Electromagnetic compatibility (EMC) - Part 4-8: Testing and measurement techniques - Power frequency magnetic field immunity test

IEC 61000-4-8:2009 relates to the immunity requirements of equipment, only under operational conditions, to magnetic disturbances at power frequencies 50 Hz and 60 Hz related to:
- residential and commercial locations;
- industrial installations and power plants;
- medium voltage and high voltage sub-stations. The applicability of IEC 61000-4-8:2009 to equipment installed in different locations is determined by the presence of the phenomenon, as specified in Clause 4. This standard does not consider disturbances due to capacitive or inductive coupling in cables or other parts of the field installation. Other IEC standards dealing with conducted disturbances cover these aspects. The object of IEC 61000-4-8:2009 is to establish a common and reproducible basis for evaluating the performance of electrical and electronic equipment for household, commercial and industrial applications when subjected to magnetic fields at power frequency (continuous and short duration field). IEC 61000-4-8:2009 defines:
- recommended test levels;
- test equipment;
- test set-up;
- test procedure.
This second edition cancels and replaces the first edition published in 1993 and its Amendment 1 (2000). It forms a technical revision. This edition includes the following significant technical changes with respect to the previous edition: the scope is extended in order to cover 60 Hz. Characteristics, performance and verification of the test generator and related inductive coils are revised. Modifications are also introduced in the test set-up (GRP) and test procedure. IEC 61000-4-8:2009 has the status of a basic EMC publication in accordance with IEC Guide 107.

Compatibilité électromagnétique (CEM) - Partie 4-8: Techniques d'essai et de mesure - Essai d'immunité au champ magnétique à la fréquence du réseau

IEC 61000-4-8:2009 traite des exigences en matière d'immunité des matériels, uniquement dans les conditions d'utilisation, contre les perturbations magnétiques à des fréquences de 50 Hz et 60 Hz relatives aux:
- locaux résidentiels et commerciaux;
- installations industrielles et centrales électriques;
- postes moyenne et haute tension. Les conditions d'application de la CEI 61000-4-8:2009 aux matériels installés dans les différents secteurs sont déterminées par la présence du phénomène dans les conditions spécifiées dans l'article 4. La présente norme ne traite pas des perturbations engendrées par le couplage capacitif ou inductif sur les câbles ou autres parties de l'installation. D'autres normes CEI traitant des perturbations conduites couvrent ces aspects. La CEI 61000-4-8:2009 a pour objet d'établir une base commune et reproductible pour évaluer la performance des matériels électriques et électroniques à vocation domestique, commerciale ou industrielle lorsqu'ils sont soumis à des champs magnétiques à la fréquence du réseau (champs permanents et courte durée). La CEI 61000-4-8:2009 définit:
- les niveaux recommandés d'essai;
- le matériel d'essai;
- l'installation d'essai;
- la procédure d'essai. Cette deuxième édition annule et remplace la première édition publiée en 1993 et son amendement 1 (2000). Elle constitue une révision technique. La présente édition inclut les modification techniques majeures suivantes par rapport à la première édition: le domaine d'application est étendu de façon à couvrir le 60 Hz. Les caractéristiques, les performances et la vérification du générateur d'essai et de la bobine d'induction associée sont révisées. Des modifications sont aussi introduites dans l'installation d'essai (PS) et dans la procédure d'essai. La CEI 61000-4-8:2009 a le statut de publication fondamentale en CEM en accord avec le Guide 107 de la CEI.

General Information

Status
Published
Publication Date
02-Sep-2009
Current Stage
PPUB - Publication issued
Start Date
03-Sep-2009
Completion Date
30-Sep-2009
Ref Project

Relations

Standard
IEC 61000-4-8:2009 - Electromagnetic compatibility (EMC) - Part 4-8: Testing and measurement techniques - Power frequency magnetic field immunity test
English and French language
65 pages
sale 15% off
Preview
sale 15% off
Preview
Standard
IEC 61000-4-8:2009 RLV - Electromagnetic compatibility (EMC) - Part 4-8: Testing and measurement techniques - Power frequency magnetic field immunity test Released:9/3/2009 Isbn:9782889103782
English and French language
141 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


IEC 61000-4-8 ®
Edition 2.0 2009-09
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
BASIC EMC PUBLICATION
PUBLICATION FONDAMENTALE EN CEM
Electromagnetic compatibility (EMC) –
Part 4-8: Testing and measurement techniques – Power frequency magnetic field
immunity test
Compatibilité électromagnétique (CEM) –
Partie 4-8: Techniques d'essai et de mesure – Essai d'immunité au champ
magnétique à la fréquence du réseau

All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form or by
any means, electronic or mechanical, including photocopying and microfilm, without permission in writing from either IEC or
IEC's member National Committee in the country of the requester.
If you have any questions about IEC copyright or have an enquiry about obtaining additional rights to this publication,
please contact the address below or your local IEC member National Committee for further information.

Droits de reproduction réservés. Sauf indication contraire, aucune partie de cette publication ne peut être reproduite
ni utilisée sous quelque forme que ce soit et par aucun procédé, électronique ou mécanique, y compris la photocopie
et les microfilms, sans l'accord écrit de la CEI ou du Comité national de la CEI du pays du demandeur.
Si vous avez des questions sur le copyright de la CEI ou si vous désirez obtenir des droits supplémentaires sur cette
publication, utilisez les coordonnées ci-après ou contactez le Comité national de la CEI de votre pays de résidence.

IEC Central Office
3, rue de Varembé
CH-1211 Geneva 20
Switzerland
Email: inmail@iec.ch
Web: www.iec.ch
About the IEC
The International Electrotechnical Commission (IEC) is the leading global organization that prepares and publishes
International Standards for all electrical, electronic and related technologies.

About IEC publications
The technical content of IEC publications is kept under constant review by the IEC. Please make sure that you have the
latest edition, a corrigenda or an amendment might have been published.
ƒ Catalogue of IEC publications: www.iec.ch/searchpub
The IEC on-line Catalogue enables you to search by a variety of criteria (reference number, text, technical committee,…).
It also gives information on projects, withdrawn and replaced publications.
ƒ IEC Just Published: www.iec.ch/online_news/justpub
Stay up to date on all new IEC publications. Just Published details twice a month all new publications released. Available
on-line and also by email.
ƒ Electropedia: www.electropedia.org
The world's leading online dictionary of electronic and electrical terms containing more than 20 000 terms and definitions
in English and French, with equivalent terms in additional languages. Also known as the International Electrotechnical
Vocabulary online.
ƒ Customer Service Centre: www.iec.ch/webstore/custserv
If you wish to give us your feedback on this publication or need further assistance, please visit the Customer Service
Centre FAQ or contact us:
Email: csc@iec.ch
Tel.: +41 22 919 02 11
Fax: +41 22 919 03 00
A propos de la CEI
La Commission Electrotechnique Internationale (CEI) est la première organisation mondiale qui élabore et publie des
normes internationales pour tout ce qui a trait à l'électricité, à l'électronique et aux technologies apparentées.

A propos des publications CEI
Le contenu technique des publications de la CEI est constamment revu. Veuillez vous assurer que vous possédez
l’édition la plus récente, un corrigendum ou amendement peut avoir été publié.
ƒ Catalogue des publications de la CEI: www.iec.ch/searchpub/cur_fut-f.htm
Le Catalogue en-ligne de la CEI vous permet d’effectuer des recherches en utilisant différents critères (numéro de référence,
texte, comité d’études,…). Il donne aussi des informations sur les projets et les publications retirées ou remplacées.
ƒ Just Published CEI: www.iec.ch/online_news/justpub
Restez informé sur les nouvelles publications de la CEI. Just Published détaille deux fois par mois les nouvelles
publications parues. Disponible en-ligne et aussi par email.
ƒ Electropedia: www.electropedia.org
Le premier dictionnaire en ligne au monde de termes électroniques et électriques. Il contient plus de 20 000 termes et
définitions en anglais et en français, ainsi que les termes équivalents dans les langues additionnelles. Egalement appelé
Vocabulaire Electrotechnique International en ligne.
ƒ Service Clients: www.iec.ch/webstore/custserv/custserv_entry-f.htm
Si vous désirez nous donner des commentaires sur cette publication ou si vous avez des questions, visitez le FAQ du
Service clients ou contactez-nous:
Email: csc@iec.ch
Tél.: +41 22 919 02 11
Fax: +41 22 919 03 00
IEC 61000-4-8 ®
Edition 2.0 2009-09
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
BASIC EMC PUBLICATION
PUBLICATION FONDAMENTALE EN CEM
Electromagnetic compatibility (EMC) –
Part 4-8: Testing and measurement techniques – Power frequency magnetic
field immunity test
Compatibilité électromagnétique (CEM) –
Partie 4-8: Techniques d'essai et de mesure – Essai d'immunité au champ
magnétique à la fréquence du réseau

INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
PRICE CODE
INTERNATIONALE
V
CODE PRIX
ICS 33.100.20 ISBN 978-2-88910-378-2
– 2 – 61000-4-8 © IEC:2009
CONTENTS
FOREWORD.4
INTRODUCTION.6
1 Scope.7
2 Normative references .7
3 Terms and definitions .7
4 General .8
5 Test levels.9
6 Test equipment.10
6.1 General .10
6.2 Test generator.10
6.2.1 Current source.10
6.2.2 Characteristics and performances of the test generator for different
inductive coils.10
6.2.3 Verification of the characteristics of the test generator .11
6.3 Inductive coil .12
6.3.1 Field distribution.12
6.3.2 Characteristics of the inductive standard coils 1 m × 1 m and
1 m × 2,6 m .12
6.3.3 Characteristics of the inductive coils for table top and floor standing
equipment .12
6.3.4 Measurement of the inductive coil factor.13
6.4 Test and auxiliary instrumentation .13
6.4.1 Test instrumentation .13
6.4.2 Auxiliary instrumentation .14
7 Test set-up .14
7.1 Test set-up components .14
7.2 Ground (reference) plane for floor standing equipment .14
7.3 Equipment under test .14
7.4 Test generator.15
7.5 Inductive coil .15
8 Test procedure .15
8.1 General .15
8.2 Laboratory reference conditions .15
8.2.1 General .15
8.2.2 Climatic conditions .15
8.2.3 Electromagnetic conditions .16
8.3 Carrying out the test.16
9 Evaluation of the test results .17
10 Test report.17
Annex A (normative) Inductive coil calibration method .22
Annex B (normative) Characteristics of the inductive coils .23
Annex C (informative) Selection of the test levels .29
Annex D (informative) Information on power frequency magnetic field strength .31
Bibliography.33

61000-4-8 © IEC:2009 – 3 –
Figure 1 – Example of application of the test field by the immersion method .18
Figure 2 – Example of schematic circuit of the test generator for power frequency
magnetic field .18
Figure 3 – Example of test set-up for table-top equipment .19
Figure 4 – Calibration of the standard coils .19
Figure 5 – Example of test set-up for floor-standing equipment.20
Figure 6 – Example of investigation of susceptibility to magnetic field by the proximity
method with the 1 m × 1 m inductive coil.20
Figure 7 – Illustration of Helmholtz coils .21
Figure B.1 – Characteristics of the field generated by a square inductive coil (1 m
side) in its plane .25
Figure B.2 – 3 dB area of the field generated by a square inductive coil (1 m side) in its
plane .25
Figure B.3 – 3 dB area of the field generated by a square inductive coil (1 m side) in
the mean orthogonal plane (component orthogonal to the plane of the coil) .26
Figure B.4 – 3 dB area of the field generated by two square inductive coils (1 m side)
0,6 m spaced, in the mean orthogonal plane (component orthogonal to the plane of
the coils).26
Figure B.5 – 3 dB area of the field generated by two square inductive coils (1 m side)
0,8 m spaced, in the mean orthogonal plane (component orthogonal to the plane of
the coils).27
Figure B.6 – 3 dB area of the field generated by a rectangular inductive coil (1 m × 2,6 m)
in its plane .27
Figure B.7 – 3 dB area of the field generated by a rectangular inductive coil (1 m × 2,6 m)
in its plane (ground plane as a side of the inductive coil) .28
Figure B.8 – 3 dB area of the field generated by a rectangular inductive coil (1 m × 2,6 m)
with ground plane, in the mean orthogonal plane (component orthogonal to the plane of
the coil) .28

Table 1 – Test levels for continuous field .9
Table 2 – Test levels for short duration: 1 s to 3 s.10
Table 3 – Specification of the generator for different inductive coils .11
Table 4 – Verification parameter for the different inductive coils .11
Table D.1 – Values of the maximum magnetic field produced by household appliances
(results of the measurements of 100 different devices of 25 basic types) .31
Table D.2 – Values of the magnetic field generated by a 400 kV line .31
Table D.3 – Values of the magnetic field in high voltage sub-station areas .32
Table D.4 – Values of the magnetic field in power plants .32

– 4 – 61000-4-8 © IEC:2009
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
ELECTROMAGNETIC COMPATIBILITY (EMC) –

Part 4-8: Testing and measurement techniques –
Power frequency magnetic field immunity test

FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with an IEC Publication.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 61000-4-8 has been prepared by subcommittee 77A: Low
frequency phenomena, of IEC technical committee 77: Electromagnetic compatibility.
This second edition cancels and replaces the first edition published in 1993 and its
Amendment 1 (2000). It forms a technical revision.
This edition includes the following significant technical changes with respect to the previous
edition: the scope is extended in order to cover 60 Hz. Characteristics, performance and
verification of the test generator and related inductive coils are revised. Modifications are also
introduced in the test set-up (GRP) and test procedure.
It forms Part 4-8 of the IEC 61000 series of standards. It has the status of a basic EMC
publication in accordance with IEC Guide 107.

61000-4-8 © IEC:2009 – 5 –
The text of this standard is based on the following documents:
FDIS Report on voting
77A/694/FDIS 77A/706/RVD
Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.
This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.
A list of all parts of the IEC 61000 series, under the general title Electromagnetic
compatibility, can be found on the IEC website.
The committee has decided that the contents of this publication will remain unchanged until
the maintenance result date indicated on the IEC web site under "http://webstore.iec.ch" in
the data related to the specific publication. At this date, the publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
– 6 – 61000-4-8 © IEC:2009
INTRODUCTION
This standard is part of the IEC 61000 series of standards, according to the following
structure:
Part 1: General
General considerations (introduction, fundamental principles)
Definitions, terminology
Part 2: Environment
Description of the environment
Classification of the environment
Compatibility levels
Part 3: Limits
Emission limits
Immunity limits (in so far as they do not fall under the responsibility of the product
committees)
Part 4: Testing and measurement techniques
Measurement techniques
Testing techniques
Part 5: Installation and mitigation guidelines
Installation guidelines
Mitigation methods and devices
Part 9: Miscellaneous
Each part is further subdivided into several parts, published either as international standards,
as technical specifications or technical reports, some of which have already been published
as sections. Others will be published with the part number followed by a dash and a second
number identifying the subdivision (example: IEC 61000-6-1).
This part is an international standard which gives immunity requirements and test procedures
related to "power frequency magnetic field".

61000-4-8 © IEC:2009 – 7 –
ELECTROMAGNETIC COMPATIBILITY (EMC) –

Part 4-8: Testing and measurement techniques –
Power frequency magnetic field immunity test

1 Scope
This part of IEC 61000 relates to the immunity requirements of equipment, only under
operational conditions, to magnetic disturbances at power frequencies 50 Hz and 60 Hz
related to:
– residential and commercial locations;
– industrial installations and power plants;
– medium voltage and high voltage sub-stations.
The applicability of this standard to equipment installed in different locations is determined by
the presence of the phenomenon, as specified in Clause 4. This standard does not consider
disturbances due to capacitive or inductive coupling in cables or other parts of the field
installation.
Other IEC standards dealing with conducted disturbances cover these aspects.
The object of this standard is to establish a common and reproducible basis for evaluating the
performance of electrical and electronic equipment for household, commercial and industrial
applications when subjected to magnetic fields at power frequency (continuous and short
duration field).
The standard defines:
– recommended test levels;
– test equipment;
– test set-up;
– test procedure.
2 Normative references
The following referenced documents are indispensable for the application of this document.
For dated references, only the edition cited applies. For undated references, the latest edition
of the referenced document (including any amendments) applies.
IEC 60050(161), International Electrotechnical Vocabulary (IEV) – Chapter 161: Electro-
magnetic compatibility
3 Terms and definitions
For the purposes of this document the following terms and definitions apply to the restricted
field of magnetic disturbances as well as the terms and definitions from IEC 60050(161) [IEV].
3.1
current distortion factor
ratio of the root-mean square value of the harmonics content of an alternating current to the
root-mean square value of the fundamental current

– 8 – 61000-4-8 © IEC:2009
3.2
EUT
equipment under test
3.3
inductive coil
conductor loop of defined shape and dimensions, in which flows a current, generating a
magnetic field of defined constancy in its plane and in the enclosed volume
3.4
inductive coil factor
ratio between the magnetic field strength generated by an inductive coil of given dimensions
and the corresponding current value; the field is that measured at the centre of the coil plane,
without the EUT
3.5
immersion method
method of application of the magnetic field to the EUT, which is placed in the centre of an
inductive coil (see Figure 1)
3.6
proximity method
method of application of the magnetic field to the EUT, where a small inductive coil is moved
along the side of the EUT in order to detect particularly sensitive areas
3.7
ground (reference) plane
GRP
flat conductive surface whose potential is used as a common reference for the magnetic field
generator and the auxiliary equipment (the ground plane can be used to close the loop of the
inductive coil, as in Figure 5)
[IEV 161-04-36, modified]
3.8
decoupling network, back filter
electrical circuit intended to avoid reciprocal influence with other equipment not submitted to
the magnetic field immunity test
4 General
The magnetic fields to which equipment is subjected may influence the reliable operation of
equipment and systems.
The following tests are intended to demonstrate the immunity of equipment when subjected to
power frequency magnetic fields related to the specific location and installation condition of
the equipment (e.g. proximity of equipment to the disturbance source).
The power frequency magnetic field is generated by power frequency current in conductors
or, more seldom, from other devices (e.g. Ieakage of transformers) in the proximity of
equipment.
As for the influence of nearby conductors, one should differentiate between:
– the current under normal operating conditions, which produces a steady magnetic field,
with a comparatively small magnitude;

61000-4-8 © IEC:2009 – 9 –
– the current under fault conditions which can produce comparatively high magnetic fields
but of short duration, until the protection devices operate (a few milliseconds with fuses, a
few seconds for protection relays).
The test with a steady magnetic field may apply to all types of equipment intended for public
or industrial low voltage distribution networks or for electrical plants.
The test with a short duration magnetic field related to fault conditions, requires test levels
that differ from those for steady-state conditions; the highest values apply mainly to
equipment to be installed in exposed places of electrical plants.
The test field waveform is that of power frequency.
In many cases (household areas, sub-stations and power plant under normal conditions), the
magnetic field produced by harmonics is negligible.
5 Test levels
The preferential range of test levels, respectively for continuous and short duration application
of the magnetic field, applicable to distribution networks at 50 Hz and 60 Hz, is given in Table 1
and Table 2.
The magnetic field strength is expressed in A/m; 1 A/m corresponds to a free space magnetic
flux density of 1,26 μT.
Table 1 – Test levels for continuous field
Level Magnetic field strength
A/m
1 1
2 3
3 10
4 30
5 100
a
x special
a
"x" can be any level, above, below or in-between
the other levels. This level can be given in the product
specification.
– 10 – 61000-4-8 © IEC:2009
Table 2 – Test levels for short duration: 1 s to 3 s
Level Magnetic field strength
A/m
b
1 n.a.
b
2 n.a.
b
3 n.a.
4 300
5 1 000
a
x special
a
"x" can be any level, above, below or in-between
the other levels. This level, as well the duration of the
test, can be given in the product specification.
b
"n.a." = not applicable.
Information on the selection of the test levels is given in Annex C.
Information on actual levels is given in Annex D.
6 Test equipment
6.1 General
The test magnetic field is obtained by a current flowing in an inductive coil; the application of
the test field to the EUT is by the immersion method.
An example of application of the immersion method is given in Figure 1.
The test equipment includes the current source (test generator), the inductive coil and
auxiliary test instrumentation, that are also given in Figure 3.
6.2 Test generator
6.2.1 Current source
The current source typically consists of a voltage regulator (connected to the mains
distribution network, or other sources), a current transformer and a circuit for the control of
short duration application. The generator shall be able to operate in continuous mode or short
duration mode.
The connection between the current transformer and the inductive coil input should be as
short as possible to avoid that the currents which flow in the connection produce magnetic
fields that affect the magnetic field in the test volume. Preferably the cables should be twisted
together.
The characteristics and performances of the current source or test generator for the different
fields and for different inductive coils considered in this standard, are given in 6.2.2.
6.2.2 Characteristics and performances of the test generator for different inductive
coils
Table 3 specifies characteristics and performances of the test generator for different inductive
coils.
61000-4-8 © IEC:2009 – 11 –
Table 3 – Specification of the generator for different inductive coils
With standard square With standard With other inductive
coil rectangular coil coils
1 m × 1 m 1 turn 1 m × 2,6 m 1 turn
As necessary to
Output current range for
1 A up to 120 A 1 A up to 160 A achieve required field
continuous operation
strength in Table 4
As necessary to
Output current range for short
320 A up to 1 200 A 500 A up to 1 600 A achieve required field
duration
strength in Table 4
Current/Magnetic field
Sinusoidal Sinusoidal Sinusoidal
waveform
Current distortion factor
≤8 % ≤8 % ≤8 %
Continuous mode Up to 8 h Up to 8 h Up to 8 h
Short time operation 1s up to 3 s 1s up to 3 s 1 s up to 3 s
Transformer output Floating not connected to Floating not connected to Floating not connected
PE PE to PE
The schematic circuit of the generator is given in Figure 2.
6.2.3 Verification of the characteristics of the test generator
In order to compare the results for different test generators, the essential characteristics of
the current parameters in the standard inductive coils shall be verified.
The characteristics to be verified are:
– current value in the standard inductive coils;
– field strength in all other inductive coils;
– total distortion factor in the inductive coils.
For standard inductive coils the verifications shall be carried out with a current probe and
measurement instrumentation having better than ±2 % accuracy. Figure 4 shows the
verification set-up.
For all other inductive coils the verification should be carried out with field strength meter,
having an <±1dB accuracy.
Table 4 – Verification parameter for the different inductive coils
Table 1 Current values for the Current values for the Field strength in the centre for
Level 1 m × 1 m standard coil 1 m × 2,6 m standard coil all other inductive coils
A/m
A A
1 1,15 1,51 1
2 3,45 4,54 3
3 11,5 15,15 10
4 34,48 45,45 30
5 114,95 151,5 100
– 12 – 61000-4-8 © IEC:2009
6.3 Inductive coil
6.3.1 Field distribution
For the two 1 turn standard coils 1 m × 1 m and 1 m × 2,6 m, the field distribution is known
and shown in Annex B. Therefore, no field verification or field calibration is necessary, the
current measurement as shown in Figure 4 is sufficient.
Other coils such as multi-turn coils may be used in order to have a lower testing current, or for
EUT not fitting into the two standard coils, inductive coils of different dimensions may be
used. For these cases, the field distribution (maximum variation of ±3 dB) shall be verified.
6.3.2 Characteristics of the inductive standard coils 1 m × 1 m and 1 m × 2,6 m
The inductance for the 1 turn standard 1 m × 1 m coil is approximately 2,5 μH, for the 1 m ×
2,6 m standard coil approximately 6 μH.
The inductive coil shall be made of copper, aluminium or any conductive non-magnetic
material, of such cross-section and mechanical arrangement as to facilitate its stable
positioning during the tests. For continuous tests up to 100 A/m the cross section of

aluminium should be 1,5 cm and for short time test up to 1 000 A/m the cross section should
be 4 cm .
The tolerance of the standard coils is ±1 cm, measured between the centre lines (centre of
the cross section). The characteristics of inductive coils with respect to the magnetic field
distribution are given in Annex B.
6.3.3 Characteristics of the inductive coils for table top and floor standing equipment
The list below gives the testing requirements for table top and floor standing equipment.
a) Inductive coil for table-top equipment
The inductive coil of standard dimensions for testing small equipment (e.g. computer
monitors, watt-hour meters, transmitters for process control, etc.) has a square form with
1 m side. The test volume of the standard square coil is 0,6 m × 0,6 m × 0,5 m (height).
Any other coils can be used to obtain a field homogeneity better than 3 dB.
For example, a double coil of standard size (Helmholtz coil) could be used in order to
obtain a field homogeneity better than 3 dB or for testing larger EUTs.
The double coil (Helmholtz coil) shall be comprised of two or more series of turns, properly
spaced (see Figure 7, Figure B.4, Figure B.5).
The test volume of a double standard size coil, 0,8 m spaced, for a 3 dB homogeneity is
0,6 m × 0,6 m × 1 m (height).
For example, the Helmholtz coils, for a 0,2 dB inhomogeneity, have dimensions and
separation distances as given in Figure 7.
No GRP is permitted as part of the coil nor on the insulating table below the EUT (see
Figure 3).
b) Inductive coil for floor-standing equipment
The inductive coil of standard dimensions for testing floor standing equipment (e.g. racks,
etc.) has a square form with 1 m side and 2,6 m height.
The test volume of the standard square coil is 0,6 m × 2 m (height) × 0,6 m.
When an EUT does not fit into the standard inductive coil 1 m × 2,6 m, the product
committee should select the test method: either the proximity method with the standard
1 m × 1 m 1 turn inductive coil (Figure 6 is an example) or inductive coils shall be made

61000-4-8 © IEC:2009 – 13 –
according to the dimensions of the EUT and the different field orientation of the magnetic
field.
Note that larger inductive coils give comparable results, but it may be not practicable to
construct very large coils. In this case the proximity method may give useful but not
necessarily reproducible results.
A GRP shall be present as in Figure 5.
NOTE Due to the possible large dimensions of EUTs, the coils may be made of "C" or "T" sections in order to
have sufficient mechanical rigidity.
6.3.4 Measurement of the inductive coil factor
In order to make it possible to compare the test results from different test equipment, the
inductive coil factor shall be measured without the EUT, in free space condition.
For the two 1 turn standard coils 1 m × 1 m and 1 m × 2,6 m, the field distribution is known
and shown in Annex B. Therefore, neither field verification nor field calibration is necessary,
the current measurement, as shown in Figure 4, is sufficient.
For all other inductive coils the following procedure shall be carried out. An inductive coil of
the correct dimensions for the EUT dimensions, shall be positioned at 1 m minimum distance
from the wall of the laboratory and any magnetic material, by using insulating supports, and
the inductive coil shall be connected to the test generator as prescribed in 6.2.
An appropriate magnetic field sensor shall be used to verify the magnetic field strength
generated by the inductive coil.
The field sensor shall be positioned at the centre of the inductive coil (without the EUT) and
with suitable orientation to detect the maximum value of the field.
The current in the inductive coil shall be adjusted to obtain the field strength specified by the
test level.
The measurement shall be carried out at power frequency.
The measurement procedure shall be carried out with the test generator and inductive coil.
The coil factor is determined (and verified) by the above procedure.
The coil factor gives the current value to be injected in the coil to obtain the required test
magnetic field (H/l) in the centre of the inductive coil.
Information on the measurement of the test magnetic field is given in Annex A.
6.4 Test and auxiliary instrumentation
6.4.1 Test instrumentation
The test instrumentation includes the current measuring system (sensors and instrument) for
setting and measuring the current injected in the inductive coil.
NOTE The termination networks, back filters, etc. on power supply, control and signal lines that is part of the test
set-up for other tests may be maintained.
The current measuring system is a calibrated current, measuring instrument, probe or shunt.
The accuracy of the measurement instrumentation shall be ±2 %.

– 14 – 61000-4-8 © IEC:2009
6.4.2 Auxiliary instrumentation
The auxiliary instrumentation comprises a simulator and any other instrument necessary for
the operation and verification of the EUT functional specifications.
7 Test set-up
7.1 Test set-up components
The test set-up comprises the following components:
– equipment under test (EUT);
– inductive coil;
– test generator;
– GRP for floor standing equipment.
Precautions shall be taken if the test magnetic field may interfere with the test instrumentation
and other sensitive equipment in the vicinity of the test set-up.
Examples of test set-ups are given in the following figures:
Figure 3: example of test set-up for table-top equipment;
Figure 5: example of test set-up for floor-standing equipment.
7.2 Ground (reference) plane for floor standing equipment
The ground plane (GRP) shall be placed in the laboratory; the floor standing EUT and
auxiliary test equipment shall be placed on it and connected to GRP or to earth terminal.
The ground plane shall be a non-magnetic metal sheet (copper or aluminium) of 0,25 mm
minimum thickness; other metals may be used but in this case they shall have at least
0,65 mm minimum thickness.
The minimum size of the ground plane is 1 m × 1 m.
The final size depends on the dimensions of the floor standing EUT.
The ground plane shall be connected to the safety earth system of the laboratory.
7.3 Equipment under test
The equipment is configured and connected to satisfy its functional requirements. Floor
standing equipment shall be placed on the GRP with the interposition of a 0,1 m thickness
insulating support (e.g. dry wood). For table top equipment see Figure 3.
The equipment cabinets which can be earthed shall be connected to the safety earth directly
on the GRP or via the earth terminal to PE.
The power supply, input and output circuits shall be connected to the sources of power
supply, control and signal.
The cables supplied or recommended by the equipment manufacturer shall be used. In
absence of any recommendation, unshielded cables shall be adopted, of a type appropriate
for the signals involved. All cables shall be exposed to the magnetic field for 1 m of their
length.
61000-4-8 © IEC:2009 – 15 –
The back filters, if any, shall be inserted in the circuits at 1 m cable length from the EUT and
connected to the ground plane.
The communication lines (data lines) shall be connected to the EUT by the cables given in the
technical specification or standard for this application.
7.4 Test generator
The test generator shall not influence the magnetic field and therefore shall not be placed
close to the inductive coil.
7.5 Inductive coil
The inductive coil, of the type specified in 6.3.2, shall enclose the EUT. The EUT shall be
positioned inside the 3 dB test volume of the inductive coil.
Different inductive coils may be selected for testing in the different orthogonal directions,
according to the general criteria specified in 6.3.3 a) and in 6.3.3 b).
The inductive coil shall be connected to the test generator in the same way as for the
procedure specified in 6.3.4.
The inductive coil selected for the tests shall be specified in the test plan.
8 Test procedure
8.1 General
The test procedure shall include:
– verification of the laboratory reference conditions;
– preliminary verification of the correct operation of the equipment;
– carrying out the test;
– evaluation of the test results.
8.2 Laboratory reference conditions
8.2.1 General
In order to minimize the effect of environmental parameters on the test results, the test shall
be carried out in climatic and electromagnetic reference conditions as specified in 8.2.2. and
8.2.3.
8.2.2 Climatic conditions
Unless otherwise specified by the committee responsible for the generic or product standard,
the climatic conditions in the laboratory shall be within any limits specified for the operation of
the EUT and the test equipment by their respective manufacturers.
Tests shall not be performed if the relative humidity is so high as to cause condensation on
the EUT or the test equipment.
NOTE Where it is considered that there is sufficient evidence to demonstrate that the effects of the phenomenon
covered by this standard are influenced by climatic conditions, this should be brought to the attention of the
committee responsible for this standard.

– 16 – 61000-4-8 © IEC:2009
8.2.3 Electromagnetic conditions
The electromagnetic conditions of the laboratory shall be such as to guarantee the correct
operation of the EUT in order not to influence the test results; otherwise, the tests shall be
carried out in a Faraday cage.
In particular, the power frequency magnetic field value of the laboratory shall be at least
20 dB lower than the selected test level.
8.3 Carrying out the test
Care should be taken for any person in the laboratory with respect to applicable requirements
regarding human exposure. If no requirements exist on human protection, a distance of 2 m is
recommended.
The test shall be carried out on the basis of a test plan including verification of the
performances of the EUT as defined in the technical specification.
The power supply, signal and other functional electrical quantities shall be applied within their
rated range.
If the actual operating signals are not available, they may be simulated.
Preliminary verification of equipment performances shall be carried out prior to applying the
test magnetic field.
The test magnetic field shall be applied by the immersion method to the EUT, previously set
up as specified in 7.3.
The test level shall not exceed the product specification.
The test field strength and the duration of the test shall be as determined by the selected test
level, according to the different type of fields (continuous or short duration field) established
in the test plan.
a) Table-top equipment
The equipment shall be subjected to the test magnetic field as shown in Figure 3.
The plane of the inductive coil shall then be rotated by 90° in order to expose the EUT to
the test field with different orientations.
b) Floor-standing equipment
The equipment shall be subjected to the test magnetic field by using inductive coils of
suitable dimensions as specified in 6.3.3 b). The test shall be repeated by moving and
shifting the inductive coils, in order to test the whole volume of the EUT for each
orthogonal direction (see Figure 5).
If the EUT is larger than the 3 dB test volume of the inductive coil, then the test shall be
repeated with the coil moved to different positions, in steps corresponding to 50 % of the
shortest side of the coil, so that the entire EUT is progressively immersed in the 3 dB test
volume.
NOTE The moving of the inductive coil in steps corresponding to 50 % of the shortest side of the coil gives
overlapping test fields.
The plane of the inductive coil shall then be rotated by 90° in order to expose the EUT to
the test field with different orientations and the same procedure.

61000-4-8 © IEC:2009 – 17 –
9 Evaluation of the test results
The test results shall be classified in terms of the loss of function or degradation of
performance of the equipment under test, relative to a performance level defined by its
manufacturer or the requestor of the test, or agreed between the manufacturer and th
...


IEC 61000-4-8 ®
Edition 2.0 2009-09
REDLINE VERSION
INTERNATIONAL
STANDARD
colour
inside
BASIC EMC PUBLICATION
PUBLICATION FONDAMENTALE EN CEM

Electromagnetic compatibility (EMC) –
Part 4-8: Testing and measurement techniques – Power frequency magnetic field
immunity test
Compatibilité électromagnétique (CEM) –
Partie 4-8: Techniques d'essai et de mesure – Essai d'immunité au champ
magnétique à la fréquence du réseau

All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form or by
any means, electronic or mechanical, including photocopying and microfilm, without permission in writing from either IEC or
IEC's member National Committee in the country of the requester.
If you have any questions about IEC copyright or have an enquiry about obtaining additional rights to this publication,
please contact the address below or your local IEC member National Committee for further information.

Droits de reproduction réservés. Sauf indication contraire, aucune partie de cette publication ne peut être reproduite
ni utilisée sous quelque forme que ce soit et par aucun procédé, électronique ou mécanique, y compris la photocopie
et les microfilms, sans l'accord écrit de la CEI ou du Comité national de la CEI du pays du demandeur.
Si vous avez des questions sur le copyright de la CEI ou si vous désirez obtenir des droits supplémentaires sur cette
publication, utilisez les coordonnées ci-après ou contactez le Comité national de la CEI de votre pays de résidence.

IEC Central Office
3, rue de Varembé
CH-1211 Geneva 20
Switzerland
Email: inmail@iec.ch
Web: www.iec.ch
About the IEC
The International Electrotechnical Commission (IEC) is the leading global organization that prepares and publishes
International Standards for all electrical, electronic and related technologies.

About IEC publications
The technical content of IEC publications is kept under constant review by the IEC. Please make sure that you have the
latest edition, a corrigenda or an amendment might have been published.
 Catalogue of IEC publications: www.iec.ch/searchpub
The IEC on-line Catalogue enables you to search by a variety of criteria (reference number, text, technical committee,…).
It also gives information on projects, withdrawn and replaced publications.
 IEC Just Published: www.iec.ch/online_news/justpub
Stay up to date on all new IEC publications. Just Published details twice a month all new publications released. Available
on-line and also by email.
 Electropedia: www.electropedia.org
The world's leading online dictionary of electronic and electrical terms containing more than 20 000 terms and definitions
in English and French, with equivalent terms in additional languages. Also known as the International Electrotechnical
Vocabulary online.
 Customer Service Centre: www.iec.ch/webstore/custserv
If you wish to give us your feedback on this publication or need further assistance, please visit the Customer Service
Centre FAQ or contact us:
Email: csc@iec.ch
Tel.: +41 22 919 02 11
Fax: +41 22 919 03 00
A propos de la CEI
La Commission Electrotechnique Internationale (CEI) est la première organisation mondiale qui élabore et publie des
normes internationales pour tout ce qui a trait à l'électricité, à l'électronique et aux technologies apparentées.

A propos des publications CEI
Le contenu technique des publications de la CEI est constamment revu. Veuillez vous assurer que vous possédez
l’édition la plus récente, un corrigendum ou amendement peut avoir été publié.
 Catalogue des publications de la CEI: www.iec.ch/searchpub/cur_fut-f.htm
Le Catalogue en-ligne de la CEI vous permet d’effectuer des recherches en utilisant différents critères (numéro de référence,
texte, comité d’études,…). Il donne aussi des informations sur les projets et les publications retirées ou remplacées.
 Just Published CEI: www.iec.ch/online_news/justpub
Restez informé sur les nouvelles publications de la CEI. Just Published détaille deux fois par mois les nouvelles
publications parues. Disponible en-ligne et aussi par email.
 Electropedia: www.electropedia.org
Le premier dictionnaire en ligne au monde de termes électroniques et électriques. Il contient plus de 20 000 termes et
définitions en anglais et en français, ainsi que les termes équivalents dans les langues additionnelles. Egalement appelé
Vocabulaire Electrotechnique International en ligne.
 Service Clients: www.iec.ch/webstore/custserv/custserv_entry-f.htm
Si vous désirez nous donner des commentaires sur cette publication ou si vous avez des questions, visitez le FAQ du
Service clients ou contactez-nous:
Email: csc@iec.ch
Tél.: +41 22 919 02 11
Fax: +41 22 919 03 00
IEC 61000-4-8 ®
Edition 2.0 2009-09
REDLINE VERSION
INTERNATIONAL
STANDARD
colour
inside
BASIC EMC PUBLICATION
PUBLICATION FONDAMENTALE EN CEM

Electromagnetic compatibility (EMC) –
Part 4-8: Testing and measurement techniques – Power frequency magnetic
field immunity test
Compatibilité électromagnétique (CEM) –
Partie 4-8: Techniques d'essai et de mesure – Essai d'immunité au champ
magnétique à la fréquence du réseau

INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE
ICS 33.100.20 ISBN 978-2-88910-378-2
IEC 61000-4-8 ®
Edition 2.0 2009-09
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
BASIC EMC PUBLICATION
PUBLICATION FONDAMENTALE EN CEM
Electromagnetic compatibility (EMC) –
Part 4-8: Testing and measurement techniques – Power frequency magnetic field
immunity test
Compatibilité électromagnétique (CEM) –
Partie 4-8: Techniques d'essai et de mesure – Essai d'immunité au champ
magnétique à la fréquence du réseau

– 2 – 61000-4-8 © IEC:2009
CONTENTS
FOREWORD.4
INTRODUCTION.6
1 Scope.7
2 Normative references .7
3 Terms and definitions .7
4 General .8
5 Test levels.9
6 Test equipment.10
6.1 General .10
6.2 Test generator.10
6.2.1 Current source.10
6.2.2 Characteristics and performances of the test generator for different
inductive coils.10
6.2.3 Verification of the characteristics of the test generator .11
6.3 Inductive coil .12
6.3.1 Field distribution.12
6.3.2 Characteristics of the inductive standard coils 1 m × 1 m and
1 m × 2,6 m .12
6.3.3 Characteristics of the inductive coils for table top and floor standing
equipment .12
6.3.4 Measurement of the inductive coil factor.13
6.4 Test and auxiliary instrumentation .13
6.4.1 Test instrumentation .13
6.4.2 Auxiliary instrumentation .14
7 Test set-up .14
7.1 Test set-up components .14
7.2 Ground (reference) plane for floor standing equipment .14
7.3 Equipment under test .14
7.4 Test generator.15
7.5 Inductive coil .15
8 Test procedure .15
8.1 General .15
8.2 Laboratory reference conditions .15
8.2.1 General .15
8.2.2 Climatic conditions .15
8.2.3 Electromagnetic conditions .16
8.3 Carrying out the test.16
9 Evaluation of the test results .17
10 Test report.17
Annex A (normative) Inductive coil calibration method .22
Annex B (normative) Characteristics of the inductive coils .23
Annex C (informative) Selection of the test levels .29
Annex D (informative) Information on power frequency magnetic field strength .31
Bibliography.33

61000-4-8 © IEC:2009 – 3 –
Figure 1 – Example of application of the test field by the immersion method .18
Figure 2 – Example of schematic circuit of the test generator for power frequency
magnetic field .18
Figure 3 – Example of test set-up for table-top equipment .19
Figure 4 – Calibration of the standard coils .19
Figure 5 – Example of test set-up for floor-standing equipment.20
Figure 6 – Example of investigation of susceptibility to magnetic field by the proximity
method with the 1 m × 1 m inductive coil.20
Figure 7 – Illustration of Helmholtz coils .21
Figure B.1 – Characteristics of the field generated by a square inductive coil (1 m
side) in its plane .25
Figure B.2 – 3 dB area of the field generated by a square inductive coil (1 m side) in its
plane .25
Figure B.3 – 3 dB area of the field generated by a square inductive coil (1 m side) in
the mean orthogonal plane (component orthogonal to the plane of the coil) .26
Figure B.4 – 3 dB area of the field generated by two square inductive coils (1 m side)
0,6 m spaced, in the mean orthogonal plane (component orthogonal to the plane of
the coils).26
Figure B.5 – 3 dB area of the field generated by two square inductive coils (1 m side)
0,8 m spaced, in the mean orthogonal plane (component orthogonal to the plane of
the coils).27
Figure B.6 – 3 dB area of the field generated by a rectangular inductive coil (1 m × 2,6 m)
in its plane .27
Figure B.7 – 3 dB area of the field generated by a rectangular inductive coil (1 m × 2,6 m)
in its plane (ground plane as a side of the inductive coil) .28
Figure B.8 – 3 dB area of the field generated by a rectangular inductive coil (1 m × 2,6 m)
with ground plane, in the mean orthogonal plane (component orthogonal to the plane of
the coil) .28

Table 1 – Test levels for continuous field .9
Table 2 – Test levels for short duration: 1 s to 3 s.10
Table 3 – Specification of the generator for different inductive coils .11
Table 4 – Verification parameter for the different inductive coils .11
Table D.1 – Values of the maximum magnetic field produced by household appliances
(results of the measurements of 100 different devices of 25 basic types) .31
Table D.2 – Values of the magnetic field generated by a 400 kV line .31
Table D.3 – Values of the magnetic field in high voltage sub-station areas .32
Table D.4 – Values of the magnetic field in power plants .32

– 4 – 61000-4-8 © IEC:2009
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
ELECTROMAGNETIC COMPATIBILITY (EMC) –

Part 4-8: Testing and measurement techniques –
Power frequency magnetic field immunity test

FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with an IEC Publication.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 61000-4-8 has been prepared by subcommittee 77A: Low
frequency phenomena, of IEC technical committee 77: Electromagnetic compatibility.
This second edition cancels and replaces the first edition published in 1993 and its
Amendment 1 (2000). It forms a technical revision.
This edition includes the following significant technical changes with respect to the previous
edition: the scope is extended in order to cover 60 Hz. Characteristics, performance and
verification of the test generator and related inductive coils are revised. Modifications are also
introduced in the test set-up (GRP) and test procedure.
It forms Part 4-8 of the IEC 61000 series of standards. It has the status of a basic EMC
publication in accordance with IEC Guide 107.

61000-4-8 © IEC:2009 – 5 –
The text of this standard is based on the following documents:
FDIS Report on voting
77A/694/FDIS 77A/706/RVD
Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.
This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.
A list of all parts of the IEC 61000 series, under the general title Electromagnetic
compatibility, can be found on the IEC website.
The committee has decided that the contents of this publication will remain unchanged until
the maintenance result date indicated on the IEC web site under "http://webstore.iec.ch" in
the data related to the specific publication. At this date, the publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
– 6 – 61000-4-8 © IEC:2009
INTRODUCTION
This standard is part of the IEC 61000 series of standards, according to the following
structure:
Part 1: General
General considerations (introduction, fundamental principles)
Definitions, terminology
Part 2: Environment
Description of the environment
Classification of the environment
Compatibility levels
Part 3: Limits
Emission limits
Immunity limits (in so far as they do not fall under the responsibility of the product
committees)
Part 4: Testing and measurement techniques
Measurement techniques
Testing techniques
Part 5: Installation and mitigation guidelines
Installation guidelines
Mitigation methods and devices
Part 9: Miscellaneous
Each part is further subdivided into several parts, published either as international standards,
as technical specifications or technical reports, some of which have already been published
as sections. Others will be published with the part number followed by a dash and a second
number identifying the subdivision (example: IEC 61000-6-1).
This part is an international standard which gives immunity requirements and test procedures
related to "power frequency magnetic field".

61000-4-8 © IEC:2009 – 7 –
ELECTROMAGNETIC COMPATIBILITY (EMC) –

Part 4-8: Testing and measurement techniques –
Power frequency magnetic field immunity test

1 Scope
This part of IEC 61000 relates to the immunity requirements of equipment, only under
operational conditions, to magnetic disturbances at power frequencies 50 Hz and 60 Hz
related to:
– residential and commercial locations;
– industrial installations and power plants;
– medium voltage and high voltage sub-stations.
The applicability of this standard to equipment installed in different locations is determined by
the presence of the phenomenon, as specified in Clause 4. This standard does not consider
disturbances due to capacitive or inductive coupling in cables or other parts of the field
installation.
Other IEC standards dealing with conducted disturbances cover these aspects.
The object of this standard is to establish a common and reproducible basis for evaluating the
performance of electrical and electronic equipment for household, commercial and industrial
applications when subjected to magnetic fields at power frequency (continuous and short
duration field).
The standard defines:
– recommended test levels;
– test equipment;
– test set-up;
– test procedure.
2 Normative references
The following referenced documents are indispensable for the application of this document.
For dated references, only the edition cited applies. For undated references, the latest edition
of the referenced document (including any amendments) applies.
IEC 60050(161), International Electrotechnical Vocabulary (IEV) – Chapter 161: Electro-
magnetic compatibility
3 Terms and definitions
For the purposes of this document the following terms and definitions apply to the restricted
field of magnetic disturbances as well as the terms and definitions from IEC 60050(161) [IEV].
3.1
current distortion factor
ratio of the root-mean square value of the harmonics content of an alternating current to the
root-mean square value of the fundamental current

– 8 – 61000-4-8 © IEC:2009
3.2
EUT
equipment under test
3.3
inductive coil
conductor loop of defined shape and dimensions, in which flows a current, generating a
magnetic field of defined constancy in its plane and in the enclosed volume
3.4
inductive coil factor
ratio between the magnetic field strength generated by an inductive coil of given dimensions
and the corresponding current value; the field is that measured at the centre of the coil plane,
without the EUT
3.5
immersion method
method of application of the magnetic field to the EUT, which is placed in the centre of an
inductive coil (see Figure 1)
3.6
proximity method
method of application of the magnetic field to the EUT, where a small inductive coil is moved
along the side of the EUT in order to detect particularly sensitive areas
3.7
ground (reference) plane
GRP
flat conductive surface whose potential is used as a common reference for the magnetic field
generator and the auxiliary equipment (the ground plane can be used to close the loop of the
inductive coil, as in Figure 5)
[IEV 161-04-36, modified]
3.8
decoupling network, back filter
electrical circuit intended to avoid reciprocal influence with other equipment not submitted to
the magnetic field immunity test
4 General
The magnetic fields to which equipment is subjected may influence the reliable operation of
equipment and systems.
The following tests are intended to demonstrate the immunity of equipment when subjected to
power frequency magnetic fields related to the specific location and installation condition of
the equipment (e.g. proximity of equipment to the disturbance source).
The power frequency magnetic field is generated by power frequency current in conductors
or, more seldom, from other devices (e.g. Ieakage of transformers) in the proximity of
equipment.
As for the influence of nearby conductors, one should differentiate between:
– the current under normal operating conditions, which produces a steady magnetic field,
with a comparatively small magnitude;

61000-4-8 © IEC:2009 – 9 –
– the current under fault conditions which can produce comparatively high magnetic fields
but of short duration, until the protection devices operate (a few milliseconds with fuses, a
few seconds for protection relays).
The test with a steady magnetic field may apply to all types of equipment intended for public
or industrial low voltage distribution networks or for electrical plants.
The test with a short duration magnetic field related to fault conditions, requires test levels
that differ from those for steady-state conditions; the highest values apply mainly to
equipment to be installed in exposed places of electrical plants.
The test field waveform is that of power frequency.
In many cases (household areas, sub-stations and power plant under normal conditions), the
magnetic field produced by harmonics is negligible.
5 Test levels
The preferential range of test levels, respectively for continuous and short duration application
of the magnetic field, applicable to distribution networks at 50 Hz and 60 Hz, is given in Table 1
and Table 2.
The magnetic field strength is expressed in A/m; 1 A/m corresponds to a free space magnetic
flux density of 1,26 µT.
Table 1 – Test levels for continuous field
Level Magnetic field strength
A/m
1 1
2 3
3 10
4 30
5 100
a
x special
a
"x" can be any level, above, below or in-between
the other levels. This level can be given in the product
specification.
– 10 – 61000-4-8 © IEC:2009
Table 2 – Test levels for short duration: 1 s to 3 s
Level Magnetic field strength
A/m
b
1 n.a.
b
2 n.a.
b
3 n.a.
4 300
5 1 000
a
x special
a
"x" can be any level, above, below or in-between
the other levels. This level, as well the duration of the
test, can be given in the product specification.
b
"n.a." = not applicable.
Information on the selection of the test levels is given in Annex C.
Information on actual levels is given in Annex D.
6 Test equipment
6.1 General
The test magnetic field is obtained by a current flowing in an inductive coil; the application of
the test field to the EUT is by the immersion method.
An example of application of the immersion method is given in Figure 1.
The test equipment includes the current source (test generator), the inductive coil and
auxiliary test instrumentation, that are also given in Figure 3.
6.2 Test generator
6.2.1 Current source
The current source typically consists of a voltage regulator (connected to the mains
distribution network, or other sources), a current transformer and a circuit for the control of
short duration application. The generator shall be able to operate in continuous mode or short
duration mode.
The connection between the current transformer and the inductive coil input should be as
short as possible to avoid that the currents which flow in the connection produce magnetic
fields that affect the magnetic field in the test volume. Preferably the cables should be twisted
together.
The characteristics and performances of the current source or test generator for the different
fields and for different inductive coils considered in this standard, are given in 6.2.2.
6.2.2 Characteristics and performances of the test generator for different inductive
coils
Table 3 specifies characteristics and performances of the test generator for different inductive
coils.
61000-4-8 © IEC:2009 – 11 –
Table 3 – Specification of the generator for different inductive coils
With standard square With standard With other inductive
coil rectangular coil coils
1 m × 1 m 1 turn 1 m × 2,6 m 1 turn
As necessary to
Output current range for
1 A up to 120 A 1 A up to 160 A achieve required field
continuous operation
strength in Table 4
As necessary to
Output current range for short
320 A up to 1 200 A 500 A up to 1 600 A achieve required field
duration
strength in Table 4
Current/Magnetic field
Sinusoidal Sinusoidal Sinusoidal
waveform
Current distortion factor
≤8 % ≤8 % ≤8 %
Continuous mode Up to 8 h Up to 8 h Up to 8 h
Short time operation 1s up to 3 s 1s up to 3 s 1 s up to 3 s
Transformer output Floating not connected to Floating not connected to Floating not connected
PE PE to PE
The schematic circuit of the generator is given in Figure 2.
6.2.3 Verification of the characteristics of the test generator
In order to compare the results for different test generators, the essential characteristics of
the current parameters in the standard inductive coils shall be verified.
The characteristics to be verified are:
– current value in the standard inductive coils;
– field strength in all other inductive coils;
– total distortion factor in the inductive coils.
For standard inductive coils the verifications shall be carried out with a current probe and
measurement instrumentation having better than ±2 % accuracy. Figure 4 shows the
verification set-up.
For all other inductive coils the verification should be carried out with field strength meter,
having an <±1dB accuracy.
Table 4 – Verification parameter for the different inductive coils
Table 1 Current values for the Current values for the Field strength in the centre for
Level 1 m × 1 m standard coil 1 m × 2,6 m standard coil all other inductive coils
A/m
A A
1 1,15 1,51 1
2 3,45 4,54 3
3 11,5 15,15 10
4 34,48 45,45 30
5 114,95 151,5 100
– 12 – 61000-4-8 © IEC:2009
6.3 Inductive coil
6.3.1 Field distribution
For the two 1 turn standard coils 1 m × 1 m and 1 m × 2,6 m, the field distribution is known
and shown in Annex B. Therefore, no field verification or field calibration is necessary, the
current measurement as shown in Figure 4 is sufficient.
Other coils such as multi-turn coils may be used in order to have a lower testing current, or for
EUT not fitting into the two standard coils, inductive coils of different dimensions may be
used. For these cases, the field distribution (maximum variation of ±3 dB) shall be verified.
6.3.2 Characteristics of the inductive standard coils 1 m × 1 m and 1 m × 2,6 m
The inductance for the 1 turn standard 1 m × 1 m coil is approximately 2,5 µH, for the 1 m ×
2,6 m standard coil approximately 6 µH.
The inductive coil shall be made of copper, aluminium or any conductive non-magnetic
material, of such cross-section and mechanical arrangement as to facilitate its stable
positioning during the tests. For continuous tests up to 100 A/m the cross section of

aluminium should be 1,5 cm and for short time test up to 1 000 A/m the cross section should
be 4 cm .
The tolerance of the standard coils is ±1 cm, measured between the centre lines (centre of
the cross section). The characteristics of inductive coils with respect to the magnetic field
distribution are given in Annex B.
6.3.3 Characteristics of the inductive coils for table top and floor standing equipment
The list below gives the testing requirements for table top and floor standing equipment.
a) Inductive coil for table-top equipment
The inductive coil of standard dimensions for testing small equipment (e.g. computer
monitors, watt-hour meters, transmitters for process control, etc.) has a square form with
1 m side. The test volume of the standard square coil is 0,6 m × 0,6 m × 0,5 m (height).
Any other coils can be used to obtain a field homogeneity better than 3 dB.
For example, a double coil of standard size (Helmholtz coil) could be used in order to
obtain a field homogeneity better than 3 dB or for testing larger EUTs.
The double coil (Helmholtz coil) shall be comprised of two or more series of turns, properly
spaced (see Figure 7, Figure B.4, Figure B.5).
The test volume of a double standard size coil, 0,8 m spaced, for a 3 dB homogeneity is
0,6 m × 0,6 m × 1 m (height).
For example, the Helmholtz coils, for a 0,2 dB inhomogeneity, have dimensions and
separation distances as given in Figure 7.
No GRP is permitted as part of the coil nor on the insulating table below the EUT (see
Figure 3).
b) Inductive coil for floor-standing equipment
The inductive coil of standard dimensions for testing floor standing equipment (e.g. racks,
etc.) has a square form with 1 m side and 2,6 m height.
The test volume of the standard square coil is 0,6 m × 2 m (height) × 0,6 m.
When an EUT does not fit into the standard inductive coil 1 m × 2,6 m, the product
committee should select the test method: either the proximity method with the standard
1 m × 1 m 1 turn inductive coil (Figure 6 is an example) or inductive coils shall be made

61000-4-8 © IEC:2009 – 13 –
according to the dimensions of the EUT and the different field orientation of the magnetic
field.
Note that larger inductive coils give comparable results, but it may be not practicable to
construct very large coils. In this case the proximity method may give useful but not
necessarily reproducible results.
A GRP shall be present as in Figure 5.
NOTE Due to the possible large dimensions of EUTs, the coils may be made of "C" or "T" sections in order to
have sufficient mechanical rigidity.
6.3.4 Measurement of the inductive coil factor
In order to make it possible to compare the test results from different test equipment, the
inductive coil factor shall be measured without the EUT, in free space condition.
For the two 1 turn standard coils 1 m × 1 m and 1 m × 2,6 m, the field distribution is known
and shown in Annex B. Therefore, neither field verification nor field calibration is necessary,
the current measurement, as shown in Figure 4, is sufficient.
For all other inductive coils the following procedure shall be carried out. An inductive coil of
the correct dimensions for the EUT dimensions, shall be positioned at 1 m minimum distance
from the wall of the laboratory and any magnetic material, by using insulating supports, and
the inductive coil shall be connected to the test generator as prescribed in 6.2.
An appropriate magnetic field sensor shall be used to verify the magnetic field strength
generated by the inductive coil.
The field sensor shall be positioned at the centre of the inductive coil (without the EUT) and
with suitable orientation to detect the maximum value of the field.
The current in the inductive coil shall be adjusted to obtain the field strength specified by the
test level.
The measurement shall be carried out at power frequency.
The measurement procedure shall be carried out with the test generator and inductive coil.
The coil factor is determined (and verified) by the above procedure.
The coil factor gives the current value to be injected in the coil to obtain the required test
magnetic field (H/l) in the centre of the inductive coil.
Information on the measurement of the test magnetic field is given in Annex A.
6.4 Test and auxiliary instrumentation
6.4.1 Test instrumentation
The test instrumentation includes the current measuring system (sensors and instrument) for
setting and measuring the current injected in the inductive coil.
NOTE The termination networks, back filters, etc. on power supply, control and signal lines that is part of the test
set-up for other tests may be maintained.
The current measuring system is a calibrated current, measuring instrument, probe or shunt.
The accuracy of the measurement instrumentation shall be ±2 %.

– 14 – 61000-4-8 © IEC:2009
6.4.2 Auxiliary instrumentation
The auxiliary instrumentation comprises a simulator and any other instrument necessary for
the operation and verification of the EUT functional specifications.
7 Test set-up
7.1 Test set-up components
The test set-up comprises the following components:
– equipment under test (EUT);
– inductive coil;
– test generator;
– GRP for floor standing equipment.
Precautions shall be taken if the test magnetic field may interfere with the test instrumentation
and other sensitive equipment in the vicinity of the test set-up.
Examples of test set-ups are given in the following figures:
Figure 3: example of test set-up for table-top equipment;
Figure 5: example of test set-up for floor-standing equipment.
7.2 Ground (reference) plane for floor standing equipment
The ground plane (GRP) shall be placed in the laboratory; the floor standing EUT and
auxiliary test equipment shall be placed on it and connected to GRP or to earth terminal.
The ground plane shall be a non-magnetic metal sheet (copper or aluminium) of 0,25 mm
minimum thickness; other metals may be used but in this case they shall have at least
0,65 mm minimum thickness.
The minimum size of the ground plane is 1 m × 1 m.
The final size depends on the dimensions of the floor standing EUT.
The ground plane shall be connected to the safety earth system of the laboratory.
7.3 Equipment under test
The equipment is configured and connected to satisfy its functional requirements. Floor
standing equipment shall be placed on the GRP with the interposition of a 0,1 m thickness
insulating support (e.g. dry wood). For table top equipment see Figure 3.
The equipment cabinets which can be earthed shall be connected to the safety earth directly
on the GRP or via the earth terminal to PE.
The power supply, input and output circuits shall be connected to the sources of power
supply, control and signal.
The cables supplied or recommended by the equipment manufacturer shall be used. In
absence of any recommendation, unshielded cables shall be adopted, of a type appropriate
for the signals involved. All cables shall be exposed to the magnetic field for 1 m of their
length.
61000-4-8 © IEC:2009 – 15 –
The back filters, if any, shall be inserted in the circuits at 1 m cable length from the EUT and
connected to the ground plane.
The communication lines (data lines) shall be connected to the EUT by the cables given in the
technical specification or standard for this application.
7.4 Test generator
The test generator shall not influence the magnetic field and therefore shall not be placed
close to the inductive coil.
7.5 Inductive coil
The inductive coil, of the type specified in 6.3.2, shall enclose the EUT. The EUT shall be
positioned inside the 3 dB test volume of the inductive coil.
Different inductive coils may be selected for testing in the different orthogonal directions,
according to the general criteria specified in 6.3.3 a) and in 6.3.3 b).
The inductive coil shall be connected to the test generator in the same way as for the
procedure specified in 6.3.4.
The inductive coil selected for the tests shall be specified in the test plan.
8 Test procedure
8.1 General
The test procedure shall include:
– verification of the laboratory reference conditions;
– preliminary verification of the correct operation of the equipment;
– carrying out the test;
– evaluation of the test results.
8.2 Laboratory reference conditions
8.2.1 General
In order to minimize the effect of environmental parameters on the test results, the test shall
be carried out in climatic and electromagnetic reference conditions as specified in 8.2.2. and
8.2.3.
8.2.2 Climatic conditions
Unless otherwise specified by the committee responsible for the generic or product standard,
the climatic conditions in the laboratory shall be within any limits specified for the operation of
the EUT and the test equipment by their respective manufacturers.
Tests shall not be performed if the relative humidity is so high as to cause condensation on
the EUT or the test equipment.
NOTE Where it is considered that there is sufficient evidence to demonstrate that the effects of the phenomenon
covered by this standard are influenced by climatic conditions, this should be brought to the attention of the
committee responsible for this standard.

– 16 – 61000-4-8 © IEC:2009
8.2.3 Electromagnetic conditions
The electromagnetic conditions of the laboratory shall be such as to guarantee the correct
operation of the EUT in order not to influence the test results; otherwise, the tests shall be
carried out in a Faraday cage.
In particular, the power frequency magnetic field value of the laboratory shall be at least
20 dB lower than the selected test level.
8.3 Carrying out the test
Care should be taken for any person in the laboratory with respect to applicable requirements
regarding human exposure. If no requirements exist on human protection, a distance of 2 m is
recommended.
The test shall be carried out on the basis of a test plan including verification of the
performances of the EUT as defined in the technical specification.
The power supply, signal and other functional electrical quantities shall be applied within their
rated range.
If the actual operating signals are not available, they may be simulated.
Preliminary verification of equipment performances shall be carried out prior to applying the
test magnetic field.
The test magnetic field shall be applied by the immersion method to the EUT, previously set
up as specified in 7.3.
The test level shall not exceed the product specification.
The test field strength and the duration of the test shall be as determined by the selected test
level, according to the different type of fields (continuous or short duration field) established
in the test plan.
a) Table-top equipment
The equipment shall be subjected to the test magnetic field as shown in Figure 3.
The plane of the inductive coil shall then be rotated by 90° in order to expose the EUT to
the test field with different orientations.
b) Floor-standing equipment
The equipment shall be subjected to the test magnetic field by using inductive coils of
suitable dimensions as specified in 6.3.3 b). The test shall be repeated by moving and
shifting the inductive coils, in order to test the whole volume of the EUT for each
orthogonal direction (see Figure 5).
If the EUT is larger than the 3 dB test volume of the inductive coil, then the test shall be
repeated with the coil moved to different positions, in steps corresponding to 50 % of the
shortest side of the coil, so that the entire EUT is progressively immersed in the 3 dB test
volume.
NOTE The moving of the inductive coil in steps cor
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.

Loading comments...