Effects of electromagnetic interference on pipelines caused by high voltage a.c. electric traction systems and/or high voltage a.c. power supply systems

The presence of ac power supply systems or of a.c. electric traction systems (in this standard also indicated as a.c. power systems) may cause voltages to build up in pipeline systems,(in this standard indicated as interfered systems) running in the close vicinity, due to one or more of the following mechanisms:  inductive coupling,  conductive coupling,  capacitive coupling. Such voltages may cause danger to persons, damage to pipelines or connected equipment or disturbance to the electrical/ electronic equipment connected to the pipeline. This European Standard deals with the situations where these effects may arise and with the maximum tolerable limits of the interference effects, taking into account the behaviour of the ac power systems both in normal operating condition and/or during faults. NOTE In the worst case, the pipe may not disperse current to ground. As a consequence, the prospective touch voltage coincides with the interference voltage. This European Standard applies to all metallic pipelines irrespective of the conveyed fluid, e.g. liquid or gas, liable to be interfered by high voltage a.c. railway and high voltage a.c. power supply systems. The objective of this standard is to establish:  the procedure for evaluating the e.m. interference;  the interference distance to be considered;  the types of coupling to be considered for operating and fault conditions of the high voltage a.c. electric traction systems and high voltage a.c. power supply systems;  the configurations to be considered for both metallic pipeline and high voltage a.c. electric traction systems or high voltage a.c. power systems;  the limits of the voltages due to the electromagnetic interference;  information on interference situations, calculation methods, measuring methods, mitigation measures, management of interference. This European Standard is applicable to all new metallic pipelines and all new high voltage a.c. electric traction systems and high voltage a.c. power supply systems and all major modifications that may change significantly the interference effect. This European Standard only relates to phenomena at the fundamental power frequency (e.g. 50 Hz or 16,7 Hz). This European Standard does not apply to:  all aspects of corrosion,  the coupling from a.c. railway and power supply systems with nominal voltages less than or equal to 1 kV,  interference effects on the equipment not electrically connected to the pipeline.

Auswirkungen elektromagnetischer Beeinflussungen von Hochspannungswechselstrombahnen und/oder Hochspannungsanlagen auf Rohrleitungen

Effets des perturbations électromagnétiques sur les canalisations causées par les systèmes de traction électrique ferroviaire en courant alternatif et/ou par les réseaux électriques H.T. en courant alternatif

Učinki elektromagnetne interference na cevovode, ki jih povzročajo visokonapetostni sistemi izmeničnega toka električne vleke in/ali visokonapetostni izmenični napajalni sistemi

Prisotnost izmeničnih napajalnih sistemov ali sistemov izmeničnega toka električne vleke (v tem standardu označeni tudi kot »izmenični napajalni sistemi«) lahko povzroči nabiranje napetosti v sistemih cevovodov (v tem standardu označeni kot »interferirani sistemi«), ki potekajo v neposredni bližini, zaradi enega naslednjega mehanizma ali več:
– induktivno sklapljanje,
– konduktivno sklapljanje,
– kapacitivno sklapljanje.
Takšne napetosti lahko ogrožajo osebe, povzročijo škodo na cevovodih ali povezani opremi ali so vzrok motenj električne/elektronske opreme, povezane s cevovodom.
Ta evropski standard obravnava situacije, v katerih lahko takšni učinki nastanejo, ter najvišje sprejemljive meje interferenčnih učinkov z upoštevanjem obnašanja izmeničnih napajalnih sistemov v običajnih delovnih pogojih in/ali med okvarami.
OPOMBA: V najslabšem primeru cev morda ne prevaja toka v tla. Zato pričakovana napetost dotika sovpada z interferenčno napetostjo.
Ta evropski standard velja za vse kovinske cevovode, na katere lahko vplivajo visokonapetostni železniški sistemi izmeničnega toka in visokonapetostni izmenični napajalni sistemi, ne glede na snov, ki jo prenašajo, npr. tekočino ali plin.
Namen tega standarda je vzpostavitev:
– postopka za vrednotenje elektromagnetne interference;
– razdalje interference, ki jo je treba upoštevati;
– tipov sklapljanja, ki jih je treba upoštevati za obratovanje in stanja napak visokonapetostnih sistemov izmeničnega toka električne vleke in visokonapetostnih izmeničnih napajalnih sistemov;
– konfiguracij, ki jih je treba upoštevati pri kovinskih cevovodih in visokonapetostnih sistemih izmeničnega toka električne vleke ali visokonapetostnih izmeničnih napajalnih sistemih;
– omejitev napetosti zaradi elektromagnetne interference;
– informacij o interferenčnih situacijah, metodah za izračun, metodah za merjenje, ukrepih za ublažitev, upravljanju interference.
Ta evropski standard velja za vse nove kovinske cevovode, za vse nove visokonapetostne sisteme izmeničnega toka električne vleke in visokonapetostne izmenične napajalne sisteme ter za vse večje spremembe, ki bi lahko znatno spremenile učinek interference.
Ta evropski standard velja le za pojave pri osnovni obratovalni frekvenci (npr. 50 Hz ali 16,7 Hz).
Ta evropski standard se ne uporablja:
– pri vseh pojavih korozije;
– za sklapljanje iz železniških sistemov izmeničnega toka in izmeničnih napajalnih sistemov z nominalnimi napetostmi, ki so manjše ali enake 1 kV;
– za učinke interference v opremi, ki ni električno povezana s cevovodom.

General Information

Status
Published
Publication Date
08-Dec-2011
Current Stage
9093 - Decision to confirm - Review Enquiry
Completion Date
14-Sep-2022

Buy Standard

Standard
EN 50443:2012
English language
27 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-februar-2012
8þLQNLHOHNWURPDJQHWQHLQWHUIHUHQFHQDFHYRYRGHNLMLKSRY]URþDMR
YLVRNRQDSHWRVWQLVLVWHPLL]PHQLþQHJDWRNDHOHNWULþQHYOHNHLQDOLYLVRNRQDSHWRVWQL
L]PHQLþQLQDSDMDOQLVLVWHPL
Effects of electromagnetic interference on pipelines caused by high voltage a.c. electric
traction systems and/or high voltage a.c. power supply systems
Auswirkungen elektromagnetischer Beeinflussungen von
Hochspannungswechselstrombahnen und/oder Hochspannungsanlagen auf
Rohrleitungen
Effets des perturbations electromagnétiques sur les canalisations causées par les
systèmes de traction électrique ferroviaire en courant alternatif et/ou par les réseaux
électriques H.T. en courant alternatif
Ta slovenski standard je istoveten z: EN 50443:2011
ICS:
23.040.99 Drugi sestavni deli za Other pipeline components
cevovode
29.280 (OHNWULþQDYOHþQDRSUHPD Electric traction equipment
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EUROPEAN STANDARD
EN 50443
NORME EUROPÉENNE
December 2011
EUROPÄISCHE NORM
ICS 23.040.99; 29.280; 33.100.01

English version
Effects of electromagnetic interference on pipelines caused by high
voltage a.c. electric traction systems and/or high voltage a.c. power
supply systems
Effets des perturbations électromagnétiques sur Auswirkungen elektromagnetischer
les canalisations causées par les systèmes de Beeinflussungen von
traction électrique ferroviaire en courant alternatif Hochspannungswechselstrombahnen und/oder
et/ou par les réseaux électriques H.T. en courant Hochspannungsanlagen auf Rohrleitungen
alternatif
This European Standard was approved by CENELEC on 2011-10-24. CENELEC members are bound to comply
with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard
the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the CEN-CENELEC Management Centre or to any CENELEC member.

This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and notified
to the CEN-CENELEC Management Centre has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus,
the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy,
Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia,
Spain, Sweden, Switzerland and the United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Management Centre: Avenue Marnix 17, B - 1000 Brussels

© 2011 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 50443:2011 E
Contents
Foreword . 4
1 Scope. 5
2 Normative references . 5
3 Terms and definitions . 6
4 Procedure . 9
5 Interference distance . 9
5.1 General . 9
5.2 Interference distance for normal operating conditions . 10
5.2.1 overhead a.c. power systems . 10
5.2.2 underground a.c. power systems . 10
5.3 Interference distance for fault condition . 10
5.3.1 General . 10
5.3.2 overhead a.c. power systems . 10
5.3.3 underground a.c. power systems . 10
5.4 Summary of the interference distances . 10
6 Interference situations. 11
7 Coupling types . 11
8 Interference . 12
9 Interference results . 13
10 Limits for permissible interference . 13
10.1 General . 13
10.2 Limits related to electrical safety of persons . 13
10.2.1 General . 13
10.2.2 Operating conditions . 13
10.2.3 Fault conditions . 14
10.3 Limits related to damage to the pipeline system . 14
10.3.1 Fault conditions . 14
10.3.2 Operating conditions . 14
10.4 Limits related to disturbance of the pipeline system . 14
11 Evaluation of the interference results . 14
12 Mitigation measures . 15
Annex A (informative) Indications to select interference situations . 16
Annex B (informative) Guidance for interference investigations . 17
B.1 Introduction . 17
B.2 Configuration of the a.c. electric traction system . 17
B.3 Configuration of the a.c. power supply system . 18
B.4 Configuration of the pipeline . 18
B.5 Calculation methods . 19
B.6 Calculation of independent interfering systems . 20
Annex C (informative) Measuring methods. 21
C.1 General . 21
C.2 Measurement methods for interference voltages at steady state . 21
Annex D (informative) Mitigation measures . 22
D.1 General . 22
D.2 Mitigation measures at the pipeline side . 22
D.3 Mitigation measures at the a.c railway system side . 23
D.4 Mitigation measures at the a.c. power supply system side. 23
Annex E (informative) Management of interference . 24
E.1 General . 24
E.2 Plant life . 24
E.3 Exchange of information . 24
E.4 Plant documentation . 24

– 3 – EN 50443:2011
Annex F (informative) A-deviations . 26
Bibliography . 27

Tables
Table 1  Interference distances . 11
Table 2  Coupling types and distances to be considered . 12
Table 3  Limits for interference voltage related to danger to (electrically) instructed persons . 14

Foreword
This document (EN 50443:2011) has been prepared by Technical Committee CLC/TC 9XC "Electric
supply and earthing systems for public transport equipment and ancillary apparatus (Fixed installations)".

This European Standard gives limits relevant to the electromagnetic interference produced by high
voltage a.c. railway and power supply systems on metallic pipelines.
Limits are relevant to the interference which can be tolerated on the metallic pipeline, by the equipment
connected to it and by persons working on them or in contact with them.

This European Standard indicates the electromagnetic interference situations to which the limits must be
related.
Suggestions concerning the interference situations to be examined are given in Annex A. Suggestions
concerning the appropriate calculation methods are given in Annex B. Suggestions concerning the
appropriate measurement methods are given in Annex C. Suggestions about the use of mitigation
measures are given in Annex D. Suggestions for management of interference are given in Annex E.

The following dates are fixed:

– latest date by which the amendment has to be implemented
at national level by publication of an identical
national standard or by endorsement (dop) 2012-10-24

– latest date by which the national standards conflicting
with the amendment have to be withdrawn (dow) 2014-10-24

Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC [and/or CEN] shall not be held responsible for identifying any or all such patent
rights.
– 5 – EN 50443:2011
1 Scope
The presence of a.c. power supply systems or of a.c. electric traction systems (in this standard also
indicated as a.c. power systems) may cause voltages to build up in pipeline systems, (in this standard
indicated as interfered systems) running in the close vicinity, due to one or more of the following
mechanisms:
− inductive coupling,
− conductive coupling,
− capacitive coupling.
Such voltages may cause danger to persons, damage to pipelines or connected equipment or
disturbance to the electrical/ electronic equipment connected to the pipeline.

This European Standard deals with the situations where these effects may arise and with the maximum
tolerable limits of the interference effects, taking into account the behaviour of the a.c power systems
both in normal operating condition and/or during faults.

NOTE In the worst case, the pipe may not disperse current to ground. As a consequence, the prospective touch voltage
coincides with the interference voltage.

This European Standard applies to all metallic pipelines irrespective of the conveyed fluid, e.g. liquid or
gas, liable to be interfered by high voltage a.c. railway and high voltage a.c. power supply systems.

The objective of this standard is to establish:
− the procedure for evaluating the electromagnetic interference;
− the interference distance to be considered;
− the types of coupling to be considered for operating and fault conditions of the high voltage a.c.
electric traction systems and high voltage a.c. power supply systems;
− the configurations to be considered for both metallic pipeline and high voltage a.c. electric traction
systems or high voltage a.c. power systems;
− the limits of the voltages due to the electromagnetic interfe
...