IEC 62305-2:2024
(Main)Protection against lightning - Part 2: Risk management
Protection against lightning - Part 2: Risk management
IEC 62305-2:2024 is applicable to the risk management of a structure due to lightning flashes to earth.
Its purpose is to provide a procedure for the evaluation of such a risk. Once an upper tolerable limit for the risk has been selected, this procedure provides a means for the selection of appropriate protection measures to be adopted to reduce the risk to or below the tolerable limit.
This third edition cancels and replaces the second edition, published in 2010. This edition constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous edition:
a) The concept of a single risk, to combine loss of human life and loss due to fire, has been introduced.
b) The concept of frequency of damage that can impair the availability of the internal systems within the structure has been introduced.
c) The lightning ground strike-point density NSG has been introduced replacing the lightning flash density NG in the evaluation of expected average annual number of dangerous events.
d) Reduction of a few risk components can be achieved by the use of preventive temporary measures activated by means of a thunderstorm warning system (TWS) compliant with IEC 62793. The risk of direct strike to people in open areas has been introduced, considering the reduction of that risk using a TWS.
The content of the corrigendum 1 (2024-10) has been included in this copy.
Protection contre la foudre - Partie 2: Évaluation des risques
L'IEC 62305-2:2024 s'applique à l'évaluation des risques auxquels une structure est exposée en raison des coups de foudre à la terre.
Elle est destinée à proposer une procédure d'évaluation d'un tel risque. Lorsque la limite supérieure du risque tolérable est fixée, la procédure permet de choisir les mesures de protection appropriées pour réduire le risque à une valeur inférieure ou égale à la valeur limite tolérable.
Cette troisième édition annule et remplace la deuxième édition parue en 2010. Cette édition constitue une révision technique.
Cette édition inclut les modifications techniques majeures suivantes par rapport à l'édition précédente:
a) adoption du concept de risque unique, afin de combiner les pertes de vies humaines et les pertes dues à un incendie;
b) adoption du concept de fréquence des dommages qui peuvent influencer la disponibilité des réseaux internes à la structure;
c) adoption de la densité de points d'impact au sol de la foudre NSG en remplacement de la densité des coups de foudre NG dans l'évaluation du nombre moyen annuel d'événements dangereux prévisibles;
d) la réduction de quelques composantes de risque peut être obtenue par l'utilisation de mesures préventives temporaires activées par un système d'alerte aux orages (TWS) conforme à l'IEC 62793. Le risque que des personnes soient directement frappées par la foudre dans des espaces ouverts a été décrit, en tenant compte de la réduction de ce risque au moyen d'un TWS.
Le contenu du corrigendum 1 (2024-10) a été pris en considération dans cet exemplaire.
General Information
Relations
Overview
IEC 62305-2:2024 is the third edition of the international standard published by the International Electrotechnical Commission (IEC) that focuses on protection against lightning through risk management. This part of the IEC 62305 series provides structured procedures to evaluate the risk posed by lightning flashes to earth affecting structures. Its main goal is to assist in selecting appropriate protection measures to reduce the lightning risk to or below a pre-established tolerable limit.
This 2024 edition replaces the 2010 second edition and introduces technical revisions, including new concepts such as combining human life loss and fire damage into a single risk, assessing the frequency of damage impairing internal systems’ availability, and utilizing lightning ground strike-point density for risk evaluation.
Key Topics
Risk Management Procedure: The standard outlines a detailed procedure for risk evaluation, including assessing potential damage sources, types of loss, and risk components relevant to a structure exposed to lightning.
Risk Components and Damage Sources: Four primary sources of damage (S1 to S4) are analyzed in the context of the structure and its environments:
- Direct lightning strikes to the structure
- Strikes to nearby structures or lines
- Strikes near lines impacting internal system availability
- Secondary effects such as fire or explosion caused by lightning
New Concepts in Risk Assessment:
- Single Risk Concept: Combines losses of human life and fire damage for comprehensive risk evaluation.
- Frequency of Damage: Focus on how often lightning damage can impair the structure’s internal systems.
- Ground Strike-Point Density (NSG): Replaces previous lightning flash density (NG) data to improve accuracy in estimating dangerous event occurrences.
- Preventive Temporary Measures: Incorporation of thunderstorm warning systems (TWS) compliant with IEC 62793 to temporarily reduce certain risk components, including risk of direct strikes in open areas.
Partitioning for Detailed Risk Evaluation: Structures can be divided into risk zones and lines into sections to assess risk components with greater precision.
Calculation of Loss and Probability: The standard provides guidance on estimating the probability of damage, expected losses, and frequency of dangerous events using comprehensive models described in informative annexes.
Applications
IEC 62305-2:2024 is critical for professionals engaged in:
- Lightning Protection System Design: Electrical engineers and safety specialists can leverage the risk management procedures to design and specify lightning protection measures optimized for safety and cost-effectiveness.
- Risk Assessment for Structures: Owners and facility managers of buildings, including houses, offices, hospitals, and industrial facilities, can evaluate their lightning risk status and mitigate threats to life, property, and system availability.
- Development of Safety Protocols: Organizations can integrate preventive temporary measures, such as TWS, into their safety policies to further minimize lightning risks during severe weather events.
- Standard Compliance and Certification: Ensures adherence to international standards in lightning protection and risk mitigation, facilitating regulatory approval and insurance requirements.
Related Standards
- IEC 62305-1, 3, and 4: Complementary parts covering general principles, physical damage to structures and life hazard, and electrical and electronic system protection respectively.
- IEC 62793: Specifies requirements for thunderstorm warning systems (TWS) used as preventive temporary lightning risk reduction measures.
- National and Regional Lightning Protection Codes: Local standards often reference IEC 62305 series for harmonized lightning risk management approaches.
Adopting IEC 62305-2:2024 supports comprehensive lightning risk management by delivering a technically updated framework for assessing, quantifying, and reducing risks, thereby enhancing protection of human life, structural integrity, and system functionality from lightning hazards. This makes it an indispensable resource for engineering, safety, and risk professionals worldwide.
Frequently Asked Questions
IEC 62305-2:2024 is a standard published by the International Electrotechnical Commission (IEC). Its full title is "Protection against lightning - Part 2: Risk management". This standard covers: IEC 62305-2:2024 is applicable to the risk management of a structure due to lightning flashes to earth. Its purpose is to provide a procedure for the evaluation of such a risk. Once an upper tolerable limit for the risk has been selected, this procedure provides a means for the selection of appropriate protection measures to be adopted to reduce the risk to or below the tolerable limit. This third edition cancels and replaces the second edition, published in 2010. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition: a) The concept of a single risk, to combine loss of human life and loss due to fire, has been introduced. b) The concept of frequency of damage that can impair the availability of the internal systems within the structure has been introduced. c) The lightning ground strike-point density NSG has been introduced replacing the lightning flash density NG in the evaluation of expected average annual number of dangerous events. d) Reduction of a few risk components can be achieved by the use of preventive temporary measures activated by means of a thunderstorm warning system (TWS) compliant with IEC 62793. The risk of direct strike to people in open areas has been introduced, considering the reduction of that risk using a TWS. The content of the corrigendum 1 (2024-10) has been included in this copy.
IEC 62305-2:2024 is applicable to the risk management of a structure due to lightning flashes to earth. Its purpose is to provide a procedure for the evaluation of such a risk. Once an upper tolerable limit for the risk has been selected, this procedure provides a means for the selection of appropriate protection measures to be adopted to reduce the risk to or below the tolerable limit. This third edition cancels and replaces the second edition, published in 2010. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition: a) The concept of a single risk, to combine loss of human life and loss due to fire, has been introduced. b) The concept of frequency of damage that can impair the availability of the internal systems within the structure has been introduced. c) The lightning ground strike-point density NSG has been introduced replacing the lightning flash density NG in the evaluation of expected average annual number of dangerous events. d) Reduction of a few risk components can be achieved by the use of preventive temporary measures activated by means of a thunderstorm warning system (TWS) compliant with IEC 62793. The risk of direct strike to people in open areas has been introduced, considering the reduction of that risk using a TWS. The content of the corrigendum 1 (2024-10) has been included in this copy.
IEC 62305-2:2024 is classified under the following ICS (International Classification for Standards) categories: 29.020 - Electrical engineering in general; 29.140.40 - Luminaires; 91.120.40 - Lightning protection. The ICS classification helps identify the subject area and facilitates finding related standards.
IEC 62305-2:2024 has the following relationships with other standards: It is inter standard links to IEC 62305-2:2024/COR1:2024, IEC 62305-2:2010. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
You can purchase IEC 62305-2:2024 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of IEC standards.
Standards Content (Sample)
IEC 62305-2 ®
Edition 3.0 2024-09
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
Protection against lightning –
Part 2: Risk management
Protection contre la foudre –
Partie 2: Évaluation des risques
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form
or by any means, electronic or mechanical, including photocopying and microfilm, without permission in writing from
either IEC or IEC's member National Committee in the country of the requester. If you have any questions about IEC
copyright or have an enquiry about obtaining additional rights to this publication, please contact the address below or
your local IEC member National Committee for further information.
Droits de reproduction réservés. Sauf indication contraire, aucune partie de cette publication ne peut être reproduite ni
utilisée sous quelque forme que ce soit et par aucun procédé, électronique ou mécanique, y compris la photocopie et
les microfilms, sans l'accord écrit de l'IEC ou du Comité national de l'IEC du pays du demandeur. Si vous avez des
questions sur le copyright de l'IEC ou si vous désirez obtenir des droits supplémentaires sur cette publication, utilisez
les coordonnées ci-après ou contactez le Comité national de l'IEC de votre pays de résidence.
IEC Secretariat Tel.: +41 22 919 02 11
3, rue de Varembé info@iec.ch
CH-1211 Geneva 20 www.iec.ch
Switzerland
About the IEC
The International Electrotechnical Commission (IEC) is the leading global organization that prepares and publishes
International Standards for all electrical, electronic and related technologies.
About IEC publications
The technical content of IEC publications is kept under constant review by the IEC. Please make sure that you have the
latest edition, a corrigendum or an amendment might have been published.
IEC publications search - webstore.iec.ch/advsearchform IEC Products & Services Portal - products.iec.ch
The advanced search enables to find IEC publications by a Discover our powerful search engine and read freely all the
variety of criteria (reference number, text, technical publications previews, graphical symbols and the glossary.
committee, …). It also gives information on projects, replaced With a subscription you will always have access to up to date
and withdrawn publications. content tailored to your needs.
IEC Just Published - webstore.iec.ch/justpublished
Electropedia - www.electropedia.org
Stay up to date on all new IEC publications. Just Published
The world's leading online dictionary on electrotechnology,
details all new publications released. Available online and once
containing more than 22 500 terminological entries in English
a month by email.
and French, with equivalent terms in 25 additional languages.
Also known as the International Electrotechnical Vocabulary
IEC Customer Service Centre - webstore.iec.ch/csc
(IEV) online.
If you wish to give us your feedback on this publication or need
further assistance, please contact the Customer Service
Centre: sales@iec.ch.
A propos de l'IEC
La Commission Electrotechnique Internationale (IEC) est la première organisation mondiale qui élabore et publie des
Normes internationales pour tout ce qui a trait à l'électricité, à l'électronique et aux technologies apparentées.
A propos des publications IEC
Le contenu technique des publications IEC est constamment revu. Veuillez vous assurer que vous possédez l’édition la
plus récente, un corrigendum ou amendement peut avoir été publié.
Recherche de publications IEC - IEC Products & Services Portal - products.iec.ch
webstore.iec.ch/advsearchform Découvrez notre puissant moteur de recherche et consultez
La recherche avancée permet de trouver des publications IEC gratuitement tous les aperçus des publications, symboles
en utilisant différents critères (numéro de référence, texte, graphiques et le glossaire. Avec un abonnement, vous aurez
comité d’études, …). Elle donne aussi des informations sur les toujours accès à un contenu à jour adapté à vos besoins.
projets et les publications remplacées ou retirées.
Electropedia - www.electropedia.org
IEC Just Published - webstore.iec.ch/justpublished
Le premier dictionnaire d'électrotechnologie en ligne au monde,
Restez informé sur les nouvelles publications IEC. Just
avec plus de 22 500 articles terminologiques en anglais et en
Published détaille les nouvelles publications parues.
français, ainsi que les termes équivalents dans 25 langues
Disponible en ligne et une fois par mois par email.
additionnelles. Egalement appelé Vocabulaire
Electrotechnique International (IEV) en ligne.
Service Clients - webstore.iec.ch/csc
Si vous désirez nous donner des commentaires sur cette
publication ou si vous avez des questions contactez-nous:
sales@iec.ch.
IEC 62305-2 ®
Edition 3.0 2024-09
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
Protection against lightning –
Part 2: Risk management
Protection contre la foudre –
Partie 2: Évaluation des risques
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE
ICS 29.020, 91.120.40 ISBN 978-2-8322-9549-6
– 2 – IEC 62305-2:2024 © IEC 2024
CONTENTS
FOREWORD . 8
INTRODUCTION . 11
1 Scope . 13
2 Normative references . 13
3 Terms and definitions . 13
4 Symbols and abbreviated terms . 21
5 Damage and loss . 25
5.1 Source of damage . 25
5.2 Cause of damage . 25
5.3 Type of loss . 25
6 Risk and risk components . 26
6.1 Risk . 26
6.2 Risk components . 27
6.2.1 Risk components for a structure due to source S1 . 27
6.2.2 Risk component for a structure due to source S2 . 28
6.2.3 Risk components for a structure due to source S3 . 28
6.2.4 Risk component for a structure due to source S4 . 28
6.2.5 Factors affecting risk components for a structure . 28
6.3 Composition of risk components . 29
6.3.1 Composition of risk components according to source of damage . 29
6.3.2 Composition of risk components according to type of loss . 30
7 Risk assessment . 31
7.1 Basic procedure . 31
7.2 Structure to be considered for risk assessment . 31
7.3 Procedure to evaluate the need of protection for risk R . 31
8 Assessment of risk components . 33
8.1 Basic equation . 33
8.2 Assessment of risk components due to different sources of damage . 34
8.3 Partitioning of a structure in risk zones Z . 36
S
8.4 Partitioning of a line into sections S . 37
L
8.5 Assessment of risk components in a zone of a structure with risk zones Z . 38
S
8.5.1 General criteria . 38
8.5.2 Single-zoned structure . 38
8.5.3 Multi-zoned structure . 38
9 Frequency of damage and its components . 39
9.1 Frequency of damage . 39
9.2 Assessment of partial frequency of damage . 39
9.3 Procedure to evaluate the need of protection for frequency of damage F . 40
9.4 Assessment of partial frequency of damage in zones . 42
9.4.1 General criteria . 42
9.4.2 Single-zoned structure . 42
9.4.3 Multi-zoned structure . 42
Annex A (informative) Assessment of annual number N of dangerous events . 43
A.1 General . 43
A.2 Assessment of the average annual number of dangerous events N due to
D
flashes to a structure and N to an adjacent structure . 44
DJ
A.2.1 Determination of the collection area A . 44
D
A.2.2 Structure as a part of a building . 46
A.2.3 Relative location of the structure . 48
A.2.4 Number of dangerous events N for the structure . 48
D
A.2.5 Number of dangerous events N for an adjacent structure . 49
DJ
A.3 Assessment of the average annual number of dangerous events N due to
M
flashes near a structure . 49
A.4 Assessment of the average annual number of dangerous events N due to
L
flashes to a line . 50
A.5 Assessment of average annual number of dangerous events N due to
I
flashes near a line . 51
A.6 Representation of the equivalent collection areas . 52
Annex B (informative) Assessment of probability P of damage . 53
X
B.1 General . 53
B.2 Probability P that a flash to a structure will cause dangerous touch and
AT
step voltages . 54
B.3 Probability P that a flash will cause damage to an exposed person on the
AD
structure . 55
B.4 Probability P that a flash to a structure will cause physical damage by fire
B
or explosion . 57
B.5 Probability P that a flash to a structure will cause failure of internal
C
systems . 59
B.6 Probability P that a flash near a structure will cause failure of internal
M
systems . 63
B.7 Probability P that a flash to a line will cause damage due to touch voltage . 65
U
B.8 Probability P that a flash to a line will cause physical damage by fire or
V
explosion . 67
B.9 Probability P that a flash to a line will cause failure of internal systems . 68
W
B.10 Probability P that a lightning flash near an incoming line will cause failure
Z
of internal systems . 69
B.11 Probability P that a person will be in a dangerous place . 69
P
B.12 Probability P that an equipment will be exposed to a damaging event . 70
e
Annex C (informative) Assessment of loss L . 71
X
C.1 General . 71
C.2 Mean relative loss per dangerous event . 71
Annex D (informative) P evaluation . 74
SPD
D.1 General . 74
D.2 P values . 75
Q
D.2.1 Probability values of both the negative and positive first strokes . 75
D.2.2 Source of damage S1 . 75
D.2.3 Source of damage S3 . 76
D.2.4 Sources of damage S2 and S4. 77
D.3 SPD protection level . 77
D.3.1 General . 77
– 4 – IEC 62305-2:2024 © IEC 2024
D.3.2 Source of damage S1 . 77
D.3.3 Source of damage S3 . 81
D.3.4 Energy coordinated SPDs: One voltage switching SPD and one voltage
limiting SPD downstream . 85
D.4 Source of damage S4 . 88
D.4.1 One voltage limiting SPD . 88
D.4.2 One voltage switching SPD . 88
D.5 Source of damage S2 . 89
Annex E (informative) Detailed investigation of additional losses L related to
E
surroundings . 90
E.1 General . 90
E.2 Calculation of risk components . 90
Annex F (informative) Case studies . 94
F.1 General . 94
F.2 House . 94
F.2.1 Relevant data and characteristics . 94
F.2.2 Calculation of expected annual number of dangerous events . 96
F.2.3 Risk management . 97
F.2.4 Definition of risk zones in the house . 97
F.2.5 Risk assessment . 99
F.2.6 Risk – Selection of protection measures . 99
F.2.7 Conclusions . 100
F.3 Office building . 100
F.3.1 Relevant data and characteristics . 100
F.3.2 Calculation of expected annual number of dangerous events . 101
F.3.3 Risk management . 102
F.3.4 Definition of zones in the office building . 103
F.3.5 Risk assessment . 107
F.3.6 Frequency of damage assessment . 108
F.3.7 Risk – Selection of protection measures . 108
F.3.8 Frequency of damage – Selection of protection measures . 109
F.3.9 Conclusions . 110
F.4 Hospital . 110
F.4.1 Relevant data and characteristics . 110
F.4.2 Calculation of expected annual number of dangerous events . 111
F.4.3 Risk management . 112
F.4.4 Definition of zones in the hospital . 112
F.4.5 Risk assessment . 117
F.4.6 Frequency of damage assessment . 118
F.4.7 Risk – Selection of protection measures . 118
F.4.8 Frequency of damage – Selection of protection measures . 120
F.4.9 Conclusions . 120
Bibliography . 121
Figure 1 – Procedure for deciding the need for protection and for the selection of
protection measures to reduce R ≤ R . 33
T
Figure 2 – Example of zone partitioning . 37
Figure 3 – Procedure for determining the need for protection and for the selection of
protection measures . 41
Figure A.1 – Collection area A of an isolated structure . 44
D
Figure A.2 – Complex-shaped structure . 45
Figure A.3 – Different methods to determine the collection area for a given structure . 46
Figure A.4 – Structure to be considered for evaluation of collection area A . 47
D
Figure A.5 – Equivalent collection areas A , A , A , A and A . 52
D DJ M L l
Figure D.1 – Charge probability of both negative and positive first strokes . 76
Figure D.2 – Probability P as a function of the SPD residual voltage U ’ at 1 kA . 78
Up p
Figure D.3 – Probability P as a function of k . 79
Up 1i
Figure D.4 – Probability P as a function of the SPD2 residual voltage U ’ at 1 kA . 80
Up p
Figure D.5 – Probability P as a function of the SPD2 residual voltage U ’ at 1 kA . 81
Up p
Figure D.6 – Probability P as a function of the residual voltage at 1 kA (U ’) . 82
Up p
Figure D.7 – Probability P as a function of different lengths of the internal circuit . 83
Up
Figure D.8 – Probability P as a function of different lengths of the internal circuit . 83
Up
Figure D.9 – Probability P as a function of the SPD2 residual voltage U ’ at 1 kA . 85
Up p
Figure D.10 – Probability P as a function of the internal loop area for n' = 2 and
Up
w = 0,1 m . 86
Figure D.11 – Probability P as a function of the internal loop area for n' = 2 and
Up
w = 0,5 m . 87
Figure D.12 – Probability P as a function of the internal loop area for n' = 20 and
Up
w = 0,1 m . 87
Figure D.13 – Probability P as a function of the SPD protection level U ’ at 1 kA for
Up p
different internal loop areas . 88
Figure D.14 – Probability P as a function of different internal loop areas for two
Up
typical protection levels of GDTs . 89
Table 1 – Sources of damage, causes of damage, types of loss and risk components
according to the point of strike . 27
Table 2 – Factors influencing the risk components . 29
Table 3 – Risk components for different sources of damage and types of loss . 35
Table 4 – Partial frequency of damage for each source of damage . 40
Table A.1 – Structure location factors C and C . 48
D DJ
Table A.2 – Line installation factor C . 50
I
Table A.3 – Line type factor C . 51
T
Table A.4 – Environmental factor C . 51
E
Table B.1 – Values of probability P that a flash to a structure will cause damage due
am
to touch and step voltages according to different protection measures . 55
Table B.2 – Reduction factor r as a function of the type of surface of soil or floor . 55
t
Table B.3 – Values of probability P depending on the protection measures to
LPS
protect the exposed areas of the structure against the direct flash and to reduce
physical damage . 56
Table B.4 – Values of probability P that a flash to a structure will cause dangerous
S
sparking . 57
– 6 – IEC 62305-2:2024 © IEC 2024
Table B.5 – Reduction factor r as a function of provisions taken to reduce the
p
consequences of fire . 58
Table B.6 – Reduction factor r as a function of risk of fire or explosion of structure. 58
f
Table B.7 – Typical values of P for SPDs on the low-voltage system, used to
SPD
protect against sources of damage S1, S2, S3, S4 . 60
Table B.8 – Typical values of P for SPDs on the telecommunications system used
SPD
to protect against sources of damage S1, S2, S3, S4 . 61
Table B.9 – Values of factors C and C depending on shielding, grounding and
LD LI
isolation conditions . 62
Table B.10 – Value of factor K depending on internal wiring . 65
S3
Table B.11 – Values of the probability P depending on the resistance R of the
LD S
cable screen and the impulse withstand voltage U of the equipment . 66
W
Table B.12 – Values of the probability P depending on the resistance R of the
LD S
cable screen and the higher impulse withstand voltage U of the equipment . 67
W
Table B.13 – Typical values of probability P relevant to protection level LPL for
EB
which the SPD is designed to protect against source of damage S3 . 67
Table C.1 – Loss values for each zone . 72
Table C.2 – Typical mean values of L , L , L , L , L and L . 73
T D F1 F2 O1 O2
Table D.1 – P values of the voltage limiting SPD for combination between a voltage
Up
limiting and a voltage switching SPD . 79
Table D.2 – P values of the voltage limiting SPD . 84
Up
Table E.1 – Risk components for different sources of damage and types of loss, valid
for damage to the surroundings . 91
Table E.2 – Type of loss L1: Proposed typical values for the related time of presence
for people t /8 760 in different environments as limited by Table E.3 . 92
zE
Table E.3 – Type of loss L1: Typical mean values of L and L outside the
F1E O1E
structure . 93
Table E.4 – Type of loss L2: Typical mean values of L and L outside the
F2E O2E
structure . 93
Table F.1 – House: environment and structure characteristics . 95
Table F.2 – House: power line . 95
Table F.3 – House: telecom line . 96
Table F.4 – House: equivalent collection areas of structure and lines . 96
Table F.5 – House: expected annual number of dangerous events . 97
Table F.6 – House: time of presence of persons and risk components into risk zones . 98
Table F.7 – House: values for zone Z (inside the building) . 98
–5
Table F.8 – House: risk for the unprotected structure (values × 10 ) . 99
–5
Table F.9 – House: risk components for protected structure (values × 10 ). 100
Table F.10 – Office building: environment and structure characteristics . 100
Table F.11 – Office building: power line . 101
Table F.12 – Office building: telecom line . 101
Table F.13 – Office building: collection areas of structure and lines . 102
Table F.14 – Office building: expected annual number of dangerous events . 102
Table F.15 – Office building: time of presence of persons and risk components in
zones . 103
Table F.16 – Office building: factors valid for zone Z (entrance area outside) . 104
Table F.17 – Office building: factors valid for zone Z (roof) . 104
Table F.18 – Office building: factors valid for zone Z (archive) . 105
Table F.19 – Office building: factors valid for zone Z (offices) . 106
Table F.20 – Office building: factors valid for zone Z (computer centre) . 107
–5
Table F.21 – Office building: risk for the unprotected structure (values × 10 ) . 108
Table F.22 – Office building: frequency of damage for the unprotected structure . 108
–5
Table F.23 – Risk components for protected structure (values × 10 ) . 109
Table F.24 – Office building: frequency of damage for protected structure . 109
Table F.25 – Hospital: environment and structure characteristics . 110
Table F.26 – Hospital: power line . 111
Table F.27 – Hospital: collection areas of structure and power line . 111
Table F.28 – Hospital: expected annual number of dangerous events . 112
Table F.29 – Hospital: time of presence of persons and risk components in zones . 113
Table F.30 – Hospital: factors valid for zone Z (outside the building) . 113
Table F.31 – Hospital: factors valid for zone Z (roof) . 114
Table F.32 – Hospital: factors valid for zone Z (rooms) . 115
Table F.33 – Hospital: factors valid for zone Z (operating block) . 116
Table F.34 – Hospital: factors valid for zone Z (intensive care unit) . 117
–5
Table F.35 – Hospital: risk for the unprotected structure (values × 10 ) . 118
Table F.36 – Hospital: frequency of damage for the unprotected structure . 118
–5
Table F.37 – Hospital: risk for the protected structure (values × 10 ) . 119
Table F.38 – Hospital: frequency of damage for the protected structure . 120
– 8 – IEC 62305-2:2024 © IEC 2024
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
PROTECTION AGAINST LIGHTNING –
Part 2: Risk management
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote international
co-operation on all questions concerning standardization in the electrical and electronic fields. To this end and
in addition to other activities, IEC publishes International Standards, Technical Specifications, Technical Reports,
Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC Publication(s)”). Their
preparation is entrusted to technical committees; any IEC National Committee interested in the subject dealt with
may participate in this preparatory work. International, governmental and non-governmental organizations liaising
with the IEC also participate in this preparation. IEC collaborates closely with the International Organization for
Standardization (ISO) in accordance with conditions determined by agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence between
any IEC Publication and the corresponding national or regional publication shall be clearly indicated in the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) IEC draws attention to the possibility that the implementation of this document may involve the use of (a)
patent(s). IEC takes no position concerning the evidence, validity or applicability of any claimed patent rights in
respect thereof. As of the date of publication of this document, IEC had not received notice of (a) patent(s), which
may be required to implement this document. However, implementers are cautioned that this may not represent
the latest information, which may be obtained from the patent database available at https://patents.iec.ch. IEC
shall not be held responsible for identifying any or all such patent rights.
IEC 62305-2 has been prepared by IEC technical committee 81: Lightning protection. It is an
International Standard.
This third edition cancels and replaces the second edition, published in 2010. This edition
constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous
edition:
a) The concept of a single risk, to combine loss of human life and loss due to fire, has been
introduced.
b) The concept of frequency of damage that can impair the availability of the internal systems
within the structure has been introduced.
c) The lightning ground strike-point density N has been introduced replacing the lightning
SG
flash density N in the evaluation of expected average annual number of dangerous events.
G
d) Reduction of a few risk components can be achieved by the use of preventive temporary
measures activated by means of a thunderstorm warning system (TWS) compliant with
IEC 62793. The risk of direct strike to people in open areas has been introduced,
considering the reduction of that risk using a TWS.
The text of this International Standard is based on the following documents:
Draft Report on voting
81/769/FDIS 81/772/RVD
Full information on the voting for its approval can be found in the report on voting indicated in
the above table.
The language used for the development of this International Standard is English.
This document was drafted in accordance with ISO/IEC Directives, Part 2, and developed in
accordance with ISO/IEC Directives, Part 1 and ISO/IEC Directives, IEC Supplement, available
at www.iec.ch/members_experts/refdocs. The main document types developed by IEC are
described in greater detail at www.iec.ch/publications.
A list of all parts in the IEC 62305 series, published under the general title Protection against
lightning, can be found on the IEC website.
The following differing practices of a less permanent nature exist in the countries indicated
below.
In Germany, the value of r = 1 applies for all cases. For the risk components R , R , R , R ,
p B C M V
R and R P = 1 is assumed. For LF1 and LF2 the highest values given in Table C.2 should
W Z TWS
be used.
In Greece, the value of P = 1 for all cases is assumed.
TWS
In Italy, calculating both the risk of loss of human life, RL1 in Equation (7), and the risk of loss
due to physical damages, RL2 in Equation (8), and comparing each risk with the tolerable risk
is required. Protection is achieved when both risks, RL1 and RL2, are less than the tolerable
value.
In the Netherlands and South Africa, Annex D and Annex E should not be applied for usual
studies.
– 10 – IEC 62305-2:2024 © IEC 2024
The committee has decided that the contents of this document will remain unchanged until the
stability date indicated on the IEC website under webstore.iec.ch in the data related to the
specific document. At this date, the document will be
• reconfirmed,
• withdrawn, or
• revised.
IMPORTANT – The "colour inside" logo on the cover page of this document indicates
that it contains colours which are considered to be useful for the correct understanding
of its contents. Users should therefore print this document using a colour printer.
INTRODUCTION
Lightning flashes to earth can be hazardous to structures and to lines supplying the structure.
These hazards can result in:
– damage to the structure and to its contents,
– failure of associated electrical and electronic systems,
– injury to living beings in or close to the structure.
Consequential effects of the damage and failures can be extended to the surroundings of the
structure or can involve its environment. Moreover, regardless of the extent of loss, the
availability of the structure and its internal systems can be unacceptably impaired if the
frequency of damage is high.
To reduce the frequency of damage and the loss due to lightning, protection measures can be
required. Whether they are necessary, and to what extent, should be determined by frequency
of damage and risk assessment.
NOTE 1 The decision to provide lightning protection can be taken regardless of the outcome of frequency of damage
or risk assessment where there is a desire that there be no avoidable damages.
NOTE 2 IEC 60364-4-44 [1] always requires the installation of a surge protective device (SPD) at the power line
entrance in the structure when the consequence caused by overvoltages affects:
– care of human life, e.g. safety services, medical care facilities,
– public services and cultural heritage, e.g. loss of public services, IT centres, museums,
– commercial or industrial activity, e.g. hotels, banks, industries, commercial markets, farms.
The frequency of damage, defined in this document as the annual number of damages in a
structure due to lightning flashes, depends on:
– the annual number of lightning flashes influencing the structure;
– the probability of damaging events by one of the influencing lightning flashes.
The risk, defined in this document as the probable average annual loss in a structure due to
lightning flashes, depends on:
– the frequency of damage;
– the mean extent of consequential loss.
Lightning flashes influencing the structure can be divided into
– flashes terminating on the structure,
– flashes terminating near the structure, directly to connected lines (power, telecom-
munication lines) or near the lines.
Flashes to the structure or a connected line can cause physical damage and life hazards.
Flashes near the structure or line as well as flashes to the structure or line can cause failure of
electrical and electronic systems due to overvoltages resulting from resistive and inductive
coupling of these systems with the lightning current.
Moreover, failures caused by lightning overvoltages in users’ installations and in power supply
lines can also generate voltage switching overvoltages in the installations.
NOTE 3 Malfunctioning of electrical and electronic systems is not covered by the IEC 62305 series. Reference is
made to IEC 61000-4-5 [2].
___________
Numbers in square brackets refer to the Bibliography.
– 12 – IEC 62305-2:2024 © IEC 2024
The number of lightning flashes influencing the structure depends on the dimensions, the
characteristics of the structure and the connected lines, on the environmental characteristics of
the structure and the lines, as well as on lightning ground strike-point density in the region
where the structure and the lines are located. Guidance on the assessment of the number of
lightning flashes influencing the structure is given in Annex A.
The probability of damage depends on the structure, the resistibility of equipment located on
the structure, the connected lines, and the lightning current characteristics, as well as on the
type and efficiency of the protection
...
IEC 62305-2:2024は、落雷による構造物のリスク管理に関する標準であり、その範囲は非常に重要です。この標準は、落雷に伴うリスク評価手続きと、そのリスクを許容限度まで低下させるための適切な保護措置の選択方法を提供します。特に、建物や構造物に対する落雷の影響を体系的に評価するためのガイドラインを示しており、実践的な安全対策を講じるために不可欠です。 この標準の強みは、技術的な見直しが行われた点です。例えば、人命の喪失と火災による損失を結合する単一リスクの概念が導入されたことは、リスク管理における包括的なアプローチを可能にします。また、構造内部のシステムの可用性を損なう損害の頻度を考慮することで、より実践的なリスク評価が実現しています。 さらに、新しい評価手法として導入された落雷の接地点密度(NSG)は、従来の落雷頻度(NG)と置き換えられ、危険なイベントの平均年間発生数を算出する上での精度が向上しています。防雷対策として、雷警報システム(TWS)を活用することで、いくつかのリスク要素を削減する方法も提案されており、特に開放された地域における直接的な落雷リスクの低減が強調されています。 このように、IEC 62305-2:2024は、落雷によるリスク管理の進展を示す重要な文書であり、最新の技術的更新が施されている点からも、その関連性と重要性が高いことが伺えます。標準の適用により、適切な防護措置を講じることが可能となり、生活環境や業務運営における安全性が向上することでしょう。
Die Norm IEC 62305-2:2024 befasst sich umfassend mit dem Risikomanagement von Bauwerken im Hinblick auf Blitzeinschläge. Ihr Hauptziel ist die Bereitstellung eines Verfahrens zur Bewertung des Risikos, das durch Blitzschläge auf die Erde entsteht. Dies macht sie besonders relevant für Planer, Ingenieure und Sicherheitsbeauftragte, die für den Schutz von Einrichtungen verantwortlich sind. Ein herausragender Vorteil der IEC 62305-2:2024 ist die Einführung eines einheitlichen Risikobegriffs, der den Verlust menschlichen Lebens und Schäden durch Feuer kombiniert. Diese integrierte Perspektive ermöglicht eine umfassendere Risikoanalyse und fördert abgestimmte Schutzmaßnahmen. Zudem wird mit dem Konzept der Schadenshäufigkeit, das die Verfügbarkeit interner Systeme innerhalb eines Bauwerks berücksichtigt, eine wichtige Neuerung präsentiert. Dies ist besonders bedeutend für moderne Gebäude, die auf eine kontinuierliche Funktionsfähigkeit ihrer Systeme angewiesen sind. Ein weiteres Stärkekriterium dieser Norm ist die Einführung der Blitz-Einschlagspunktdichte (NSG), die die vorherige Blitzhäufigkeit (NG) ersetzt. Dies verbessert die Genauigkeit bei der Bewertung der erwarteten durchschnittlichen jährlichen Anzahl gefährlicher Ereignisse, was für die Risikoeinschätzung von entscheidender Bedeutung ist. Die Norm adressiert auch präventive Maßnahmen zur Risikominderung, indem sie die Nutzung eines Thunderstorm Warning Systems (TWS) gemäß IEC 62793 hervorhebt. Diese temporären Maßnahmen können das Risiko von direkten Blitzeinschlägen auf Personen in offenen Bereichen signifikant senken und zeigen, wie moderne Technologien in das Risikomanagement integriert werden können. Insgesamt stellt die IEC 62305-2:2024 eine wertvolle Aktualisierung dar, die nicht nur die technischen Aspekte des Blitzschutzes optimiert, sondern auch praxisnahe Ansätze zur Risikominderung bietet. Die Berücksichtigung von Korrekturhinweisen sowie die Klarstellung von Begrifflichkeiten sind zusätzlich für die Anwendung der Norm von Bedeutung und verbessern deren Funktionalität in der Praxis.
IEC 62305-2:2024 is a comprehensive standard dedicated to the risk management of structures against lightning flashes to earth. This standard is paramount as it delineates a structured procedure for the evaluation of risks associated with lightning strikes, allowing stakeholders to take informed actions regarding their safety and asset protection strategies. One of the significant strengths of IEC 62305-2:2024 is its introduction of the single risk concept. By combining the loss of human life with potential fire damage, the standard provides a more integrated view of risk, facilitating better decision-making processes. This holistic approach enhances the relevance of the standard in today's environment, where both human safety and structural integrity are critical. Furthermore, the introduction of the frequency of damage impacting internal system availability is a notable advancement. This highlights the standard’s adaptability to modern structures, emphasizing the importance of maintaining operational functionality post-lightning events. Addressing this concern is essential for industries relying heavily on uninterrupted services, making the standard particularly valuable. The standard's update to include lightning ground strike-point density (NSG) instead of lightning flash density (NG) signifies an improvement in evaluating the expected average annual number of dangerous events. This refined metric allows for more accurate risk assessments tailored to specific geographical and structural conditions. Additionally, the incorporation of preventive temporary measures activated by a thunderstorm warning system (TWS) compliant with IEC 62793 illustrates a forward-thinking approach to risk mitigation measures. This enables owners and operators to actively reduce risks associated with direct strikes to individuals in open areas, enhancing overall safety during adverse weather conditions. In conclusion, IEC 62305-2:2024 stands out as a vital standard that effectively combines risk assessment and management methodologies for lightning protection. Its technical revisions and updates provide a robust framework for reducing lightning strike risks while ensuring the safety and reliability of structures in hazardous scenarios. This makes it an indispensable tool for engineers, safety professionals, and facility managers involved in lightning protection planning and implementation.
IEC 62305-2:2024 문서는 번개에 의한 구조물의 위험 관리를 다루고 있으며, 이는 구조물에 대한 번개 충격의 위험을 평가하는 절차를 제공합니다. 이 표준은 위험의 허용 가능한 한계를 선택한 후, 해당 위험을 허용한계 이하로 줄이기 위해 채택할 적절한 보호 조치를 선택할 수 있는 방법을 제시합니다. 이 표준의 가장 큰 강점 중 하나는 인명 손실과 화재로 인한 손실을 결합한 단일 위험 개념을 도입한 점입니다. 이로 인해 위험 평가가 보다 포괄적이고 실질적인 관점에서 이루어질 수 있게 되었습니다. 또한, 내부 시스템의 가용성을 저하시키는 손상의 빈도 개념이 추가되어, 다양한 상황에서의 위험 관리 접근 방식을 개선했습니다. 다음으로, 번개 지점 밀도 NSG의 도입은 기대되는 평균 연간 위험 사건 수의 평가에서 번개 플래시 밀도 NG를 대체함으로써 더욱 정교한 위험 평가를 가능하게 합니다. 이러한 변화는 번개에 의한 사고를 미리 예측하고, 보다 효과적인 안전 조치를 마련하는 데 기여합니다. 또한, 개선된 일시적 예방 조치를 통해 위험 요소 중 일부를 줄일 수 있다는 점도 큰 장점입니다. IEC 62793에 부합하는 뇌우 경고 시스템(TWS)의 사용으로, 개방 지역에서의 직접적인 번개 타격 위험을 감소시키는 방법이 도입되었습니다. 이러한 예방적 조치는 특히 인명과 재산 보호에 있어 중요한 역할을 할 수 있습니다. IEC 62305-2:2024는 2010년에 발행된 두 번째 판을 대체하며, 기술적으로 전면 개정된 내용을 포함하고 있습니다. 이러한 점에서 최신 기술 기준을 반영하여 더 높은 안전성을 제공하고 있으며, 현대 사회의 안전 요구 사항에 부합하는 표준으로 자리 잡고 있습니다.
La norme IEC 62305-2:2024, intitulée « Protection contre la foudre - Partie 2 : Gestion des risques », offre une approche systématique et rigoureuse pour la gestion des risques liés aux coups de foudre sur les structures. Cette norme est essentielle pour évaluer les risques associés aux impacts des éclairs sur la vie humaine et sur les infrastructures, en particulier dans les contextes où les événements foudroyants peuvent causer des dommages importants. Le champ d'application de cette norme est clairement défini, permettant aux utilisateurs de comprendre les procédures et méthodes à adopter pour évaluer les risques de façon efficace. L’introduction d’un plafond de risque tolérable permet de mieux encadrer la mise en œuvre des mesures de protection appropriées, ce qui est un point fort de cette norme. Cela aide les professionnels du secteur à concevoir des stratégies de protection adaptées aux besoins spécifiques de chaque structure. Les changements techniques significatifs par rapport à l'édition précédente de 2010 apportent une valeur ajoutée à cette norme. L’introduction d’un risque unique, combinant la perte de vies humaines et les pertes dues aux incendies, et la notion de fréquence des dommages qui peuvent entraver la disponibilité des systèmes internes, sont des avancées cruciales pour une évaluation des risques plus exhaustive. De plus, la norme introduit la densité de point de coup de foudre (NSG), remplaçant ainsi la densité de coups de foudre (NG), ce qui améliore la précision des évaluations des événements dangereux attendus. Une autre force notable est l'accent mis sur l'utilisation de mesures préventives temporaires, activées par un système d'alerte de tempête (TWS), conforme à la norme IEC 62793. Cela permet de réduire certains composants de risque, notamment le risque de coups directs sur des personnes en plein air, une préoccupation de plus en plus pertinente dans les zones urbaines. En somme, la norme IEC 62305-2:2024 est d'une grande pertinence pour tous les professionnels impliqués dans la gestion des risques liés aux coups de foudre. Elle répond aux besoins actuels en matière de protection des infrastructures, offrant des solutions pragmatiques aux défis posés par les aléas climatiques. Grâce à ses mises à jour techniques et à sa portée clairement définie, cette norme s'impose comme un outil indispensable dans le cadre de la gestion des risques.








Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.
Loading comments...