Compression and mechanical connectors for power cables - Part 1-3: Test methods and requirements for compression and mechanical connectors for power cables for rated voltages above 1 kV (Um = 1,2 kV) up to 36 kV (Um = 42 kV) tested on non-insulated conductors

This part of EN 61238 applies to compression and mechanical connectors for power cables for rated voltages above 1 kV (Um = 1,2 kV) up to 36 kV (Um = 42 kV), for example buried cables or cables installed in buildings, having a) conductors complying with EN 60228 having nominal cross-sectional areas between 2,5 mm2 and 1 200 mm2 for copper and between 16 mm2 and 1 200 mm2 for aluminium, excluding Milliken conductors; b) a maximum continuous conductor temperature not exceeding 90 °C. This document is not applicable to connectors for overhead line conductors nor to connectors with a sliding contact. The object of this document is to define the type test methods and requirements which apply to compression and mechanical connectors for power cables with copper or aluminium conductors. The reference method is to perform the tests on unused conductors.

Pressverbinder und Schraubverbinder für Starkstromkabel - Teil 1-3: Prüfverfahren für und Anforderungen an Pressverbinder und Schraubverbinder für Starkstromkabel für Nennspannungen über 1 kV (Um = 1,2 kV) bis zu 36 kV (Um = 42 kV), geprüft an nicht isolierten Leitern

Raccords sertis et à serrage mécanique pour câbles d’énergie - Partie 1-3: Méthodes et exigences d’essai relatives aux raccords sertis et à serrage mécanique pour les câbles d’énergie de tensions assignées supérieures à 1 kV (Um = 1,2 kV) jusqu’à 36 kV (Um = 42 kV) soumis à essai sur des conducteurs non isolés

L’IEC 61238-1-3:2018 est applicable aux raccords sertis et à serrage mécanique pour câbles d'énergie de tensions assignées supérieures à 1 kV (Um = 1,2 kV) jusqu’à 30 kV (Um = 36 kV), par exemple pour les câbles enterrés ou ceux installés à l'intérieur des bâtiments, ayant a) des âmes conformes à l’IEC 60228, de section nominale comprise entre 2,5 mm2 et 1 200 mm2 pour le cuivre et entre 16 mm2 et 1 200 mm2 pour l’aluminium, à l’exception des âmes Milliken; b) une température maximale de fonctionnement en service permanent au plus égale à 90 °C. Le présent document n'est pas applicable aux raccords pour conducteurs de ligne aérienne ni aux raccords équipés d’un contact glissant. L'objet du présent document est de définir les méthodes d'essais de type et les exigences qui s’appliquent aux raccords sertis et à serrage mécanique utilisables sur les câbles d'énergie à conducteurs en cuivre ou en aluminium. La méthode de référence consiste à réaliser les essais sur des conducteurs neufs. Cette première édition, conjointement avec l'IEC 61238-1-1 et l'IEC 61238-1-2, annule et remplace l'IEC 61238-1:2003. Cette édition inclut les modifications techniques majeures suivantes par rapport à l'IEC 61238-1:2003: a) Le domaine d’application a été élargi afin de couvrir les raccords de connexion pour âmes jusqu’à 2,5 mm2 (précédemment 10 mm2); il a été limité à 1 200 mm2 pour les âmes en cuivre et en aluminium car les expériences et applications d’essai des raccords à perforation d’isolant sont rares pour les âmes de fortes sections. b) Une nouvelle classe mécanique a été introduite pour répondre à la demande concernant les raccords soumis à des forces mécaniques supérieures à celles spécifiées dans la Classe 1 pour les âmes de fortes sections. c) Pour l’essai électrique, un courant de chauffage élevé maximal a été défini afin d’éviter l’apparition de densités de courant irréalistes pendant l’essai, qui peuvent modifier les propriétés des raccords en essai. d) Pour l’essai de court-circuit, la méthode de calcul et les exigences ont été mises à jour. e) Pour l’essai mécanique, les méthodes et exigences ont été mises à jour. f) Une proposition d’essai électrique sur les cosses d’extrémité de câble a été introduite pour les applications de connecteurs séparables.

Stisljivi in vijačni konektorji za električne kable - 1-3. del: Preskusne metode in zahteve za stisljive in vijačne konektorje za električne kable za naznačene napetosti nad 1 kV (Um = 1,2 kV) do 36 kV (Um = 42 kV), preskušene na neizoliranih vodnikih (IEC 61238-1-3:2018)

Ta del standarda EN 61238 se uporablja za stisljive in vijačne konektorje za električne kable za naznačene napetosti nad 1 kV (Um = 1,2 kV) do 36 kV (Um = 42 kV), na primer za v zemljo položene kable ali kable, vgrajene v stavbah, ki imajo:
a) vodnike, ki so skladni s standardom EN 60228 ter imajo nominalni premer med 2,5 mm2 in 1200 mm2, če so bakreni, ter med 16 mm2 in 1200 mm2, če so aluminijasti, razen segmentnih vodnikov.
b) največjo enakomerno temperaturo vodnika, ki ne presega 90 °C.
Ta dokument se ne uporablja za konektorje vodnikov nadzemnih vodov ali za konektorje z drsnimi kontakti.
Namen tega dokumenta je opredeliti metode in zahteve tipskih preskusov, ki se uporabljajo za stisljive in vijačne konektorje za električne kable z bakrenimi ali aluminijastimi vodniki. Referenčna metoda je namenjena za izvajanje preskusov na neuporabljenih vodnikih.

General Information

Status
Published
Publication Date
19-Sep-2019
Withdrawal Date
18-Jul-2022
Technical Committee
Drafting Committee
Current Stage
6060 - Document made available - Publishing
Start Date
20-Sep-2019
Due Date
04-Dec-2020
Completion Date
20-Sep-2019

Relations

Standard
EN IEC 61238-1-3:2019
English language
47 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-december-2019
Nadomešča:
SIST EN 61238-1:2004
Stisljivi in vijačni konektorji za električne kable - 1-3. del: Preskusne metode in
zahteve za stisljive in vijačne konektorje za električne kable za naznačene
napetosti nad 1 kV (Um = 1,2 kV) do 36 kV (Um = 42 kV), preskušene na
neizoliranih vodnikih (IEC 61238-1-3:2018)
Compression and mechanical connectors for power cables - Part 1-3: Test methods and
requirements for compression and mechanical connectors for power cables for rated
voltages above 1 kV (Um = 1,2 kV) up to 36 kV (Um = 42 kV) tested on non-insulated
conductors (IEC 61238-1-3:2018)
Pressverbinder und Schraubverbinder für Starkstromkabel - Teil 1-3: Prüfverfahren für
und Anforderungen an Pressverbinder und Schraubverbinder für Starkstromkabel für
Nennspannungen über 1 kV (Um = 1,2 kV) bis zu 36 kV (Um = 42 kV), geprüft an nicht
isolierten Leitern (IEC 61238-1-3:2018)
Raccords sertis et à serrage mécanique pour câbles d’énergie - Partie 1-3: Méthodes et
exigences d’essai relatives aux raccords sertis et à serrage mécanique pour les câbles
d’énergie de tensions assignées supérieures à 1 kV (Um = 1,2 kV) jusqu’à 36 kV (Um =
42 kV) soumis à essai sur des conducteurs non isolés (IEC 61238-1-3:2018)
Ta slovenski standard je istoveten z: EN IEC 61238-1-3:2019
ICS:
29.060.20 Kabli Cables
29.120.20 Spojni elementi Connecting devices
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EUROPEAN STANDARD EN IEC 61238-1-3

NORME EUROPÉENNE
EUROPÄISCHE NORM
September 2019
ICS 29.060.20 Supersedes EN 61238-1:2003 (partially) and all of its
amendments and corrigenda (if any)
English Version
Compression and mechanical connectors for power cables -
Part 1-3: Test methods and requirements for compression and
mechanical connectors for power cables for rated voltages
above 1 kV (U = 1,2 kV) up to 36 kV (U = 42 kV) tested on
m m
non-insulated conductors
(IEC 61238-1-3:2018)
Raccords sertis et à serrage mécanique pour câbles Pressverbinder und Schraubverbinder für Starkstromkabel -
d'énergie - Partie 1-3: Méthodes et exigences d'essai Teil 1-3: Prüfverfahren für und Anforderungen an
relatives aux raccords sertis et à serrage mécanique pour Pressverbinder und Schraubverbinder für Starkstromkabel
les câbles d'énergie de tensions assignées supérieures à für Nennspannungen über 1 kV (U = 1,2 kV) bis zu 36 kV
m
1 kV (U = 1,2 kV) jusqu'à 36 kV (U = 42 kV) soumis à (U = 42 kV), geprüft an nicht isolierten Leitern
m m m
essai sur des conducteurs non isolés (IEC 61238-1-3:2018)
(IEC 61238-1-3:2018)
This European Standard was approved by CENELEC on 2019-07-19. CENELEC members are bound to comply with the CEN/CENELEC
Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the
same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the
Netherlands, Norway, Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom.

European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2019 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Ref. No. EN IEC 61238-1-3:2019 E

European foreword
This document (EN IEC 61238-1-3:2019) consists of the text of IEC 61238-1-3:2018 prepared by
IEC/TC 20 "Electric cables".
The following dates are fixed:
• latest date by which this document has to be (dop) 2020-07-19
implemented at national level by publication of an
identical national standard or by endorsement
• latest date by which the national standards (dow) 2022-07-19
conflicting with this document have to be withdrawn
This document partially supersedes EN 61238-1:2003 and all of its amendments and corrigenda (if
any).
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC shall not be held responsible for identifying any or all such patent rights.
Endorsement notice
The text of the International Standard IEC 61238-1-3:2018 was approved by CENELEC as a
European Standard without any modification.
In the official version, for Bibliography, the following notes have to be added for the standards
indicated:
IEC 61238-1 NOTE  Harmonized as EN 61238-1.
IEC 61238-1-1 NOTE  Harmonized as EN IEC 61238-1-1.
IEC 61238-1-2 NOTE  Harmonized as EN IEC 61238-1-2.
IEC 62475:2010 NOTE  Harmonized as EN 62475:2010 (not modified).

Annex ZA
(normative)
Normative references to international publications
with their corresponding European publications
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments)
applies.
NOTE 1  Where an International Publication has been modified by common modifications, indicated by (mod), the relevant
EN/HD applies.
NOTE 2  Up-to-date information on the latest versions of the European Standards listed in this annex is available here:
www.cenelec.eu.
Publication Year Title EN/HD Year
IEC 60050-461 -  International Electrotechnical Vocabulary - - -
Part 461: Electric cables
IEC 60228 -  Conductors of insulated cables EN 60228 -
IEC 60493-1 -  Guide for the statistical analysis of ageing - -
test data - Part 1: Methods based on mean
values of normally distributed test results
IEC 60949 1988 Calculation of thermally permissible short-- -
+ A1 2008 circuit currents, taking into account non-
adiabatic heating effects
IEC 61238-1-3 ®
Edition 1.0 2018-05
INTERNATIONAL
STANDARD
Compression and mechanical connectors for power cables –

Part 1-3: Test methods and requirements for compression and mechanical

connectors for power cables for rated voltages above 1 kV (U = 1,2 kV) up to

m
30 kV (U = 36 kV) tested on non-insulated conductors
m
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
ICS 29.060.20 ISBN 978-2-8322-5647-3

– 2 – IEC 61238-1-3:2018 © IEC 2018
CONTENTS
FOREWORD . 5
INTRODUCTION . 7
1 Scope . 8
2 Normative references . 8
3 Terms and definitions . 8
4 Symbols . 10
5 General . 11
5.1 Definition of classes . 11
5.2 Conductor . 11
5.3 Connectors and installation procedure . 12
5.4 Range of approval. 12
6 Electrical tests . 13
6.1 Installation . 13
6.1.1 General . 13
6.1.2 Through connectors and terminations . 14
6.1.3 Branch connectors . 14
6.2 Measurements . 14
6.2.1 General . 14
6.2.2 Electrical resistance measurements . 14
6.2.3 Temperature measurements . 15
6.3 Heat cycling test . 15
6.3.1 General . 15
6.3.2 First heat cycle . 15
6.3.3 Second heat cycle . 16
6.3.4 Subsequent heat cycles . 17
6.4 Short-circuit test . 18
6.4.1 General . 18
6.4.2 Aluminium conductors with cross-sectional areas below 1 000 mm and
copper conductors with cross-sectional areas below 630 mm . 18
6.4.3 Aluminium conductors with cross-sectional areas ≥ 1 000 mm and
copper conductors with cross-sectional areas ≥ 630 mm . 19
6.5 Assessment of results . 19
6.6 Requirements . 19
6.7 Examples of electrical test loop configurations and associated parameters . 20
7 Mechanical test . 26
7.1 General . 26
7.2 Method . 26
7.3 Requirements . 27
8 Test report . 27
8.1 General . 27
8.2 Electrical tests . 27
8.3 Mechanical test . 27
Annex A (normative) Equalizers and their preparation . 28
A.1 Requirements for equalizers . 28
A.2 Recommendations for welding equalizers . 28
Annex B (normative) Measurements . 30

IEC 61238-1-3:2018 © IEC 2018 – 3 –
B.1 Potential measuring positions for typical connectors . 30
B.2 Temperature measurement . 30
B.3 Equivalent conductor resistance . 30
Annex C (informative) Recommendations to decrease uncertainties of measurement . 31
C.1 Handling the test loop . 31
C.2 Measurements, instruments and readings . 31
Annex D (normative) Calculation of adiabatic short-circuit current . 32
Annex E (informative) Determination of the value of the short-circuit current . 33
Annex F (normative) Calculation method . 34
F.1 General . 34
F.2 Measurements made . 34
F.3 Connector resistance factor k . 34
F.4 Initial scatter δ . 35
F.5 Mean scatter β . 35
F.6 Change in resistance factor of each connector . 37
F.6.1 General . 37
F.6.2 Line of best fit . 37
F.6.3 Confidence interval δ . 37
i
F.6.4 Change in resistance factor D . 38
F.7 Resistance factor ratio λ. 38
F.8 Maximum temperatures θ . 38
max
Annex G (informative) Explanation on assessment of results of electrical tests on
connectors . 39
G.1 History . 39
G.2 Short examination of the assessment methods of IEC 61238-1 compared

with the Italian standard CEI 20-28 and the British standard BS 4579-3 . 39
G.3 The IEC 61238-1 method of assessing test results . 40
Annex H (informative) Electrical tests on cable terminal lugs for application in
separable connectors . 42
H.1 Principle . 42
H.2 Lengths . 42
H.3 Temperature measurement . 42
H.4 Median connector . 43
H.5 Electrical test parameters . 43
Bibliography . 44

Figure 1 – Example of second heat cycle profile . 17
Figure 2 – Typical electrical test loops for through connectors and terminal lugs . 22
Figure 3 – Typical electrical test loop for branch connectors . 23
Figure 4 – Typical cases of resistance measurements . 26
Figure A.1 – Preparation of equalizers . 29
Figure E.1 – Determination of equivalent RMS value of current during the short-circuit test . 33
Figure F.1 – Graphic example of assessment of a Class A individual connector . 36
Figure H.1 – Test arrangement . 43

Table 1 – Minimum period of temperature stability . 16
Table 2 – Electrical resistance measurements during the electrical test . 18

– 4 – IEC 61238-1-3:2018 © IEC 2018
Table 3 – Electrical test requirements . 20
Table 4 – Selection of tensile force withstand values for the mechanical test . 27
Table D.1 – Material properties . 32
Table G.1 – Summary of assessed behaviour of a tested connector . 40

IEC 61238-1-3:2018 © IEC 2018 – 5 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
COMPRESSION AND MECHANICAL
CONNECTORS FOR POWER CABLES –
Part 1-3: Test methods and requirements for compression and mechanical
connectors for power cables for rated voltages above 1 kV (U = 1,2 kV)
m
up to 30 kV (U = 36 kV) tested on non-insulated conductors
m
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 61238-1-3 has been prepared by IEC technical committee 20:
Electric cables.
This first edition, together with IEC 61238-1-1 and IEC 61238-1-2, cancels and replaces
IEC 61238-1:2003.
This edition includes the following significant technical changes with respect to
IEC 61238-1:2003:
a) The scope has been widened to cover connectors for conductors from 10 mm down to
2 2
2,5 mm and has been limited to 1 200 mm for connectors for copper and aluminium
conductors because test experience and applications are rare for conductors of larger
cross-sectional areas.
– 6 – IEC 61238-1-3:2018 © IEC 2018
b) A new mechanical class has been introduced to satisfy the demand for connectors
subjected to higher mechanical forces than those specified in Class 1 for conductors of
larger cross-sectional areas.
c) For the electrical test, a maximum elevated heating current has been set in order to avoid
unrealistic current densities during the test which may change the properties of tested
connectors.
d) For the short-circuit test, the method of calculation and requirements have been updated.
e) For the mechanical test, the methods and requirements have been updated.
f) A proposal for an electrical test on cable terminal lugs for application in separable
connectors has been introduced.
The text of this standard is based on the following documents:
FDIS Report on voting
20/1790/FDIS 20/1805/RVD
Full information on the voting for the approval of this International Standard can be found in
the report on voting indicated in the above table.
This document has been drafted in accordance with the ISO/IEC Directives, Part 2.
A list of all parts in the IEC 61238 series, published under the general title Compression and
mechanical connectors for power cables, can be found on the IEC website.
The committee has decided that the contents of this document will remain unchanged until the
stability date indicated on the IEC website under "http://webstore.iec.ch" in the data related to
the specific document. At this date, the document will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
A bilingual version of this publication may be issued at a later date.

IEC 61238-1-3:2018 © IEC 2018 – 7 –
INTRODUCTION
The IEC 61238 series has been divided into the following parts:
Part 1-1: Test methods and requirements for compression and mechanical connectors for
power cables for rated voltages up to 1 kV (U = 1,2 kV) tested on non-insulated
m
conductors
Part 1-2: Test methods and requirements for insulation piercing connectors for power
cables for rated voltages up to 1 kV (U = 1,2 kV) tested on insulated conductors
m
Part 1-3: Test methods and requirements for compression and mechanical connectors for
power cables for rated voltages above 1 kV (U = 1,2 kV) up to 30 kV
m
(U = 36 kV) tested on non-insulated conductors
m
This Part 1-3 of IEC 61238 deals with type tests for compression and mechanical connectors
for use on copper or aluminium conductors of power cables for rated voltages above 1 kV
(U = 1,2 kV) up to 30 kV (U = 36 kV).
m m
When a design of connector meets the requirements of this document, then it is expected that
in service:
a) the resistance of the connection will remain stable within specified limits;
b) the temperature of the connector will be of the same order or less than that of the
conductor during current heating;
c) if the intended use demands it, application of short-circuit currents will not affect a)
and b);
d) independently from the electrical performance, conforming axial tensile strength will
ensure an acceptable mechanical performance for the connections to the cable
conductors.
It should be stressed that, although the object of the electrical and mechanical tests specified
in this document is to prove the suitability of connectors for most operating conditions, they do
not necessarily apply to situations where a connector may be raised to a high temperature by
virtue of connection to a highly rated plant, to corrosive conditions, or where the connector is
subjected to external mechanical stresses such as excessive vibration, shock and large
displacement after installation. In these instances, the tests in this document may need to be
supplemented by special tests agreed between supplier and purchaser.
This document does not invalidate existing approvals of products achieved on the basis of
national standards and specifications and/or the demonstration of satisfactory service
performance. However, products approved according to such national standards or
specifications cannot directly claim approval to this document.
Once successfully completed, these tests are not repeated unless changes are made in
material, manufacturing process and design which might adversely change the connector
performance characteristics.
– 8 – IEC 61238-1-3:2018 © IEC 2018
COMPRESSION AND MECHANICAL
CONNECTORS FOR POWER CABLES –
Part 1-3: Test methods and requirements for compression and mechanical
connectors for power cables for rated voltages above 1 kV (U = 1,2 kV)
m
up to 30 kV (U = 36 kV) tested on non-insulated conductors
m
1 Scope
This part of IEC 61238 applies to compression and mechanical connectors for power cables
for rated voltages above 1 kV (U = 1,2 kV) up to 30 kV (U = 36 kV), for example buried
m m
cables or cables installed in buildings, having
a) conductors complying with IEC 60228 having nominal cross-sectional areas between
2 2 2 2
2,5 mm and 1 200 mm for copper and between 16 mm and 1 200 mm for aluminium,
excluding Milliken conductors;
b) a maximum continuous conductor temperature not exceeding 90 °C.
This document is not applicable to connectors for overhead line conductors nor to connectors
with a sliding contact.
The object of this document is to define the type test methods and requirements which apply
to compression and mechanical connectors for power cables with copper or aluminium
conductors. The reference method is to perform the tests on unused conductors.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their
content constitutes requirements of this document. For dated references, only the edition
cited applies. For undated references, the latest edition of the referenced document (including
any amendments) applies.
IEC 60050-461, International Electrotechnical Vocabulary – Part 461: Electric cables
(available at http://www.electropedia.org)
IEC 60228, Conductors of insulated cables
IEC 60493-1, Guide for the statistical analysis of ageing test data – Part 1: Methods based on
mean values of normally distributed test results
IEC 60949:1988, Calculation of thermally permissible short-circuit currents, taking into
account non-adiabatic heating effects
IEC 60949:1988/AMD1:2008
3 Terms and definitions
For the purposes of this document, the terms and definitions given in IEC 60050-461 and the
following apply.
ISO and IEC maintain terminological databases for use in standardization at the following
addresses:
IEC 61238-1-3:2018 © IEC 2018 – 9 –
• IEC Electropedia: available at http://www.electropedia.org/
• ISO Online browsing platform: available at http://www.iso.org/obp
3.1
connector
device for connecting a conductor to an equipment terminal or for connecting two
or more conductors to each other
[SOURCE: IEC 60050-461:2008, 461-17-03, modified – the definition has been revised.]
3.2
through connector
device for connecting two consecutive lengths of conductor together
[SOURCE: IEC 60050-461:2008, 461-17-04, modified – the term "joint ferrule" has been
deleted and the definition revised.]
3.3
branch connector
device for connecting a branch conductor to a main conductor at an intermediate point on the
latter
[SOURCE: IEC 60050-461:2008, 461-17-05, modified – the term "branch ferrule" has been
deleted and in the definition "metallic" has been deleted.]
3.4
termination
device fitted to the end of a cable conductor to ensure electrical connection with other parts of
the system
[SOURCE: IEC 60050-461:2008, 461-10-01, modified – "conductor" has been added and "and
to maintain insulation up to the point of connection" has been deleted.]
3.5
terminal lug
device to connect a cable conductor to other electrical equipment
[SOURCE: IEC 60050-461:2008, 461-17-01, modified – "metallic" has been deleted.]
3.6
palm
part of a terminal lug used to make the connection to electrical equipment
[SOURCE: IEC 60050-461:2008, 461-17-07]
3.7
barrel
part of a device into which the conductor to be connected is
introduced
[SOURCE: IEC 60050-461:2008, 461-17-06]
3.8
reference conductor
length of unjointed bare conductor or conductor with the insulation removed, which is included
in the test loop and which enables the reference temperature and reference resistance to be
determined
– 10 – IEC 61238-1-3:2018 © IEC 2018
3.9
equalizer
arrangement used in the test loop to ensure a point of equipotential and uniform current
distribution in a stranded conductor
3.10
compression jointing
method of securing a connector to a conductor by using a special tool to produce permanent
deformation of the connector and the conductor
3.11
mechanical jointing
method of securing a connector to a conductor, for example by means of a bolt or screw
acting on the latter or by alternative methods
3.12
median connector
connector which during the first heat cycle records the third highest temperature of the six
connectors in the test loop
3.13
conductor
part of a cable which has the specific function of carrying current
[SOURCE: IEC 60050-461:2008, 461-01-01]
3.14
family of connectors
group of connectors of a manufacturer to be considered of the same design criteria, the same
material characteristic and the same installation procedure
4 Symbols
A nominal cross-sectional area of the conductor
D change in the resistance factor of the connector
I direct current flowing through a connection during resistance measurement
I equivalent RMS short-circuit current
RMS
I alternating current necessary to maintain the reference conductor at its
N
equilibrium temperature
I direct current flowing through the reference conductor/conductors during
r
resistance measurement
k
connector resistance factor: ratio of the resistance of a connector to that of the
resistance of the equivalent length of the reference conductor
k initial connector resistance factor: ratio of the resistance of a connector to that of
the resistance of the equivalent length of the reference conductor at cycle no. 0
l , l , l lengths of each connector assembly associated with the measurement positions
a b j
in the test set-up after installation
l
length of the reference conductor between measurement positions
r
R measured resistance value of connector/conductor installation under an electrical
test corrected to 20 °C
R measured resistance value of the reference conductor corrected to 20 °C
r
R length related calculated resistance value of a connector under an electrical test
j
corrected to 20 °C
IEC 61238-1-3:2018 © IEC 2018 – 11 –
t heating time
t time necessary for the connectors and the reference conductor to cool to a value
equal to or less than 35 °C
U potential difference between measurement positions while current I is applied
U potential difference between measurement positions on a reference conductor
r
while current I is applied
r
temperature coefficient of resistance at 20 °C
α
mean scatter of the connector resistance factors
β
initial scatter of the connector resistance factors
δ
λ resistance factor ratio: the actual resistance factor of the connector at each
measurement stage divided by its initial resistance factor
θ temperature of a connector
maximum temperature recorded on a connector over the total period of test
θ
max
during heat cycling
temperature of the reference conductor determined in the first heat cycle
θ
R
temperature of the related reference conductor at the moment of measuring
θ
ref
θ
max
5 General
5.1 Definition of classes
Although it is not possible to define precisely the service conditions for all applications, the
following requirements have been identified.
a) Electrical requirements:
Class A
Connectors related to this document are intended for electricity distribution or industrial
networks in which they can be subjected to short-circuits of relatively high intensity and
duration.
b) Mechanical requirements:
Class 1
Connectors subjected to a mechanical pull-out force related to the conductor nominal
cross-sectional area and material (according to Table 4) but limited to 20 kN pull-out force.
These are, for example, connectors for underground cable joints.
Class 2
Connectors subjected to a mechanical pull-out force above 20 kN and related to the
conductor nominal cross-sectional area and material (according to Table 4). This class is
only applicable to conductor nominal cross-sectional areas ≥ 400 mm copper and
≥ 630 mm aluminium. These are, for example, connectors in cable installations where
thermomechanical forces are estimated to exceed 20 kN.
Hence, the three classes correspond to the following tests:
Class A: heat cycling and short-circuit tests;
Class 1: mechanical test with limited maximum tensile force;
Class 2: mechanical test with no maximum tensile force.
5.2 Conductor
The following information shall be recorded in the test report:

– 12 – IEC 61238-1-3:2018 © IEC 2018
– conductor material;
– nominal cross-sectional area, dimensions and shape;
– detail of conductor construction shall be given when known, or can be determined by
inspection, for example:
• class according to IEC 60228 (solid, stranded and flexible);
• compacted or non-compacted for stranded conductor;
• number and arrangement of strands;
• type of plating, if applicable;
• type of impregnation, water blocking, etc., if applicable.
5.3 Connectors and installation procedure
The following information shall be recorded in the test report:
– the assembly method or the installation instruction that is to be used;
– tooling, dies and any necessary setting;
– if not part of the delivered product, for example at cable conductor termination: bolts, nuts,
washers, lubricant, torque, etc.;
– preparation of contact surfaces, if applicable, for example cleaning, brushing and/or
greasing of inner and/or outer conductor and/or connector surfaces;
– identification of the connector, for example name of the supplier, drawing, reference
number, type.
5.4 Range of approval
In general, tests made on one type of connector/conductor combination apply to that
arrangement only. However, to limit the number of tests, using the same conductor material,
the following is permitted:
– a connector which can be used on stranded round conductors or on stranded sector-
shaped conductors which have been rounded, is approved for both types if satisfactory
results are obtained on a compacted round conductor;
– a connector which covers a range of consecutive cross-sectional areas shall be approved,
if satisfactory results are obtained on the smallest and the largest cross-sectional area;
– if a connector is a through connector for two conductors of different cross-sectional areas,
shapes, or materials, and if the jointing method and the connector barrels used have
already been tested separately for each cross-sectional area, no additional test is
necessary. If not, and if it is required for bimetallic through connectors, additional tests
shall be made using the conductor having the highest temperature of the two conductors,
as reference conductor;
– if a type test for a range taking mechanical connector is passed on the biggest possible
conductor cross-sectional area, this result is also valid for similar connector designs with
the same material of the connector body but bigger outer diameter provided that the
design of the conductor clamping channel (inner diameter, shape, etc.), quantity and
design of clamping screws (torque, material, size, shear-off characteristic, etc.) are
identical;
– if a manufacturer can clearly demonstrate that common and relevant connector design
criteria were used for a family of connectors, conformity to this document is achieved by
successfully testing the largest, the smallest and two intermediate connector sizes;
exception no.1: for a family of connectors consisting of five sizes, only the largest
connector, the smallest connector, and one connector of a representative intermediate
size need to be tested;
exception no.2: for a family of connectors consisting of four sizes or less, only the
largest connector and the smallest connector need to be tested;

IEC 61238-1-3:2018 © IEC 2018 – 13 –
– if conformity to this document is achieved by successfully testing a connector on dry
conductor then approval is achieved for the same conductor used in an impregnated paper
insulated cable;
– for connectors where one or both sides are designed for a range of cross-sectional areas,
and a common clamping or crimping arrangement serves for the connection of the
different cross-sectional areas, then mechanical tests on conductors with the largest and
smallest cross-sectional areas shall be carried out according to Clause 7;
– if conformity to this document is achieved by successfully testing a mechanical connector
on round stranded aluminium conductors, this type test approval can be applied to solid
aluminium conductors of the same cross-sectional area(s);
– if conformity to this document is achieved by successful testing of a through connector,
this type test approval can apply to the barrel of a termination which uses the same design
criteria. Approval of the complete termination can be achieved if the termination
connection does not influence the barrel performance, proven through design parameters,
drawings or through thermal verification test;
– if conformity to this document is achieved by successfully testing a connector on a
conductor with water blocking, approval is achieved for the same conductor without any
water blocking but not for the same conductor with different types of water blocking.
6 Electrical tests
6.1 Installation
6.1.1 General
All conductors of the same cross-sectional area in the test loop shall be taken from the same
conductor length.
For each series of tests, six connectors shall be installed in accordance with the
manufacturer’s instructions, on a bare conductor or on a conductor that has had the insulation
removed before assembly, to form a test loop together with the corresponding reference
conductor.
For stranded conductors, potential differences between the strands at potential measuring
positions can cause errors in measuring electrical resistance. Equalizers according to
Annex A shall be used to overcome this problem and to ensure uniform current distribution in
the reference conductor and between connectors at the equalizer positions. The
recommended method is to prepare equalizers on the test loop before installing connectors.
The test loop shall be installed in a location where the air is calm.
The ambient temperature of the test location shall be between 15 °C and 30 °C.
For conductor cross-sectional areas above 1 000 mm , increasing the ambient temperature
range of the test location between 15 °C and 40 °C is allowed. At the end of the cooling phase
the ambient temperature shall be between 15 °C and 30 °C.
In the case of solid conductors, the potential measuring positions shall be as close as
possible to the connector in order to reduce l and l close to zero.
a b
The test loop may be of any shape according to Figures 2 or 3 provided that it is arranged in
such a way that there is no adverse effect from the floor, walls and ceiling, other test loops
and adjacent test branches.
To facilitate the short-circuit test, the loop may be disassembled as shown in Figure 2 b). In
this case, the sectioning connections shall not influence the temperatures of the test objects
during heating.
– 14 – IEC 61238-1-3:2018 © IEC 2018
Retightening of bolts or screws of the connectors under test is not permitted.
6.1.2 Through connectors and terminations
The test loop shown in Figure 2 indicates the dimensions that shall be used.
Where terminal lugs or mechanical connectors for terminal bars are to be tested, they shall be
bolted to linking bars in accordance with the manufacturer's instructions or the relevant
standards/specifications defining methods and instructions for fastening terminations. These
linking bars shall, at the point of connection, be of the same dimen
...