltage dips, short interruptions
generators
In order to compare the test results obtained from different test generators, the generator
characteristics shall be verified according to the following:
• the 100 %, 80 %, 70 % and 40 % RMS output voltages of the generator shall conform to
the percentages of the selected operating voltage: 230 V, 120 V, etc.;
• the 100 %, 80 %, 70 % and 40 % RMS output voltages of the generator shall be measured
at no load, and shall be maintained within a specified percentage of the U ;
T
• load regulation shall be verified at nominal load current at each of the output voltages and
the variation shall not exceed 5 % of the nominal power supply voltage at 100 %, 80 %,
70 % and 40 % of the nominal power supply voltage.

– 16 – IEC 61000-4-11:2020 © IEC 2020
For output voltage of 80 % of the nominal value, the above requirements need only be verified
for a maximum of 5 s duration.
For output voltages of 70 % and 40 % of the nominal value, the above requirements need only
be verified for a maximum of 3 s duration.
For output voltages of 40% of the nominal value it is acceptable to verify the load regulation
requirements either at 200 V to 240 V nominal voltage or at 100 V to 120 V nominal voltage.
If it is necessary to verify the peak inrush drive current capability, the generator shall be
switched from 0 % to 100 % of full output, when driving a load consisting of a suitable rectifier
with an uncharged capacitor whose value is 1 700 µF on the DC side. The test shall be
carried out at phase angles of both 90° and 270°. The circuit required to measure the
generator inrush current drive capability is given in Figure A.1.
When it is believed that a generator with less than the specified standard generator peak
inrush current can be used because the EUT can draw less than the specified standard
generator peak inrush current (e.g., 500 A for 220 V to 240 V mains), this shall first be
confirmed by measuring the EUT peak inrush current. When power is applied from the test
generator, the measured EUT peak inrush current shall be less than 70 % of the peak current
drive capability of the generator, as already verified according to Annex A. The actual EUT
inrush current shall be measured both from a cold start and after a 5 s turn-off, using the
procedure of Clause A.3.
Generator switching characteristics shall be measured with a 100 Ω load of suitable power-
dissipation rating.
The 100 Ω resistive load used to test the generator should not have additional inductivity.
Rise and fall time, as well as overshoot and undershoot, shall be verified for switching at both
90° and 270°, from 0 % to 100 %, 100 % to 80 %, 100 % to 70 %, 100 % to 40 %, and 100 %
to 0 %.
Phase angle accuracy shall be verified for switching from 0 % to 100 % and 100 % to 0 %,
at nine phase angles from 0° to 360° in 45° increments. It shall also be verified for switching
from 100 % to 80 % and 80 % to 100 %, 100 % to 70 % and 70 % to 100 %, as well as from
100 % to 40 % and 40 % to 100 %, at 90° and 180°.
The voltage generators shall, preferably, be recalibrated at defined time periods in
accordance with a recognized quality assurance system.
Annex D provides the rationale for generator specification regarding the voltage rise and fall
time and the inrush current capability.
6.2 Power source
The frequency of the test voltage shall be within ±2 % of rated frequency.
7 Test set-up
The test shall be performed with the EUT connected to the test generator with the shortest
power supply cable as specified by the EUT manufacturer. If no cable length is specified, it
shall be the shortest possible length suitable to the application of the EUT.
The test set-ups for the three types of phenomena described in this document are:
• voltage dips;
IEC 61000-4-11:2020 © IEC 2020 – 17 –

• short interruptions;
• voltage variations with gradual transition between the rated voltage and the changed
voltage (option).
Examples of test set-ups are given in Annex C.
Figure C.1a) shows a schematic for the generation of voltage dips, short interruptions and
voltage variations with gradual transition between rated and changed voltage using a
generator with internal switching. In Figure C.1b) a generator and a power amplifier are used.
Figure C.2 shows a schematic for the generation of voltage dips, short interruptions and
voltage variations using a generator and a power amplifier for three-phase equipment.
8 Test procedures
8.1 General
Before starting the test of a given EUT, a test plan shall be prepared.
The test plan should be representative of the way the system is actually used.
Systems can require a precise pre-analysis to define which system configurations shall be
tested to reproduce field situations.
Test cases shall be explained and indicated in the test report.
It is recommended that the test plan include the following items:
• the type designation of the EUT;
• information on possible connections (plugs, terminals, etc.) and corresponding cables, and
peripherals;
• input power port of equipment to be tested;
• representative operational modes of the EUT for the test;
• performance criteria used and defined in the technical specifications;
• operational mode(s) of equipment;
• description of the test set-up.
If the actual operating signal sources are not available to the EUT, they can be simulated.
For each test, any degradation of performance shall be recorded. The monitoring equipment
should be capable of displaying the status of the operational mode of the EUT during and
after the tests. After each group of tests, a full functional check shall be performed.
8.2 Laboratory reference conditions
8.2.1 Climatic conditions
Unless otherwise specified by the committee responsible for the generic or product standard,
the climatic conditions in the laboratory shall be within any limits specified for the operation of
the EUT and the test equipment by their respective manufacturers.
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.

Loading comments...