IEC 61347-2-10:2024
(Main)Controlgear for electric light sources - Safety - Part 2-10: Particular requirements - Electronic controlgear for high-frequency operation of tubular cold-cathode discharge lamps (neon tubes)
Controlgear for electric light sources - Safety - Part 2-10: Particular requirements - Electronic controlgear for high-frequency operation of tubular cold-cathode discharge lamps (neon tubes)
IEC 61347-2-10:2024 specifies safety requirements for electronic controlgear for high-frequency operation of tubular cold-cathode discharge lamps used in signs and luminous discharge tube installations and operating with an output voltage exceeding 1 000 V but not exceeding 10 000 V for direct connection to DC or AC supply voltages not exceeding 1 000 V (at 50 Hz or 60 Hz in case of alternating current). This second edition cancels and replaces the first edition published in 2000 and Amendment 1:2008. This edition constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous edition:
a) introduction of dated references as appropriate;
b) clarification of sample item numbers.
Appareillages de commande pour les sources de lumière électriques - Sécurité - Partie 2-10: Exigences particulières - Appareillages électroniques destinés à l'alimentation en haute fréquence des lampes à décharge tubulaires à cathode froide (tubes néon)
L'IEC 61347-2-10:2024 spécifie les exigences de sécurité des appareillages électroniques destinés à l'alimentation en haute fréquence des lampes à décharge tubulaires à cathode froide utilisées dans les enseignes et les installations à tubes à décharge lumineux et qui fonctionnent à une tension de sortie supérieure à 1 000 V, mais ne dépassant pas 10 000 V, pour la connexion directe à des tensions d'alimentation inférieures ou égales à 1 000 V en courant continu ou courant alternatif (à 50 Hz ou 60 Hz en courant alternatif). Cette seconde édition annule et remplace la première édition parue en 2000 et l'Amendement 1:2008. Cette édition constitue une révision technique.
Cette édition inclut les modifications techniques majeures suivantes par rapport à l'édition précédente:
a) ajout de références datées le cas échéant;
b) clarification des numéros d'entités d'échantillonnage.
General Information
Relations
Overview
IEC 61347-2-10:2024 is the International Electrotechnical Commission standard that specifies safety requirements for electronic controlgear (inverters and converters) used for the high‑frequency operation of tubular cold‑cathode discharge lamps (neon tubes). It applies to controlgear with an output voltage exceeding 1 000 V but not exceeding 10 000 V, intended for direct connection to DC or AC supplies up to 1 000 V (50 Hz or 60 Hz). Edition 2.0 (2024) replaces the 2000 edition and its 2008 amendment and constitutes a technical revision, introducing dated references and clarifying sample item numbers.
Key topics and technical requirements
This part of IEC 61347 is intended to be used together with IEC 61347-1 and covers particular safety and test requirements specific to neon-tube controlgear. Major technical topics include:
- Scope and classification of controlgear for neon signage and luminous-discharge tube installations
- Marking and information: mandatory markings, legibility and durability, and built‑in controlgear labelling
- Terminals and earthing provisions to ensure safe connections and earth-fault protection
- Protection against accidental contact with live parts and insulation requirements
- Moisture resistance, creepage distances and clearances, and resistance to heat, fire and corrosion
- Electric strength and thermal endurance tests for windings and components
- Normal, abnormal and fault condition testing including protective circuits and earth‑leakage protection
- No‑load rated output voltage and rated output current requirements for safe operation
- Construction and mechanical requirements, including screws, current‑carrying parts and connections
- Measurement guidance (Annex IA / Annex I): instrumentation and methods for measuring no‑load output voltage, output current, earth fault currents, amplitude modulation, spikes and high‑frequency harmonics to ensure reproducible test results
- Annex B (informative): schedule of more onerous requirements where applicable
Practical applications and users
IEC 61347-2-10:2024 is essential for:
- Manufacturers and designers of electronic inverters and converters for neon signage and architectural luminous-tube installations
- Product safety and compliance engineers preparing technical files for certification and testing
- Test laboratories and certification bodies performing type testing against IEC lamp-controlgear safety requirements
- Specifiers, procurement teams and installers who require compliance verification for high‑voltage neon controlgear
Related standards
- IEC 61347-1 (general requirements for controlgear) - this part is used in conjunction with IEC 61347-2-10 for complete compliance.
- Refer to the IEC webstore for authoritative publication and updates.
For authoritative purchase or the latest corrigenda/amendments, consult the IEC webstore or your national IEC member committee.
Standards Content (Sample)
IEC 61347-2-10 ®
Edition 2.0 2024-05
REDLINE VERSION
INTERNATIONAL
STANDARD
colour
inside
Lamp controlgear –
Controlgear for electric light sources – Safety –
Part 2-10: Particular requirements for electronic invertors
and convertors for high-frequency operation of cold start
tubulardischarge lamps (neon tubes) Particular requirements – Electronic
controlgear for high-frequency operation of tubular cold-cathode discharge
lamps (neon tubes)
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form
or by any means, electronic or mechanical, including photocopying and microfilm, without permission in writing from
either IEC or IEC's member National Committee in the country of the requester. If you have any questions about IEC
copyright or have an enquiry about obtaining additional rights to this publication, please contact the address below or
your local IEC member National Committee for further information.
IEC Secretariat Tel.: +41 22 919 02 11
3, rue de Varembé info@iec.ch
CH-1211 Geneva 20 www.iec.ch
Switzerland
About the IEC
The International Electrotechnical Commission (IEC) is the leading global organization that prepares and publishes
International Standards for all electrical, electronic and related technologies.
About IEC publications
The technical content of IEC publications is kept under constant review by the IEC. Please make sure that you have the
latest edition, a corrigendum or an amendment might have been published.
IEC publications search - webstore.iec.ch/advsearchform IEC Products & Services Portal - products.iec.ch
The advanced search enables to find IEC publications by a Discover our powerful search engine and read freely all the
variety of criteria (reference number, text, technical publications previews, graphical symbols and the glossary.
committee, …). It also gives information on projects, replaced With a subscription you will always have access to up to date
and withdrawn publications. content tailored to your needs.
IEC Just Published - webstore.iec.ch/justpublished
Electropedia - www.electropedia.org
Stay up to date on all new IEC publications. Just Published
The world's leading online dictionary on electrotechnology,
details all new publications released. Available online and once
containing more than 22 500 terminological entries in English
a month by email.
and French, with equivalent terms in 25 additional languages.
Also known as the International Electrotechnical Vocabulary
IEC Customer Service Centre - webstore.iec.ch/csc
(IEV) online.
If you wish to give us your feedback on this publication or need
further assistance, please contact the Customer Service
Centre: sales@iec.ch.
IEC 61347-2-10 ®
Edition 2.0 2024-05
REDLINE VERSION
INTERNATIONAL
STANDARD
colour
inside
Lamp controlgear –
Controlgear for electric light sources – Safety –
Part 2-10: Particular requirements for electronic invertors
and convertors for high-frequency operation of cold start
tubulardischarge lamps (neon tubes) Particular requirements – Electronic
controlgear for high-frequency operation of tubular cold-cathode discharge
lamps (neon tubes)
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
ICS 29.140.99 ISBN 978-2-8322-8917-4
– 2 – IEC 61347-2-10:2024 RLV © IEC 2024
CONTENTS
FOREWORD . 4
INTRODUCTION . 7
1 Scope . 8
2 Normative references . 9
3 Terms and definitions . 9
4 General requirements . 11
5 General notes on tests . 11
6 Classification . 11
7 Marking . 12
7.1 Marking and information . 12
7.1.1 Items to be marked Mandatory marking . 12
7.1.2 Durability and legibility of marking Information to be provided . 12
7.2 Durability and legibility . 13
7.3 Built-in controlgear . 13
8 Terminals . 13
9 Provisions for Earthing . 13
10 Protection against accidental contact with live parts . 13
11 Moisture resistance and insulation . 14
12 Electric strength . 14
13 Thermal endurance test for windings . 14
14 Normal conditions . 14
15 Abnormal conditions . 15
16 Fault conditions . 16
17 Construction . 16
18 Creepage distances and clearances . 16
19 Protective circuits . 17
19.1 General . 17
19.2 Earth-leakage protection . 17
20 Screws, current-carrying parts and connections . 19
21 Resistance to heat, fire and tracking . 19
22 Resistance to corrosion . 19
23 No-load rated output voltage and rated output current . 19
24 Applicable annexes of IEC 61347-1 . 20
Annex AAnnex I (normative) Measurement of current and voltages in the output
circuits of electronic controlgear for neon tubes . 23
IA.1 General . 23
IA.1.1 Information to be provided by manufacturers . 23
IA.1.2 Measurement of output voltage and current . 23
IA.1.3 Amplitude modulations. 24
IA.1.4 Spikes and high-frequency harmonics. 24
IA.1.5 Test conditions . 24
IA.2 Instrumentation . 24
IA.3 Measurements . 25
IA.3.1 Measurement of no-load output voltage . 25
IA.3.2 Measurement of output current . 26
IA.3.3 Measurement of earth fault currents . 26
Annex B (informative) Schedule of more onerous requirements . 27
Bibliography . 28
– 4 – IEC 61347-2-10:2024 RLV © IEC 2024
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
LAMP CONTROLGEAR –
CONTROLGEAR FOR ELECTRIC LIGHT SOURCES – SAFETY –
Part 2-10: Particular requirements for electronic invertors
and convertors for high-frequency operation of cold start
tubulardischarge lamps (neon tubes)
Particular requirements – Electronic controlgear for high-frequency
operation of tubular cold-cathode discharge lamps (neon tubes)
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote international
co-operation on all questions concerning standardization in the electrical and electronic fields. To this end and
in addition to other activities, IEC publishes International Standards, Technical Specifications, Technical Reports,
Publicly Available Specifications (PAS) and Guides (hereafter referred to as "IEC Publication(s)"). Their
preparation is entrusted to technical committees; any IEC National Committee interested in the subject dealt with
may participate in this preparatory work. International, governmental and non-governmental organizations liaising
with the IEC also participate in this preparation. IEC collaborates closely with the International Organization for
Standardization (ISO) in accordance with conditions determined by agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence between
any IEC Publication and the corresponding national or regional publication shall be clearly indicated in the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) IEC draws attention to the possibility that the implementation of this document may involve the use of (a)
patent(s). IEC takes no position concerning the evidence, validity or applicability of any claimed patent rights in
respect thereof. As of the date of publication of this document, IEC had not received notice of (a) patent(s), which
may be required to implement this document. However, implementers are cautioned that this may not represent
the latest information, which may be obtained from the patent database available at https://patents.iec.ch. IEC
shall not be held responsible for identifying any or all such patent rights.
This redline version of the official IEC Standard allows the user to identify the changes
made to the previous edition IEC 61347-2-10:2000+AMD1:2008 CSV. A vertical bar
appears in the margin wherever a change has been made. Additions are in green text,
deletions are in strikethrough red text.
IEC 61347-2-10 has been prepared by subcommittee 34C: Auxiliaries for lamps, of IEC
technical committee 34: Lighting. It is an International Standard.
This second edition cancels and replaces the first edition published in 2000 and
Amendment 1:2008. This edition constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous
edition:
a) introduction of dated references as appropriate;
b) clarification of sample item numbers.
The text of this International Standard is based on the following documents:
Draft Report on voting
34C/1584/CDV 34C/1592/RVC
Full information on the voting for its approval can be found in the report on voting indicated in
the above table.
The language used for the development of this International Standard is English.
This document was drafted in accordance with ISO/IEC Directives, Part 2, and developed in
accordance with ISO/IEC Directives, Part 1 and ISO/IEC Directives, IEC Supplement, available
at www.iec.ch/members_experts/refdocs. The main document types developed by IEC are
described in greater detail at www.iec.ch/publications.
This document is intended to be used in conjunction with IEC 61347-1:2015 and
IEC 61347-1:2015/AMD1:2017. Where the requirements of any of the clauses of
IEC 61347-1:2015 and IEC 61347-1:2015/AMD1:2017 are referred to in this document by the
phrase "IEC 61347-1:2015, Clause n and IEC 61347-1:2015/AMD1:2017, Clause n apply", this
phrase is interpreted as meaning that all the requirements of the clause in question of
IEC 61347-1:2015 and IEC 61347-1:2015/AMD1:2017 apply, except any which are clearly
inapplicable to the specific type of controlgear covered by this document.
NOTE In this document, the following print type is used:
– compliance statements: in italic type.
A list of all parts in the IEC 61347 series, published under the general title Controlgear for
electric light sources – Safety, can be found on the IEC website.
Future documents in this series will carry the new general title as cited above. Titles of existing
documents in this series will be updated at the time of the next edition.
– 6 – IEC 61347-2-10:2024 RLV © IEC 2024
The committee has decided that the contents of this document will remain unchanged until the
stability date indicated on the IEC website under webstore.iec.ch in the data related to the
specific document. At this date, the document will be
• reconfirmed,
• withdrawn, or
• revised.
IMPORTANT – The "colour inside" logo on the cover page of this document indicates
that it contains colours which are considered to be useful for the correct understanding
of its contents. Users should therefore print this document using a colour printer.
INTRODUCTION
This part of IEC 61347, and the parts which make up IEC 61347-2, in referring to any of the
clauses of IEC 61347-1, specify the extent to which such a clause is applicable and the order
in which the tests are to be performed; they also include additional requirements, as necessary.
All parts which make up IEC 61347-2 are self-contained and, therefore, do not include
references to each other.
Where the requirements of any of the clauses of IEC 61347-1 are referred to in this standard
by the phrase ”The requirements of clause n of IEC 61347-1 apply”, this phrase is interpreted
as meaning that all requirements of the clause in question of part 1 apply, except any which are
clearly inapplicable to the specific type of lamp controlgear covered by this particular part of
IEC 61347-2.
The technical requirements in this document compared to IEC 61347-2-10:2000 and
IEC 61347-2-10:2000/AMD1:2008 are essentially unchanged. Nevertheless, a new edition of
this document could not be avoided, as without the introduction of dated references to
IEC 61347-1:2015 and IEC 61347-1:2015/AMD1:2017, the fourth edition of IEC 61347-1:—
would have been implicitly applicable due to the undated nature of the references to
IEC 61347-1 in IEC 61347-2-10:2000 and IEC 61347-2-10:2000/AMD1:2008.
This document, in referring to any of the clauses of IEC 61347-1:2015 and
IEC 61347-1:2015/AMD1:2017, specifies the extent to which such a clause is applicable.
Additional requirements are also included, as necessary.
In order to check the safety of controlgear, it is necessary to check their performance. However,
since no standardization of the characteristics of neon tubes exists, reference loads are
specified in this document to ensure reproducible test results.
___________
Fourth edition under preparation. Stage at the time of publication IEC FDIS 61347-1:2024.
– 8 – IEC 61347-2-10:2024 RLV © IEC 2024
LAMP CONTROLGEAR –
CONTROLGEAR FOR ELECTRIC LIGHT SOURCES – SAFETY –
Part 2-10: Particular requirements for electronic invertors
and convertors for high-frequency operation of cold start
tubulardischarge lamps (neon tubes)
Particular requirements – Electronic controlgear for high-frequency
operation of tubular cold-cathode discharge lamps (neon tubes)
1 Scope
This part of IEC 61347 specifies particular safety requirements for electronic invertors and
convertors controlgear for high-frequency operation of tubular cold-cathode discharge lamps
used in signs and luminous discharge tube installations and operating with an output voltage
exceeding 1 000 V but not exceeding 10 000 V for direct connection to DC or AC supply
voltages not exceeding 1 000 V (at 50 Hz or 60 Hz or 1 000 V d.c in case of alternating current).
NOTE 1 Historically, such types of controlgear were referred to as invertors or convertors.
NOTE 12 In Japan, the output voltage limit for the application of this document is set to 15 000 V is acceptable.
The requirements for two types of invertors and convertors, types A and B, are specified as
follows:
– Type A unit: an invertor or convertor operating within the frequency range 20 kHz to 50 kHz,
and having an output voltage (between terminals) not exceeding 5 000 V peak, a maximum
output current limited to 35 mA (r.m.s.) and 50 mA (peak value). The supply voltage does
not exceed 250 V at 50 Hz or 60 Hz or 250 V d.c.
NOTE 2 The output current of a type A unit may be considered as not presenting an electric shock hazard due to
the limits on the current and frequency range.
NOTE 3 In Japan, the output voltage of 15 000 V is acceptable.
– Type B unit: an invertor or convertor having a no-load output voltage not exceeding 5 000 V
to earth or 10 000 V between terminals, operating within the frequency range 10 kHz to
100 kHz with a maximum output current limited to 200 mA (r.m.s.) and 400 mA (peak value).
NOTE 4 Type B units require additional protection in the output circuit.
NOTE 5 In Japan, a type B unit exceeding 50 mA and/or the secondary grounded is not acceptable.
In order to check the safety of invertors or convertors, it is necessary to check their
performance. However, since no standardization of the characteristics of neon tubes exists,
reference loads are specified in this standard to ensure reproducible test results.
The rated maximum operating temperature of the winding, t , is not applicable to this standard.
w
This document applies for controlgear of type A and controlgear of type B, which are specified
as follows:
– Type A: controlgear operating within the frequency range 20 kHz to 50 kHz, and having an
output voltage not exceeding 5 000 V peak between terminals, with a maximum output
current limited to 35 mA (RMS) and 50 mA (peak value) and a supply voltage not exceeding
250 V.
NOTE 3 The output current of a type A unit can be considered as not presenting an electric shock hazard due
to the limits on the current and frequency range.
NOTE 4 In Japan, the output voltage of 15 000 V is acceptable.
– Type B: controlgear operating within the frequency range 10 kHz to 100 kHz and having a
no-load output voltage not exceeding 10 000 V between terminals or not exceeding 5 000 V
to earth, with a maximum output current limited to 200 mA (RMS) and 400 mA (peak value).
NOTE 5 In Japan, a type B controlgear providing an output current exceeding 50 mA is not acceptable.
2 Normative references
For the purpose of this part of IEC 61347, the normative references given in clause 2 of
IEC 61347-1 which are mentioned in this standard apply, together with the following normative
references:
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies.
For undated references, the latest edition of the referenced document (including any
amendments) applies.
IEC 60417, Graphical symbols for use on equipment, available at https://www.graphical-
symbols.info/equipment
IEC 60598-1:2020, Luminaires – Part 1: General requirements and tests
IEC 61347-1:2015, Lamp controlgear – Part 1: General and safety requirements
IEC 61347-1:2015/AMD1:2017
ISO 3864:1984, Safety colours and safety signs
ISO 3864-1:2011, Graphical symbols – Safety colours and safety signs – Part 1: Design
principles for safety signs and safety markings
3 Terms and definitions
For the purpose of this part of IEC 61347, the definitions given in clause 3 of IEC 61347-1, with
the exception of definitions 3.14, 3.16 and 3.17 apply, together with the following:
For the purposes of this document, the terms and definitions given in IEC 61347-1 and the
following apply.
ISO and IEC maintain terminology databases for use in standardization at the following
addresses:
• IEC Electropedia: available at https://www.electropedia.org/
• ISO Online browsing platform: available at https://www.iso.org/obp
3.1
tubular cold-cathode discharge lamp
neon tube
discharge tube having cathodes which may be coated with an electron emitting material and
which, during the starting process without external heating, emits electrons by field emission.
tubular discharge lamp in which the light is produced by the positive column of a glow discharge
Note 1 to entry: These lamps have a low-pressure filling of a rare gas (or a mixture of rare gases) and possibly
mercury vapour. They can have an inside coating of fluorescent materials.
– 10 – IEC 61347-2-10:2024 RLV © IEC 2024
3.2
rated no-load rated output voltage
U
o
rated maximum rated voltage between the output terminals or the ends of the integral
connecting leads of the invertor or convertor connected to the rated supply voltage at rated
frequency with no load on the output circuit
Note 1 to entry: For sinusoidal wave forms, the rated no-load output voltage is the RMS value or the peak value
divided by square root of 2. For other waveforms, it is the RMS value or the equivalent value deduced from the peak
value, obtained by mathematical calculation.
Note 2 to entry: For the purposes of this document this definition overrules the one given in IEC 61347-1.
[SOURCE: IEC 61347-1:2015, 3.9, modified – The definition has been adapted for the purposes
of this document and the Notes to entry have been added.]
3.3
invertor
electric energy transducer that converts direct current to alternating current
3.4
convertor
unit for the electronic conversion of AC supply at one frequency to an AC supply at another
frequency
3.5
earth-leakage protective device
device which removes the output power from an invertor or convertor the controlgear in the
event of an earth fault current flowing between any part of the output high-voltage circuit and
earth
3.6
open-circuit protective device
device which removes the output power from an invertor or convertor the controlgear in the
event of non-operation of the tube load or an interruption in the output high-voltage circuit
Note 1 to entry: An open-circuit protective device may operate by detecting an increase in the output voltage or by
other suitable means.
3.7
upper shut-down limit
output voltage of an invertor or convertor the controlgear at which an open-circuit protective
device operates
3.8
output high-voltage circuit
that part of the circuit consisting of
a) cables between the output terminals of the convertor or invertor controlgear and the
discharge tubes,
b) discharge tubes,
c) any series connections between the discharge tubes,
It does not include any internal components or wiring of the invertor or convertor. but not
including any internal components or wiring of the controlgear
3.9
sample
one or more sampling items intended to provide information on the population or on the material
provided by the manufacturer or responsible vendor
[SOURCE: IEC 60050-151:2001, 151-16-19, modified – "provided by the manufacturer or
responsible vendor" has been added.]
3.10
sample item
one of the individual items in a population of similar items, or a portion of material forming a
cohesive entity and taken from one place and at one time
[SOURCE: IEC 60050-151:2001, 151-16-18]
4 General requirements
IEC 61347-1:2015, Clause 4 applies.
For electronic lamp controlgear with means of protection against overheating, additionally
IEC 61347-1:2015, Annex C applies.
Provisions for the rated maximum temperature of the winding t , are not applicable.
w
5 General notes on tests
IEC 61347-1:2015, Clause 5, applies, together with the following:
– IEC 61347-1:2015, Annex H applies.
– One sample item shall be used for all tests, unless otherwise specified in the corresponding
clause.
To allow for parallel testing and reduced test times, additional sample items may be used
except where the outcome of the test can be affected by preceding tests, for example the
tests of Clause 11 and Clause 12.
Specially prepared sample items may be used where required.
For information on requalification of products compliant with the previous edition of this
document, i.e. IEC 61347-2-10:2000 and IEC 61347-2-10:2000/AMD1:2008, refer to Annex B.
6 Classification
IEC 61347-1:2015, Clause 6 applies, together with the following:
Invertors and convertors Additionally, controlgear shall be classified according to their rated
no-load output voltage, the rating of the operating frequency and output current range, as one
of the following:
a) type A invertor or convertor controlgear;
b) type B invertor or convertor controlgear.
Type B invertors or convertors controlgear may have more than one output. In this case, each
output shall comply with the above.
– 12 – IEC 61347-2-10:2024 RLV © IEC 2024
7 Marking
7.1 Marking and information
7.1.1 Items to be marked Mandatory marking
Electronic invertors and convertors for high-frequency operation of cold start tubular discharge
lamps shall be clearly and durably marked, in accordance with the requirements of 7.2 of
IEC 61347-1, with the following markings:
Controlgear, other than integral controlgear, shall be marked with the following:
– items a), b), c), d), e) and f) of IEC 61347-1:2015, 7.1 and IEC 61347-1:2015/AMD1:2017,
7.1;
– on independent electronic invertors and convertors controlgear, a warning notice for high
voltage, e.g. "HIGH VOLTAGE" and a symbol in the form of an arrow in accordance with
IEC 60417-6042:2010-11 and figure 1 of ISO 3864 ISO 3864-1:2011, Figure 3.
This marking shall be placed on the outside of the enclosure of the electronic invertor or
convertor controlgear so that it is clearly visible.
NOTE It is not necessary to mark integral invertors or convertors separately as their marking is the subject of
relevant sign or luminaire standards.
– type A or type B as applicable.
If the electronic invertor or convertor consists of more than one separate unit, the units providing
the output shall be marked with the necessary information about other associated units such as
DC power supplies or capacitors.
7.1.2 Durability and legibility of marking Information to be provided
In addition to the above mandatory marking, The following information, if applicable, shall be
given on the electronic invertor or convertor controlgear, or be made available in the
manufacturer's catalogue or similar:
– items h), k), m), n) and o) of IEC 61347-1:2015, 7.1;
– if the electronic invertor or convertor consists of more than one separate unit, the units
providing the output shall be marked with necessary information about other associated
units such as d.c power supplies or capacitors;
– the range and number of tube types, diameters and lengths recommended for the invertor
or convertor controlgear;
– where the invertor or convertor controlgear is not supplied with integral leads (tails), details
of the recommended cable types and maximum cable lengths;
– details of suitable types of mounting surfaces and recommended mounting arrangements;
– details of earthing arrangements, including connections to the invertor or convertor
controlgear output winding, where appropriate;
– details of any protective circuits incorporated in the invertor or convertor controlgear;
– the following nominal electrical characteristics:
1) output rated no-load output voltage. This marking shall be in the following terms:
• if the output terminal is not connected to an earthing terminal:
".kV" (e.g. 4 kV),
• if one output terminal is connected to an earthing terminal:
"E -.kV" (e.g. E – 4 kV),
• if the centre point of the output winding is referred to an earthing terminal:
". - E -.kV" (e.g. 3 – E – 3 kV);
NOTE In Japan, E -.kV and - E - kV are not used.
For type A units, this will be is equivalent to the peak value. For type B units, it will be
this is equivalent to the RMS value or 0,5 times the peak value, whichever is the greater
larger.
2) rated output current with rated load;
3) rated output frequency.
Where appropriate, the details in items 1) and 2) above shall be marked for each independent
output circuit of an invertor or convertor a controlgear.
7.2 Durability and legibility
IEC 61347-1:2015, 7.2 applies.
7.3 Built-in controlgear
For controlgear without an enclosure and classified as built-in (e.g. open printed circuit board
assembly), only items a) and b) according to IEC 61347-1:2015, 7.1 shall be marked on the
controlgear.
Other mandatory markings shall be provided as information to be given either on the controlgear
or made available in the manufacturer's catalogue or similar.
8 Terminals
IEC 61347-1:2015, Clause 8 and IEC 61347-1:2015/AMD1:2017, Clause 8 apply, together with
the following:
Invertors or convertors Controlgear provided with tails shall comply with the relevant
requirements of IEC 60598-1:2020.
9 Provisions for Earthing
IEC 61347-1:2015, Clause 9 applies, together with the following:
For type B invertors or convertors controlgear, the earthing terminal shall be connected to a
part of the output circuit except where
– the earthing terminal is connected to a part of the output circuit through means to detect
earth-fault currents, or
– there is no direct connection between any part of the output circuit and the earth terminal,
and for example, part(s) of that output circuit are referenced to earth potential by means of
the internal circuits.
Compliance is checked by inspection.
NOTE In Japan, this clause is not applicable.
10 Protection against accidental contact with live parts
IEC 61347-1:2015, Clause 10 and IEC 61347-1:2015/AMD1:2017, Clause 10 apply, together
with the following:
The remaining charge between terminals in the output circuit of an invertor or convertor a
controlgear following a worst case of disconnection shall not exceed 45 µC.
– 14 – IEC 61347-2-10:2024 RLV © IEC 2024
Compliance is checked by measurement.
Where part(s) of the output circuit of an invertor or convertor a controlgear is(are) not connected
to earth, or is(are) not referenced to earth by means of internal circuits, the insulation barrier
between the input and output circuits shall consist of double or reinforced insulation (see test
voltages in Clause 12).
Compliance is checked by the test of Clause 12 (see test voltages).
11 Moisture resistance and insulation
IEC 61347-1:2015, Clause 11 and IEC 61347-1:2015/AMD1:2017, Clause 11 apply, together
with the following:
For type A units controlgear, the capacitance between the output terminals and the metal foil
of not less than 100 cm area placed anywhere on the surface of the enclosure of the invertor
or convertor controlgear shall not exceed 50 pF. During the test the convertor shall not operate.
Compliance is checked by measurement.
12 Electric strength
IEC 61347-1:2015, Clause 12 applies, together with the following:
Test voltages
The test voltages for all invertors and convertors controlgear are:
– twice the rated input voltage plus 1 000 V on the input side, with the output circuits
connected to external metal parts;
– twice the no-load rated output voltage on the output side, the input circuits being connected
to external metal parts.
NOTE In Japan, 1,5 times the test voltage is approved.
IEC 60598-1:2020, Table 10.2 applies for independent invertors or convertors controlgear.
13 Thermal endurance test for windings
An invertor or convertor Controlgear or its support shall not, under normal or abnormal
conditions, have too high a temperature or impair safety.
Compliance is checked by the tests specified in Clause 14, Clause 15 and Clause 16.
14 Normal conditions
The invertor or convertor controlgear shall be installed in its normal operating position arranged
in accordance with the manufacturer's instructions and mounted as shown in IEC 61347-1:2015,
Figure H.1. The test shall be carried out in a draught-free enclosure as specified in IEC 61347-
1:2015, Annex F.
The invertor or convertor controlgear shall be operated with the tube load replaced by the
specified load resistor R (see Annex IA) and with nominal supply voltage.
– In the case of invertors or convertors controlgear which provide near constant current output,
the supply voltage shall be maintained at the nominal value until steady-state temperatures
are obtained.
– In the case of invertors or convertors controlgear which do not provide near constant current
output, adjustments shall be made to the supply voltage until the output current is the same
as the nominal value specified on the label of the invertor or convertor controlgear. The
output current is then maintained at this value until steady-state temperatures are obtained.
If the invertor or convertor controlgear has more than one output, the appropriate load
resistors (R ) shall be connected to each pair of output terminals.
During the test, the temperature on the relevant parts shall not exceed the values specified in
IEC 60598-1:2020, Table 12.1 and Table 12.2.
15 Abnormal conditions
The invertor or convertor controlgear shall be operated under the test conditions specified in
15.2, and according to the manufacturer's instructions (including heatsinks and spacers, if
specified) at the most onerous voltage between 90 % and 110 % of the rated supply voltage for
a period of 1 h. The test shall be carried out in a draught-free enclosure as specified in
IEC 61347-1:2015, Annex F.
The test shall be carried out with one of the following combination of conditions, whichever is
the most onerous. The time interval between tests shall not exceed 15 min.
a) Conditions 1) to 3) applied sequentially.
b) Conditions 2) and 3) applied simultaneously.
1) The output circuit(s) shall be short-circuited.
If there is more than one output circuit, all circuits shall be short-circuited at the same
time.
NOTE 1 If the invertor or convertor controlgear includes means to remove the shut off
output power in the event of a short-circuit of the output load, this test may be omitted.
2) The abnormal load resistor R (see Annex IA) shall be connected across the output
terminals. If the invertor or convertor controlgear has more than one output, the
appropriate abnormal resistors R shall be connected to each pair of output terminals at
the same time.
3) The invertor or convertor controlgear shall be mounted on a 1 mm thick metal sheet,
whose material shall be specified by the manufacturer.
If not specified, then either steel or aluminium (whichever provides the worst condition)
shall be used.
NOTE 2 In addition, other materials may be taken into consideration.
During and at the end of the tests specified in 15.2, the invertor or convertor controlgear shall
show no defect impairing safety, nor shall any smoke be produced.
The temperature of any part of the outer surface of an independent invertor or convertor
controlgear shall not exceed 90 °C. In addition, the output current and voltage shall not exceed
the values specified in Clause 23.
– 16 – IEC 61347-2-10:2024 RLV © IEC 2024
16 Fault conditions
IEC 61347-1:2015, Clause 14 and IEC 61347-1:2015/AMD1:2017, Clause 14 apply, together
with the following:
a) the output shall be short-circuited, or in the case of an invertor or convertor a controlgear
having short-circuit protection, the output shall be connected to resistor R as described in
Annex IA;
b) an earth fault of negligible impedance shall be applied on one or both of the output terminals.
The output current shall not exceed 1,5 times the value specified by the manufacturer in both
cases a) and b).
NOTE The test of b) need is not be applied applicable if there is no earth connection to any part
of the output circuit; or if the invertor or convertor controlgear includes means to remove the
shut off output power in the event of a short-circuit between one of the output terminals and
earth, in accordance with Clause 19.
17 Construction
IEC 61347-1:2015, Clause 15 applies, together with following:
Independent invertors or convertors of class II controlgear construction shall be provided with
an enclosure of insulating material only.
Compliance is checked by inspection.
The cable between the output terminals of an invertor or convertor a controlgear and the
discharge tube shall be of a type specified by the manufacturer of the invertor or convertor
controlgear and shall satisfy the following requirements:
a) be suitable for operation at high frequency;
b) be suitable for operation at the output voltage of the invertor or convertor controlgear.
18 Creepage distances and clearances
IEC 61347-1:2015, Clause 16 and IEC 61347-1:2015/AMD1:2017, Clause 16 apply, together
with the following:
Creepage distances and clearances in the output circuit, whether the invertor or convertor
controlgear is installed in dry or damp situations, shall be not less than the following, expressed
in millimetres:
– minimum creepage distance d = 12 + 6 U
o
– minimum clearance c = 9 + 4,5 U
o
where
U is the rated no-load rated output voltage of the invertor or convertor controlgear supplying
o
the circuit in kilovolts.
The distance through insulation shall be dimensioned according to the application of the
insulation and the working voltage (exceeding 50 V RMS or 71 V peak or DC) and in accordance
with the following:
– supplementary insulation shall have a minimum thickness of 0,4 mm;
– reinforced insulation shall have a minimum thickness of 0,4 mm when not subjected to any
mechanical stress which, at nominal operating temperature, would be likely to lead to
deformation or deterioration of the insulating material.
NOTE Under mechanical stress conditions, it may can be necessary to increase the thickness.
Compliance is checked by measurement and, where specified, by electric strength tests.
19 Protective circuits
Protective circuits in type B invertors and convertors shall comply with the requirements of 19.1,
19.2 and 19.3.
19.1 General
Type A controlgear may, and type B invertors or convertors controlgear shall include earth-
leakage protection to remove the shut off output power in the event of an earth fault occurring
in the output circuits. Protection shall comply with 19.5. If provided, 19.2 applies.
Open circuit protection may be provided. If provided, 19.3 applies.
19.2 If provided, the open-circuit protection of the type B invertors or convertors shall remove
the output power in the event of a disconnection or tube failure occurring in the output circuits.
Protection shall comply with 19.6.
19.3 After an earth fault or open circuit has caused the protective device in an invertor or
convertor to operate, it shall remain as it is until the mains supply is also switched off. When
the mains supply is switched on again, the protective device to remove the output power shall
automatically reset. If the earth-leakage or open-circuit fault is still present at the time of the
reset, the protective device shall operate in accordance with 19.5.3 or 19.6.3.
NOTE Special arrangements may be required in circuits with animation to ensure that any protective device does
not continue to reset.
19.4 Compliance is checked by carrying out the relevant tests in accordance with 19.5 and 19.6.
19.2 Earth-leakage protection
The earth-leakage current shall be measured in accordance with Annex A.
If provided, an earth-leakage protective device shall comply with the requirements of 19.5.1
to 19.5.3.
19.5.1 Earth leakage current
The earth leakage current shall be measured in accordance with Annex I.
19.5.2 Accidental contact
In the event of accidental contact between the high-voltage circuit and earth, the earth-leakage
protective device shall remove the output power of the invertor or convertor.
19.5.3 Earth-lea
...
IEC 61347-2-10 ®
Edition 2.0 2024-05
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
Controlgear for electric light sources – Safety –
Part 2-10: Particular requirements – Electronic controlgear for high-frequency
operation of tubular cold-cathode discharge lamps (neon tubes)
Appareillages de commande pour les sources de lumière électriques – Sécurité –
Partie 2-10: Exigences particulières – Appareillages électroniques destinés à
l'alimentation en haute fréquence des lampes à décharge tubulaires à cathode
froide (tubes néon)
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form
or by any means, electronic or mechanical, including photocopying and microfilm, without permission in writing from
either IEC or IEC's member National Committee in the country of the requester. If you have any questions about IEC
copyright or have an enquiry about obtaining additional rights to this publication, please contact the address below or
your local IEC member National Committee for further information.
Droits de reproduction réservés. Sauf indication contraire, aucune partie de cette publication ne peut être reproduite ni
utilisée sous quelque forme que ce soit et par aucun procédé, électronique ou mécanique, y compris la photocopie et
les microfilms, sans l'accord écrit de l'IEC ou du Comité national de l'IEC du pays du demandeur. Si vous avez des
questions sur le copyright de l'IEC ou si vous désirez obtenir des droits supplémentaires sur cette publication, utilisez
les coordonnées ci-après ou contactez le Comité national de l'IEC de votre pays de résidence.
IEC Secretariat Tel.: +41 22 919 02 11
3, rue de Varembé info@iec.ch
CH-1211 Geneva 20 www.iec.ch
Switzerland
About the IEC
The International Electrotechnical Commission (IEC) is the leading global organization that prepares and publishes
International Standards for all electrical, electronic and related technologies.
About IEC publications
The technical content of IEC publications is kept under constant review by the IEC. Please make sure that you have the
latest edition, a corrigendum or an amendment might have been published.
IEC publications search - webstore.iec.ch/advsearchform IEC Products & Services Portal - products.iec.ch
The advanced search enables to find IEC publications by a Discover our powerful search engine and read freely all the
variety of criteria (reference number, text, technical publications previews, graphical symbols and the glossary.
committee, …). It also gives information on projects, replaced With a subscription you will always have access to up to date
and withdrawn publications. content tailored to your needs.
IEC Just Published - webstore.iec.ch/justpublished
Electropedia - www.electropedia.org
Stay up to date on all new IEC publications. Just Published
The world's leading online dictionary on electrotechnology,
details all new publications released. Available online and once
containing more than 22 500 terminological entries in English
a month by email.
and French, with equivalent terms in 25 additional languages.
Also known as the International Electrotechnical Vocabulary
IEC Customer Service Centre - webstore.iec.ch/csc
(IEV) online.
If you wish to give us your feedback on this publication or need
further assistance, please contact the Customer Service
Centre: sales@iec.ch.
A propos de l'IEC
La Commission Electrotechnique Internationale (IEC) est la première organisation mondiale qui élabore et publie des
Normes internationales pour tout ce qui a trait à l'électricité, à l'électronique et aux technologies apparentées.
A propos des publications IEC
Le contenu technique des publications IEC est constamment revu. Veuillez vous assurer que vous possédez l’édition la
plus récente, un corrigendum ou amendement peut avoir été publié.
Recherche de publications IEC - IEC Products & Services Portal - products.iec.ch
webstore.iec.ch/advsearchform Découvrez notre puissant moteur de recherche et consultez
La recherche avancée permet de trouver des publications IEC gratuitement tous les aperçus des publications, symboles
en utilisant différents critères (numéro de référence, texte, graphiques et le glossaire. Avec un abonnement, vous aurez
comité d’études, …). Elle donne aussi des informations sur les toujours accès à un contenu à jour adapté à vos besoins.
projets et les publications remplacées ou retirées.
Electropedia - www.electropedia.org
IEC Just Published - webstore.iec.ch/justpublished
Le premier dictionnaire d'électrotechnologie en ligne au monde,
Restez informé sur les nouvelles publications IEC. Just
avec plus de 22 500 articles terminologiques en anglais et en
Published détaille les nouvelles publications parues.
français, ainsi que les termes équivalents dans 25 langues
Disponible en ligne et une fois par mois par email.
additionnelles. Egalement appelé Vocabulaire
Electrotechnique International (IEV) en ligne.
Service Clients - webstore.iec.ch/csc
Si vous désirez nous donner des commentaires sur cette
publication ou si vous avez des questions contactez-nous:
sales@iec.ch.
IEC 61347-2-10 ®
Edition 2.0 2024-05
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
Controlgear for electric light sources – Safety –
Part 2-10: Particular requirements – Electronic controlgear for high-frequency
operation of tubular cold-cathode discharge lamps (neon tubes)
Appareillages de commande pour les sources de lumière électriques – Sécurité –
Partie 2-10: Exigences particulières – Appareillages électroniques destinés à
l'alimentation en haute fréquence des lampes à décharge tubulaires à cathode
froide (tubes néon)
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE
ICS 29.140.99 ISBN 978-2-8322-8839-9
– 2 – IEC 61347-2-10:2024 © IEC 2024
CONTENTS
FOREWORD . 4
INTRODUCTION . 6
1 Scope . 7
2 Normative references . 7
3 Terms and definitions . 8
4 General requirements . 9
5 General notes on tests . 9
6 Classification . 10
7 Marking . 10
7.1 Marking and information . 10
7.1.1 Mandatory marking . 10
7.1.2 Information to be provided . 10
7.2 Durability and legibility . 11
7.3 Built-in controlgear . 11
8 Terminals . 11
9 Earthing . 11
10 Protection against accidental contact with live parts . 11
11 Moisture resistance and insulation . 12
12 Electric strength . 12
13 Thermal endurance test for windings . 12
14 Normal conditions . 12
15 Abnormal conditions . 13
16 Fault conditions . 13
17 Construction . 14
18 Creepage distances and clearances . 14
19 Protective circuits . 14
19.1 General . 14
19.2 Earth-leakage protection . 15
19.3 Open-circuit protection . 15
20 Screws, current-carrying parts and connections . 16
21 Resistance to heat, fire and tracking . 16
22 Resistance to corrosion . 16
23 No-load rated output voltage and rated output current . 16
24 Applicable annexes of IEC 61347-1 . 16
Annex A (normative) Measurement of current and voltages in the output circuits of
electronic controlgear for neon tubes . 17
A.1 General . 17
A.1.1 Information to be provided by manufacturers . 17
A.1.2 Measurement of output voltage and current . 17
A.1.3 Amplitude modulations. 17
A.1.4 Spikes and high-frequency harmonics. 18
A.1.5 Test conditions . 18
A.2 Instrumentation . 18
A.3 Measurements . 19
A.3.1 Measurement of no-load output voltage . 19
A.3.2 Measurement of output current . 19
A.3.3 Measurement of earth fault currents . 20
Annex B (informative) Schedule of more onerous requirements . 21
Bibliography . 22
– 4 – IEC 61347-2-10:2024 © IEC 2024
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
CONTROLGEAR FOR ELECTRIC LIGHT SOURCES – SAFETY –
Part 2-10: Particular requirements –
Electronic controlgear for high-frequency operation of tubular
cold-cathode discharge lamps (neon tubes)
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote international
co-operation on all questions concerning standardization in the electrical and electronic fields. To this end and
in addition to other activities, IEC publishes International Standards, Technical Specifications, Technical Reports,
Publicly Available Specifications (PAS) and Guides (hereafter referred to as "IEC Publication(s)"). Their
preparation is entrusted to technical committees; any IEC National Committee interested in the subject dealt with
may participate in this preparatory work. International, governmental and non-governmental organizations liaising
with the IEC also participate in this preparation. IEC collaborates closely with the International Organization for
Standardization (ISO) in accordance with conditions determined by agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence between
any IEC Publication and the corresponding national or regional publication shall be clearly indicated in the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) IEC draws attention to the possibility that the implementation of this document may involve the use of (a)
patent(s). IEC takes no position concerning the evidence, validity or applicability of any claimed patent rights in
respect thereof. As of the date of publication of this document, IEC had not received notice of (a) patent(s), which
may be required to implement this document. However, implementers are cautioned that this may not represent
the latest information, which may be obtained from the patent database available at https://patents.iec.ch. IEC
shall not be held responsible for identifying any or all such patent rights.
IEC 61347-2-10 has been prepared by subcommittee 34C: Auxiliaries for lamps, of IEC
technical committee 34: Lighting. It is an International Standard.
This second edition cancels and replaces the first edition published in 2000 and
Amendment 1:2008. This edition constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous
edition:
a) introduction of dated references as appropriate;
b) clarification of sample item numbers.
The text of this International Standard is based on the following documents:
Draft Report on voting
34C/1584/CDV 34C/1592/RVC
Full information on the voting for its approval can be found in the report on voting indicated in
the above table.
The language used for the development of this International Standard is English.
This document was drafted in accordance with ISO/IEC Directives, Part 2, and developed in
accordance with ISO/IEC Directives, Part 1 and ISO/IEC Directives, IEC Supplement, available
at www.iec.ch/members_experts/refdocs. The main document types developed by IEC are
described in greater detail at www.iec.ch/publications.
This document is intended to be used in conjunction with IEC 61347-1:2015 and
IEC 61347-1:2015/AMD1:2017. Where the requirements of any of the clauses of
IEC 61347-1:2015 and IEC 61347-1:2015/AMD1:2017 are referred to in this document by the
phrase "IEC 61347-1:2015, Clause n and IEC 61347-1:2015/AMD1:2017, Clause n apply", this
phrase is interpreted as meaning that all the requirements of the clause in question of
IEC 61347-1:2015 and IEC 61347-1:2015/AMD1:2017 apply, except any which are clearly
inapplicable to the specific type of controlgear covered by this document.
NOTE In this document, the following print type is used:
– compliance statements: in italic type.
A list of all parts in the IEC 61347 series, published under the general title Controlgear for
electric light sources – Safety, can be found on the IEC website.
Future documents in this series will carry the new general title as cited above. Titles of existing
documents in this series will be updated at the time of the next edition.
The committee has decided that the contents of this document will remain unchanged until the
stability date indicated on the IEC website under webstore.iec.ch in the data related to the
specific document. At this date, the document will be
• reconfirmed,
• withdrawn, or
• revised.
– 6 – IEC 61347-2-10:2024 © IEC 2024
INTRODUCTION
The technical requirements in this document compared to IEC 61347-2-10:2000 and
IEC 61347-2-10:2000/AMD1:2008 are essentially unchanged. Nevertheless, a new edition of
this document could not be avoided, as without the introduction of dated references to
IEC 61347-1:2015 and IEC 61347-1:2015/AMD1:2017, the fourth edition of IEC 61347-1:—
would have been implicitly applicable due to the undated nature of the references to
IEC 61347-1 in IEC 61347-2-10:2000 and IEC 61347-2-10:2000/AMD1:2008.
This document, in referring to any of the clauses of IEC 61347-1:2015 and
IEC 61347-1:2015/AMD1:2017, specifies the extent to which such a clause is applicable.
Additional requirements are also included, as necessary.
In order to check the safety of controlgear, it is necessary to check their performance. However,
since no standardization of the characteristics of neon tubes exists, reference loads are
specified in this document to ensure reproducible test results.
___________
Fourth edition under preparation. Stage at the time of publication IEC FDIS 61347-1:2024.
CONTROLGEAR FOR ELECTRIC LIGHT SOURCES – SAFETY –
Part 2-10: Particular requirements –
Electronic controlgear for high-frequency operation of tubular
cold-cathode discharge lamps (neon tubes)
1 Scope
This part of IEC 61347 specifies safety requirements for electronic controlgear for high-
frequency operation of tubular cold-cathode discharge lamps used in signs and luminous
discharge tube installations and operating with an output voltage exceeding 1 000 V but not
exceeding 10 000 V for direct connection to DC or AC supply voltages not exceeding 1 000 V
(at 50 Hz or 60 Hz in case of alternating current).
NOTE 1 Historically, such types of controlgear were referred to as invertors or convertors.
NOTE 2 In Japan, the voltage limit for the application of this document is set to 15 000 V.
This document applies for controlgear of type A and controlgear of type B, which are specified
as follows:
– Type A: controlgear operating within the frequency range 20 kHz to 50 kHz, and having an
output voltage not exceeding 5 000 V peak between terminals, with a maximum output
current limited to 35 mA (RMS) and 50 mA (peak value) and a supply voltage not exceeding
250 V.
NOTE 3 The output current of a type A unit can be considered as not presenting an electric shock hazard due
to the limits on the current and frequency range.
NOTE 4 In Japan, the output voltage of 15 000 V is acceptable.
– Type B: controlgear operating within the frequency range 10 kHz to 100 kHz and having a
no-load output voltage not exceeding 10 000 V between terminals or not exceeding 5 000 V
to earth, with a maximum output current limited to 200 mA (RMS) and 400 mA (peak value).
NOTE 5 In Japan, a type B controlgear providing an output current exceeding 50 mA is not acceptable.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies.
For undated references, the latest edition of the referenced document (including any
amendments) applies.
IEC 60417, Graphical symbols for use on equipment, available at https://www.graphical-
symbols.info/equipment
IEC 60598-1:2020, Luminaires – Part 1: General requirements and tests
IEC 61347-1:2015, Lamp controlgear – Part 1: General and safety requirements
IEC 61347-1:2015/AMD1:2017
ISO 3864-1:2011, Graphical symbols – Safety colours and safety signs – Part 1: Design
principles for safety signs and safety markings
– 8 – IEC 61347-2-10:2024 © IEC 2024
3 Terms and definitions
For the purposes of this document, the terms and definitions given in IEC 61347-1 and the
following apply.
ISO and IEC maintain terminology databases for use in standardization at the following
addresses:
• IEC Electropedia: available at https://www.electropedia.org/
• ISO Online browsing platform: available at https://www.iso.org/obp
3.1
tubular cold-cathode discharge lamp
neon tube
tubular discharge lamp in which the light is produced by the positive column of a glow discharge
Note 1 to entry: These lamps have a low-pressure filling of a rare gas (or a mixture of rare gases) and possibly
mercury vapour. They can have an inside coating of fluorescent materials.
3.2
rated no-load output voltage
U
o
rated maximum voltage between the output terminals or the ends of the integral connecting
leads of the invertor or convertor connected to the rated supply voltage at rated frequency with
no load on the output circuit
Note 1 to entry: For sinusoidal wave forms, the rated no-load output voltage is the RMS value or the peak value
divided by square root of 2. For other waveforms, it is the RMS value or the equivalent value deduced from the peak
value, obtained by mathematical calculation.
Note 2 to entry: For the purposes of this document this definition overrules the one given in IEC 61347-1.
[SOURCE: IEC 61347-1:2015, 3.9, modified – The definition has been adapted for the purposes
of this document and the Notes to entry have been added.]
3.3
invertor
electric energy transducer that converts direct current to alternating current
3.4
convertor
unit for the electronic conversion of AC supply at one frequency to an AC supply at another
frequency
3.5
earth-leakage protective device
device which removes the output power from the controlgear in the event of an earth fault
current flowing between any part of the output high-voltage circuit and earth
3.6
open-circuit protective device
device which removes the output power from the controlgear in the event of non-operation of
the tube load or an interruption in the output high-voltage circuit
Note 1 to entry: An open-circuit protective device may operate by detecting an increase in the output voltage or by
other suitable means.
3.7
upper shut-down limit
output voltage of the controlgear at which an open-circuit protective device operates
3.8
output high-voltage circuit
that part of the circuit consisting of
a) cables between the output terminals of the controlgear and the discharge tubes,
b) discharge tubes,
c) any series connections between the discharge tubes,
but not including any internal components or wiring of the controlgear
3.9
sample
one or more sampling items intended to provide information on the population or on the material
provided by the manufacturer or responsible vendor
[SOURCE: IEC 60050-151:2001, 151-16-19, modified – "provided by the manufacturer or
responsible vendor" has been added.]
3.10
sample item
one of the individual items in a population of similar items, or a portion of material forming a
cohesive entity and taken from one place and at one time
[SOURCE: IEC 60050-151:2001, 151-16-18]
4 General requirements
IEC 61347-1:2015, Clause 4 applies.
For electronic lamp controlgear with means of protection against overheating, additionally
IEC 61347-1:2015, Annex C applies.
Provisions for the rated maximum temperature of the winding t , are not applicable.
w
5 General notes on tests
IEC 61347-1:2015, Clause 5, applies, together with the following:
– IEC 61347-1:2015, Annex H applies.
– One sample item shall be used for all tests, unless otherwise specified in the corresponding
clause.
To allow for parallel testing and reduced test times, additional sample items may be used
except where the outcome of the test can be affected by preceding tests, for example the
tests of Clause 11 and Clause 12.
Specially prepared sample items may be used where required.
For information on requalification of products compliant with the previous edition of this
document, i.e. IEC 61347-2-10:2000 and IEC 61347-2-10:2000/AMD1:2008, refer to Annex B.
– 10 – IEC 61347-2-10:2024 © IEC 2024
6 Classification
IEC 61347-1:2015, Clause 6 applies, together with the following:
Additionally, controlgear shall be classified according to their rated no-load output voltage, the
rating of the operating frequency and output current range, as one of the following:
a) type A controlgear;
b) type B controlgear.
Type B controlgear may have more than one output. In this case, each output shall comply with
the above.
7 Marking
7.1 Marking and information
7.1.1 Mandatory marking
Controlgear, other than integral controlgear, shall be marked with the following:
– items a), b), c), d), e) and f) of IEC 61347-1:2015, 7.1 and IEC 61347-1:2015/AMD1:2017,
7.1;
– on independent controlgear, a warning notice for high voltage, e.g. "HIGH VOLTAGE" and
a symbol in the form of an arrow in accordance with IEC 60417-6042:2010-11 and
ISO 3864-1:2011, Figure 3.
This marking shall be placed on the outside of the enclosure of the controlgear so that it is
clearly visible.
– type A or type B as applicable.
If the electronic invertor or convertor consists of more than one separate unit, the units providing
the output shall be marked with the necessary information about other associated units such as
DC power supplies or capacitors.
7.1.2 Information to be provided
The following information, if applicable, shall be given on the controlgear, or be made available
in the manufacturer's catalogue or similar:
– items h), k), m), n) and o) of IEC 61347-1:2015, 7.1;
– the range and number of tube types, diameters and lengths recommended for the
controlgear;
– where the controlgear is not supplied with integral leads (tails), details of the recommended
cable types and maximum cable lengths;
– details of suitable types of mounting surfaces and recommended mounting arrangements;
– details of earthing arrangements, including connections to the controlgear output winding,
where appropriate;
– details of any protective circuits incorporated in the controlgear;
– the following electrical characteristics:
1) rated no-load output voltage. This marking shall be in the following terms:
• if the output terminal is not connected to an earthing terminal:
".kV" (e.g. 4 kV),
• if one output terminal is connected to an earthing terminal:
"E -.kV" (e.g. E – 4 kV),
• if the centre point of the output winding is referred to an earthing terminal:
". - E -.kV" (e.g. 3 – E – 3 kV);
NOTE In Japan, E -.kV and - E - kV are not used.
For type A units, this is equivalent to the peak value. For type B units this is equivalent
to the RMS value or 0,5 times the peak value, whichever is larger.
2) rated output current with rated load;
3) rated output frequency.
Where appropriate, the details in items 1) and 2) above shall be marked for each independent
output circuit of a controlgear.
7.2 Durability and legibility
IEC 61347-1:2015, 7.2 applies.
7.3 Built-in controlgear
For controlgear without an enclosure and classified as built-in (e.g. open printed circuit board
assembly), only items a) and b) according to IEC 61347-1:2015, 7.1 shall be marked on the
controlgear.
Other mandatory markings shall be provided as information to be given either on the controlgear
or made available in the manufacturer's catalogue or similar.
8 Terminals
IEC 61347-1:2015, Clause 8 and IEC 61347-1:2015/AMD1:2017, Clause 8 apply, together with
the following:
Controlgear provided with tails shall comply with the relevant requirements of
IEC 60598-1:2020.
9 Earthing
IEC 61347-1:2015, Clause 9 applies, together with the following:
For type B controlgear, the earthing terminal shall be connected to a part of the output circuit
except where
– the earthing terminal is connected to a part of the output circuit through means to detect
earth-fault currents, or
– there is no direct connection between any part of the output circuit and the earth terminal,
and for example, part(s) of that output circuit are referenced to earth potential by means of
the internal circuits.
Compliance is checked by inspection.
10 Protection against accidental contact with live parts
IEC 61347-1:2015, Clause 10 and IEC 61347-1:2015/AMD1:2017, Clause 10 apply, together
with the following:
The remaining charge between terminals in the output circuit of a controlgear following a worst
case of disconnection shall not exceed 45 µC.
– 12 – IEC 61347-2-10:2024 © IEC 2024
Compliance is checked by measurement.
Where part(s) of the output circuit of a controlgear is(are) not connected to earth, or is(are) not
referenced to earth by means of internal circuits, the insulation barrier between the input and
output circuits shall consist of double or reinforced insulation (see test voltages in Clause 12).
Compliance is checked by the test of Clause 12 (see test voltages).
11 Moisture resistance and insulation
IEC 61347-1:2015, Clause 11 and IEC 61347-1:2015/AMD1:2017, Clause 11 apply, together
with the following:
For type A controlgear, the capacitance between the output terminals and the metal foil of not
less than 100 cm area placed anywhere on the surface of the enclosure of the controlgear
shall not exceed 50 pF. During the test the convertor shall not operate.
Compliance is checked by measurement.
12 Electric strength
IEC 61347-1:2015, Clause 12 applies, together with the following:
The test voltages for all controlgear are:
– twice the rated input voltage plus 1 000 V on the input side, with the output circuits
connected to external metal parts;
– twice the no-load rated output voltage on the output side, the input circuits being connected
to external metal parts.
NOTE In Japan, 1,5 times the test voltage is approved.
IEC 60598-1:2020, Table 10.2 applies for independent controlgear.
13 Thermal endurance test for windings
Controlgear or its support shall not, under normal or abnormal conditions, have too high a
temperature or impair safety.
Compliance is checked by the tests specified in Clause 14, Clause 15 and Clause 16.
14 Normal conditions
The controlgear shall be installed in its normal operating position arranged in accordance with
the manufacturer's instructions and mounted as shown in IEC 61347-1:2015, Figure H.1. The
test shall be carried out in a draught-free enclosure as specified in IEC 61347-1:2015, Annex F.
The controlgear shall be operated with the tube load replaced by the specified load resistor R
(see Annex A) and with nominal supply voltage.
– In the case of controlgear which provide near constant current output, the supply voltage
shall be maintained at the nominal value until steady-state temperatures are obtained.
– In the case of controlgear which do not provide near constant current output, adjustments
shall be made to the supply voltage until the output current is the same as the nominal value
specified on the label of the controlgear. The output current is then maintained at this value
until steady-state temperatures are obtained. If the controlgear has more than one output,
the appropriate load resistors (R ) shall be connected to each pair of output terminals.
During the test, the temperature on the relevant parts shall not exceed the values specified in
IEC 60598-1:2020, Table 12.1 and Table 12.2.
15 Abnormal conditions
The controlgear shall be operated according to the manufacturer's instructions (including
heatsinks and spacers, if specified) at the most onerous voltage between 90 % and 110 % of
the rated supply voltage for a period of 1 h. The test shall be carried out in a draught-free
enclosure as specified in IEC 61347-1:2015, Annex F.
The test shall be carried out with one of the following combination of conditions, whichever is
the most onerous. The time interval between tests shall not exceed 15 min.
a) Conditions 1) to 3) applied sequentially.
b) Conditions 2) and 3) applied simultaneously.
1) The output circuit(s) shall be short-circuited.
If there is more than one output circuit, all circuits shall be short-circuited at the same
time.
If the controlgear includes means to shut off output power in the event of a short-circuit
of the output load, this test may be omitted.
2) The abnormal load resistor R (see Annex A) shall be connected across the output
terminals. If the controlgear has more than one output, the appropriate abnormal
resistors R shall be connected to each pair of output terminals at the same time.
3) The controlgear shall be mounted on a 1 mm thick metal sheet, whose material shall be
specified by the manufacturer.
If not specified, then either steel or aluminium (whichever provides the worst condition)
shall be used.
During and at the end of the tests the controlgear shall show no defect impairing safety, nor
shall any smoke be produced.
The temperature of any part of the outer surface of an independent controlgear shall not exceed
90 °C. In addition, the output current and voltage shall not exceed the values specified in
Clause 23.
16 Fault conditions
IEC 61347-1:2015, Clause 14 and IEC 61347-1:2015/AMD1:2017, Clause 14 apply, together
with the following:
a) the output shall be short-circuited, or in the case of a controlgear having short-circuit
protection, the output shall be connected to resistor R as described in Annex A;
b) an earth fault of negligible impedance shall be applied on one or both of the output terminals.
The output current shall not exceed 1,5 times the value specified by the manufacturer in both
cases a) and b).
– 14 – IEC 61347-2-10:2024 © IEC 2024
The test of b) is not applicable if there is no earth connection to any part of the output circuit;
or if the controlgear includes means to shut off output power in the event of a short-circuit
between one of the output terminals and earth, in accordance with Clause 19.
17 Construction
IEC 61347-1:2015, Clause 15 applies, together with following:
Independent class II controlgear construction shall be provided with an enclosure of insulating
material only.
Compliance is checked by inspection.
The cable between the output terminals of a controlgear and the discharge tube shall be of a
type specified by the manufacturer of the controlgear and shall satisfy the following
requirements:
a) be suitable for operation at high frequency;
b) be suitable for operation at the output voltage of the controlgear.
18 Creepage distances and clearances
IEC 61347-1:2015, Clause 16 and IEC 61347-1:2015/AMD1:2017, Clause 16 apply, together
with the following:
Creepage distances and clearances in the output circuit, whether the controlgear is installed in
dry or damp situations, shall be not less than the following, expressed in millimetres:
– minimum creepage distance d = 12 + 6 U
o
– minimum clearance c = 9 + 4,5 U
o
where
U is the rated no-load output voltage of the controlgear supplying the circuit in kilovolts.
o
The distance through insulation shall be dimensioned according to the application of the
insulation and the working voltage (exceeding 50 V RMS or 71 V peak or DC) and in accordance
with the following:
– supplementary insulation shall have a minimum thickness of 0,4 mm;
– reinforced insulation shall have a minimum thickness of 0,4 mm when not subjected to any
mechanical stress which, at nominal operating temperature, would be likely to lead to
deformation or deterioration of the insulating material.
NOTE Under mechanical stress conditions, it can be necessary to increase the thickness.
Compliance is checked by measurement and, where specified, by electric strength tests.
19 Protective circuits
19.1 General
Type A controlgear may, and type B controlgear shall include earth-leakage protection to shut
off output power in the event of an earth fault occurring in the output circuits. If provided, 19.2
applies.
Open circuit protection may be provided. If provided, 19.3 applies.
19.2 Earth-leakage protection
The earth-leakage current shall be measured in accordance with Annex A.
The earth-leakage protective device shall comply with the following requirements:
a) If any part of the sensor or of the protective switch or of the device to shut off output power,
or more than one of these, are mounted within the case of the controlgear, the device shall
operate correctly over the temperature range as specified by the manufacturer.
b) If the sensor or the protective device to shut off output power, or both, are mounted in a
position not within the case of the controlgear, the device shall operate correctly over a
temperature range of –25 °C to +65 °C.
c) The rated operating current of the protective device shall be less than the rated output
current of the controlgear to be protected and shall not exceed 25 mA.
NOTE 1 The actual current which flows through the sensor circuit during an earth fault is determined by the
impedance of that fault path and the output characteristics of the controlgear feeding the fault. It does not depend
on the operating current of the protection device.
d) The time to operate, at rated fault current, shall not exceed 200 ms.
After an earth fault or open circuit has caused the protective device in a controlgear to operate,
it shall remain as it is until the mains supply is also switched off. When the mains supply is
switched on again, the protective device to shut off output power shall automatically reset. If
the earth-leakage or open-circuit fault is still present at the time of the reset, the protective
device shall operate in accordance with a) to d).
NOTE 2 Special arrangements can be necessary in circuits with animation to ensure that any protective device
does not continue to reset.
In the event of accidental contact between the high-voltage circuit and earth, the earth-leakage
protective device shall shut off the output power of the controlgear.
19.3 Open-circuit protection
For open circuit protection the following requirements apply:
The open-circuit voltage shall be measured in accordance with Annex A.
In the event of the upper shut-down limit being exceeded, the open-circuit protective device
shall shut off the output power of the controlgear. Detection of a fault condition shall be by
means of sensor(s) connected in the output circuit(s), or other suitable means.
The open-circuit protective device shall comply with the following requirements:
a) If any part of the sensor or of the protective switch or of the device to shut off output power,
or more than one of these, are mounted within the case of the controlgear, the device shall
operate correctly over the temperature range as specified by the manufacturer.
b) If the sensor or the protective device to shut off output power, or both, are mounted in a
position not within the case of the controlgear, the device shall operate correctly over a
temperature range of –25 °C to +65 °C.
c) If the controlgear is switched on with an open-circuit condition as described in A.3.1, the
protective device shall operate in not more than 5 s.
d) If an open circuit occurs, as described in A.3.1, whilst the installation is switched on, the
protective device shall operate in a time not exceeding 200 ms. If the mains supply is then
switched off and switched on again, with the open-circuit condition still persisting, the device
shall operate in not more than 5 s.
– 16 – IEC 61347-2-10:2024 © IEC 2024
NOTE Special arrangements can be necessary in circuits with animation to ensure that any protective device does
not continue to reset.
After an open circuit has caused the protective device in a controlgear to operate, it shall remain
as it is until the mains supply is also switched off. When the mains supply is switched on again,
the protective device to shut off output power shall automatically reset. If the open-circuit fault
is still present at the time of the reset, the protective device shall operate in accordance with a)
to d).
20 Screws, current-carrying parts and connections
IEC 61347-1:2015, Clause 17 applies.
21 Resistance to heat, fire and tracking
IEC 61347-1:2015, Clause 18 applies.
22 Resistance to corrosion
IEC 61347-1:2015, Clause 19 applies.
23 No-load rated output voltage and rated output current
The rated no-load output voltage of type A controlgear shall not exceed 5 000 V peak either
between terminals or to earth.
The rated no-load output voltage of type B controlgear shall not exceed 5 000 V to earth or
10 000 V between terminals.
Compliance of the rated no-load output voltage is checked by measurement.
The rated output current of type A controlgear, measured in accordance with Annex A, shall not
exceed either 35 mA (RMS) or 50 mA peak, whichever is larger.
The rated output current of type B controlgear, measured in accordance with Annex A, shall not
...
Frequently Asked Questions
IEC 61347-2-10:2024 is a standard published by the International Electrotechnical Commission (IEC). Its full title is "Controlgear for electric light sources - Safety - Part 2-10: Particular requirements - Electronic controlgear for high-frequency operation of tubular cold-cathode discharge lamps (neon tubes)". This standard covers: IEC 61347-2-10:2024 specifies safety requirements for electronic controlgear for high-frequency operation of tubular cold-cathode discharge lamps used in signs and luminous discharge tube installations and operating with an output voltage exceeding 1 000 V but not exceeding 10 000 V for direct connection to DC or AC supply voltages not exceeding 1 000 V (at 50 Hz or 60 Hz in case of alternating current). This second edition cancels and replaces the first edition published in 2000 and Amendment 1:2008. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition: a) introduction of dated references as appropriate; b) clarification of sample item numbers.
IEC 61347-2-10:2024 specifies safety requirements for electronic controlgear for high-frequency operation of tubular cold-cathode discharge lamps used in signs and luminous discharge tube installations and operating with an output voltage exceeding 1 000 V but not exceeding 10 000 V for direct connection to DC or AC supply voltages not exceeding 1 000 V (at 50 Hz or 60 Hz in case of alternating current). This second edition cancels and replaces the first edition published in 2000 and Amendment 1:2008. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition: a) introduction of dated references as appropriate; b) clarification of sample item numbers.
IEC 61347-2-10:2024 is classified under the following ICS (International Classification for Standards) categories: 29.140.99 - Other standards related to lamps. The ICS classification helps identify the subject area and facilitates finding related standards.
IEC 61347-2-10:2024 has the following relationships with other standards: It is inter standard links to IEC 61347-2-10:2000/AMD1:2008, IEC 61347-2-10:2000. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
You can purchase IEC 61347-2-10:2024 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of IEC standards.
La norme IEC 61347-2-10:2024 se révèle être un document fondamental pour assurer la sécurité des équipements électroniques destinés au fonctionnement à haute fréquence des lampes à décharge à cathode froide tubulaires, telles que les tubes néon. Son étendue précise les exigences de sécurité pour les dispositifs de contrôle utilisés dans des installations d'enseigne lumineuse qui fonctionnent avec des tensions de sortie dépassant 1 000 V, mais ne dépassant pas 10 000 V. Cette norme est particulièrement pertinente pour les systèmes qui doivent se connecter directement à des tensions d'alimentation en courant continu ou alternatif ne dépassant pas 1 000 V, à des fréquences de 50 Hz ou 60 Hz. L'une des forces majeures de cette norme réside dans sa mise à jour par rapport à l'édition précédente de 2000 ainsi que l'amendement 1:2008, car elle comprend des précisions techniques cruciales. La révision technique apporte des références datées appropriées, ce qui facilite la navigation et la compréhension des exigences. De plus, la clarification des numéros d'articles des échantillons permet de mieux s’y retrouver dans l’application des critères de sécurité établis. Ces améliorations renforcent la précision et la fiabilité des équipements conçus selon ces spécifications. En intégrant des exigences de sécurité spécifiques et des clarifications sur les articles, la norme IEC 61347-2-10:2024 se positionne comme un guide essentiel pour les fabricants et les installateurs d’équipements pour lampes à décharge. Elle contribue non seulement à la protection des opérateurs et utilisateurs finaux, mais aussi à la promotion de pratiques industrielles sûres et durables dans le domaine des éclairages publics et privés. Ce standard est donc d'une pertinence indéniable, répondant aux besoins contemporains tout en garantissant une conformité rigoureuse avec les normes de sécurité internationales.
The standard IEC 61347-2-10:2024 provides comprehensive safety requirements for electronic controlgear specifically designed for the high-frequency operation of tubular cold-cathode discharge lamps, commonly known as neon tubes. This standard is of utmost relevance to manufacturers and users in the lighting industry, particularly for applications involving signs and luminous discharge tube installations. One of the key strengths of IEC 61347-2-10:2024 is its clear delineation of the operational parameters, specifying that it applies to controlgear operating with output voltages exceeding 1,000 V but not exceeding 10,000 V. This precise voltage specification is crucial for ensuring safety in installations connected directly to DC or AC supply voltages of up to 1,000 V, which is typical for standard commercial and industrial applications. The focus on 50 Hz or 60 Hz frequency ensures global applicability, accommodating the diverse electrical standards found worldwide. In its second edition, this standard not only cancels and replaces the first edition from 2000 and its 2008 amendment but also reflects technical advancements and industry needs. The introduction of dated references enhances the document’s usability and reliability, guiding users to the most current and applicable technical information. Furthermore, the clarification of sample item numbers aids in the accurate identification and application of the standard, reducing ambiguity for manufacturers and inspectors alike. Overall, IEC 61347-2-10:2024 stands out as a critical document for ensuring safety and operational reliability in high-voltage applications of tubular cold-cathode discharge lamps. Its comprehensive scope and the recent technical revisions make it an essential reference for compliance and best practices within the lighting sector.
Die Norm IEC 61347-2-10:2024 legt die Sicherheitsanforderungen für elektronische Vorschaltgeräte fest, die für den Hochfrequenzbetrieb von tubularen Kaltkathodenentladungslampen, wie Neonröhren, verwendet werden. Diese Vorschaltgeräte finden hauptsächlich Anwendung in Beschilderungen und Leuchtkörperinstallationen, wobei sie mit einer Ausgangsspannung von über 1 000 V, jedoch maximal 10 000 V, betrieben werden können. Diese Norm ist besonders relevant für Betriebsbedingungen, die eine direkte Verbindung zu Gleich- oder Wechselstromversorgungen mit Spannungen von nicht mehr als 1 000 V (bei einer Frequenz von 50 Hz oder 60 Hz) erfordern. Die Stärken der IEC 61347-2-10:2024 liegen in ihrer umfassenden technischen Revision, die wesentlich zur Verbesserung der Sicherheit und Zuverlässigkeit der Geräte beiträgt. Diese zweite Ausgabe hebt sich durch die Einführung von datierten Referenzen ab, was die Nachverfolgbarkeit und die Anwendung der Norm in der Praxis erleichtert. Zudem werden die Artikelnummern für Muster klarer definiert, was eine bessere Benutzerfreundlichkeit zur Folge hat und den Herstellern hilft, die spezifischen Anforderungen besser zu verstehen und umzusetzen. Darüber hinaus ist die Norm von großem praktischem Nutzen, da sie sicherstellt, dass alle elektronischen Vorschaltgeräte, die in der Hochfrequenztechnik für Kaltkathodenlampen verwendet werden, strengen Sicherheitsstandards entsprechen. Dies fördert nicht nur die Sicherheit bei der Installation, sondern auch die Langlebigkeit der Produkte. Die Relevanz dieser Norm erstreckt sich somit über verschiedene Branchen, in denen Neon-Technologie verwendet wird, und unterstützt die Einhaltung von Sicherheitsanforderungen, die entscheidend für die Sicherheit der Verbraucher und Betriebe sind. Zusammenfassend ist IEC 61347-2-10:2024 eine essenzielle Norm, die ein wichtiges Rahmenwerk für Sicherheitsanforderungen im Bereich elektronischer Vorschaltgeräte schafft. Ihre Aktualisierungen und klaren Vorgaben ermöglichen eine hohe Anwendungssicherheit und sind eine wertvolle Ressource für Hersteller sowie Anwender in der Beleuchtungsindustrie.
IEC 61347-2-10:2024は、チューブ型冷陰極放電ランプ(ネオンチューブ)の高周波運転用電子制御装置に関する安全要件を定めた標準であり、特にサインや発光放電管設置において使用される装置を対象としています。本標準は、出力電圧が1,000 Vを超え、10,000 Vを超えない範囲での直接接続が可能なDCまたはAC供給電圧(50 Hzまたは60 Hz)における安全性を確保することを目的としています。 この標準の強みは、特定の用途に特化した詳細な安全要件を提供する点にあります。特に、冷陰極放電ランプの特性や動作環境を考慮した設計基準が盛り込まれているため、業界での実用性が非常に高いと言えるでしょう。また、最新の技術動向に対応するための技術的改訂が行われていることも、その重要なポイントです。 本書は、2000年に発行された初版及び2008年の改正を取り消し、技術修正を加えた第二版として発行されています。特に注目すべきは、日付の付された参照文献の導入やサンプルアイテム番号の明確化といった、具体的な技術的変更が行われている点です。これにより、利用者はより正確で信頼性のある情報を得ることができるようになっています。 IEC 61347-2-10:2024は、特定の安全要件が明確に定義されており、効果的なリスク管理を可能にすることで、業界内での信頼性向上に寄与します。このように、本標準は現代の技術基準において不可欠な役割を果たしており、電子制御装置の安全性と効率性を確保するための重要なガイドラインとして位置付けられています。
IEC 61347-2-10:2024は、チューブ型冷陰極放電灯(ネオンチューブ)の高周波動作用電子制御装置に関する安全要件を定めています。この規格は、10,000 Vを超えない出力電圧で、1,000 Vを超えないDCまたはAC電源に直接接続して使用されるサイン及び発光放電管設備における制御機器に焦点を当てています。初版の2000年版と改正1号(2008年)を取り消し、置き換えるものであり、技術的な改訂を構成しています。 この標準の強みは、安全基準の明確な定義と、特定の条件下での高周波動作装置に求められる技術的要件を包括的に包含している点にあります。特に、適切な日付付きの参照文献の導入や、サンプルアイテム番号の明確化といった技術的変更が含まれており、業界における実務運用との整合性が向上しています。これにより、利用者はより正確かつ安全に製品を使用するための指針を得ることができます。 また、IEC 61347-2-10:2024は、業界の最新の技術進展を反映しているため、ネオンチューブの使用における安全基準の向上に寄与しています。このように、標準は技術的な信頼性と安全性を兼ね備えており、特に高電圧環境での利用を考慮した重要な文書となっています。したがって、この標準はチューブ型冷陰極放電灯を使用するすべての業界にとって極めて関連性が高いと言えます。
Die Norm IEC 61347-2-10:2024 beschäftigt sich mit den Sicherheitsanforderungen für elektronische Vorschaltgeräte, die für den Hochfrequenzbetrieb von Rohr-Entladungslampen (Neonröhren) entwickelt wurden. Der Anwendungsbereich dieser Norm ist klar definiert: Sie gilt für Lampen, die mit Ausgangsspannungen über 1.000 V und bis zu 10.000 V betrieben werden und direkt an Gleich- oder Wechselstromversorgungen, die 1.000 V (bei 50 Hz oder 60 Hz im Falle von Wechselstrom) nicht überschreiten, angeschlossen werden. Eine der Stärken dieser Norm ist ihre Relevanz für die Sicherheitspraktiken im Bereich der Beleuchtungstechnik, insbesondere bei der Anwendung in Schildern und leuchtenden Entladungslampensystemen. Die Norm liefert spezifische Anforderungen, die dazu beitragen können, Risiken zu minimieren, die mit der Verwendung von Hochspannungsgeräten verbunden sind. Die technische Überarbeitung in dieser zweiten Ausgabe bringt wichtige Änderungen mit sich, wie die Einführung datierter Verweise und die Klarstellung von Musterartikelnummern. Diese Änderungen verbessern nicht nur die Verständlichkeit der Norm, sondern erhöhen auch deren Anwendbarkeit in der Praxis. Insgesamt bietet die IEC 61347-2-10:2024 eine solide Grundlage für Hersteller und Betreiber, um sicherzustellen, dass ihre Produkte nicht nur den aktuellen Sicherheitsstandards entsprechen, sondern auch innovative und sichere Lösungen für die Verwendung von Hochfrequenz-Vorschaltgeräten in der Beleuchtungstechnik fördern.
IEC 61347-2-10:2024 표준은 전자 제어 장치의 안전 요구 사항을 명확히 규정하고 있으며, 고주파 작동을 위한 관형 냉음극 방전 램프(네온 튜브)의 안전성을 보장하는 데 중점을 두고 있습니다. 이 표준의 범위는 1,000V를 초과하나 10,000V 미만의 출력 전압에서 직접 DC 또는 AC 전원 전압(50Hz 또는 60Hz)의 공급에 연결될 수 있는 전자 제어 장치에 관련된 내용을 포함하고 있습니다. 이 표준의 강점은 특히 고주파 작동을 위한 전자 제어 장치의 안전성 측면에서 요구 사항을 세부적으로 설정해 준다는 점입니다. 이는 광고 표지판 및 발광 방전 튜브 설치와 같은 분야에서 중요한 역할을 하며, 사용자의 안전을 보장하고 전기적 사고를 예방하는 데 기여합니다. 또한, IEC 61347-2-10:2024는 이전 판(2000년 출판)과 Amendment 1:2008을 취소하고 대체하는 기술적 개정판으로, 업계의 발전과 변화된 기술적 요구에 부응하고 있습니다. 이번 개정판에서는 적절한 날짜 참조의 도입 및 샘플 항목 번호의 명확화와 같은 중요한 기술적 변경 사항이 포함되어 있어, 표준의 실용성을 더욱 강화하고 있습니다. 결론적으로, IEC 61347-2-10:2024는 전자 제어 장치의 안전성을 보장하는 데 필수적인 표준으로, 관련 산업에서의 널리 사용될 수 있는 필수 요소로 자리 잡을 가능성이 높습니다.
IEC 61347-2-10:2024 표준은 전자 제어장치에 대한 안전 요구사항을 규명하며, 특히 튜브형 냉음극 방전등(네온 튜브)의 고주파 작동에 중점을 두고 있습니다. 이 표준의 범위는 1,000V를 초과하나 10,000V를 초과하지 않는 출력 전압을 사용하는 신호 및 발광 방전관 설치에 적합한 전자 제어장치를 포괄합니다. 또한, 이 표준은 1,000V 이하의 DC 또는 AC 전원(50Hz 또는 60Hz)의 직접 연결 가능성을 포함하고 있습니다. IEC 61347-2-10:2024의 강점은 첫째, 전자 제어장치의 안전성을 강화하기 위한 명확한 요구사항을 제시하여 사용자와 설치 환경의 안전을 보장한다는 점입니다. 둘째, 이 개정판은 2000년에 발행된 첫 번째 버전과 2008년에 개정된 내용을 대체하며, 기술적 수정을 통해 현대의 요구에 부합하는 정보를 제공하고 있습니다. 특히, 이 개정판에서는 날짜가 명시된 참조의 도입과 샘플 항목 번호의 명확화가 이루어져, 표준 문서의 신뢰성과 적용성을 더욱 높이고 있습니다. 이러한 변경 사항들은 전자 제어장치의 고주파 작동에 대한 명확한 기준을 설정함으로써 업계 관행을 개선시키고, 제품 설계 및 검증 과정에서의 참고 자료로서의 활용도를 증대시킬 수 있습니다. 결론적으로, IEC 61347-2-10:2024 표준은 전자 제어장치의 안전성을 확보하고 개선하기 위한 중요한 자료로써, 관련 업계에서 필수적으로 고려해야 할 문서입니다. 기술적 진보와 안전 기준을 조화롭게 통합한 이 표준은 고주파 작동의 본질적인 요건을 충족하며, 사용자의 안전과 제품의 신뢰성을 강화하는 데 기여합니다.
La norme IEC 61347-2-10:2024 se concentre sur les exigences de sécurité pour les équipements de contrôle électroniques destinés à l'exploitation à haute fréquence de lampes à décharge à cathode froide tubulaires, spécifiquement des tubes néon. Son champ d'application est clairement défini, englobant les installations d'enseigne et de tubes à décharge lumineuse, tout en précisant des tensions de sortie supérieures à 1 000 V, mais ne dépassant pas 10 000 V, pour une connexion directe à des réseaux d'alimentation en courant continu ou alternatif ne dépassant pas 1 000 V sur des fréquences de 50 Hz ou 60 Hz. Cette norme, qui annule et remplace la première édition publiée en 2000 ainsi que l'amendement 1 de 2008, constitue une révision technique significative. Parmi les améliorations notables de cette seconde édition, on trouve l'introduction de références datées, qui assurent une conformité actualisée et facilitent l'application de la norme dans un environnement en constante évolution. De plus, la clarification des numéros d'articles des échantillons contribue à une meilleure compréhension et mise en œuvre des prescriptions techniques. Les points forts de IEC 61347-2-10:2024 résident dans son approche rigoureuse en matière de sécurité, garantissant que les équipements de contrôle électroniques répondent à des critères stricts avant leur mise sur le marché. Sa pertinence est indéniable dans le secteur des éclairages à haute fréquence, où la sécurité des installations et des utilisateurs est primordiale. En suivant cette norme, les fabricants et les utilisateurs peuvent avoir l'assurance que les dispositifs proposés respectent des standards élevés de qualité et de sécurité, favorisant ainsi un environnement lumineux fiable. En somme, la norme IEC 61347-2-10:2024 se révèle comme un document essentiel pour quiconque s'engage dans l'utilisation ou la production d'équipements de contrôle pour tubes néon, alliant sécurité, clarté et actualisation technique.
IEC 61347-2-10:2024 sets a comprehensive framework that focuses specifically on the safety requirements for electronic controlgear facilitating high-frequency operations of tubular cold-cathode discharge lamps. This standard is crucial for manufacturers and users involved with neon tube installations, as it delineates safety protocols necessary for equipment operating with high output voltages between 1,000 V and 10,000 V while being powered by DC or AC supply voltages not exceeding 1,000 V. One of the strengths of IEC 61347-2-10:2024 lies in its clear and structured approach to safety, ensuring that all relevant aspects concerning high-frequency operation are addressed comprehensively. The revision demonstrates a commitment to continuous improvement by canceling and replacing the previous edition from 2000 and its amendment, reflecting the evolving technological landscape and increasing awareness of safety standards in the industry. Significant technical changes introduced in this edition enhance its applicability and clarity. The addition of dated references ensures that users are consistent with industry standards, promoting better comprehension of regulatory compliance. Furthermore, the clarification of sample item numbers aids in the precise identification and categorization of products, thereby facilitating safer and more efficient design and implementation processes. IEC 61347-2-10:2024 is highly relevant in today’s market, where the use of tubular cold-cathode lamps is prevalent in signage and decorative applications. This standard not only supports manufacturers in meeting safety compliance but also instills confidence in users regarding the reliability and safety of their lighting solutions. As the industry shifts towards more advanced technologies, the updated safety requirements reflect the importance of innovation aligned with public safety considerations in electrical installations. The relevance, strengths, and scope of IEC 61347-2-10:2024 make it a foundational document for ensuring the safe operation of electronic controlgear across various applications.










Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.
Loading comments...