IEC 60730-2-15:2008
(Main)Automatic electrical controls for household and similar use - Part 2-15: Particular requirements for automatic electrical air flow, water flow and water level sensing controls
Automatic electrical controls for household and similar use - Part 2-15: Particular requirements for automatic electrical air flow, water flow and water level sensing controls
This part of IEC 60730 applies to automatic electrical air flow, water flow and water level sensing controls for use in, or in association with, boilers with a maximum pressure rating of 2 000 kPA (20 bar) and equipment for general household and similar use including controls for heating, air- conditioning and similar applications. This second edition cancels and replaces the first edition published in 1994 and its Amendment 1 (1997), the first edition of IEC 60730-2-16 published in 1995 and its Amendments 1 (1997) and 2 (2001) and the first edition of IEC 60730-2-18 published in 1997. This second edition constitutes a technical revision. This second edition is a consolidation of three standards IEC 60725-2-15, IEC 60730-2-16 and IEC 60730-2-18. The title and scope were revised to reflect the additional topics covered by the standard.
Dispositifs de commande électrique automatiques à usage domestique et analogue - Partie 2-15: Exigences particulières pour les dispositifs de commande électrique automatiques détecteurs de débit d'air, de débit d'eau et de niveau d'eau
La présente partie de la CEI 60730 s'applique aux dispositifs de commande électrique automatiques détecteurs de débit d'air, de débit d'eau et de niveau d'eau utilisés dans, ou en association avec, les chaudières de pression nominale maximale de 2 000 kPa (20 bar) et les matériels à usage domestique et analogue, y compris les dispositifs de commande pour le chauffage, le conditionnement d'air et les applications analogues. Cette deuxième édition annule et remplace la première édition publiée en 1994 et son Amendement 1 (1997), la première édition de la CEI 60730-2-16 publiée en 1995 et ses Amendements 1 (1997) et 2 (2001) ainsi que la première édition de la CEI 60730-2-18 publiée en 1997. Cette deuxième édition constitue une révision technique. Cette deuxième édition est une consolidation des trois normes CEI 60725-2-15, CEI 60730-2-16 et CEI 60730-2-18. Le titre et le domaine d'application ont été révisés pour refléter les thèmes additionnels couverts par la norme.
General Information
Relations
Standards Content (Sample)
IEC 60730-2-15
Edition 2.0 2008-01
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
Automatic electrical controls for household and similar use –
Part 2-15: Particular requirements for automatic electrical air flow, water flow
and water level sensing controls
Dispositifs de commande électrique automatiques à usage domestique et
analogue –
Partie 2-15: Exigences particulières pour les dispositifs de commande électrique
automatiques détecteurs de débit d'air, de débit d'eau et de niveau d'eau
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form or by
any means, electronic or mechanical, including photocopying and microfilm, without permission in writing from either IEC or
IEC's member National Committee in the country of the requester.
If you have any questions about IEC copyright or have an enquiry about obtaining additional rights to this publication,
please contact the address below or your local IEC member National Committee for further information.
Droits de reproduction réservés. Sauf indication contraire, aucune partie de cette publication ne peut être reproduite
ni utilisée sous quelque forme que ce soit et par aucun procédé, électronique ou mécanique, y compris la photocopie
et les microfilms, sans l'accord écrit de la CEI ou du Comité national de la CEI du pays du demandeur.
Si vous avez des questions sur le copyright de la CEI ou si vous désirez obtenir des droits supplémentaires sur cette
publication, utilisez les coordonnées ci-après ou contactez le Comité national de la CEI de votre pays de résidence.
IEC Central Office
3, rue de Varembé
CH-1211 Geneva 20
Switzerland
Email: inmail@iec.ch
Web: www.iec.ch
About the IEC
The International Electrotechnical Commission (IEC) is the leading global organization that prepares and publishes
International Standards for all electrical, electronic and related technologies.
About IEC publications
The technical content of IEC publications is kept under constant review by the IEC. Please make sure that you have the
latest edition, a corrigenda or an amendment might have been published.
ƒ Catalogue of IEC publications: www.iec.ch/searchpub
The IEC on-line Catalogue enables you to search by a variety of criteria (reference number, text, technical committee,…).
It also gives information on projects, withdrawn and replaced publications.
ƒ IEC Just Published: www.iec.ch/online_news/justpub
Stay up to date on all new IEC publications. Just Published details twice a month all new publications released. Available
on-line and also by email.
ƒ Electropedia: www.electropedia.org
The world's leading online dictionary of electronic and electrical terms containing more than 20 000 terms and definitions
in English and French, with equivalent terms in additional languages. Also known as the International Electrotechnical
Vocabulary online.
ƒ Customer Service Centre: www.iec.ch/webstore/custserv
If you wish to give us your feedback on this publication or need further assistance, please visit the Customer Service
Centre FAQ or contact us:
Email: csc@iec.ch
Tel.: +41 22 919 02 11
Fax: +41 22 919 03 00
A propos de la CEI
La Commission Electrotechnique Internationale (CEI) est la première organisation mondiale qui élabore et publie des
normes internationales pour tout ce qui a trait à l'électricité, à l'électronique et aux technologies apparentées.
A propos des publications CEI
Le contenu technique des publications de la CEI est constamment revu. Veuillez vous assurer que vous possédez
l’édition la plus récente, un corrigendum ou amendement peut avoir été publié.
ƒ Catalogue des publications de la CEI: www.iec.ch/searchpub/cur_fut-f.htm
Le Catalogue en-ligne de la CEI vous permet d’effectuer des recherches en utilisant différents critères (numéro de référence,
texte, comité d’études,…). Il donne aussi des informations sur les projets et les publications retirées ou remplacées.
ƒ Just Published CEI: www.iec.ch/online_news/justpub
Restez informé sur les nouvelles publications de la CEI. Just Published détaille deux fois par mois les nouvelles
publications parues. Disponible en-ligne et aussi par email.
ƒ Electropedia: www.electropedia.org
Le premier dictionnaire en ligne au monde de termes électroniques et électriques. Il contient plus de 20 000 termes et
définitions en anglais et en français, ainsi que les termes équivalents dans les langues additionnelles. Egalement appelé
Vocabulaire Electrotechnique International en ligne.
ƒ Service Clients: www.iec.ch/webstore/custserv/custserv_entry-f.htm
Si vous désirez nous donner des commentaires sur cette publication ou si vous avez des questions, visitez le FAQ du
Service clients ou contactez-nous:
Email: csc@iec.ch
Tél.: +41 22 919 02 11
Fax: +41 22 919 03 00
IEC 60730-2-15
Edition 2.0 2008-01
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
Automatic electrical controls for household and similar use –
Part 2-15: Particular requirements for automatic electrical air flow, water flow
and water level sensing controls
Dispositifs de commande électrique automatiques à usage domestique et
analogue –
Partie 2-15: Exigences particulières pour les dispositifs de commande
électrique automatiques détecteurs de débit d'air, de débit d'eau et de niveau
d'eau
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
PRICE CODE
INTERNATIONALE
U
CODE PRIX
ICS 97.120 ISBN 2-8318-9587-1
– 2 – 60730-2-15 © IEC:2008
CONTENTS
FOREWORD.3
1 Scope and normative references.5
2 Definitions .6
3 General requirements .8
4 General notes on tests.8
5 Rating.9
6 Classification .9
7 Information .10
8 Protection against electric shock.11
9 Provision for protective earthing.11
10 Terminals and terminations.11
11 Constructional requirements .11
12 Moisture and dust resistance .13
13 Electric strength and insulation resistance.14
14 Heating.14
15 Manufacturing deviation and drift .14
16 Environmental stress .15
17 Endurance.15
18 Mechanical strength.17
19 Threaded parts and connections .18
20 Creepage distances, clearances and distances through solid insulation.18
21 Fire hazard testing.18
22 Resistance to corrosion .18
23 Electromagnetic compatibility (EMC) requirements – emission .18
24 Components .18
25 Normal operation .18
26 Electromagnetic compatibility (EMC) requirements – immunity .19
27 Abnormal operation.19
28 Guidance on the use of electronic disconnection .19
Annex H (normative) Requirements for electronic controls .20
Annex AA (normative) Number of cycles for independently mounted controls for boiler .
applications.25
Annex BB (normative) Requirements for response delay.26
Annex CC (informative) Number of cycles for independently mounted air flow and water
flow sensing controls.27
60730-2-15 © IEC:2008 – 3 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
AUTOMATIC ELECTRICAL CONTROLS
FOR HOUSEHOLD AND SIMILAR USE –
Part 2-15: Particular requirements for automatic electrical air flow, water
flow and water level sensing controls
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with an IEC Publication.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 60730-2-15 has been prepared by IEC technical committee 72:
Automatic controls for household use.
This second edition cancels and replaces the first edition published in 1994 and its Amendment
1 (1997), the first edition of IEC 60730-2-16 published in 1995 and its Amendments 1 (1997)
and 2 (2001) and the first edition of IEC 60730-2-18 published in 1997. This second edition
constitutes a technical revision.
This second edition is a consolidation of three standards IEC 60725-2-15, IEC 60730-2-16 and
IEC 60730-2-18. The title and scope were revised to reflect the additional topics covered by the
standard.
– 4 – 60730-2-15 © IEC:2008
The text of this standard is based upon the following documents:
FDIS Report on voting
72/757A/FDIS 72/761/RVD
Full information on the voting for the approval of this part can be found in the report on voting
indicated in the above table.
This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.
This Part 2-15 is intended to be used in conjunction with IEC 60730-1. It was established on
the basis of the third edition of that standard (1999) and its Amendments 1 (2003) and 2
(2007). Consideration may be given to future editions of, or amendments to, IEC 60730-1.
This Part 2-15 supplements or modifies the corresponding clauses in IEC 60730-1 so as to
convert that publication into the IEC standard: Particular requirements for automatic electrical
air flow, water flow and water level sensing controls.
Where this Part 2-15 states "addition", "modification" or "replacement", the relevant
requirement, test specification or explanatory matter in Part 1 should be adapted accordingly.
Where no change is necessary, this Part 2-15 indicates that the relevant clause or subclause
applies.
In the development of a fully international standard, it has been necessary to take into
consideration the differing requirements resulting from practical experience in various parts of
the world and to recognize the variation in national electrical systems and wiring rules.
The "in some countries" notes regarding differing national practice are contained in the following subclauses:
- 10.1.4
- 12.1.1.101
In this publication:
1) The following print types are used:
– Requirements proper: in roman type.
– Test specifications: in italic type.
– Explanatory matter: in smaller roman type.
2) Subclauses or figures which are additional to those in Part 1 are numbered starting from 101.
A list of all parts of the IEC 60730 series, under the general title: Automatic electrical controls
for household and similar use, can be found on the IEC website.
The committee has decided that the contents of this publication will remain unchanged until the
maintenance result date indicated on the IEC web site under "http://webstore.iec.ch" in the data
related to the specific publication. At this date, the publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
60730-2-15 © IEC:2008 – 5 –
AUTOMATIC ELECTRICAL CONTROLS
FOR HOUSEHOLD AND SIMILAR USE –
Part 2-15: Particular requirements for automatic electrical air flow, water
flow and water level sensing controls
1 Scope and normative references
This clause of Part 1 is replaced as follows:
1.1 This part of IEC 60730 applies to automatic electrical air flow, water flow and water level
sensing controls for use in, or in association with, boilers with a maximum pressure rating of
2 000 kPA (20 bar) and equipment for general household and similar use including controls for
heating, air- conditioning and similar applications.
Examples are water flow and water level sensing controls of the float or electrode-sensor type used in boiler
applications and air flow, water flow and water level sensing controls for swimming pool pumps, water tank pumps,
cooling towers, dishwashers, washing machines, air conditioning chillers and ventilation applications.
1.1.1 This standard applies to the inherent safety, to the operating values, operating
sequences where such are associated with equipment protection, and to the testing of
automatic electrical air flow, water flow and water level sensing controls used in, or in
association with, household and similar equipment.
This standard is also applicable to controls for appliances within the scope of IEC 60335-1
and IEC 60364-7-702.
Automatic electrical air flow, water flow and water level sensing controls for equipment not
intended for normal household use, but which nevertheless may be used by the public, such
as equipment intended to be used by laymen in shops, in light industry and on farms, are
within the scope of this standard.
This standard is also applicable to individual controls utilized as part of a control system or
controls which are mechanically integral with multifunctional controls having non-electrical
outputs.
This standard is not applicable to pressure-operated air flow, water flow and water level
)
sensing controls, requirements for which are contained in IEC 60730-2-6 .
This standard does not apply to air flow, water flow and water level sensing controls designed
exclusively for industrial applications.
Throughout this standard, the word "equipment" means "appliance and equipment".
1.1.2 This standard applies to automatic electrical controls, mechanically or electrically
operated, responsive to or controlling air flow, water flow and water level.
___________
)
IEC 60730-2-6, Automatic electrical controls for household and similar use – Part 2-6: Particular requirements
for automatic electrical pressure sensing controls including mechanical requirements
– 6 – 60730-2-15 © IEC:2008
1.1.3 This standard contains requirements for electrical features of air flow, water flow and
water level sensing controls and requirements for mechanical features that may affect their
intended operation and electrical safety.
1.1.4 This standard applies to manual controls when such are electrically and/or mechanically
integral with air flow, water flow and water level sensing controls.
Requirements for manual switches not forming part of an automatic control are contained in
IEC 60669 and IEC 61058-1.
1.1.5 In general, these air flow, water flow and water level sensing controls are integrated or
incorporated with the equipment or are intended to be integrated or incorporated in or on the
equipment. This standard also covers controls when they are independently mounted or of in-
line cord construction.
1.2 This standard applies to controls with a rated voltage not exceeding 690 V and a rated
current not exceeding 63 A.
1.3 This standard takes into account the response value of an automatic action of a control
where such a response value is dependent upon the method of mounting the control. Where a
response value is of significant purpose for the protection of the user, or surroundings, the
value defined in the appropriate household equipment standard or as determined by the
manufacturer shall apply.
1.4 This standard applies also to controls incorporating electronic devices, requirements for
which are contained in Annex H.
This standard applies also to controls using NTC and PTC thermistors, requirements for which
are contained in Annex J.
1.5 Normative references
This subclause of Part 1 is applicable except as follows:
Addition:
IEC 60364-7-702, Electrical installation of buildings – Part 7: Requirements for special
installations or locations – Section 702: Swimming pools and other basins
IEC 60669 (all parts), Switches for household and similar fixed-electrical installations
2 Definitions
This clause of Part 1 is applicable except as follows:
2.2 Definitions of types of control according to purpose
2.2.19
Addition:
See 2.2.103, 2.2.104, 2.2.106 and 2.2.107.
2.2.20
Addition:
60730-2-15 © IEC:2008 – 7 –
See 2.2.101, 2.2.105, 2.2.108 and 2.2.109.
Additional definitions:
2.2.101
boiler water level cut-out
water level sensing control of the float or electrode-sensor type for boiler applications intended
to respond to a low water level during abnormal operating conditions and which has no
provision for setting by the user
A water level cut-out may be of the automatic or of the manual reset type. A boiler water level cutout is a type of
water level protective control (see 2.2.105).
2.2.102
boiler water level limiter
water level sensing control of the float or electrode-sensor type for boiler applications which is
intended to keep a water level below or above one particular value during normal operating
conditions and which may have provision for setting by the user
A boiler water level limiter is normally of the automatic reset type.
2.2.103
boiler water feed control
water level sensing control of the float or electrode-sensor type for boiler applications which is
intended to keep the water level in a boiler above one particular value during normal operating
conditions and which may have provision for setting by the user
A boiler water feed control is of the automatic reset type. A boiler water feed control is used on a boiler to cycle a
feeder pump or feeder water valve. For the purposes of this standard, a Type 2 boiler water feed control is
considered to be a boiler water level limiter.
2.2.104
water level operating control
control which is intended to keep the water level below or above one particular value during
normal operating conditions and which may have provision for setting by the user
A water level operating control is of the automatic reset type.
2.2.105
water level protective control
control which is intended to prevent a hazardous situation during abnormal operation of the
equipment either by
a) keeping the water level below or above one or more particular values, or by
b) energizing or de-energizing the associated equipment at one or more particular values of
water level
2.2.106
water flow operating control
flow sensing control intended to sense or maintain the water flow between two particular values
during normal operating conditions and which may have provision for setting by the user
A water flow operating control is of the automatic reset type.
2.2.107
air flow operating control
flow sensing control intended to sense or maintain the air flow between two particular values
during normal operating conditions and which may have provision for setting by the user
An air flow operating control is of the automatic reset type.
– 8 – 60730-2-15 © IEC:2008
2.2.108
water flow cut-out
flow sensing control intended to respond to a lack of water flow during abnormal operating
conditions and which has no provision for setting by the user
A water flow cut-out is of the automatic or manual reset type.
2.2.109
air flow cut-out
flow sensing control intended to respond to a lack of air flow during abnormal operating
conditions and which has no provision for setting by the user
An air flow cut-out is of the automatic or manual reset type.
2.3 Definitions relating to the function of controls
Additional definition:
2.3.101
response delay
delay provided to increase the response value of a water level operating control for the purpose
of preventing unnecessary cycling of the equipment due to fluctuating liquid level
This is usually expressed in units of time.
3 General requirements
This clause of Part 1 is applicable.
4 General notes on tests
This clause of Part 1 is applicable except as follows:
4.1 Conditions of test
4.1.7
Addition:
The rates of change shall have tolerances agreed between the manufacturer and test house.
Additional subclause:
4.1.101 The values in Annex AA apply for the testing of independently mounted water level
sensing controls used in boiler applications in Clause 17 unless a higher number is declared.
The values in Annex CC apply for the testing of independently mounted air and water flow
sensing controls in Clause 17 unless otherwise declared. Values for integrated and
incorporated controls are specified in the appropriate equipment standard.
60730-2-15 © IEC:2008 – 9 –
4.3 Instructions for test
4.3.5.1 Modification:
The second sentence is not applicable to combinations of boiler water level sensing controls
using a common sensing mechanism.
5 Rating
This clause of Part 1 is applicable.
6 Classification
This clause of Part 1 is applicable except as follows:
6.3 According to their purpose
6.3.9
Additional subclauses:
6.3.9.101 – boiler water level cut-out;
6.3.9.102 – boiler water level limiter;
6.3.9.103 – boiler water feed control;
6.3.9.104 – water level operating control;
6.3.9.105 – water level protective control;
6.3.9.106 – air flow operating control;
6.3.9.107 – water flow operating control;
6.3.9.108 – air flow cut-out;
6.3.9.109 – water flow cut-out.
6.4 According to features of automatic action
6.4.1
Additional subclause:
6.4.1.101 Boiler water feed controls within the scope of this standard are classified as
having Type 1 action.
For the purpose of this standard, a Type 2 boiler water feed control is considered to be a boiler water level limiter.
– 10 – 60730-2-15 © IEC:2008
6.4.2
Additional subclause:
6.4.2.101 Boiler water level cut-outs and boiler water level limiters within the scope of this
standard are classified as having Type 2 action.
6.4.3
Additional subclauses:
6.4.3.101 – manual reset boiler water level sensing controls within the scope of this standard
shall have a trip-free mechanism classified as Type 2.D, 2.H or 2.J action;
6.4.3.102 – an action incorporating response delay (Type 1.AJ or 2.AJ).
6.5 According to the degree of protection and control pollution degree
6.5.2 Addition:
Controls declared in Item 107 of Table 7.2 to be wholly or partially submerged in water during
usage shall have enclosures classified as IPX8 which provide protection against continuous
immersion in water as specified in IEC 60529.
7 Information
This clause of Part 1 is applicable except as follows:
Table 7.2
Modification:
Clause
Information or Method
subclause
Modifications:
23 Temperature limits of mounting surfaces (T ) 6.12.2, 14.1, 17.3 D
s
101)
27 Number of automatic cycles (A) for each automatic action 6.11, 17.8, 17.9 X
34 Not applicable
44 Not applicable
Additional items:
101 14.5.1 D
Maximum fluid temperature (TL) in °C
102 Response time, if applicable, for boiler water level sensing controls 15 C
(104)
103 Maximum working pressure, if applicable 2.3.29, 18.102 C/D
104 Method of determining response time for boiler water level sensing 15.6.101 X
controls
105 Test method for 18.101.2 for boiler water level sensing controls 18.101.2 X
106 Any special environmental conditions in which the control is intended 12.1.101 D
102)
to be used (other than declared in Table 7.2 Item 15)
107 Cord-connected float control which may be wholly or partially 6.5.2, 11.7.1.1, D
submerged in water or any other special environmental conditions 11.7.1.2.1,
declared in Item 106 11.7.1.2.2,
12.1.1.101
60730-2-15 © IEC:2008 – 11 –
108 Response delay 2.3.101, 6.4.3.102, D
11.4.101,
H.11.12.8,
Annex BB
109 Unique or common type reference of special mounting means, if 11.6.3.1 C
103)
any
110 Leveling indication for mounting, if any 11.11.101 C
Additional notes:
101)
The minimum number of automatic cycles is 6 000 for water level sensing controls of the float type.
102)
This information may be taken from the appropriate IEC equipment standard or may be as declared by the
manufacturer.
103)
The unique or common type reference(s) shall be marked on both the mounting means and the control.
104)
Method C is required for air flow, water flow and boiler water level sensing controls.
Modify the table in Note 4:
Change "Air flow" to "Air flow or water flow".
Add, to Note 4, the following text:
For water level controls, limits of activating quantity are specified either in the applicable household appliance
standard, by the appliance manufacturer or as declared by the water level control manufacturer (see 17.7 and 17.8).
8 Protection against electric shock
This clause of Part 1 is applicable.
9 Provision for protective earthing
This clause of Part 1 is applicable.
10 Terminals and terminations
This clause of Part 1 is applicable except as follows:
10.1 Terminals and terminations for external copper conductors
10.1.4 Addition:
In Canada and the USA, controls for operation above 50 V shall be provided with suitable wiring terminals or leads
for the connection of fixed wiring conductors having an ampere rating of no less than:
– 1,25 times the ampere rating of a fixed electric space-heating equipment load;
– 1,25 times the full-load motor current rating of a single motor;
– 1,25 times the combination load of a full-load motor current and 1,25 times a fixed electric space-heating
equipment load;
– 1,25 times the full load current of the largest motor plus the full load amperes of the other loads;
– 1,0 times all other loads.
Compliance is checked by inspection.
11 Constructional requirements
This clause of Part 1 is applicable except as follows:
– 12 – 60730-2-15 © IEC:2008
11.4 Actions
11.4.11 Modification:
Delete the last sentence of the first paragraph.
11.4.12 Modification:
Delete the last sentence of the first paragraph.
Additional subclause:
11.4.101 Type 1.AJ or 2.AJ action
A Type 1.AJ or 2.AJ action shall be designed such that a response delay, as declared, is
provided.
For Type 2.AJ action, response delay is checked by the test of Subclause 15.5.
11.7 Attachment of cords
11.7.1 Flexing
11.7.1.1 Addition:
For controls declared in Item 107 of Table 7.2, the appropriate test of 11.7.1.2.1 shall be
conducted.
11.7.1.2.1 Modification:
This clause of Part 1 is applicable except for controls declared in Item 107 of Table 7.2.
Controls so declared are subjected to the following test only, and not that of Part 1.
Three samples of controls declared in Item 107 of Table 7.2 shall be subjected to a flexing test
while mounted in the flexing apparatus shown in Figure 9. The cord shall be subjected to a
minimum backward and forward movement through an angle of 90°. The cord shall be
conducting the maximum rated current at maximum rated voltage. The number of flexings (that
is one movement through 90°) shall be 30 000 at a rate of 60 flexings per minute.
For this test, the cord is not loaded with additional weight.
Additional subclause:
11.7.1.2.1.101 Immediately following the flexing test, the control shall be subjected to the
following immersion test:
The controls, including their cords, shall be immersed and maintained in water or other special
environmental condition as declared in Items 106 and 107 of Table 7.2, at T for seven days
L
such that the water, or other environmental condition, is at least 1 m above the highest point of
the float control.
11.7.1.2.2 Addition:
For controls tested in accordance with Subclause 11.7.1.2.1.101, the following evaluation
criteria are used: After the test, the control shall comply with the requirements of Clause 8,
Subclause 12.3 and Clause 13 for basic insulation, and there shall be no evidence of ingress of
the test medium, compliance for which is checked by inspection.
11.11 Requirements during mounting, maintenance and servicing
60730-2-15 © IEC:2008 – 13 –
Additional subclause:
11.11.101 If the operation of a Type 2 water level control of the float type is affected by its
being placed out of level, the control shall be provided with a leveling indicator (e.g. a bubble,
pendulum, horizontal or vertical line).
Compliance is checked by inspection and the test of 15.5.
Additional subclauses:
11.101 Construction requirements relating to operating mechanism
11.101.1 Screws and nuts which attach parts to movable members shall be swaged or
otherwise locked.
For example, this would apply to the float hinge pivot of a water level sensing control.
11.101.2 Operating parts shall be separated by barriers or by their physical location from
conductors to be connected to the control to avoid interference with the movement of such
parts by the conductors.
Compliance with 11.101.1 and 11.101.2 is checked by inspection.
12 Moisture and dust resistance
This clause of Part 1 is applicable except as follows.
12.1 Protection against ingress of water and dust
Additional subclauses:
12.1.1.101 For controls declared in Item 107 of Table 7.2, and having enclosures classified
as IPX8, the requirements of 12.1.2 to 12.1.6, inclusive, do not apply. These controls shall
withstand the following test:
Prior to subjecting three samples of the cord-connected float control to the following immersion
test, the control shall be subjected to the impact resistance test in 18.2.
In the USA, the impact resistance test shall be conducted as described in Subclause D.2.11.2.
The controls are to be immersed and maintained in the test medium or other special
environmental condition as declared in Items 106 and 107 of Table 7.2, at T for seven days
L
such that the test medium, or other environmental condition, is at least 1 m above the highest
point of the float control.
After the test, the control shall comply with the requirements of Clauses 8 and 13 and
Subclause 12.3 for basic insulation, and there shall be no evidence of ingress of the test
medium when compliance is checked by inspection.
12.1.101 Air flow, water flow and water level operating controls which are declared in
Item 106 of Table 7.2 for use in a special environmental condition shall be evaluated further for
use in this environment.
Compliance is checked by the appropriate tests for the declared environment described in the
relevant IEC standard or by a test method agreed between manufacturer and testing authority.
After the test, the control is deemed to comply if:
– 14 – 60730-2-15 © IEC:2008
– there is no evidence of ingress of the test medium;
– all actions function automatically and manually in the intended and declared manner, and
– the requirements of 17.5 are still met.
13 Electric strength and insulation resistance
This clause of Part 1 is applicable except as follows:
Additional subclause:
13.101 Electric strength of probes
Probes of electrode-sensor type boiler water level sensing controls shall be subjected to the
following tests:
The purpose of this test is to evaluate degradation of probe insulating material as a result of exposure to conditions
in the boiler.
Three samples of the probe shall be conditioned for 10 days in a test boiler operating at the
manufacturer's declared maximum working pressure and water temperature. The samples are
then removed from the test boiler and any surface contamination is removed.
The conditioned samples and three unconditioned samples are then immediately subjected to
an increasing voltage until dielectric breakdown occurs.
The average breakdown voltage of the conditioned samples shall be not less than 50 % of the
breakdown voltage of the unconditioned samples and, furthermore, shall be not less than the
appropriate value in Table 13.2.
14 Heating
This clause of Part 1 is applicable except as follows:
14.4.3.1 Not applicable.
14.5.1 Replacement:
For water flow and water level sensing controls, the control is mounted in the declared manner
with the water maintained at T (Table 7.2, Item 101) and, if applicable, at maximum working
L
pressure. The test is conducted with the switch head in an ambient temperature maintained
between T and either (T + 5) °C or 1,05 times T , whichever is greater. For water flow
max max max
sensing controls, the test is conducted with and without water flowing.
15 Manufacturing deviation and drift
This clause of Part 1 is applicable except as follows:
15.2 to 15.4 Replacement:
For evaluating the deviation and drift of the air flow, water flow or water level at which a Type 2
control operates, a method of test is agreed between manufacturer and testing authority.
60730-2-15 © IEC:2008 – 15 –
15.6
Additional subclause:
15.6.101 If a response time has been declared, the response time of the sample shall be
initially measured at T and T and, if an absolute value is declared, shall be within the
max min
manufacturer's declared time. If a range is declared, the initial measured response time shall
be within the declared range.
The measured values for each sample shall be recorded as a reference value, so that
the repeat tests after the environmental tests of Clause 16 and the endurance tests of
Clause 17 will enable the drift to be determined. The values measured during the repeat test
shall be within ±5 % of the initial measured value and, if a range is declared, shall be within the
declared range.
16 Environmental stress
This clause of Part 1 is applicable.
17 Endurance
This clause of Part 1 is applicable except as follows:
17.1 General requirements
Additional subclause:
17.1.1.101 Air and water flow sensing controls shall operate as intended. When subjecting the
controls to the requirements of Clause 17, the flow sensing controls shall be actuated and
cycled by means simulating the actual applications. The simulated mechanical cycling means
shall be agreed to between the manufacturer and the test authority. The specified fluid and/or
specific flow rate are not required.
17.1.2.1 Modification:
Compliance with 17.1.1 and 17.1.2 is checked by the tests of 17.16.
17.16 Test for particular purpose controls
Additional subclauses:
17.16.101 Boiler water level cut-out
– 17.1 to 17.5 inclusive are applicable.
– 17.6 is applicable to actions classified as Type 2.M, the value of "X" being as small as
practicable.
– 17.7 and 17.8 are applicable except that, where necessary, the reset operation is obtained
by actuation. This actuation shall be as specified in 17.4 for accelerated speed, as soon as
permitted by the mechanism, or as declared by the manufacturer in 7.2.
– 17.9, 17.11 and 17.12 are not applicable.
– 17.10 and 17.13 do not apply to the normal reset manual action which is tested during the
automatic test of 17.7 and 17.8. If the water level cut-out has other manual actions which
are not tested during the automatic tests, then these subclauses are applicable.
– 16 – 60730-2-15 © IEC:2008
– 17.14 is applicable.
17.16.102 Boiler water level limiter
– 17.1 to 17.5 inclusive are applicable.
– 17.6 is applicable to actions classified as Type 2.M, the value of "X" being as small as
practicable.
– 17.7 and 17.8 are applicable except that, where necessary, the reset operation is obtained
by actuation. This actuation shall be as specified in 17.4 for accelerated speed, as soon as
permitted by the mechanism, or as declared by the manufacturer in Table 7.2.
– 17.9 to 17.13 inclusive are not applicable.
– 17.14 is applicable.
17.16.103 Boiler water feed controls
– 17.1 to 17.5 inclusive are applicable.
– 17.6 is applicable to actions classified as Type 2.M, the value of "X" being as small as
practicable.
– 17.7 and 17.8 are applicable except that, where necessary, the reset operation is obtained
by actuation. This actuation shall be as specified in 17.4 for accelerated speed, as soon as
permitted by the mechanism, or as declared by the manufacturer in Table 7.2.
– 17.9 is applicable.
– 17.10 to 17.13 are not applicable.
– 17.14 is applicable.
17.16.104 Water level operating controls
– 17.1 to 17.5 inclusive are applicable.
– 17.6 is not applicable.
– 17.7 and 17.8 are applicable.
– 17.9 to 17.13 are not applicable.
– 17.14 is applicable.
17.16.105 Water level protective controls
– 17.1 to 17.5 inclusive are applicable.
– 17.6 is not applicable.
– 17.7 and 17.8 are applicable.
– 17.9 to 17.13 are not applicable.
– 17.14 is applicable.
17.16.106 Air and water flow sensing controls
– 17.1 to 17.5 inclusive are applicable.
– 17.6 is not applicable.
– 17.7 and 17.8 are applicable except that, where necessary, the reset operation is obtained
by actuation. This actuation shall be as specified in 17.4 for accelerated speed, as
permitted by the mechanism, or as declared by the manufacturer in Table 7.2.
– 17.9 to 17.14 inclusive are applicable.
60730-2-15 © IEC:2008 – 17 –
18 Mechanical strength
This clause of Part 1 is applicable except as follows:
Additional subclauses:
18.101 Those parts of a boiler water level sensing control which are exposed to boiler
pressure shall be capable of withstanding for 1 min without bursting, a hydraulic pressure equal
to 400 % of the maximum working pressure declared in Table 7.2, Item 103.
The float assembly of a float-operated boiler water level sensing control shall withstand 200 %
of the maximum working pressure declared in Table 7.2, Item 103, when tested as declared in
Table 7.2, Item 105.
Compliance is checked by the tests of this subclause.
18.101.1 Except for electrode-sensor type boiler water level sensing controls, one sample is
subjected to the test.
For electrode-sensor type boiler water level sensing controls, one sample subjected to the
test of 13.101 shall be used. In addition, a second previously untested sample of the
electrode-sensor type is used after being conditioned for 30 days in an oven maintained at a
temperature between 102 % and 105 % of the declared maximum water temperature
(Table 7.2, Item 101).
The boiler water level sensing control is to be fitted to a tank filled with water and connected
to a hydraulic pump. The pressure is to be raised gradually to 400 % of the declared
maximum working pressure and held for 1 min.
Leakage at a gasket or fitting is permitted provided the leakage does not occur below 200 %
of the declared maximum working pressure.
18.101.2 The float assembly of a float-operated boiler water level sensing control shall
withstand 200 % of the declared maximum working pressure when tested as declared in
Table 7.2, Item 105.
18.102 Strength of parts (hydrostatic)
18.102.1 A flow sensing control employing a Bourdon tube, a flexible metal bellows, a
diaphragm or the like rated 2 000 kPa or more which is not contained within an enclosure
shall withstand for 1 min without bursting a hydraulic pressure equal to four times the
maximum working pressure of the control.
The control under test
...








Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.
Loading comments...