Amendment 2 - Railway applications - Fixed installations - DC switchgear - Part 6: DC switchgear assemblies

General Information

Status
Published
Publication Date
25-May-2020
Drafting Committee
MT 61992 - TC 9/MT 61992
Current Stage
PPUB - Publication issued
Start Date
26-May-2020
Completion Date
12-May-2020

Relations

Effective Date
05-Sep-2023

Overview

IEC 61992-6:2006/AMD2:2020 is Amendment 2 to Part 6 of IEC 61992 - the International Electrotechnical Commission standard for railway applications - fixed installations - DC switchgear assemblies. This amendment introduces a normative test method (Annex B) and additional requirements focused on internal arcing (internal arc faults) in metal‑enclosed DC switchgear used in indoor stationary railway installations. It provides guidance for assigning a rated short‑circuit current under internal arcing conditions (I_Narc) and specifies how to test assemblies to verify protection of operating staff against gas, pressure and hot products generated by internal arcs.

Key Topics and Technical Requirements

  • Internal arc definition and rating: Clarifies terminology (internal arc) and allows manufacturers to assign a rated internal‑arcing short‑circuit current (I_Narc), which shall equal the rated earth‑fault current (I_Ncwe).
  • Normative internal arc test (Annex B): A type test required when I_Narc is assigned. Key aspects:
    • Test duration: 150 ms
    • Test specimen: representative, metal‑enclosed, fully equipped assemblies; modular units tested as assembled in service
    • Test circuit: adjustable resistors/reactors to reproduce prospective sustained short‑circuit current; calibration per IEC 61992‑1 amendments
    • Arc initiation: ignition wire between live part and earthed part, with specified minimum wire cross‑sections depending on test current
    • Earthing: enclosure earthed to negative conductor; protections that would trip the circuit must be made ineffective during test
  • Assessment criteria (Clause B.5): Five pass/fail criteria covering retained door/covers, absence of enclosure fragmentation or ejected parts (>60 g), no burn‑through holes up to 2 000 mm, non‑ignition of vertical indicators, and maintained earthing continuity.
  • Test reporting: Detailed test report requirements including currents, Joule integral, oscillograms, photos and assessment against criteria.

Applications and Who Uses It

This amendment is essential for:

  • Switchgear manufacturers designing and certifying DC switchgear assemblies for railway traction power
  • Railway system integrators and operators validating equipment safety for indoor substations and depots
  • Test laboratories and certification bodies performing internal arc type tests and producing compliance reports
  • Safety and compliance engineers assessing risk, earthing arrangements and mechanical containment for switchgear installations

Adoption supports safer fixed DC installations by ensuring assemblies limit risk from internal arcing and meet traceable test evidence.

Related Standards

  • IEC 61992-1 (general test methods and definitions)
  • IEC 61992-7-1 (earthing considerations for DC switchgear)
  • IEC 62271-200 (accessibility classes / internal arc equivalence references)

Keywords: IEC 61992-6:2006/AMD2:2020, DC switchgear assemblies, internal arc test, railway applications, fixed installations, rated short‑circuit current under internal arcing conditions.

Standard

IEC 61992-6:2006/AMD2:2020 - Amendment 2 - Railway applications - Fixed installations - DC switchgear - Part 6: DC switchgear assemblies

English language
12 pages
sale 15% off
Preview
sale 15% off
Preview

Frequently Asked Questions

IEC 61992-6:2006/AMD2:2020 is a standard published by the International Electrotechnical Commission (IEC). Its full title is "Amendment 2 - Railway applications - Fixed installations - DC switchgear - Part 6: DC switchgear assemblies". This standard covers: Amendment 2 - Railway applications - Fixed installations - DC switchgear - Part 6: DC switchgear assemblies

Amendment 2 - Railway applications - Fixed installations - DC switchgear - Part 6: DC switchgear assemblies

IEC 61992-6:2006/AMD2:2020 is classified under the following ICS (International Classification for Standards) categories: 45.060.01 - Railway rolling stock in general. The ICS classification helps identify the subject area and facilitates finding related standards.

IEC 61992-6:2006/AMD2:2020 has the following relationships with other standards: It is inter standard links to IEC 61992-6:2006. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

You can purchase IEC 61992-6:2006/AMD2:2020 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of IEC standards.

Standards Content (Sample)


IEC 61992-6 ®
Edition 1.0 2020-05
INTERNATIONAL
STANDARD
AMENDMENT 2
Railway applications – Fixed installations – DC switchgear –
Part 6: DC switchgear assemblies

IEC 61992-6:2006-02/AMD2:2020-05(en)

All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form
or by any means, electronic or mechanical, including photocopying and microfilm, without permission in writing from
either IEC or IEC's member National Committee in the country of the requester. If you have any questions about IEC
copyright or have an enquiry about obtaining additional rights to this publication, please contact the address below or
your local IEC member National Committee for further information.

IEC Central Office Tel.: +41 22 919 02 11
3, rue de Varembé info@iec.ch
CH-1211 Geneva 20 www.iec.ch
Switzerland
About the IEC
The International Electrotechnical Commission (IEC) is the leading global organization that prepares and publishes
International Standards for all electrical, electronic and related technologies.

About IEC publications
The technical content of IEC publications is kept under constant review by the IEC. Please make sure that you have the
latest edition, a corrigendum or an amendment might have been published.

IEC publications search - webstore.iec.ch/advsearchform Electropedia - www.electropedia.org
The advanced search enables to find IEC publications by a The world's leading online dictionary on electrotechnology,
variety of criteria (reference number, text, technical containing more than 22 000 terminological entries in English
committee,…). It also gives information on projects, replaced and French, with equivalent terms in 16 additional languages.
and withdrawn publications. Also known as the International Electrotechnical Vocabulary

(IEV) online.
IEC Just Published - webstore.iec.ch/justpublished
Stay up to date on all new IEC publications. Just Published IEC Glossary - std.iec.ch/glossary
details all new publications released. Available online and 67 000 electrotechnical terminology entries in English and
once a month by email. French extracted from the Terms and definitions clause of
IEC publications issued between 2002 and 2015. Some
IEC Customer Service Centre - webstore.iec.ch/csc entries have been collected from earlier publications of IEC
If you wish to give us your feedback on this publication or TC 37, 77, 86 and CISPR.

need further assistance, please contact the Customer Service

Centre: sales@iec.ch.
IEC 61992-6 ®
Edition 1.0 2020-05
INTERNATIONAL
STANDARD
AMENDMENT 2
Railway applications – Fixed installations – DC switchgear –

Part 6: DC switchgear assemblies

INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
ICS 45.060.01 ISBN 978-2-8322-8149-9

– 2 – IEC 61992-6:2006/AMD2:2020
© IEC 2020
FOREWORD
This amendment has been prepared by IEC technical committee 9: Electrical equipment and
systems for railways.
The text of this amendment is based on the following documents:
CDV Report on voting
9/2542/CDV 9/2584A/RVC
Full information on the voting for the approval of this amendment can be found in the report
on voting indicated in the above table.
The committee has decided that the contents of this amendment and the base publication will
remain unchanged until the stability date indicated on the IEC website under
"http://webstore.iec.ch" in the data related to the specific publication. At this date, the
publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
This amendment was elaborated to provide guidance to the requirement of 6.6.3, Internal
arcing, that gas or vapour escaping under pressure does not endanger operating staff.

_____________
3 Terms and definitions
Replace the text of Clause 3 by the following:
For the purposes of this document, the terms and definitions given in IEC 61992-1 and the
following apply.
ISO and IEC maintain terminological databases for use in standardization at the following
addresses:
• IEC Electropedia: available at http://www.electropedia.org/
• ISO Online browsing platform: available at http://www.iso.org/obp
3.1
internal arc
arcing within a switchgear assembly arising from a fault between active parts and/or between
active parts and other conductive parts

© IEC 2020
3.2
rated short-circuit current under internal arcing conditions
I
Narc
current, during the test duration of 150 ms, indicating the maximum allowable value of
sustained short-circuit current at the terminals of the incoming unit for which the requirements
of this test specification are fulfilled
Note 1 to entry: The value is the maximum value of the prospective sustained short-circuit current.
3.3
compartment under test
compartment of a switchgear assembly which is subject to an internal arc test
6.6.2 Internal arcing
Add the following at the end of 6.6.2:
A manufacturer may assign a rated short-circuit current under internal arcing conditions I
Narc
to the equipment. Requirements are given in Clause B.2.
8.2 List of the applicable tests
Add the following at the end of, and after, Table 2:
Internal arc test Type 8.3.9
Routine and type tests are mandatory tests if related characteristics are assigned to the
equipment.
8.3 Performance of tests
Add the following new subclause after 8.3.8:
8.3.9 Internal arc test
The internal arc test is a type test and shall be performed if a rated short-circuit current under
internal arcing conditions (I ) is assigned to the equipment. The test shall be performed
Narc
according to the procedure specified in Annex B. The criteria for successful passing are given
in Clause B.5.
Add the following new Annex B after Annex A:

– 4 – IEC 61992-6:2006/AMD2:2020
© IEC 2020
Annex B
(normative)
Method for testing under conditions of arcing due to an internal fault
B.1 Purpose of the test
Annex B applies to metal-enclosed DC switchgear assemblies - hereinafter called assemblies
- used in indoor stationary installations.
The test procedure described below is intended:
– to assess the ability of the assembly to limit the risk of personal injury,
– to verify the effectiveness of the design in protecting persons,
in case of an internal arc.
The testing conditions take into account that assemblies are installed in areas restricted to
authorized personnel.
NOTE This is equivalent to accessibility class A of IEC 62271-200:2011.
B.2 Characteristics – Rated short-circuit current under internal arcing
conditions (I )
Narc
If a rated short-circuit current under internal arcing conditions I is assigned by the
Narc
manufacturer to the equipment the value shall be equal to the rated earth fault current I .
Ncwe
The peak of the short-circuit current value is conventionally assumed to be 1,42 times the
prospective sustained short-circuit current (fault of negligible impedance).
NOTE The current level during internal arcing depends on the earthing of the switchboard frame (see
IEC 61992-7-1:2006, 6.5.7). High fault currents can be expected where the switchboard frame is:
– directly connected to the return circuit as shown in IEC 61992-7-1:2006, 6.5.7, Figure 4b, or
– connected to substation earth as shown in IEC 61992-7-1:2006, 6.5.7, Figure 4a, and a voltage limiting device
is installed between substation earth and the return circuit.
Lower fault currents can be expected where the bedding resistance of the track and the earth resistance limit the
fault current.
B.3 Test arrangements
B.3.1 Test specimen
The test shall be carried out on representative samples. In case of an assembly with a
continuous main busbar, consisting of extensible (modular) standalone units, the test
specimen shall consist of minimum two units connected together as in service.
The following points shall be observed.
– The test shall be carried out on a test specimen not previously subjected to an arcing test
or on a specimen cleaned and prepared accordingly. The specimen and the equipment in
it may be repaired or replaced before each test.
NOTE Degradation of insulation due to carbonisation or moderate erosion of metal parts is not necessarily
considered to render a unit unsuitable for a further test.
– The test specimen shall be placed in an open area and shall be fixed by its designed
means.
© IEC 2020
– Vertical indicators shall be installed all around.
– A ceiling shall be located at a distance of (200 ± 50) mm from the upper part of the test
specimen unless differently stated by the manufacturer.
If a test specimen includes a roof according to the following specification, and as shown in
Figure B.1, it shall be tested with the roof installed and an additional ceiling is not
required. The roof:
• covers the top surface completely, and
• is of a protection degree of IPX1 or higher, and
• is mounted at minimum distance dc to the top of the assembly of no more than
200 mm.
– The test specimen shall be fully equipped. Earthing and bonding shall be as for normal
service.
– Mock-ups of internal components are permitted provided that:
• they have the same volume and shape as the original items,
• similar external materials, with any metallic external material is earthed in a similar
manner to normal service.
– All doors and covers provided are closed.
– The test specimen shall be earthed at the earthing point provided.
– Secondary devices need not be installed if inside a separate compartment for control
circuits. Means for wiring from the control compartment to the compartment under test
shall be installed.
B.3.2 Test circuit
A typical diagram of the test circuit is shown
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.

Loading comments...

IEC 61992-6:2006/AMD2:2020 is an amendment to the international standard for railway applications, specifically for fixed installations and DC switchgear assemblies. This amendment provides updates and revisions to the original standard, including changes to technical specifications and requirements for DC switchgear. The goal of this amendment is to ensure the safe and efficient operation of DC switchgear in railway applications.

記事のタイトル:IEC 61992-6:2006 / AMD2:2020-改正2-鉄道応用-固定設置物-直流スイッチギア - 第6部:直流スイッチギアアセンブリ 記事内容:IEC 61992-6:2006 / AMD2:2020は、鉄道応用、特に固定設置物と直流スイッチギアアセンブリに関する国際規格の改正です。この改正では、直流スイッチギアの技術的仕様と要件についての変更を含む、元の規格の更新と改訂が提供されています。この改正の目的は、鉄道応用における直流スイッチギアの安全かつ効率的な運用を確保することです。

제목: IEC 61992-6:2006/AMD2:2020 - 제2 개정안 - 철도 응용 - 고정 설치물 - 직류 스위치기어 - 제6부: 직류 스위치기어 어셈블리 내용: IEC 61992-6:2006/AMD2:2020은 철도 응용 분야, 특히 고정 설치물과 직류 스위치기어 어셈블리에 대한 국제 표준의 개정안입니다. 이 개정안은 기존 표준을 업데이트하고 개정하여, 직류 스위치기어에 대한 기술적 사양과 요구사항을 변경합니다. 이 개정안의 목표는 철도 응용에서의 직류 스위치기어의 안전하고 효율적인 운영을 보장하는 것입니다.