IEC 60364-5-51:1997
(Main)Electrical installations of buildings - Part 5: Selection and erection of electrical equipment - Chapter 51: Common rules
Electrical installations of buildings - Part 5: Selection and erection of electrical equipment - Chapter 51: Common rules
Sets out rules which govern selection and erection of equipment in general and stipulates compliance with measures of protection of safety, requirements for proper functioning for intended use and those appropriate to external influences. Gives in tabular form characteristics required for selection and erection of equipment with respect to external influences.
Installations électriques des bâtiments - Partie 5: Choix et mise en oeuvre des matériels électriques - Chapitre 51: Règles communes
Donne les règles qui régissent le choix et la mise en oeuvre du matériel en général, et stipule la conformité aux mesures de protection pour assurer la sécurité, les prescriptions pour assurer un fonctionnement satisfaisant pour l'utilisation prévue et les prescriptions appropriées aux influences externes. Donne sous forme tabulaire les caractéristiques requises pour le choix et la mise en oeuvre du matériel en fonction de ces influences externes.
General Information
Relations
Standards Content (Sample)
NORME
CEI
INTERNATIONALE
IEC
60364-5-51
INTERNATIONAL
Troisième édition
STANDARD
Third edition
1997-06
Installations électriques des bâtiments –
Partie 5:
Choix et mise en oeuvre des matériels
électriques –
Chapitre 51: Règles communes
Electrical installations of buildings –
Part 5:
Selection and erection of electrical equipment –
Chapter 51: Common rules
Numéro de référence
Reference number
CEI/IEC 60364-5-51: 1997
Validité de la présente publication Validity of this publication
Le contenu technique des publications de la CEI est The technical content of IEC publications is kept under
constamment revu par la CEI afin qu'il reflète l'état constant review by the IEC, thus ensuring that the
actuel de la technique. content reflects current technology.
Des renseignements relatifs à la date de Information relating to the date of the reconfirmation
reconfirmation de la publication sont disponibles of the publication is available from the IEC Central
auprès du Bureau Central de la CEI. Office.
Les renseignements relatifs à ces révisions, à Information on the revision work, the issue of revised
l'établissement des éditions révisées et aux editions and amendments may be obtained from IEC
amendements peuvent être obtenus auprès des National Committees and from the following IEC
Comités nationaux de la CEI et dans les documents sources:
ci-dessous:
• Bulletin de la CEI • IEC Bulletin
• Annuaire de la CEI • IEC Yearbook
Publié annuellement Published yearly
• Catalogue des publications de la CEI • Catalogue of IEC publications
Publié annuellement et mis à jour régulièrement Published yearly with regular updates
Terminologie Terminology
En ce qui concerne la terminologie générale, le lecteur For general terminology, readers are referred to
se reportera à la CEI 60050: Vocabulaire IEC 60050: International Electrotechnical Vocabulary
Electrotechnique International (VEI), qui se présente (IEV), which is issued in the form of separate chapters
sous forme de chapitres séparés traitant chacun d'un each dealing with a specific field. Full details of the
sujet défini. Des détails complets sur le VEI peuvent IEV will be supplied on request. See also the IEC
être obtenus sur demande. Voir également le Multilingual Dictionary.
dictionnaire multilingue de la CEI.
Les termes et définitions figurant dans la présente The terms and definitions contained in the present
publication ont été soit tirés du VEI, soit publi-cation have either been taken from the IEV or
spécifiquement approuvés aux fins de cette have been specifically approved for the purpose of this
publication. publication.
Symboles graphiques et littéraux Graphical and letter symbols
Pour les symboles graphiques, les symboles littéraux For graphical symbols, and letter symbols and signs
et les signes d'usage général approuvés par la CEI, le approved by the IEC for general use, readers are
lecteur consultera: referred to publications:
– IEC 60027: Letter symbols to be used in electrical
– la CEI 60027: Symboles littéraux à utiliser en
technology;
électrotechnique;
– IEC 60417: Graphical symbols for use on
– la CEI 60417: Symboles graphiques utilisables sur
equipment. Index, survey and compilation of the
le matériel. Index, relevé et compilation des feuilles
individuelles; single sheets;
Symboles graphiques pour schémas; – IEC 60617: Graphical symbols for diagrams;
– la CEI 60617:
and for medical electrical equipment,
et pour les appareils électromédicaux,
– IEC 60878: Graphical symbols for electromedical
– la CEI 60878: Symboles graphiques pour
equipment in medical practice.
équipements électriques en pratique médicale.
Les symboles et signes contenus dans la présente The symbols and signs contained in the present
publication ont été soit tirés de la CEI 60027, de la publication have either been taken from IEC 60027,
IEC 60417, IEC 60617 and/or IEC 60878, or have
CEI 60417, de la CEI 60617 et/ou de la CEI 60878,
been specifically approved for the purpose of this
soit spécifiquement approuvés aux fins de cette
publication.
publication.
Publications de la CEI établies par le IEC publications prepared by the same
même comité d'études technical committee
The attention of readers is drawn to the end pages of
L'attention du lecteur est attirée sur les listes figurant
this publication which list the IEC publications issued
à la fin de cette publication, qui énumèrent les
by the technical committee which has prepared the
publications de la CEI préparées par le comité
present publication.
d'études qui a établi la présente publication.
NORME
CEI
INTERNATIONALE
IEC
60364-5-51
INTERNATIONAL
Troisième édition
STANDARD
Third edition
1997-06
Installations électriques des bâtiments –
Partie 5:
Choix et mise en oeuvre des matériels
électriques –
Chapitre 51: Règles communes
Electrical installations of buildings –
Part 5:
Selection and erection of electrical equipment –
Chapter 51: Common rules
IEC 1997 Droits de reproduction réservés Copyright - all rights reserved
Aucune partie de cette publication ne peut être reproduite ni No part of this publication may be reproduced or utilized in
utilisée sous quelque forme que ce soit et par aucun any form or by any means, electronic or mechanical,
procédé, électronique ou mécanique, y compris la photo- including photocopying and microfilm, without permission in
copie et les microfilms, sans l'accord écrit de l'éditeur. writing from the publisher.
International Electrotechnical Commission 3, rue de Varembé Geneva, Switzerland
Telefax: +41 22 919 0300 e-mail: inmail@iec.ch IEC web site http: //www.iec.ch
CODE PRIX
Commission Electrotechnique Internationale
R
PRICE CODE
International Electrotechnical Commission
Pour prix, voir catalogue en vigueur
For price, see current catalogue
– 2 – 60364-5-51 © CEI:1997
SOMMAIRE
Pages
AVANT-PROPOS . 4
Articles
510 Règles communes. 6
511 Conformité aux normes . 8
512 Conditions de service et influences externes . 10
513 Accessibilité. 30
514 Identification. 30
515 Indépendance des matériels. 32
Tableau 51A . 14 à 30
Annexe A – Bibliographie . 36
60364-5-51 © IEC:1997 – 3 –
CONTENTS
Page
FOREWORD . 5
Clause
510 Common rules. 7
511 Compliance with standards . 9
512 Operational conditions and external influences . 11
513 Accessibility . 31
514 Identification . 31
515 Prevention of mutual detrimental influence . 33
Table 51A. 15 to 31
Annex A – Bibliography. 37
– 4 – 60364-5-51 © CEI:1997
COMMISSION ÉLECTROTECHNIQUE INTERNATIONALE
__________
INSTALLATIONS ÉLECTRIQUES DES BÂTIMENTS –
Partie 5: Choix et mise en oeuvre des matériels électriques –
Chapitre 51: Règles communes
AVANT-PROPOS
1) La CEI (Commission Electrotechnique Internationale) est une organisation mondiale de normalisation composée
de l'ensemble des comités électrotechniques nationaux (Comités nationaux de la CEI). La CEI a pour objet de
favoriser la coopération internationale pour toutes les questions de normalisation dans les domaines de
l'électricité et de l'électronique. A cet effet, la CEI, entre autres activités, publie des Normes Internationales.
Leur élaboration est confiée à des comités d'études, aux travaux desquels tout Comité national intéressé par le
sujet traité peut participer. Les organisations internationales, gouvernementales et non gouvernementales, en
liaison avec la CEI, participent également aux travaux. La CEI collabore étroitement avec l'Organisation
Internationale de Normalisation (ISO), selon des conditions fixées par accord entre les deux organisations.
2) Les décisions ou accords officiels de la CEI concernant les questions techniques, représentent, dans la mesure
du possible un accord international sur les sujets étudiés, étant donné que les Comités nationaux intéressés
sont représentés dans chaque comité d’études.
3) Les documents produits se présentent sous la forme de recommandations internationales. Ils sont publiés
comme normes, rapports techniques ou guides et agréés comme tels par les Comités nationaux.
4) Dans le but d'encourager l'unification internationale, les Comités nationaux de la CEI s'engagent à appliquer de
façon transparente, dans toute la mesure possible, les Normes internationales de la CEI dans leurs normes
nationales et régionales. Toute divergence entre la norme de la CEI et la norme nationale ou régionale
correspondante doit être indiquée en termes clairs dans cette dernière.
5) La CEI n’a fixé aucune procédure concernant le marquage comme indication d’approbation et sa responsabilité
n’est pas engagée quand un matériel est déclaré conforme à l’une de ses normes.
6) L’attention est attirée sur le fait que certains des éléments de la présente Norme internationale peuvent faire
l’objet de droits de propriété intellectuelle ou de droits analogues. La CEI ne saurait être tenue pour
responsable de ne pas avoir identifié de tels droits de propriété et de ne pas avoir signalé leur existence.
La Norme internationale CEI 60364-5-51 a été établie par le comité d'études 64 de la CEI:
Installations électriques des bâtiments.
Cette troisième édition annule et remplace la deuxième édition parue en 1994, l'amende-
ment 1 (1995) et le corrigendum relatif au nouveau tableau 51A diffusé pour approbation sous
les références 64/899/Q et 64/933/RQ.
Cette édition constitue une réimpression mise à jour de la deuxième édition de la norme
internationale.
Le texte de cette norme est issu de la première édition et des documents suivants:
FDIS Rapports de vote
64(BC)246 64(BC)253
64/770/FDIS 64/821/RVD
ainsi que du corrigendum relatif au nouveau tableau 51A.
Les rapports de vote indiqués dans le tableau ci-dessus donnent toute information sur le vote
ayant abouti à l'approbation de cette norme.
L'annexe A est donnée uniquement à titre d'information.
60364-5-51 © IEC:1997 – 5 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
________
ELECTRICAL INSTALLATIONS OF BUILDINGS –
Part 5: Selection and erection of electrical equipment –
Chapter 51: Common rules
FOREWORD
1) The IEC (International Electrotechnical Commission) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of the IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, the IEC publishes International Standards. Their preparation is
entrusted to technical committees; any IEC National Committee interested in the subject dealt with may
participate in this preparatory work. International, governmental and non-governmental organizations liaising
with the IEC also participate in this preparation. The IEC collaborates closely with the International Organization
for Standardization (ISO) in accordance with conditions determined by agreement between the two
organizations.
2) The formal decisions or agreements of the IEC on technical matters express, as nearly as possible, an
international consensus of opinion on the relevant subjects since each technical committee has representation
from all interested National Committees.
3) The documents produced have the form of recommendations for international use and are published in the form
of standards, technical reports or guides and they are accepted by the National Committees in that sense.
4) In order to promote international unification, IEC National Committees undertake to apply IEC International
Standards transparently to the maximum extent possible in their national and regional standards. Any
divergence between the IEC Standard and the corresponding national or regional standard shall be clearly
indicated in the latter.
5) The IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with one of its standards.
6) Attention is drawn to the possibility that some of the elements of this International Standard may be the subject
of patent rights. The IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 60364-5-51 has been prepared by IEC technical committee 64:
Electrical installations of buildings.
This third edition cancels and replaces the second edition published in 1994, amendment 1
(1995) and corrigendum relative to the new table 51A circulated for approval under the
references 64/899/Q and 64/933/RQ.
This edition constitutes an updated reprint of the second edition of the International
Standard.
The text of this standard is based on the first edition and on the following documents:
FDIS Reports on voting
64(CO)246 64(CO)253
64/770/FDIS 64/821/RVD
and also on the corrigendum relative to the new table 51A.
Full information on the voting for the approval of this standard can be found in the reports on
voting indicated in the above table.
Annex A is given for information only.
– 6 – 60364-5-51 © CEI:1997
COMMISSION ÉLECTROTECHNIQUE INTERNATIONALE
__________
INSTALLATIONS ÉLECTRIQUES DES BÂTIMENTS –
Partie 5: Choix et mise en oeuvre des matériels électriques –
Chapitre 51: Règles communes
510 RÈGLES COMMUNES
510.1 Domaine d'application
Le présente chapitre traite du choix du matériel et de sa mise en oeuvre. Il doit permettre de
satisfaire aux mesures de protection pour assurer la sécurité, aux prescriptions pour assurer
un fonctionnement satisfaisant de l'installation pour l'utilisation prévue, et aux prescriptions
appropriées aux conditions d'influences externes prévisibles. Les matériels doivent être
choisis et installés de façon à satisfaire aux règles énoncées dans le présent chapitre et, pour
autant qu'elles leur soient applicables, à celles des autres chapitres de cette norme.
510.2 Références normatives
Les documents normatifs suivants contiennent des dispositions qui, par suite de la référence
qui y est faite, constituent des dispositions valables pour la présente partie de la CEI 60364.
Au moment de la publication, les éditions indiquées étaient en vigueur. Tout document
normatif est sujet à révision et les parties prenantes aux accords fondés sur la présente partie
de la CEI 60364 sont invitées à rechercher la possibilité d'appliquer les éditions les plus
récentes des documents normatifs indiqués ci-après. Les membres de la CEI et de l'ISO
possèdent le registre des Normes internationales en vigueur.
CEI 60073: 1991, Codage des dispositifs indicateurs et des organes de commande par
couleurs et moyens supplémentaires
CEI 60255-22-1: 1988, Relais électriques – Partie 22: Essais d'influence électrique
concernant les relais de mesure et dispositifs de protection – Première partie: Essais à l'onde
oscillatoire amortie à 1 MHz
CEI 60364-3: 1993, Installations électriques des bâtiments – Partie 3: Détermination des
caractéristiques générales
CEI 60364-4-41: 1992, Installations électriques des bâtiments – Quatrième partie: Protection
pour assurer la sécurité – Chapitre 41: Protection contre les chocs électriques
CEI 60364-4-442: 1993, Installations électriques des bâtiments – Partie 4: Protection pour
assurer la sécurité – Chapitre 44: Protection contre les surtensions – Section 442: Protection
des installations à basses tensions contre les défauts à la terre dans les installations à haute
tension
CEI 60364-4-443: 1990, Installations électriques des bâtiments – Partie 4: Protection pour
assurer la sécurité – Chapitre 44: Protection contre les surtensions – Section 443: Protection
contre les surtensions d'origine atmosphérique ou dues à des manoeuvres
CEI 60364-4-444: 1996, Installations électriques des bâtiments – Partie 4: Protection pour
assurer la sécurité – Chapitre 44: Protection contre les surtensions – Section 444: Protection
contre les interférences électromagnétiques (IEM) dans les installations des bâtiments
60364-5-51 © IEC:1997 – 7 –
ELECTRICAL INSTALLATIONS OF BUILDINGS –
Part 5: Selection and erection of electrical equipment –
Chapter 51: Common rules
510 COMMON RULES
510.1 Scope
This chapter deals with the selection of equipment and its erection. It shall provide
compliance with the measures of protection for safety, the requirements for proper
functioning for intended use of the installation, and the requirements appropriate to the
external influences foreseen. Every item of equipment shall be selected and erected so as to
allow compliance with the rules stated in the following clauses of this chapter and the
relevant rules in other chapters of this standard.
510.2 Normative references
The following normative documents contain provisions which, through reference in this text,
constitute provisions of this part of IEC 60364. At the time of publication, the editions
indicated were valid. All normative documents are subject to revision, and parties to
agreements based on this part of IEC 60364 are encouraged to investigate the possibility of
applying the most recent editions of the normative documents indicated below. Members of
IEC and ISO maintain registers of currently valid International Standards.
IEC 60073: 1991, Coding of indicating devices and actuators by colours and supplementary
means
IEC 60255-22-1: 1988, Electrical relays – Part 22: Electrical disturbance tests for measuring
relays and protection equipment – Part 1: 1 MHz burst disturbance tests
IEC 60364-3: 1993, Electrical installations of buildings – Part 3: Assessment of general
characteristics
IEC 60364-4-41: 1992, Electrical installations of buildings – Part 4: Protection for safety –
Chapter 41: Protection against electric shock
IEC 60364-4-442: 1993, Electrical installations of buildings – Part 4: Protection for safety –
Chapter 44: Protection against overvoltages – Section 442: Protection of low-voltage
installations against faults between high-voltage systems and earth
IEC 60364-4-443: 1990, Electrical installations of buildings – Part 4: Protection for safety –
Chapter 44: Protection against overvoltages – Section 443: Protection against overvoltages
of atmospheric origin or due to switching
IEC 60364-4-444: 1996, Electrical installations of buildings – Part 4: Protection for safety –
Chapter 44: Protection against overvoltages – Section 444: Protection against
electromagnetic interferences (EMI) in installations of buildings
– 8 – 60364-5-51 © CEI:1997
CEI 60364-4-45: 1984, Installations électriques des bâtiments – Partie 4: Protection pour
assurer la sécurité – Chapitre 45: Protection contre les baisses de tension
CEI 60364-5-54: 1980, Installations électriques des bâtiments – Cinquième partie: Choix et
mise en oeuvre des matériels électriques – Chapitre 54: Mise à la terre et conducteurs de
protection
CEI 60446: 1989, Identification des conducteurs par les couleurs ou par des repères
numériques
CEI 60447: 1993, Interface homme-machine (IHM) – Principes de manoeuvre
CEI 60617: Symboles graphiques pour schémas
CEI 60707: 1981, Méthodes d'essai pour évaluer l'inflammabilité des matériaux isolants
électriques solides soumis à une source d'allumage
CEI 60721-3-3: 1987, Classification des conditions d'environnement – Troisième partie:
Classification des groupements des agents d'environnement et de leurs sévérités – Utilisation
à poste fixe, protégé contre les intempéries
CEI 60721-3-4: 1987, Classification des conditions d'environnement – Troisième partie:
Classification des groupements des agents d'environnement et de leurs sévérités – Utilisation
à poste fixe, non protégé contre les intempéries
CEI 60750: 1993, Repérage d'identification du matériel en électrotechnique
CEI 61000-2-5: 1995, Compatibilité électromagnétique (CEM) – Partie 2: Environnement –
Section 5: Classification des environnements électromagnétiques
CEI 61000-4-12: 1995, Compatibilité électromagnétique (CEM) – Partie 4: Techniques d'essai
et de mesure – Section 12: Essai d'immunité aux ondes oscillatoires – Publication
fondamentale en CEM
CEI 61024-1: 1990, Protection des structures contre la foudre – Première partie: Principes
généraux
CEI 61082: Etablissement des documents utilisés en électrotechnique
511 CONFORMITÉ AUX NORMES
511.1 Les matériels doivent satisfaire aux normes de la CEI qui leur sont applicables ainsi
qu'à toute norme de l'ISO qui les concerne.
511.2 A défaut de normes CEI ou ISO applicables, les matériels concernés doivent être
choisis par accord spécial entre le maître d'oeuvre et l'installateur.
60364-5-51 © IEC:1997 – 9 –
IEC 60364-4-45: 1984, Electrical installations of buildings – Part 4: Protection for safety –
Chapter 45: Protection against undervoltage
IEC 60364-5-54: 1980, Electrical installations of buildings – Part 5: Selection and erection of
electrical equipment – Chapter 54: Earthing arrangements and protective conductors
IEC 60446: 1989, Identification of conductors by colours or numerals
IEC 60447: 1993, Man-machine interface (MMI) – Actuating principles
IEC 60617: Graphic symbols for diagram
IEC 60707: 1981, Methods of test for the determination of the flammability of solid electrical
insulating materials when exposed to an igniting source
IEC 60721-3-3: 1987, Classification of environmental conditions – Part 3: Classification of
groups of environmental parameters and their severities – Stationary use at weather-
protected locations
IEC 60721-3-4: 1987, Classification of environmental conditions – Part 3: Classification of
groups of environmental parameters and their severities – Stationary use at non-
weatherprotected locations
IEC 60750: 1993, Item designation in electrotechnology
IEC 61000-2-5: 1995, Electromagnetic compatibility (EMC) – Part 2: Environment – Section
5: Classification of electromagnetic environments
IEC 61000-4-12: 1995, Electromagnetic compatibility (EMC) – Part 4: Testing and
measurement techniques – Section 12: Oscillatory waves immunity test – Basic EMC
Publication
IEC 61024-1: 1990, Protection of structures against lightning – Part 1: General principles
IEC 61082: Preparation of documents used in electrotechnology
511 COMPLIANCE WITH STANDARDS
511.1 Every item of equipment shall comply with such IEC standards as are appropriate
and, in addition, with any applicable standards of the ISO.
511.2 Where there are no applicable IEC or ISO standards, the item of equipment
concerned shall be selected by special agreement between the person specifying the
installation, and the installer.
– 10 – 60364-5-51 © CEI:1997
512 CONDITIONS DE SERVICE ET INFLUENCES EXTERNES
512.1 Conditions de service
512.1.1 Tension
Les matériels doivent être adaptés à la tension nominale (valeur efficace en courant
alternatif) de l'installation.
Si, dans une installation IT, le conducteur neutre est distribué, les matériels connectés entre
une phase et le neutre doivent être isolés pour la tension entre phases.
NOTE – Pour certains matériels, il peut être nécessaire de tenir compte de la tension la plus élevée ou la plus
faible susceptible de se présenter en régime normal.
512.1.2 Courant
Les matériels doivent être choisis compte tenu du courant d'emploi (valeur efficace en
courant alternatif) qui les parcourt en service normal.
Il y a également lieu de considérer le courant susceptible de les parcourir dans des conditions
anormales, en tenant compte de la durée du passage d'un tel courant en fonction des
caractéristiques de fonctionnement des dispositifs de protection.
512.1.3 Fréquence
Si la fréquence a une influence sur les caractéristiques des matériels, la fréquence assignée
des matériels doit correspondre à la fréquence du courant dans le circuit correspondant.
514.1.4 Puissance
Les matériels choisis d'après leurs caractéristiques de puissance, doivent être appropriés aux
conditions normales de service compte tenu de coefficients d'utilisation.
512.1.5 Compatibilité
A moins que les dispositions appropriées ne soient prises lors de la mise en oeuvre, les
matériels doivent être choisis de manière à n'apporter, en service normal, de troubles ni aux
autres matériels ni au réseau d'alimentation, y compris lors de manoeuvres.
512.2 Influences externes
512.2.1 Les matériels électriques doivent être choisis et mis en oeuvre conformément aux
prescriptions du tableau 51A; ce tableau indique les caractéristiques des matériels en
fonction des influences externes auxquelles ils peuvent être soumis, et qui sont définies au
chapitre 32.
Les caractéristiques des matériels sont déterminées, soit par un degré de protection, soit par
la conformité à des essais.
512.2.2 Lorsqu'un matériel ne comporte pas, par construction, les caractéristiques
correspondant aux influences externes du local (ou de l'emplacement), il peut néanmoins être
utilisé à condition qu'il soit pourvu, lors de la réalisation de l'installation, d'une protection
complémentaire appropriée. Cette protection ne doit pas nuire aux conditions de
fonctionnement du matériel ainsi protégé.
60364-5-51 © IEC:1997 – 11 –
512 OPERATIONAL CONDITIONS AND EXTERNAL INFLUENCES
512.1 Operational conditions
512.1.1 Voltage
Equipment shall be suitable for the nominal voltage (r.m.s. value for a.c.) of the installation.
If, in IT installations, the neutral conductor is distributed, equipment connected between
phase and neutral shall be insulated for the voltage between phases.
NOTE – For certain equipment, it may be necessary to take account of the highest and/or lowest voltage likely
to occur in normal service.
512.1.2 Current
Equipment shall be selected for the design current (r.m.s. value for a.c.) which it has to carry
in normal service.
Equipment shall also be capable of carrying the currents likely to flow in abnormal conditions
for such periods of time as are determined by the characteristics of the protective devices.
512.1.3 Frequency
If frequency has an influence on the characteristics of equipment, the rated frequency of the
equipment shall correspond to the frequency of the current in the circuit concerned.
512.1.4 Power
Equipment selected for its power characteristics shall be suitable for the normal operational
conditions taking account of the load factor.
512.1.5 Compatibility
Unless other suitable precautions are taken during erection, all equipment shall be selected
so that it will not cause harmful effects on other equipment nor impair the supply during
normal service, including switching operations.
512.2 External influences
512.2.1 Electrical equipment shall be selected and erected in accordance with the
requirements of table 51A, which indicates the characteristics of equipment necessary
according to the external influences to which the equipment may be subjected, as such
influences are defined in chapter 32.
Equipment characteristics shall be determined either by a degree of protection or by
conformity to tests.
512.2.2 If the equipment does not, by its construction, have the characteristics relevant to
the external influences of its location, it may nevertheless by used on condition that it is
provided with appropriate additional protection in the erection of the installation. Such
protection shall not adversely affect the operation of the equipment thus protected.
– 12 – 60364-5-51 © CEI:1997
512.2.3 Lorsque différentes influences externes se produisent simultanément, leurs effets
peuvent être indépendants ou s'influencer mutuellement et les degrés de protection doivent
être choisis en conséquence.
512.2.4 Le choix des caractéristiques des matériels en fonction des influences externes est
nécessaire, non seulement pour leur fonctionnement correct, mais aussi pour garantir la
fiabilité des mesures de protection pour assurer la sécurité conformément aux règles des
chapitres 41 à 46. Les mesures de protection associées à la construction des matériels sont
en effet valables pour des conditions d'influences externes données dans la mesure où les
essais correspondants prévus par les spécifications des matériels sont effectués dans ces
conditions d'influences externes.
NOTES
1 Dans le cadre de la présente norme, les classes suivantes d'influences externes sont considérées
conventionnellement comme normales:
AA Température ambiante AA4
AB Humidité atmosphérique AB4
Autres conditions d'environnement XX1 de chaque paramètre
(AC à AR)
Conditions d'utilisation XX1 pour tous les paramètres, excepté
et de construction des bâtiments (B et C) XX2 pour le paramètre BC
2 Le mot «normal» figurant dans la troisième colonne du tableau signifie que le matériel doit satisfaire d'une
façon générale aux normes de la CEI qui lui sont applicables.
60364-5-51 © IEC:1997 – 13 –
512.2.3 When different external infuences occur simultaneously, they may have
independent or mutual effect and the degree of protection shall be provided accordingly.
512.2.4 The selection of equipment according to external influences is necessary not only
for proper functioning, but also to ensure the reliability of the measures of protection for
safety complying with the rules of chapters 41 to 46. Measures of protection afforded by the
construction of equipment are valid only for the given conditions of external influence if the
corresponding equipment specification tests are made in these conditions of external
influence.
NOTES
1 For the purpose of this standard, the following classes of external influences are conventionally regarded as
normal:
AA Ambient temperature AA4
AB Atmospheric humidity AB4
Other environmental conditions XX1 of each parameter
(AC to AR)
Utilization and construction XX1 of each parameter, except
of buildings (B and C) XX2 for the parameter BC
2 The word "normal" appearing in the third column of the table signifies that the equipment must generally
satisfy applicable IEC standards.
– 14 – 60364-5-51 © CEI:1997
Tableau 51A
Code Influences externes Caractéristiques prescrites Référence
pour le choix et la mise en
oeuvre des matériels
A Conditions d’environnement
AA Température ambiante (321.1)
AA1 –60 °C + 5 °C
− Comprend la plage de
température de la classe
3K8 de la CEI 60721-3-3,
la température supérieure
de l’air étant limitée à
+5 °C. Partie de la plage
de température de la
classe 4K4 de la
CEI 60721-3-4, la
température inférieure de
l’air étant limitée à
–60 °C et la température
supérieure de l’air à +5 °C.
− Partie de la plage de
AA2
–40 °C + 5 °C
température de la classe
3K7 de la CEI 60721-3-3,
Matériel spécialement
la température supérieure
étudié ou dispositions
de l’air étant limitée à
appropriées*
+5 °C. Comprend partie de
la plage de température de
la classe 4K3 de la
CEI 60721-3-4, la
température supérieure de
l’air étant limitée à +5 °C.
− Partie de la plage de
température de la classe
–25 °C + 5 °C
AA3
3K6 de la CEI 60721-3-3,
la température supérieure
de l’air étant limitée à
+5 °C. Comprend la plage
de température de la
classe 4K1 de la
CEI 60721-3-4, la
température supérieure de
l’air étant limitée à +5 °C.
AA4 –5 °C + 40 °C Normal (dans certains cas
− Partie de la plage de
des précautions spéciales
température de la classe
peuvent être nécessaires)
3K5 de la CEI 60721-3-3,
la température supérieure
de l’air étant limitée à
+40 °C.
AA5 + 5°C +40 °C Normal
− Identique à la plage de
température de la classe
3K3 de la CEI 60721-3-3.
AA6 + 5 °C +60 °C Matériel spécialement
− Partie de la plage de
étudié ou dispositions
température de la classe
appropriées*
3K7 de la CEI 60721-3-3,
la température inférieure
de l’air étant limitée à
+5 °C et la température
supérieure de l’air à
+60 °C. Comprend la
plage de température de la
classe 4K4 de la
CEI 60721-3-4, la plage
inférieure étant limitée à
+5 °C.
* Peut nécessiter certaines précautions supplémentaires (par exemple lubrification spéciale)
** Signifie qu’un matériel ordinaire fonctionnera de manière sûre dans les conditions d’influences externes décrites.
*** Signifie que des dispositions particulières doivent être prises, par exemple, entre le concepteur de l’installation et le
fabricant de matériels, par exemple pour des matériels spécialement étudiés.
60364-5-51 © IEC:1997 – 15 –
Table 51A
Code External influences Characteristics required for Reference
selection and erection of
equipment
A Environmental conditions
AA Ambient temperature (321.1)
AA1 –60 °C + 5 °C Includes temperature
range of IEC 60721-3-3,
class 3K8, with high air
temperature restricted to
+5 °C. Part of temperature
range of IEC 60721-3-4,
class 4K4, with low air
temperature restricted to
–60 °C and high air
temperature restricted to
+5 °C.
AA2 –40 °C + 5 °C Part of temperature range
of IEC 60721-3-3, class
Specially designed
3K7, with high air
equipment or appropriate
temperature restricted to
arrangements*
+5 °C. Includes part of
temperature range of
IEC 60721-3-4, class 4K3,
with high air temperature
restricted to +5 °C.
Part of temperature range
AA3 –25 °C + 5 °C of IEC 60721-3-3, class
3K6, with high air
temperature restricted to
+5 °C. Includes
temperature range of
IEC 60721-3-4, class 4K1,
with high air temperature
restricted to +5 °C.
AA4 –5 °C + 40 °C Normal (in certain cases Part of the temperature
special precautions may range of IEC 60721-3-3,
be necessary) class 3K5, with the high air
temperatures restricted to
+40 °C.
AA5 + 5°C +40 °C Normal Identical to temperature
range of IEC 60721-3-3,
class 3K3
AA6 + 5 °C +60 °C Specially designed Part of temperature range
equipment or appropriate of IEC 60721-3-3, class
arrangements* 3K7, with low air
temperature restricted to
+5 °C and high air
temperature restricted to
+60 °C. Includes
temperature range of
IEC 60721-3-4, class 4K4
with low air temperature
restricted to +5 °C
* May necessitate certain supplementary precautions (e.g. special lubrication).
** This means that ordinary equipment will operate safely under the described external influences.
*** This means that special arrangements should be made, for example, between the designer of the installation and the
equipment manufacturer, e.g. for specially designed equipment.
– 16 – 60364-5-51 © CEI:1997
Tableau 51A (suite)
Code Influences externes Caractéristiques prescrites Référence
pour le choix et la mise en
oeuvre des matériels
– Identique à la plage de
AA7 –25 °C +55 °C température de la classe
Matériel spécialement
3K6 de la CEI 60721-3-3
étudiés ou dispositions
– Identique à la plage de
appropriées.*
AA8 –50 °C +40 °C température de la classe
4K3 de la CEI 60721-3-4
AB Humidité atmosphérique (321.2)
Se référer à la note 2 de l’article 321.2 et à l’annexe B
du chapitre 32
Température de Humidité relative Humidité
l’air % absolue
c) faible d) élevée 3
°C
g/m
a) faible b) élevée
e) faible f) élevée
AB1 –60 +5 3100 0,003 7 Des dispositions parti- Comprend la plage de
culières doivent être température de la classe
prises*** 3K8 de la CEI 60721-3-3,
la température supérieure
de l’air étant limitée à
+5 °C. Partie de la plage
de température de la
classe 4K4 de la
CEI 60721-3-4, la
température inférieure de
l’air étant limitée à –60 °C
et la température
supérieure de l’air à +5 °C.
AB2 –40 +5 10 100 0,1 7 Des dispositions parti- Partie de la plage de
culières doivent être température de la classe
prises*** 3K7 de la CEI 60721-3-3,
la température supérieure
de l’air étant limitée à
+5 °C. Comprend une
partie de la plage de
température de la classe
4K3 de la CEI 60721-3-4,
la température supérieure
de l’air étant limitée à
+5 °C.
AB3 –25 +5 10 100 0,5 7 Des dispositions parti- Partie de la plage de
culières doivent être température de la classe
prises*** 3K6 de la CEI 60721-3-3,
la température supérieure
de l’air étant limitée à
+5 °C. Comprend une
partie de la plage de
température de la classe
4K1 de la CEI 60721-3-4,
la température supérieure
de l’air étant limitée à
+5 °C.
AB4 –5 +40 595 1 29 Normal** Identique à la plage de
température de la classe
3K5 de la CEI 60721-3-3,
la température supérieure
de l’air étant limitée à
+40 °C.
AB5 +5 +40 585 1 25 Normal** Identique à la plage de
température de la classe
3K3 de la CEI 60721-3-3.
* Peut nécessiter certaines précautions supplémentaires (par exemple lubrification spéciale)
** Signifie qu’un matériel ordinaire fonctionnera de manière sûre dans les conditions d’influences externes décrites.
*** Signifie que des dispositions particulières doivent être prises, par exemple, entre le concepteur de l’installation et le
fabricant de matériels, par exemple pour des matériels spécialement étudiés.
60364-5-51 © IEC:1997 – 17 –
Table 51A (continued)
Code External influences Characteristics required for Reference
selection and erection of
equipment
– Identical with
AA7 –25 °C +55 °C temperature range of
Specially designed
IEC 60721-3-3, class 3K6
equipment or appropriate
arrangements.* – Identical with
AA8 –50 °C +40 °C temperature range of
IEC 60721-3-4, class 4K3
AB Atmospheric humidity (321.2)
Refer to note 2 of clause 321.2 and appendix B of
chapter 32
Air temperature Relative Absolute
humidity humidity
°C %
g/m
a) low b) high c) low d) high
e) low f) high
AB1 –60 +5 3100 0,003 7 Appropriate arrangements Includes temperature
shall be made*** range of IEC 60721-3-3,
class 3K8 with high air
temperature restricted to
+5 °C. Part of temperature
range of IEC 60721-3-4,
class 4K4, with low air
temperature restricted to
–60 °C and high air
temperature restricted to
+5 °C.
AB2 –40 +5 10 100 0,1 7 Appropriate arrangements Part of temperature range
shall be made*** of IEC 60721-3-3, class
3K7, with high temperature
restricted to +5 °C. Part of
temperature range of
IEC 60721-3-4, class 4K4,
with low air temperature
restricted to –60 °C and
high air temperature
restricted to +5 °C.
AB3 –25 +5 10 100 0,5 7 Appropriate arrangements Part of temperature range
shall be made*** of IEC 60722-3-3, class
3K6, with high air
temperature restricted to
+5 °C. Includes
temperature range of
IEC 60721-3-4, class 4K1,
with high air temperature
range restricted to +5 °C.
AB4 –5 +40 595 1 29 Normal** Identical with temperature
range of IEC 60721-3-3,
class 3K5. The high air
temperature restricted to
+40 °C.
AB5 +5 +40 585 1 25 Normal** Identical with temperature
range of IEC 60721-3-3,
class 3K3.
* May necessitate certain supplementary precautions (e.g. special lubrication).
** This means that ordinary equipment will operate safely under the described external influences.
*** This means that special arrangements should be made, for example, between the designer of the installation and the
equipment manufacturer, e.g. for specially designed equipment.
– 18 – 60364-5-51 © CEI:1997
Tableau 51A (suite)
Code Influences externes Caractéristiques prescrites Référence
pour le choix et la mise en
oeuvre des matériels
AB6 +5 +60 10 100 1 35 Des dispositions parti- Partie de la plage de
culières doivent être température de la classe
prises*** 3K7 de la CEI 60721-3-3,
la température inférieure
de l’air étant limitée à +5 °C
et la température supérieure
de l’air à +60 °C. Comprend
la plage de température de
la classe 4K4 de la
CEI 60721-3-4, la
température inférieure étant
limitée à +5 °C.
AB7 –25 +55 10 100 0,5 29 Des dispositions parti- Identique à la plage de
culières doivent être température de la classe
prises*** 3K6 de la CEI 60721-3-3.
AB8 –50 +40 15 100 0,04 36 Des dispositions parti- Identique à la plage de
culières doivent être température de la classe
prises*** 4K3 de la CEI 60721-3-4.
AC Altitude (321.3)
AC1 Normal **
≤2 000 m
AC2 Peut nécessiter des
>2 000 m
précautions spéciales
telles qu’application de
facteurs de déclassement
NOTE – Pour certaines
catégories de matériels,
des mesures spéciales
peuvent être nécessaires à
partir de 1 000 m d’altitude
AD Présence d’eau (321.4)
AD1 Négligeable IPX0 CEI 60721-3-4 classe 4Z6
AD2 Chutes de gouttes d’eau IPX1 ou IPX2 CEI 60721-3-3 classe 3Z7
AD3 Aspersion d’eau IPX3 CEI 60721-3-3 classe 3Z8
CEI 60721-3-4 classe 4Z7
AD4 IPX4 CEI 60721-3-3 classe 3Z9
Projections d’eau
CEI 60721-3-4 classe 4Z7
AD5 IPX5 CEI 60721-3-3 classe 3Z10
Jets d’eau
CEI 60721-3-4 classe 4Z8
AD6 Paquets d’eau IPX6 CEI 60721-3-4 classe 4Z9
AD7 Immergeables IPX7
AD8 Submersibles IPX8
AE
Présence de corps solides (321.5)
AE1 Négligeable IP0X CEI 60721-3-3 classe 3S1
voir CEI 60721-3-4 classe 4S1
AE2 Petits objets (2,5 mm) IP3X aussi
CEI 60721-3-3 classe 3S2
section 412
CEI 60721-3-4 classe 4S2
AE3 Très petits objets (1 mm) IP4X
CEI 60721-3-3 classe 3S3
CEI 60721-3-4 classe 4S3
AE4 Poussière légère IP5X si la pénétration de la CEI 60721-3-3,.classe 3S2
poussière ne perturbe pas CEI 60721-3-4, classe 4S2
le fonctionnement des
matériels. IP6X si la
AE5 Poussière moyenne poussière ne doit pas CEI 60721-3-3, classe 3S3
pénétrer dans les matériels CEI 60721-3-4, classe 4S3
AE6 Poussière importante IP6X CEI 60721-3-3, classe 3S4
CEI 60721-3-4, classe 4S4
* Peut nécessiter certaines précautions supplémentaires (par exemple lubrification spéciale)
** Signifie qu’un matériel ordinaire fonctionnera de manière sûre dans les conditions d’influences externes décrites.
*** Signifie que des dispositions particulières doivent être prises, par exemple, entre le concepteur de l’installation et le
fabricant de matériels, par exemple pour des matériels spécialement étudiés.
60364-5-51 © IEC:1997 – 19 –
Table 51A (continued)
Code External influences Characteristics required for Reference
selection and erection of
equipment
AB6 +5 +60 10 100 1 35 Appropriate arrangements Part of temperature range
shall be made*** of IEC 60721-3-3, class
3K7, with low air
temperature restricted to
+5 °C and high air
temperature restricted to
...








Questions, Comments and Discussion