Rotating electrical machines - Part 18-42: Partial discharge resistant electrical insulation systems (Type II) used in rotating electrical machines fed from voltage converters - Qualification tests

IEC/TS 60034-18-42:2008 defines criteria for assessing the insulation system of stator/rotor windings of single or polyphase AC machines which are subjected to repetitive impulse voltages, such as pulse width modulation converters, and expected to withstand partial discharge activity during service. It specifies electrical qualification and acceptance tests on representative samples which verify fitness for operation with voltage-source converters.

Drehende elektrische Maschinen - Teil 18-42: Teilentladungsresistente Isoliersysteme (Typ II) von drehenden elektrischen Maschinen, die von Spannungsumrichtern gespeist werden - Qualifizierungsprüfungen

Machines électriques tournantes - Partie 18-42: Systèmes d'isolation électrique résistants aux décharges partielles (Type II) utilisés dans des machines électriques tournantes alimentées par convertisseurs de tension - Essais de qualification

La CEI/TS 60034-18-42:2008 définit les critères d'évaluation du système d'isolation des enroulements statorique et rotorique des machines à courant alternatif monophasées ou polyphasées qui sont soumises à des tensions de choc répétitives, comme par exemple les convertisseurs à modulation de largeur d'impulsion, et susceptibles d'endurer des décharges partielles pendant leur fonctionnement. Elle spécifie des essais de qualification électrique et d'acceptation réalisés sur des échantillons représentatifs, en vue de vérifier leur adéquation à un fonctionnement avec des convertisseurs de source de tension.

Električni rotacijski stroji - 18-42. del: Električni izolacijski sistemi, odporni proti delni razelektritvi (tip II), ki se uporabljajo v električnih rotacijskih strojih, napajanih prek napetostnih pretvornikov - Preskusi zahtevanih pogojev (IEC 60034-18-42:2017)

Standard IEC/TS 60034-18-42:2008 določa merila za ocenjevanje izolacijskega sistema navitja statorja/rotorja enofaznih ali večfaznih strojev na izmenični tok, ki so izpostavljeni ponavljajočim se impulznim napetostim, kot so pretvorniki s pulzno-širinsko modulacijo, in ki med obratovanjem predvidoma prenesejo delno izpraznitev. Določa električno kvalifikacijo in preskuse sprejemljivosti pri reprezentativnih vzorcih, s čimer se preveri primernost stroja za delovanje z napetostnimi pretvorniki.

General Information

Status
Published
Publication Date
08-Jun-2017
Withdrawal Date
13-Mar-2020
Technical Committee
Drafting Committee
Current Stage
6060 - Document made available - Publishing
Start Date
09-Jun-2017
Completion Date
09-Jun-2017

Relations

Standard
EN 60034-18-42:2018
English language
47 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-januar-2018
1DGRPHãþD
SIST-TS CLC/TS 60034-18-42:2011
(OHNWULþQLURWDFLMVNLVWURMLGHO(OHNWULþQLL]RODFLMVNLVLVWHPLRGSRUQLSURWL
GHOQLUD]HOHNWULWYL WLS,, NLVHXSRUDEOMDMRYHOHNWULþQLKURWDFLMVNLKVWURMLK
QDSDMDQLKSUHNQDSHWRVWQLKSUHWYRUQLNRY3UHVNXVL]DKWHYDQLKSRJRMHY ,(&

Rotating electrical machines - Part 18-42: Partial discharge resistant electrical insulation
systems (Type II) used in rotating electrical machines fed from voltage converters -
Qualification tests (IEC 60034-18-42:2017)
Drehende elektrische Maschinen - Teil 18-42: Teilentladungsresistente Isoliersysteme
(Typ II) von drehenden elektrischen Maschinen, die von Spannungsumrichtern gespeist
werden - Qualifizierungsprüfungen (IEC 60034-18-42:2017)
Machines électriques tournantes - Partie 18-42: Systèmes d'isolation électrique
résistants aux décharges partielles (Type II) utilisés dans des machines électriques
tournantes alimentées par convertisseurs de tension - Essais de qualification (IEC 60034
-18-42:2017)
Ta slovenski standard je istoveten z: EN 60034-18-42:2017
ICS:
29.080.30 Izolacijski sistemi Insulation systems
29.160.01 Rotacijski stroji na splošno Rotating machinery in
general
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EUROPEAN STANDARD EN 60034-18-42

NORME EUROPÉENNE
EUROPÄISCHE NORM
June 2017
ICS 29.160.01 Supersedes CLC/TS 60034-18-42:2011
English Version
Rotating electrical machines -
Part 18-42: Partial discharge resistant electrical insulation
systems (Type II) used in rotating electrical machines fed from
voltage converters - Qualification tests
(IEC 60034-18-42:2017)
Machines électriques tournantes - Partie 18-42: Systèmes Drehende elektrische Maschinen - Teil 18-42:
d'isolation électrique résistants aux décharges partielles Teilentladungsresistente Isoliersysteme (Typ II) von
(Type II) utilisés dans des machines électriques tournantes drehenden elektrischen Maschinen, die von
alimentées par convertisseurs de tension - Essais de Spannungsumrichtern gespeist werden -
qualification Qualifizierungsprüfungen
(IEC 60034-18-42:2017) (IEC 60034-18-42:2017)
This European Standard was approved by CENELEC on 2017-03-14. CENELEC members are bound to comply with the CEN/CENELEC
Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the
same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden,
Switzerland, Turkey and the United Kingdom.

European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2017 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Ref. No. EN 60034-18-42:2017 E

European foreword
The text of document 2/1854/FDIS, future edition 1 of IEC 60034-18-42, prepared by IEC/TC 2
"Rotating machinery" was submitted to the IEC-CENELEC parallel vote and approved by CENELEC
as EN 60034-18-42:2017.
The following dates are fixed:
• latest date by which the document has to be implemented at (dop) 2017-12-14
national level by publication of an identical national
standard or by endorsement
• latest date by which the national standards conflicting with (dow) 2020-03-14
the document have to be withdrawn

This document supersedes CLC/TS 60034-18-42:2011.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC shall not be held responsible for identifying any or all such patent rights.
Endorsement notice
The text of the International Standard IEC 60034-18-42:2017 was approved by CENELEC as a
European Standard without any modification.
In the official version, for Bibliography, the following note has to be added for the standard indicated :
IEC 60034-15:2009 NOTE Harmonized as EN 60034-15:2009 (not modified).
Annex ZA
(normative)
Normative references to international publications
with their corresponding European publications
The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application. For dated references, only the edition cited applies. For undated
references, the latest edition of the referenced document (including any amendments) applies.
NOTE 1 When an International Publication has been modified by common modifications, indicated by (mod),
the relevant EN/HD applies.
NOTE 2 Up-to-date information on the latest versions of the European Standards listed in this annex is
available here: www.cenelec.eu.

Publication Year Title EN/HD Year
IEC 60034-1 (mod) 2010 Rotating electrical machines - EN 60034-1 2010
Part 1: Rating and performance
- -  + corr. Oct. 2010
IEC 60034-18-1 2010 Rotating electrical machines - EN 60034-18-1 2010
Part 18-1: Functional evaluation of insulation
systems - General guidelines
IEC 60034-18-31 -  Rotating electrical machines - EN 60034-18-31 -
Part 18-31: Functional evaluation of
insulation systems - Test procedures for
form-wound windings - Thermal evaluation
and classification of insulation systems used
in rotating machines
IEC 60034-18-32 -  Rotating electrical machines - EN 60034-18-32 -
Part 18-32: Functional evaluation of
insulation systems - Test procedures for
form-wound windings - Evaluation of
electrical endurance
IEC 60034-18-41 2014 Rotating electrical machines - EN 60034-18-41 2014
Part 18-41: Partial discharge free electrical
insulation systems (Type I) used in rotating
electrical machines fed from voltage
converters - Qualification and quality control
tests
IEC/TS 60034-27 -  Rotating electrical machines - CLC/TS 60034-27 -
Part 27: Off-line partial discharge
measurements on the stator winding
insulation of rotating electrical machines
IEC/TS 61934 -  Electrical insulating materials and systems - - -
Electrical measurement of partial discharges
(PD) under short rise time and repetitive
voltage impulses
IEC 62539 -  Guide for the statistical analysis of electrical - -
insulation breakdown data
IEC 60034-18-42 ®
Edition 1.0 2017-02
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
colour
inside
Rotating electrical machines –

Part 18-42: Partial discharge resistant electrical insulation systems (Type II)

used in rotating electrical machines fed from voltage converters – Qualification

tests
Machines électriques tournantes –

Partie 18-42: Systèmes d’isolation électrique résistants aux décharges partielles

(Type II) utilisés dans des machines électriques tournantes alimentées par

convertisseurs de tension – Essais de qualification

INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE
ICS 29.160.01 ISBN 978-2-8322-3822-6

– 2 – IEC 60034-18-42:2017 © IEC 2017
CONTENTS
FOREWORD . 5
INTRODUCTION . 7
1 Scope . 8
2 Normative references . 8
3 Terms and definitions . 9
4 Machine terminal voltages arising from converter operation . 12
5 Electrical stresses in the insulation system of machine windings . 15
5.1 General . 15
5.2 Voltages stressing the phase to phase insulation . 16
5.3 Voltages stressing the phase to ground insulation . 16
5.4 Voltages stressing the turn to turn insulation . 16
5.4.1 General . 16
5.4.2 Random-wound windings . 16
5.4.3 Form-wound windings . 17
6 Voltage rating for Type II insulation systems . 17
7 Stress factors for converter-fed Type II insulation systems . 18
8 Qualification tests . 19
8.1 General . 19
8.2 Qualification tests . 19
9 Qualification of mainwall insulation system . 20
9.1 General . 20
9.2 Test methods . 20
9.3 Use of 50 Hz or 60 Hz life data to predict the service life with a converter
drive . 22
10 Qualification of turn insulation . 23
10.1 General . 23
10.2 Test methods . 24
11 Qualification of the stress control system . 25
11.1 General . 25
11.2 Test methods . 26
12 Preparation of test objects . 27
12.1 General . 27
12.2 Mainwall specimens . 27
12.3 Turn to turn specimens . 27
12.4 Stress control specimens . 27
13 Qualification test procedures . 27
13.1 General . 27
13.2 Mainwall insulation . 27
13.3 Turn to turn insulation . 28
13.4 Stress control system . 28
14 Qualification test pass criteria . 29
14.1 Mainwall insulation . 29
14.2 Turn to turn insulation . 29
14.3 Stress control system . 29
15 Routine test . 29

IEC 60034-18-42:2017 © IEC 2017 – 3 –
16 Optional screening tests . 30
17 Analysis, reporting and classification . 30
Annex A (informative) Contributions to ageing of the mainwall insulation . 31
A.1 Life time consumption of the mainwall insulation . 31
A.2 Calculation of the contributions to ageing from a 3-level converter drive . 31
A.3 Calculation to derive an equivalent voltage amplitude and frequency . 32
Annex B (informative) Examples of circuits for impulse testing . 34
B.1 Impulse test circuit using a semiconducting switch . 34
B.2 Typical waveform generated from the impulse generator . 34
B.3 Alternative impulse test circuit using a semiconducting switch . 35
Annex C (informative) Derivation of the short term endurance test voltage . 37
Annex D (informative) Derivation of the impulse voltage insulation class for the
machine insulation . 38
Annex E (normative) Derivation of an IVIC in the absence of a manufacturer’s
reference life line . 40
E.1 Derivation of an IVIC from endurance tests . 40
E.1.1 Mainwall insulation . 40
E.1.2 Turn insulation . 41
E.1.3 Stress control system . 41
E.2 Derivation of the IVIC X on the basis of satisfactory service experience . 41
E.3 Derivation of an IVIC S on the basis of satisfactory service experience . 41
Annex F (informative) Optional screening tests . 42
F.1 General . 42
F.2 Short term endurance test on the mainwall insulation . 42
F.3 Voltage withstand test . 42
Bibliography . 43

Figure 1 – Voltage impulse waveshape parameters . 12
Figure 2 – Waveform representing one complete cycle of the phase to phase voltage
at the terminals of a machine fed from a 3-level converter . 13
Figure 3 – Jump voltage (U ) at the terminals of a machine fed from a converter drive . 14
j
Figure 4 – Maximum voltage enhancement at the machine terminals at infinite
impedance as a function of cable length for various impulse rise times . 15
Figure 5 – Example of a random-wound design . 16
Figure 6 – Example of a form-wound design . 16
Figure 7 – Worst case voltage stressing the turn to turn insulation in a variety of
random-wound stators as a function of the rise time of the impulse . 17
Figure 8 – Example of a life curve for a Type II mainwall insulation system . 23
Figure 9 – Example of a life curve for turn insulation . 25
Figure A.1 – Representation of the phase to ground voltage at the terminals of a
machine fed from a 3-level converter . 31
Figure A.2 – Ratio of the life time consumption (y-axis) of impulse voltage (U ) to
pk/pk
fundamental voltage (U’ ) expressed as a percentage for various
pk/pk
impulse/fundamental frequency ratios (n=10) . 33
Figure B.1 – Example of a simple converter voltage simulation circuit . 34
Figure B.2 – Typical waveform generated from the impulse generator . 35
Figure B.3 – Example of a simple converter voltage simulation circuit . 36

– 4 – IEC 60034-18-42:2017 © IEC 2017
Figure B.4 – Typical waveform generated from the impulse generator . 36
Figure E.1 – Reference life line for mainwall insulation . 40

Table 1 – Examples of the values of characteristics of the terminal voltages for two
converter-fed machines. 13
Table 2 – Influence of features of the converter drive voltage on acceleration of
ageing of components of Type II insulation systems . 18
Table A.1 – Contribution to electrical ageing by 1 kHz impulses from a 3-level
converter as a percentage of the ageing from the 50 Hz fundamental voltage
(endurance coefficient of 10). 32
Table D.1 – Phase to ground test voltages according to IVIC for Type II insulation
systems . 38
Table D.2 – Impulse voltage insulation classes (IVIC) . 39

IEC 60034-18-42:2017 © IEC 2017 – 5 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
ROTATING ELECTRICAL MACHINES –

Part 18-42: Partial discharge resistant electrical insulation systems
(Type II) used in rotating electrical machines fed from voltage
converters – Qualification tests

FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 60034-18-42 has been prepared by IEC Technical Committee 2:
Rotating machinery.
IEC 60034-18-42 cancels and replaces IEC TS 60034-18-42 (2008).
The text of this standard is based on the following documents:
FDIS Report on voting
2/1854/FDIS 2/1856/RVD
Full information on the voting for the approval of this International Standard can be found in
the report on voting indicated in the above table.

– 6 – IEC 60034-18-42:2017 © IEC 2017
This document has been drafted in accordance with the ISO/IEC Directives, Part 2.
NOTE A table of cross-references of all TC 2 publications can be found on the IEC TC 2 dashboard on the IEC
website.
The committee has decided that the contents of this document will remain unchanged until the
stability date indicated on the IEC website under "http://webstore.iec.ch" in the data related to
the specific document. At this date, the document will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
IMPORTANT – The 'colour inside' logo on the cover page of this publication indicates
that it contains colours which are considered to be useful for the correct
understanding of its contents. Users should therefore print this document using a
colour printer.
IEC 60034-18-42:2017 © IEC 2017 – 7 –
INTRODUCTION
The approval of electrical insulation systems for use in rotating electrical machines fed from
voltage converters is set out in two International Standards. These standards separate the
systems into those which are not expected to experience partial discharge activity within
specified conditions in their service lives (Type I) and those which are expected to experience
and withstand partial discharge activity in any part of the insulation system throughout their
service lives (Type II). For both Type I and Type II insulation systems, the power drive system
integrator (the person responsible for co-ordinating the electrical performance of the entire
power drive system) shall inform the machine manufacturer what voltage will appear at the
machine terminals in service. The machine manufacturer will then decide upon the severity of
the tests appropriate for qualifying the insulation system. For insulation systems which have
been qualified through IEC 60034-18-41 or IEC 60034-18-42 for use in converter-fed
applications, an impulse voltage insulation class may be derived. This indicates the ability of
the insulation to withstand the electric stresses resulting from converter operation. For Type I
systems, the severity is based on the impulse rise time and the peak to peak voltage. For
Type II systems, the severity is additionally affected by the impulse voltage repetition rate and
the fundamental voltage characteristics. After installation of the converter/machine system, it
is recommended that the system integrator measures the phase to phase and phase to
ground voltages between the terminals and ground to check for compliance.
IEC 60034-18-41
Type I insulation systems are dealt with in IEC 60034-18-41. These systems are generally
used in rotating machines with rated voltage less than 700 V r.m.s. and tend to have random-
wound coils. In IEC 60034-18-41, the necessary normative references and definitions are
given together with a review of the effects arising from converter operation. Having
established the technical basis for the evaluation procedure, the conceptual approach and
test programmes are then described.
IEC 60034-18-42
In IEC 60034-18-42, tests are described for qualification of Type II insulation systems. These
insulation systems are generally used in rotating machines which have form-wound windings,
mostly rated above 700 V r.m.s. The qualification procedure is completely different from that
used for Type I insulation systems and involves destructive ageing of test objects under
accelerated conditions. The manufacturer requires a life curve (as described in IEC 60034-18-
32) for the insulation system that can be interpreted by use of appropriate calculations and/or
experimental procedures to provide an estimate of life under the service conditions with
converter drive. Great importance is attached to the qualification of any stress control system
that is used and testing here should be performed under sinusoidal and repetitive impulse
conditions applied separately. If the insulation system can be shown to provide an acceptable
life under the specified ageing conditions, it is qualified for use.

– 8 – IEC 60034-18-42:2017 © IEC 2017
ROTATING ELECTRICAL MACHINES –

Part 18-42: Partial discharge resistant electrical insulation systems
(Type II) used in rotating electrical machines fed from voltage
converters – Qualification tests

1 Scope
This part of IEC 60034 defines criteria for assessing the insulation system of stator/rotor
windings of single or polyphase AC machines which are subjected to repetitive impulse
voltages, such as those generated by pulse width modulation (PWM) converters, and are
expected to experience and withstand partial discharge activity during service. It specifies
electrical qualification tests on representative specimens to verify fitness for operation with
voltage-source converters. It also describes an additional classification system which defines
the limits of reliable performance under converter-fed conditions.
Although this document deals with voltage converters, it is recognised that there are other
types of converters that can create repetitive impulse voltages. For these converters, a similar
approach to testing can be used.
Qualification of insulation systems may not be required for rotating machines which are only
fed from voltage converters for starting and so they are excluded from this document.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their
content constitutes requirements of this document. For dated references, only the edition
cited applies. For undated references, the latest edition of the referenced document (including
any amendments) applies.
IEC 60034-1:2010, Rotating electrical machines – Part 1: Rating and performance
IEC 60034-18-1:2010, Rotating electrical machines – Part 18-1: Functional evaluation of
insulation systems. General guidelines
IEC 60034-18-31, Rotating electrical machines – Part 18-31: Functional evaluation of
insulation systems – Test procedures for form-wound windings – Thermal evaluation and
classification of insulation systems used in rotating machines
IEC 60034-18-32, Rotating electrical machines – Part 18-32: Functional evaluation of
insulation systems – Test procedures for form-wound windings – Evaluation by electrical
endurance
IEC 60034-18-41:2014, Rotating electrical machines – Part 18-41: Partial discharge free
(Type I) electrical insulation systems used in rotating electrical machines fed from voltage
converters – Qualification and quality control tests
IEC TS 60034-27, Rotating electrical machines – Part 27: Off-line partial discharge
measurements on the stator winding insulation of rotating electrical machines
IEC TS 61934, Electrical insulating materials and systems – Electrical measurement of partial
discharges (PD) under short rise time and repetitive voltage impulses

IEC 60034-18-42:2017 © IEC 2017 – 9 –
IEC 62539, Guide for the statistical analysis of electrical insulation breakdown data
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
ISO and IEC maintain terminological databases for use in standardization at the following
addresses:
• IEC Electropedia: available at http://www.electropedia.org/
• ISO Online browsing platform: available at http://www.iso.org/obp
3.1
partial discharge
PD
electric discharge that only partially bridges the insulation between electrical conductors
Note 1 to entry: It may occur inside or outside the insulation or adjacent to an electrical conductor.
3.2
partial discharge inception voltage
PDIV
lowest voltage at which partial discharges are initiated in the test arrangement when the
voltage applied to the test object is gradually increased from a lower value at which no such
discharges are observed
Note 1 to entry: With sinusoidal applied voltage, the PDIV is defined as the r.m.s. value of the voltage. With
impulse voltages, the PDIV is defined as the peak to peak voltage.
3.3
repetitive partial discharge inception voltage
RPDIV
minimum peak to peak impulse voltage at which more than five PD pulses occur on ten
voltage impulses of the same polarity
Note 1 to entry: This is a mean value for the specified test time and a test arrangement where the voltage applied
to the test object is gradually increased from a value at which no partial discharges can be detected.
3.4
peak (impulse) voltage
U
p
maximum numerical value of voltage reached during a unipolar voltage impulse (e.g. U in
p
Figure 1)
Note 1 to entry: For bipolar voltage impulses, it is half the peak to peak voltage.
3.5
steady state impulse voltage magnitude
U
a
final magnitude of the voltage impulse
SEE: Figure 1.
3.6
voltage overshoot
U
b
magnitude of the peak voltage in excess of the steady state impulse voltage
SEE: Figure 1.
– 10 – IEC 60034-18-42:2017 © IEC 2017
3.7
peak to peak impulse voltage
U’
pk/pk
peak to peak voltage at the impulse voltage repetition rate
SEE: Figure 2.
3.8
peak to peak voltage
U
pk/pk
peak to peak phase to phase voltage at the fundamental frequency
SEE: Figure 2.
Note 1 to entry: The definition of peak to peak voltage is clarified in Clause 4.
3.9
unipolar voltage impulse
voltage impulse, the polarity of which is either positive or negative
Note 1 to entry: The term impulse is used to describe the transient stressing voltage applied to the test object and
the term pulse is used to describe the partial discharge signal.
3.10
bipolar voltage impulse
voltage impulse, the polarity of which changes alternately from positive to negative or vice
versa
3.11
impulse voltage repetition rate
f
inverse of the average time between two successive impulses of the same polarity, whether
unipolar or bipolar
3.12
impulse rise time
t
r
time for the voltage to rise from 10 % to 90 % of its final value
SEE: Figure 1.
3.13
electrical insulation system
insulating structure containing one or more electrical insulating materials together with
associated conducting parts employed in an electrotechnical device
3.14
motorette
special test model used for the evaluation of the electrical insulation system for random-
wound windings
3.15
formette
special test model used for the evaluation of the electrical insulation system for form-wound
windings
3.16
electric stress
electric field in V/mm
IEC 60034-18-42:2017 © IEC 2017 – 11 –
3.17
rated voltage
U
N
voltage assigned by the manufacturer for a specified power frequency operating condition of a
machine and indicated on its rating plate
3.18
impulse voltage insulation class
IVIC
limits of the applied voltage for operation of a Type I or Type II converter-fed machine
Note 1 to entry: The limits are shown as severity levels for which the machine has been qualified.
Note 2 to entry: The severity levels are to be shown in the documentation for the machine.
3.19
fundamental frequency
first frequency, in the spectrum obtained from a Fourier transform of a periodic time function,
to which all the frequencies of the spectrum are referred
Note 1 to entry: For the purposes of this document, the fundamental frequency of the machine terminal voltage is
the one defining the speed of the converter-fed machine.
Note 2 to entry: It is calculated as the reciprocal of the time taken for one complete cycle of the applied voltage
(Figure 2).
3.20
impulse duration
interval of time between the first and last instants at which the instantaneous value of an
impulse reaches a specified fraction of its impulse magnitude or a specified threshold
3.21
jump voltage
U
j
change in voltage at the terminals of the machine occurring at the start of each impulse when
fed from a converter
SEE: Figure 3.
3.22
dc bus voltage
U
dc
voltage of the intermediate circuit of the voltage converter (dc-link-circuit)
Note 1 to entry: For a 2-level converter U is equal to U in Figure 1.
dc a
Note 2 to entry: For a multilevel converter, U is equal to ½ U minus the overshoot in Figure 2.
dc pk/pk
3.23
power drive system
PDS
complete drive module and rotating machine together with the connecting cable if necessary
3.24
voltage endurance coefficient
n
exponent of the inverse power model or exponential model on which the relationship between
life and stressing voltage amplitude for a specific insulation system depends
3.25
life
time to failure
– 12 – IEC 60034-18-42:2017 © IEC 2017
3.26
conductive slot coating
conductive paint or tape layer in intimate contact with the mainwall insulation in the slot
portion of the coil side, often called semi-conductive coating
Note 1 to entry: The purpose of the coating is to prevent slot discharges from occurring.
3.27
stress control coating
paint or tape on the surface of the mainwall insulation that extends beyond the conductive slot
coating in high-voltage stator bars and coils
Note 1 to entry: The purpose of the coating is to grade the surface electric stress.
3.28
stress control system
generic name for the combination of the conductive slot coating and stress control coating in
high-voltage stator bars and coils
3.29
maximum allowable peak to peak phase to ground voltage
U
IVIC
maximum allowable peak to peak phase to ground voltage in service
4 Machine terminal voltages arising from converter operation
The voltage appearing at the terminals of a converter-fed machine may be estimated using
IEC TS 61800-8 [1] and depends upon several characteristics of the PDS. In order to apply
this standard to the qualification and testing of the insulation system of a winding, it is
necessary to specify the required parameters of the voltage appearing at the machine
terminals (Clause 7).
U
p
0,9 U
p
0,1 U
p
t
r
t t
t
10 90
IEC
Key
U voltage
t time
Figure 1 – Voltage impulse waveshape parameters
The amplitude and rise time of the voltage at the machine terminals depend upon the
grounding system, various design aspects of the cable, the machine surge impedance and the
___________
Numbers in square brackets refer to the Bibliography.
U
U
b
U
a
IEC 60034-18-42:2017 © IEC 2017 – 13 –
presence of any filters that increase the impulse rise time. Examples of characteristics of
converter impulses at the machine terminals of two motors are given in Table 1.
Table 1 – Examples of the values of characteristics
of the terminal voltages for two converter-fed machines
Machine rating 3,3 kV 6,6 kV
Peak to peak voltage on the phase to ground insulation 5,4 kV 10,8 kV
Fundamental frequency 50/60 Hz 50/60 Hz
Number of levels for the converter voltage 5 3
Overshoot of the impulse voltage 60 % 60 %
Nominal voltage per step 650 V 3 kV
Impulse rise time at the motor terminals 1 µs 3 µs
Impulse repetition rate 1 kHz 900 Hz
IVIC required to qualify the insulation for this service (see Table D.2) 3 3

In the case of 2-level or other voltage converters, the impulses generate voltage overshoots
at the machine terminals, depending on the rise time of the voltage impulse at the converter
output and on the cable length and machine impedance. This voltage overshoot is created by
reflected waves at the interface between cable and machine or converter terminals due to
impedance mismatch. The voltage appearing at the machine terminals when fed from a 3-
level converter is shown in Figure 2. The figure shows one cycle at the fundamental
frequency.
The maximum change in voltage or jump voltage (U ) at the impulse repetition rate is shown in
j
Figure 3. This parameter is important in defining the voltage enhancement that can occur
across the first or last coil in the winding. A double jump transition (Figure 3) is possible but it
is the duty of the PDS integrator to ensure that the software controlling the PDS minimises its
occurrence. When the double jump transition occurs in multilevel converter voltages, its effect
is insignificant.
t
IEC
Figure 2 – Waveform representing one complete cycle of the phase to
phase voltage at the terminals of a machine fed from a 3-level converter
U
U′
pk/pk
U
pk/pk
– 14 – IEC 60034-18-42:2017 © IEC 2017
t
IEC
Figure 3 – Jump voltage (U ) at the terminals of a machine fed from a converter drive
j
Examples of the enhancements that are produced for various rise times and cable lengths are
given in Figure 4, where the worst case is shown, arising from an infinite impedance load. In
this case, the enhancement to the voltage for an impulse rise time of 1,0 µs is insignificant
below about 15 m and only exceeds a factor of 1,2 when the cable length is greater than
about 50 m.
Voltages above 2U can be produced at the terminals of the machine by converter drive
dc
double transitions and by a converter-fed drive algorithm that does not allow a minimum time
between successive pulses. Double transition occurs, for example, when one phase switches
from minus to plus dc bus voltage at the same instant that another phase switches from plus
to minus. This generates a 2U voltage wave which travels to the machine and can then
dc
increase in magnitude when reflected at the machine terminals. If there is no minimum
impulse time control in the converter drive and if the time between two impulses is matched
with the time constant of the cable between the converter and the machine, an over voltage
>2U can be generated at the machine terminals. The reflection can be reduced or prevented
dc
by using a filter in the converter, at the machine terminals or both.
In the event of an earth fault on one of the phases, further damage is avoided by protective
systems in the converter that switch it off.
U
U
j
IEC 60034-18-42:2017 © IEC 2017 – 15 –
2,1
2,0
1,9
1,8
1,7
1,6
1,5
1,4
1,3
1,2
1,1
1,0
1 10 100
l (m)
IEC
Key
● t 0,05 µs
r
○ t 0,1 µs
r
▼ t 0,2 µs
r
∇ t 1,0 µs
r
l cable length
Figure 4 – Maximum voltage enhancement at the machine terminals at infinite
impedance as a function of cable length for various impulse rise times
5 Electrical stresses in the insulation system of machine windings
5.1 General
If a winding experiences short rise time voltage impulses with significant magnitude, high
voltage stresses will be created in the following locations (Figures 5 and 6):
• between conductors in different phases
• between a conductor and ground
• between adjacent turns, generally in the line-end coil
• in the area of the stress control coating
Due to space and surface charge creation within the insulation components, the electric
stress is not only defined by the instantaneous voltage itself but also by the voltages that
have been stressing the insulation previously. Generally, it has been shown by experience
that, within certain limits valid for converter drive systems, the most significant stressing
parameter is the
...