IEC 62271-101:2012/AMD1:2017 – 1 –

COR1:2018  IEC 2018
INTERNATIONAL ELECTROTECHNICAL COMMISSION

COMMISSION ÉLECTROTECHNIQUE INTERNATIONALE

____________
IEC 62271-101:2012/AMD1:2017 IEC 62271-101:2012/AMD1:2017

Edition 2.0  2017-11 Édition 2.0  2017-11

HIGH-VOLTAGE SWITCHGEAR AND APPAREILLAGE A HAUTE TENSION –
CONTROLGEAR –
Partie 101:Essais synthétiques
Part 101: Synthetic testing
CO RRI G E NDUM 1
Corrections to the French version appear after the English text.
Les corrections à la version française sont données après le texte anglais.

Table I.1 Corrected TRV values for the first-pole-to-clear for k = 1,3 and f = 50 Hz
pp r
Replace, in Table I.1 as modified by Amendment 1, the row "τ = 75 ms  major loop" with the
following new row:
550 349 580 388 669 409 722 421 754 428 775
τ = 75 ms
800 501 785 560 928 592 1 015 610 1 070 621 1 106
major loop
Table I.2 – Corrected TRV values for the first-pole-to-clear for k = 1,3 and f = 60 Hz
pp r
Replace, in Table I.2 as modified by Amendment 1, the row "τ = 45 ms  subsequent minor

loop" with the following new row:
100 69 132 75 141 77 145
173 95 178
123 85 163 92
145 101 192 108 205 112 211
170 118 227 127 241 131 247
τ = 45 ms
245 171 331 183 351 189 359
a a
subsequent
300 210 410 225 432 232 441
minor loop
501 272 525 280 535
362 254
420 295 587 315 614 325 624
550 388 787 414 816 426 825
800 570 1 196 607 1 223 623 1 225

Replace, in Table I.2 as modified by Amendment 1, the row "τ = 60 ms  major loop" with the
following new row:
– 2 – IEC 62271-101:2012/AMD1:2017

COR1:2018  IEC 2018
100 66 120 72 133 76 140 78 144

123 81 146 89 162 93 171 95 176

145 95 171 104 191 110 201 112 207
τ = 60 ms
170 111 199 122 222 128 235 132 242

a a
245 159 281 176 316 185 335 189 346
major loop
300 194 338 215 382 226 407 232 422

362 234 400 259 455 272 487 279 505
420 270 456 299 522 315 560 324 582

Table I.6 – Corrected TRV values for the first-pole-to-clear for k = 1,2 and f = 60 Hz
pp r
Replace, in Table I.6 as modified by Amendment 1, t
...

Questions, Comments and Discussion