Amendment 2 - Switches for household and similar fixed electrical installations - Part 2-1: Particular requirements - Electronic switches

Amendement 2 - Interrupteurs pour installations électriques fixes domestiques et analogues - Partie 2-1: Prescriptions particulières - Interrupteurs électroniques

General Information

Status
Published
Publication Date
29-Mar-2015
Current Stage
DELPUB - Deleted Publication
Start Date
05-Feb-2021
Completion Date
26-Oct-2025
Ref Project

Relations

Standard
IEC 60669-2-1:2002/AMD2:2015 - Amendment 2 - Switches for household and similar fixed electrical installations - Part 2-1: Particular requirements - Electronic switches
English and French language
47 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


IEC 60669-2-1 ®
Edition 4.0 2015-03
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
colour
inside
A MENDMENT 2
AM ENDEMENT 2
Switches for household and similar fixed electrical installations –
Part 2-1: Particular requirements – Electronic switches

Interrupteurs pour installations électriques fixes domestiques et analogues –
Partie 2-1: Prescriptions particulières – Interrupteurs électroniques

IEC 60669-2-1:2002-09/AMD2:2015-03(en-fr)

All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form
or by any means, electronic or mechanical, including photocopying and microfilm, without permission in writing from
either IEC or IEC's member National Committee in the country of the requester. If you have any questions about IEC
copyright or have an enquiry about obtaining additional rights to this publication, please contact the address below or
your local IEC member National Committee for further information.

Droits de reproduction réservés. Sauf indication contraire, aucune partie de cette publication ne peut être reproduite
ni utilisée sous quelque forme que ce soit et par aucun procédé, électronique ou mécanique, y compris la photocopie
et les microfilms, sans l'accord écrit de l'IEC ou du Comité national de l'IEC du pays du demandeur. Si vous avez des
questions sur le copyright de l'IEC ou si vous désirez obtenir des droits supplémentaires sur cette publication, utilisez
les coordonnées ci-après ou contactez le Comité national de l'IEC de votre pays de résidence.

IEC Central Office Tel.: +41 22 919 02 11
3, rue de Varembé Fax: +41 22 919 03 00
CH-1211 Geneva 20 info@iec.ch
Switzerland www.iec.ch
About the IEC
The International Electrotechnical Commission (IEC) is the leading global organization that prepares and publishes
International Standards for all electrical, electronic and related technologies.

About IEC publications
The technical content of IEC publications is kept under constant review by the IEC. Please make sure that you have the
latest edition, a corrigenda or an amendment might have been published.

IEC Catalogue - webstore.iec.ch/catalogue Electropedia - www.electropedia.org
The stand-alone application for consulting the entire The world's leading online dictionary of electronic and
bibliographical information on IEC International Standards, electrical terms containing more than 30 000 terms and
Technical Specifications, Technical Reports and other definitions in English and French, with equivalent terms in 15
documents. Available for PC, Mac OS, Android Tablets and additional languages. Also known as the International
iPad. Electrotechnical Vocabulary (IEV) online.

IEC publications search - www.iec.ch/searchpub IEC Glossary - std.iec.ch/glossary
The advanced search enables to find IEC publications by a More than 60 000 electrotechnical terminology entries in
variety of criteria (reference number, text, technical English and French extracted from the Terms and Definitions
committee,…). It also gives information on projects, replaced clause of IEC publications issued since 2002. Some entries
and withdrawn publications. have been collected from earlier publications of IEC TC 37,

77, 86 and CISPR.
IEC Just Published - webstore.iec.ch/justpublished
Stay up to date on all new IEC publications. Just Published IEC Customer Service Centre - webstore.iec.ch/csc
details all new publications released. Available online and If you wish to give us your feedback on this publication or
also once a month by email. need further assistance, please contact the Customer Service
Centre: csc@iec.ch.
A propos de l'IEC
La Commission Electrotechnique Internationale (IEC) est la première organisation mondiale qui élabore et publie des
Normes internationales pour tout ce qui a trait à l'électricité, à l'électronique et aux technologies apparentées.

A propos des publications IEC
Le contenu technique des publications IEC est constamment revu. Veuillez vous assurer que vous possédez l’édition la
plus récente, un corrigendum ou amendement peut avoir été publié.

Catalogue IEC - webstore.iec.ch/catalogue Electropedia - www.electropedia.org
Application autonome pour consulter tous les renseignements
Le premier dictionnaire en ligne de termes électroniques et
bibliographiques sur les Normes internationales,
électriques. Il contient plus de 30 000 termes et définitions en
Spécifications techniques, Rapports techniques et autres
anglais et en français, ainsi que les termes équivalents dans
documents de l'IEC. Disponible pour PC, Mac OS, tablettes
15 langues additionnelles. Egalement appelé Vocabulaire
Android et iPad.
Electrotechnique International (IEV) en ligne.

Recherche de publications IEC - www.iec.ch/searchpub
Glossaire IEC - std.iec.ch/glossary
Plus de 60 000 entrées terminologiques électrotechniques, en
La recherche avancée permet de trouver des publications IEC
en utilisant différents critères (numéro de référence, texte, anglais et en français, extraites des articles Termes et
comité d’études,…). Elle donne aussi des informations sur les Définitions des publications IEC parues depuis 2002. Plus
projets et les publications remplacées ou retirées. certaines entrées antérieures extraites des publications des

CE 37, 77, 86 et CISPR de l'IEC.
IEC Just Published - webstore.iec.ch/justpublished

Service Clients - webstore.iec.ch/csc
Restez informé sur les nouvelles publications IEC. Just
Published détaille les nouvelles publications parues. Si vous désirez nous donner des commentaires sur cette
Disponible en ligne et aussi une fois par mois par email. publication ou si vous avez des questions contactez-nous:
csc@iec.ch.
IEC 60669-2-1 ®
Edition 4.0 2015-03
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
colour
inside
A MENDMENT 2
AM ENDEMENT 2
Switches for household and similar fixed electrical installations –

Part 2-1: Particular requirements – Electronic switches

Interrupteurs pour installations électriques fixes domestiques et analogues –

Partie 2-1: Prescriptions particulières – Interrupteurs électroniques

INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE
ICS 29.120.40 ISBN 978-2-8322-2303-1

– 2 – IEC 60669-2-1:2002/AMD2:2015
 IEC 2015
FOREWORD
This amendment has been prepared by subcommittee 23B: Plugs, Socket outlets and
switches, of IEC technical committee 23: Electrical accessories.
The text of this amendment is based on the following documents:
FDIS Report on voting
23B/1175/FDIS 23B/1183/RVD
Full information on the voting for the approval of this amendment can be found in the report
on voting indicated in the above table.
The committee has decided that the contents of this amendment and the base publication will
remain unchanged until the stability date indicated on the IEC web site under
"http://webstore.iec.ch" in the data related to the specific publication. At this date, the
publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
IMPORTANT – The 'colour inside' logo on the cover page of this publication indicates
that it contains colours which are considered to be useful for the correct
understanding of its contents. Users should therefore print this document using a
colour printer.
_____________
2 Normative references
Modify the date of "CISPR 15:2000" to "CISPR 15:2013".
Add the following new reference:
IEC 62756-1, Digital load side transmission lighting control – Part 1: Basic requirements
3 Definitions
Add the following new terms and definitions:
3.126
self ballasted lamp
unit which cannot be dismantled without being permanently damaged which is provided with a
lamp cap or caps and incorporating a light source and any additional elements necessary for
starting and stable operation of the light source
NOTE In the text self ballasted lamp are also called CFLi or LEDi where “i” means that the control gear is
incorporated in the lamp.
3.127
externally ballasted lamp
lamp other than an incandescent lamp which cannot be dismantled without being permanently
damaged which is provided with a lamp cap and incorporating a light source to be controlled
by a separate lamp control gear

 IEC 2015
NOTE For lamp control gear, see definitions in IEC 61347-1
3.128
conduction angle
a) for a leading edge (forward phase) dimmer, phase angle measured from the point where
conduction begins to the end of the half wave (zero crossing)
b) for a trailing edge (reverse phase) dimmer, phase angle measured from the beginning of a
half wave (zero crossing) to the point where conduction is switched off
5 General notes on tests
5.4 Replace the existing Table 101 by the following new Table 101:
Table 101 – Number of specimens
Additional specimens for clause or subclause
Number
Type of electronic for
18.2 19.101 19.102 19.109 24 26 101
switch general
and
tests
Marked with one
rated current and
a c
a a a
one rated voltage 3 3 3 3 3 3 1 3
a
a a a b,c,d
two rated voltages 6 6 6 6 6 6 1 6
a
Only for electronic switches with mechanical and electromechanical switching devices; only the complete
contact mechanism may be submitted.
b
It may be necessary to provide three additional specimens for the test of 101.3.
c
When the tests of Clause 26 have been passed successfully, the specimen can be used for these tests.
d
It may be necessary to provide 3 additional specimens for the test of 101.1.1.2.

7 Classification
7.1.101 Replace the existing list of dashed items, by the following new list:
– incandescent lamps
– externally ballasted lamps (e.g. fluorescent lamps, CFL, LED)
– motors
– self ballasted lamps (e.g. CFLi, LEDi)
– declared load.
8 Marking
8.1 Replace, the penultimate paragraph starting with "For general purpose" by the following
new paragraph:
For electronic switches with included automatic function if the manufacturer’s declared
number of operations is higher than that indicated in subclauses 19.101, 19.102, 19.104 and
19.109, then this shall be stated in the accompanying instruction sheet.
8.2 Replace “Fluorescent lamps” by “Externally ballasted fluorescent lamps”.
8.3 Replace the text of the addition by:
If a dimmer is intended to be used together with an iron core transformer, information shall be
given in the manufacturer’s instructions that only a transformer intended to be used with a
dimmer shall be used.
11 Provision for earthing
Add the following new subclause 11.101:

– 4 – IEC 60669-2-1:2002/AMD2:2015
 IEC 2015
11.101 The printed conductors of printed circuit boards may be used to provide protective
earthing continuity only under the following conditions:
– at least two tracks are used each having independent soldering points which will withstand
a single short circuit test similar to 101.3 and immediately after the switch shall fulfill the
requirements of 11.4, or
– a single track is used with two independent means of connection on each end which will
withstands a single short circuit test similar to 101.3 and immediately after the switch shall
fulfill the requirements of 11.4.
In addition,
– the material of the printed circuit board shall consist of epoxide woven glass fabric copper-
clad laminated sheet and
– the printed circuit board shall comply with the overload test according to 101.1.1.2.
13 Constructional requirements
13.101 Delete the first paragraph.
17 Temperature rise
Replace, in the compliance statement, the existing text starting with "Electronic switches for
incandescent lamps" through to and including Note 3 by the following:
For electronic switches which can be loaded with incandescent lamps (lamps rated for the
supply voltage, including halogen lamps) the following applies:
• If the rated power of some of the loads is expressed in W and is higher or equal to the
rated power of other loads expressed in VA, electronic switches shall be loaded with
halogen lamps or tungsten filament lamps so that, at the rated voltage of the load, the
rated load will be obtained.
NOTE 1 As the characteristics of halogen lamps of different power are equivalent, lamps of any power can be
used to reach the rated load.
• If the rated power of some of the loads is expressed in W and is lower than the rated power of other
loads expressed in VA, electronic switches shall be loaded with all types of load in
accordance with the manufacturer's instructions.
• If the rated power of the self ballasted lamps, or externally ballasted lamps, expressed in
W is higher than 25 % of the rated power of the incandescent lamps the test shall be done
with all types of load.
For electronic switches which are not designed for incandescent lamps the following applies:
• Electronic switches for self ballasted lamps (eg. LEDi, CFLi) are loaded with lamps so
that, at the rated voltage of the load, the rated load will be obtained. Dimmers shall be
loaded with dimmable self ballasted lamps. If for these types of electronic switches, the
maximum number of self ballasted lamps and the rating of the lamp are given by the
manufacturer, the electronic switch is loaded accordingly. If more than one configuration is
given by the manufacturer, the test is repeated for all configurations.
• Electronic switches for other types of lamp are tested in accordance with the
manufacturer’s instructions.
Other electronic switches shall be loaded with the type of load as stated in the manufacturer’s
instructions.
NOTE 2 The rated loads are verified with the electronic switch short-circuited.
For electronic TDS, 17.1 of IEC 60669-2-3:2006 is applicable.
The electronic switches are loaded until steady-state temperature is reached at a voltage
between 0,9 and 1,1 times rated voltage, whichever is the more unfavourable.

 IEC 2015
Dimmers operating with leading and trailing edge shall be tested in both modes with the
relevant load.
In lamp dimmers and speed controllers, the setting is adjusted such that the highest
temperature rise will occur.
Flush-mounted electronic switches are mounted in flush-mounted boxes. The box is placed in
a block of wood filled around the box with plaster, so that the front edge of the box does not
protrude and is not more than 5 mm below the front surface of the wood block.
The test assembly shall be allowed to dry for not less than seven days when first made.
Renumber existing notes 4, 5, 6, 7 and 8 as notes 3, 4, 5, 6 and 7 respectively.
18 Making and breaking capacity
Add, at the end of the list of dashed items, the following new dashed item:
– for electronic switches for the control of self ballasted lamps, as specified in 18.1 of part 1.
18.1 Delete “or more” at the end of the last dashed item.
19 Normal operation
Replace the existing fourth and fifth paragraphs by the following new paragraphs:
Compliance is checked by the tests of 19.101, 19.102, 19.103, 19.104, 19.105 and 19.109,
during which the electronic switches are tested at their rated voltage and loaded as specified
in Clause 17, unless otherwise specified.
For electronic switches with included automatic function the number of operations for tests of
subclauses 19.101, 19.102, 19.104 and 19.109 is that specified in the relevant subclause. If a
manufacturer declares a number of operations higher than those indicated in the relevant
subclause, the tests shall be made according to the declared value.
NOTE 1 The correlation between the tests of 19.102 and 19.109 is under consideration.
Sticking of the contacts, which does not prevent the next operation of the switch, is not
regarded as welding.
Sticking of contacts is permitted if the contacts can be separated with a force applied to the
actuator of a value which does not damage the switch mechanically.
Electronic switches including electronic circuits which close the contact of the contact
mechanism always at zero-crossing ± 20° phase angle, shall be tested together with their
electronic circuit.
Renumber the existing notes as notes 2, 3, 4, and 5 respectively.
19.101 Add, in the first sentence, "with or without step down converters" after "lamp circuits".
19.102 Replace the entire existing text of this subclause by the following new text:
Contact mechanisms incorporated in electronic switches, intended for externally ballasted
lamps (e.g. fluorescent lamps, CFL, LED) are checked by the test circuit indicated in Figure
103 Load A with the following test conditions.
NOTE The test with Load B is not applicable.
The prospective short-circuit current (rms) of the supply shall be between 3 kA and 4 kA at
cos ϕ = 0,9 ± 0,05 (lagging). F is a copper-wire fuse of 0,1 mm nominal diameter having a
length not less than 50 mm.
R1 is a resistor limiting the current to approximately 100 A.

– 6 – IEC 60669-2-1:2002/AMD2:2015
 IEC 2015
The twin-core cable shall have a suitable length to give a resistance R3 equal to 0,25 Ω in the
test circuit to the load. It shall have a cross-sectional area of 1,5 mm when switches with

rated current up to and including 10 A are being tested and 2,5 mm when switches with rated
current over 10 A up to and including 16 A are being tested.
The load shall consist of:
– a capacitor bank C , giving a capacitance according to Table 103. The capacitors shall be
connected with 2,5 mm conductors having the shortest possible length;
– an inductor L and a resistor R , adjusted to give the power factor 0,9 ± 0,05 (lagging) and
1 2
+5
the test current I % through the specimen.
n
Table 103 – Relationship between rated current and capacitance
Rated current Capacitance
A
µF
Up to and including 1 12
Up to and including 2 24
Up to and including 3 35
Up to and including 4 48
Up to and including 5 58
Up to and including 6 70
Up to and including 7 77
Up to and including 8 96
Up to and including 9 105
Up to and including 10 140
Up to and including 16 140
NOTE The circuit parameters have been chosen to
represent the lamp loads used in the most practical
applications.
Compliance is checked by the following test.
For the test, new specimens are used.
The tolerance of the test voltage is ± 5 %. The circuit details and the manner of operation of
the selector switch S are as described in 18.1.
The number of operations is as follows.
For electronic switches with a rated current up to and including 10 A: 10 000 operations with
30 operations per minute.
For electronic switches with rated current above 10 A up to and including 16 A:
5 000 operations with 15 operations per minute.
The test specimens shall be connected to the test circuit with cables of length (1 ± 0,1) m
so that the temperature rise measurement can be made without disturbing the terminals.
The metal support of the switch, if any, on which the switch is mounted, and the accessible
metal parts of the switch, if any, shall be earthed through a wire fuse which shall not blow
during the test. The fuse element shall consist of a copper wire of 0,1 mm diameter and not
less than 50 mm in length.
During this test, the switch shall be operated so that the test apparatus does not interfere with
the normal action of the switch mechanism and the free movement of the actuating member.

 IEC 2015
+5
There shall be no forced actuation. The on-period shall be 25 ( ) % of the total cycle and
the off-period 75 ( ) %.
−5
Add the following new subclause:
19.109 Contact mechanisms incorporated in electronic switches intended for self ballasted
lamps are tested as in 19.102 except for the requirements related to the power supply which
are given for information only.
NOTE 1 The calculations are based on the following parameters in order to have the required values for inrush
current and I t
– a prospective short-circuit current (rms) of the supply of 3 kA at cos ϕ = 0,9 (lagging).
– a resistance R3 equal to 0,25 Ω and an inductance L equal to 20 µH simulating the twin-core cable in the test
circuit.
Compliance is checked by connecting the load B as given in Figure 103 via the electronic
switch under test to a power supply. The values for the maximum peak value and the
maximum I t of the inrush current are given in Table 108.
NOTE 2 The test with Load A is not applicable.
For electronic switches with rated power for SBL lamps up to and including 250 W: 40 000
operations with 30 operations per minute.
For electronic switches with rated power for SBL lamps higher than 250 W: 40 000 operations
with 15 operations per minute.
NOTE 3 R1 is the total series resistance in the lamp circuit including the ESR (equivalent series resistance) value
of the capacitor.
The values of R1 and C in load B shall be chosen in order to reach the values (± 5 %) for I
peak
and I t as given in Table 108 when the switching contact closes at (90 ± 5)º phase-angle. The
value of R2 shall be chosen to reach the rated power in W (± 5 %).
Table 108 – Values for I and I t depending on the type of distribution system
peak
2 2
I
I t I t
peak
I 2 2
peak A s A A s
A
Distribution Distribution Distribution
system: system: system:
Distribution
system: 220/380, 120/208 120/208
220/380, 230/400 230/400 127/220 127/220
Rated Power (W) 240/415 240/415
15 22 0,08 69 0,56
30 41 0,3 109 1,9
60 73 1,2 162 5,9
100 108 2,8 200 11,5
150 142 5,5 231 18,5
200 170 9 248 24,5
250 192 13 255 30
300 209 16,5 260 35
350 223 20,5 262 39
400 235 24,5 263 43
NOTE For values not given in the table the test values are determined by interpolation.

– 8 – IEC 60669-2-1:2002/AMD2:2015
 IEC 2015
Table 109 – Calculated circuit parameters
Rated power (W) R1 (Ω) C (µF) R1 (Ω) C (µF)

230 V 230 V 120 V 120 V
15 13 20 1,36 70
30 6,5 40 0,65 140
60 3,25 80 0,28 280
100 1,9 125 0,17 445
150 1,25 180 0,11 640
200 0,95 240 0,10 830
250 0,8 310 0.10 1000
300 0,7 355 0.11 1250
350 0,64 420 0.13 1500
400 0,59 480 0.135 1660
The values in Table 109 are given for information only. The circuit shall be adjusted to reach
the I and I t values of Table 108.
peak
23 Creepage distances, clearances and distances through sealing compound
Add, in Table 20, the following new Note 3 after the existing Note 2:
NOTE 3 Items 101 and 102 apply to electronic RCS and TDS only.
26 EMC requirements
Replace, in the fourth paragraph, "three new specimens" by "one new specimen".
26.1 Immunity
Replace the existing text of this subclause by the following new text:
Electronic switches shall be designed so that the switch state (on or off) and/or the setting
value are protected against interference. The operation of the switch shall be protected
against continuous interference (e.g. IEC 61000-4-3; IEC 61000-4-6; IEC 61000-4-8).
For the following tests, the electronic switch is mounted as in normal use in the relevant box,
if any, and loaded with all kinds of loads according to the manufacturers specifications, unless
otherwise stated in the relevant paragraph of Clause 26.
The electronic switch is loaded at 100 % of the rated load for dimming devices and with a
functional load for other electronic switches.
The electronic switch shall be tested according to Table 104 with or without operation as
specified in the relevant paragraph of Clause 26.
If the load connected to the electronic switch is controlled by mechanical switching devices
(e.g. relays), and no semiconductor devices are present in the load circuit, the test is
conducted with a resistive load only.
For the tests without operation, the electronic switch is tested in the following states:
a) in the on-state,
For electronic switches where the setting can alter (e.g. dimming devices) the conduction
angle is set at (100 ± 5)° which results in an output power (rms).
A variation of P less than ± 10 % is not considered to be a change of the setting.
o
b) in the off-state.
 IEC 2015
For the tests with operation, the electronic switch shall be switched ON/OFF with a
minimum operating rate of 1 operation/second. As an alternative, where the setting can
alter (e.g. dimming devices), the setting value can be changed e.g. from minimum to
maximum.
For electronic switches whose cycle of operation is limited by their application (for
example, passive infrared, time delay electronic switches, etc.), the rate of operation
during the tests shall be specified by the manufacturer.
Table 104 – Immunity tests (overview)
EM phenomena Test set-up Subclause Test specification
Voltage dips and short interruptions IEC 61000-4-11:1994 26.1.1 Table 105
Surge IEC 61000-4-5: 1995 26.1.2 Table 110
Fast transients (burst) IEC 61000-4-4:1995 26.1.3 Table 106
Electrostatic discharge IEC 61000-4-2:1995 26.1.4
± 4 kV contact discharge
± 8 kV air discharge
Radiated electromagnetic field test IEC 61000-4-3:2002 26.1.5 3 V/m
Radio frequency voltage IEC 61000-4-6:1996 26.1.6 3 V r.m.s

a
Power frequency magnetic field IEC 61000-4-8:1993 3 A/m, 50 Hz
26.1.7
a
This test is applicable only to electronic switches containing devices susceptible to magnetic fields, for
example, Hall elements, electrodynamic microphones, etc.

26.1.1 Voltage dips and short interruptions
Add, after the existing first paragraph, the following new paragraphs:
The test shall be done on the power supply lines of the electronic switch.
During the test, the electronic switch is not operated.
Replace the first three existing paragraphs after Table 105 by the following new paragraphs:
During the test, the state and setting of the electronic switch may alter, flickering is neglected.
After the test, the electronic switch shall be in the original state and setting and shall operate
as intended.
26.1.2 Surge immunity test for 1,2/50 wave impulses
Replace the existing second to sixth paragraphs by the following:
During the test, the electronic switch is not operated.
The test is carried out according to IEC 61000-4-5 by applying two positive discharges and
two negative discharges at each of the following angles 0°, 90°, 180° and 270°, at a repetition
rate of (60 ± 5) s with an open-circuit test voltage according to Table 110.
A test with lower voltages is not required.
If the product has a metallic mounting surface when mounted as in normal use, the test is
repeated between line and earth with a test voltage according to Table 110.
Table 110 – Surge immunity test voltages
Conductors / Terminals Coupling Test voltage
kV
Line to line 1
Mains
Line to earth 2
During the test, the state and setting of the electronic switch may alter, flickering is neglected.

– 10 – IEC 60669-2-1:2002/AMD2:2015
 IEC 2015
After the test, the electronic switch shall be in the original state and setting and shall operate
as intended.
26.1.3 Electrical fast transient/burst test
Add after the existing first paragraph the following new paragraph:
During the test, the electronic switch is not operated.
Replace the existing third to seventh paragraphs including Table 106 by the following:
The levels of the repetitive fast transients consisting of bursts coupled into the supply and
control terminals/terminations of the electronic switch is specified in Table 106.
Table 106 – Fast transient test values
Open-circuit output test voltage ± 10 %
Level Supply terminals/terminations Control terminals/terminations
kV kV
± 1 ± 0,5
The repetition rate is 5 kHz.
+5
The duration of the test shall be not less than 60 s, but not less than the time necessary
for the electronic switch to respond for each positive and negative polarity.
During the test, the state and setting of the electronic switch may alter, flickering caused by
the electronic switch is allowed.
After the test, the electronic switch shall be in the original state and setting and shall operate
as intended.
26.1.4 Electrostatic discharge test
Replace in the first paragraph, second sentence the words “incandescent lamps” by “resistive
load”.
Add after the existing first paragraph the following new paragraphs:
During the test, the electronic switch is not operated.
A test with lower voltages is not required.
Replace the existing sixth to eighth paragraphs included by the following new paragraphs:
During the test, the state and setting of the electronic switch may alter, flickering is neglected.
After the test, the electronic switch shall be in the original state and setting and shall operate
as intended.
Electronic switches with an adjustable time delay device (for example, passive infra-red
switches) shall be adjusted in such a way that the time delay is higher than the testing time.
26.1.5 Radiated electromagnetic field test
Add at the end of the existing first paragraph the following new paragraph:
Electronic switches shall be loaded with resistive load only.
Replace the exisiting third to seventh paragraphs by the following new paragraphs:
The test is carried out according to IEC 61000-4-3 by applying a field strength of 3 V/m in the
frequency range 80 MHz to 1 000 MHz and 1 400 MHz to 2 000 MHz with the exception of the

 IEC 2015
exclusion band as defined in the relevant product standard for transmitters, receivers and
duplex transceivers.
During the test, the electronic switch is operated, if it contains automatic functions or can be
remotely controlled.
During and after the test, the electronic switch shall operate as intended, flickering is not
allowed.
Flickering of lamps or irregular running of motors due to switching transients caused by
frequencey changes of the test equipment during the test procedure is neglected.
26.1.6 Radio-frequency voltage test
Add at the end of the existing first paragraph the following new paragraph:
Electronic switches shall be loaded with resistive load only.
Replace the fourth to sixth existing paragraphs by the following new paragraphs:
During the test, the electronic switch is operated, if it contains automatic functions or can be
remotely controlled.
During and after the test, the electronic switch shall operate as intended, flickering is not
allowed.
Flickering of lamps or irregular running of motors due to switching transients caused by
frequencey changes of the test equipment during the test procedure is neglected.
26.1.7 Power-frequency magnetic field test
Add at the end of the existing first paragraph the following new paragraph:
Electronic switches shall be loaded with resistive load only.
Replace the existing fourth to sixth paragraphs by the following new paragraphs:
During the test, the electronic switch is operated, if it contains automatic functions or can be
remotely controlled.
During and after the test, the electronic switch shall operate as intended, flickering is not
allowed.
Flickering of lamps or irregular running of motors due to switching transients caused by
frequencey changes of the test equipment during the test procedure is neglected.
26.2 Emission
26.2.1 Low-frequency emission
Add after the existing second paragraph the following new paragraph:
This requirement applies to each channel of a multichannel dimmer provided that the
channels are independent from each other.
Replace the existing Note 2 by the following new note:
NOTE 2 Independent dimmers designed to dim different kinds of loads including incandescent lamps are
considered as dimmers for incandescent lamps and according to IEC 61000-3-2 they need not to be tested with all
different kinds of load according to Clause 7 of IEC 61000-3-2:2009, if their rated power per channel (provided that
the control of the channels are independent) is less than or equal to 1000 W. Electronic switches with
semiconductor switching for the load current are regarded as dimmers.
Replace the existing last paragraph by the following new paragraph:
Load terminals/terminations of electronic switches with electromechanically operated contact
mechanism (for example, a relay), do not cause harmonic current emissions and are deemed

– 12 – IEC 60669-2-1:2002/AMD2:2015
 IEC 2015
to meet the requirements of IEC 61000-3-2 without need for testing. Therefore only the mains
supply terminals/terminations of those products shall be tested.
26.2.2 Radio-frequency emission
Replace the existing test sequences by the following new test sequences:
a) at the main terminals (8.1.4.2 of CISPR 15:2013):
An initial survey or scan of the complete frequency range 9 kHz to 30 MHz shall be made
in on-state at the highest setting. In addition, at the following frequencies and at all
frequencies at which there is a local maximum disturbance found in the initial survey
above the predetermined level of 6 dB and below the limits given in CISPR 15, the control
setting shall be varied for maximum disturbance while connected to the maximum load:
9 kHz, 50 kHz, 100 kHz, 160 kHz, 240 kHz, 550 kHz, 1 MHz, 1,4 MHz, 2 MHz, 3,5 MHz,
6 MHz, 10 MHz, 22 MHz and 30 MHz;
b) at the load and/or control terminals (8.1.4.3 of CISPR 15:2013):
An initial survey or scan of the complete frequency range 160 kHz to 30 MHz shall be
made in on-state at the highest setting. In addition, at the following frequencies and at all
frequencies at which there is a local maximum disturbance above the predetermined level
of 6 dB below the limits given in CISPR 15, the control setting shall be varied for maximum
disturbance while connected to the maximum load:
160 kHz, 240 kHz, 550 kHz, 1 MHz, 1,4 MHz, 2 MHz, 3,5 MHz, 6 MHz, 10 MHz, 22 MHz
and 30 MHz.
101 Abnormal conditions
Add after the existing first paragraph the following new paragraph:
If in case of failure the maximum power taken by the electronic switches is less than 0,5 W,
the requirements of the abnormal conditions are deemed to be met.
101.1.1.2 Add after the existing last paragraph the following new paragraphs:
If any of the tests specified above turn off the electronic switch before the temperature has
been steady state, the following additional test shall be performed on a new set of specimens:
– The electronic switch shall be loaded to 1,1 times the rated current.
– The current is then increased by 10 % and then the temperature is allowed to stabilize.
This is repeated until the conventional tripping current of the protective device is reached
or the electronic switch is destroyed (no longer functioning properly or safety is impaired
within the meaning of this standard).
101.3 Replace the existing text of 101.3 by the following new text:
Electronic switches shall, without endangering their surroundings, withstand the short circuit
currents they may be subjected to in the load circuit.
Compliance is checked by the following test.
The electronic switch is mounted as in normal use. If additional boxes or enclosures are used
they shall be tested in an enclosure complying with the relevant Part of the IEC 60670 series.
NOTE 1 In the following countries boxes and enclosures shall comply with both IEC 60670-1 and BS 4662: UK.
The electronic switch is tested in a substantially non-inductive circuit in series with a load
impedance and a device for limiting the let-through I t.
The prospective short-circuit current of the supply shall be 1 500 A r.m.s. at a voltage equal to
the rated voltage of the electronic switch under test.
2 2
The prospective let-through I t minimum value shall be 15 000 A s.

 IEC 2015
NOTE 2 The prospective current is a current that would flow in the circuit if the electronic switch, the limitation
device and the load impedance were replaced by links of negligible impedance without any other change in the
circuit.
NOTE 3 The prospective I t value is a value that would be let through by the current limiting device if the
electronic switch and the load impedance were replaced by links of negligible impedance. The I t value may be
limited by using an open wire fuse, an ignitron or other suitable devices.
2 2 2
NOTE 4 The I t value of 15 000 A s corresponds to an unfavourable let-through I t value of 16 A miniature
circuit-breakers measured at 1 500 A prospective short-circuit current.
The diagram of the circuit in which the electronic switch is tested is shown in Figure 102.
The impedance Z (short-circuit impedance) shall be adjusted to satisfy the specified
prospective short-circuit current.
The impedance Z (load impedance) shall be adjusted that the electronic switch is loaded with
its minimum load or with approximately 10 % of the rated load, whichever is the higher.
NOTE 5 A load is necessary for the electronic switch to be in the on-state.
The circuit is calibrated with the following tolerances: current 0/+5 %, voltage 0/+10 %,
frequency ± 5 %.
The automatic overcurrent protective device including fuses, if any, incorporated or not
incorporated in the electronic switch, recommended by the manufacturer, is inserted into the
circuit which is loaded. The variable control, if any, is set at the position of maximum output.
The short circuit is applied six times by the auxiliary switch A without any synchronization with
respect to the voltage.
NOTE 6 Six tests are made in order to avoid the complication of point-on-wave timing.
During the test, emission of flames or burning particles, if any, shall not be dangerous to the
environment.
The above requirement is fulfilled if during the test there are no emissions of flames or
burning particles visible with normal or corrected vision without additional magnification.
If there is visible emission of flames or burning particles, the test shall be repeated on new
specimens. Before repeating the test, a clear polyethylene film (0,05 ± 0,01) mm thick, of a
size at least 50 mm larger in each direction than the area where the flames or burning
particles were seen, is fixed and reasonably stretched in a frame.The film is placed
approximately perpendicular to the trajectory of the flame at a maximum distance of 10 mm
from the surface of the product where the flame was emitted.
The film should have the following physical properties:
– Density at +23 °C (0,915 g/cm² up to 0,935 g/cm²);
– Melting point between +110 °C to +120 °C.
After the test
– accessible metal parts shall not be live (see Clause 10);
– emissions of flames or burning particles have not visibly perforated the film when
examined by normal or corrected vision without additional magnification and the film shall
be in one piece;
– the conductors, the flush mounting box and the mounting surface shall not show traces of
burns. Traces which can be cleaned and do not prevent the further use of the cables or
housing are ignored.
It is not necessary for the specimens to remain in operating condition. However, the contacts
of any incorporated automatic protective device shall not be welded unless the electronic
switch is obviously useless.
After the short circuit test the specimen is re-energized in its normal operating position,
incorporated fuses if any being replaced, and its behaviour is monitored for 4 hours. The

– 14 – IEC 60669-2-1:2002/AMD2:2015
 IEC 2015
specimen shall show no dangerous behaviour during this period such as smoke or excessive
heat. In case of doubt the maximum temperature rise values given in table 102 shall not be
exceeded.
The six tests may be carried out on the same specimen provided that, with the replacement of
an incorporated fuse, the electronic switch is still capable of operation. Otherwise, new
specimens shall be used until a total of six tests have been completed.
Moreover, the electronic switch shall withstand the dielectric strength test according to
Clause 16 when the specimen has reached the temperature of the environment after the
short-circuit test with the voltages prescribed in Clause 19. This test shall not be applied
according to item 3 of Table 14.
Overcurrent protective devices which can be manually reset shall be switched on before the
test.
Add, after the existing subclause 101.4, the following new subclause:
101.5 Dimmers classified for incandescent and/or self ballasted lamps shall be so designed
that no part shall reach such a temperature that there is danger of fire to the surroundings of
the dimmer when non-dimmable self ballasted lamps are installed in the load circuit.
The tests are made on dimmers mounted and connected as specified in Clause 17.
The dimmer is loaded with a number of lamp simulation circuits as given in Figure 103 Load B
providing the rated self ballasted lamp load of the dimmer. The simulation circuit represents a
25 W non dimmable self ballasted lamp.
In case of dimmers not classified for self ballasted lamps the dimmer is loaded with a number
of lamp simulation circuits as given in Load B of Figure 103 having a total power equivalent to
1/5th of the declared incandescent lamp load.
For example, if an electronic switch has a calculated power of 110 W for self-ballasted lamps,
then the electronic switch is loaded with 5 simulation circuits.
Where:
R1 = 4,4 Ω ± 5 %.
C = 14 µF capacitor
R2 is adjusted to give a power of 25 W.
Compliance is checked by subjecting the electronic switches to a heating test. The test
procedure is as specified in Clause 17 unless otherwise stated.
The setting is adjusted to a stable condition so that the maximum current peaks occur.
During the test, emission of flames or burning particles shall not occur and the temperature
rises shall not exceed the values given in Table 102, column concerning Clause 101.
After the test, accessible metal parts shall not be live.
It is not necessary for the specimens to remain in operating condition. However, the contacts
of any incorporated automatic protective device shall not be welded, unless the electronic
switch is obviously useless.
102 Components
102.4 Automatic protective devices (other than fuses)
102.4.1.2
Replace the last paragraph by:
The cut-outs shall withstand for 1 min a test voltage between the open contacts, the voltage
being
 IEC 2015
– For cut-outs in electronic switches for lighting circuits: 500 V;
– For cut-outs in electronic switches for speed control circuits: 1 200 V for rated voltages up
to 130 V and 2000 V for rated voltages above 130 V.
Add the following new figure:
Specimen
L
F
Supply
C
R
R
R
Twin-core cable Load A
D D
1 2
R
R
C
D D
3 4
Load B
IEC
Figure 103 – Circuit diagrams for testing switches according
to subclauses 19.102 and 19.109

Annex AA
Add the following row before the existing last row in the table of Annex AA:
DLT control devices Electronically operated controller with an electronic
control circuit and a semiconductor switching device

Add the following new annexes:

– 16 – IEC 60669-2-1:2002/AMD2:2015
 IEC 2015
Annex BB
(informative)
Circuit development: subclause 19.109 explained
BB.1 Rationale
Due to the phasing out of incandescent lamps and the replacement of these lamps by self
ballasted lamps, a work was done by the Technical Committees concerned to addre
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.

Loading comments...