Tests for electric cables under fire conditions - Circuit integrity - Part 2: Test method for fire with shock at a temperature of at least 830 °C for cables of rated voltage up to and including 0,6/1,0 kV and with an overall diameter not exceeding 20 mm

IEC 60331-2:2009 specifies the test apparatus and procedure and gives the performance requirements, including recommended flame application times, for low-voltage power cables of rated voltage up to and including 0,6/1,0 kV and control cables with a rated voltage which are required to maintain circuit integrity when subject to fire and mechanical shock under specified conditions. It is intended for use when testing cables not greater than 20 mm overall diameter. NOTE Cables of larger diameter should be tested using the apparatus, procedure and requirements of IEC 60331-1. This standard describes the means of test specimen preparation, the continuity checking arrangements, the electrical testing procedure, the method of burning the cables and the method of shock production, and gives requirements for evaluating test results. Annex A provides the method of verification of the burner and control system used for the test. Requirements are stated for an identification that may optionally be marked on the cable to signify compliance with this standard. It has the status of a horizontal standard in accordance with IEC Guide 104.

Essais pour câbles électriques soumis au feu - Intégrité des circuits - Partie 2: Méthode d'essai au feu avec chocs pour les câbles de tension assignée au plus égale à 0,6/1,0 kV et de diamètre externe inférieur ou égal à 20 mm, à une température d'au moins 830 °C

La CEI 60331-2:2009 donne des précisions sur l'appareillage, la procédure d'essai et les exigences de performance, y compris des recommandations pour la durée des temps d'application de la flamme, pour les câbles de puissance à basse tension, de tension assignée au plus égale à 0,6/1,0 kV, et les câbles de contrôle ayant une tension assignée, qui sont réputés conserver l'intégrité du circuit quand ils sont soumis à un incendie et à des chocs mécaniques dans des conditions spécifiées. Elle est prévue pour être utilisée pour essayer des câbles de diamètre externe inférieur ou égal à 20 mm. NOTE Pour les câbles de diamètre plus grand, il convient d'utiliser l'appareillage, la procédure et les exigences de la CEI 60331-1. Cette norme décrit les moyens de préparation de l'éprouvette d'essai, les dispositions de contrôle de la continuité du circuit, la procédure d'essai électrique, la méthode pour brûler les câbles et la méthode de production des chocs, et indique les exigences pour évaluer les resultats. L'Annexe A donne la méthode de vérification du brûleur et le système de contrôle utilisé pour l'essai. Les conditions requises sont indiquées pour une identification signifiant la conformité à la présente norme par un éventuel marquage sur le câble. Elle a le statut de norme horizontale conformément au IEC Guide 104.

General Information

Status
Published
Publication Date
18-May-2009
Technical Committee
Drafting Committee
Current Stage
DELPUB - Deleted Publication
Start Date
28-Mar-2018
Completion Date
26-Oct-2025
Ref Project

Relations

Standard
IEC 60331-2:2009 - Tests for electric cables under fire conditions - Circuit integrity - Part 2: Test method for fire with shock at a temperature of at least 830 °C for cables of rated voltage up to and including 0,6/1,0 kV and with an overall diameter not exceeding 20 mm Released:5/19/2009
English and French language
49 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


IEC 60331-2 ®
Edition 1.0 2009-05
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
GROUP SAFETY PUBLICATION
PUBLICATION GROUPÉE DE SÉCURITÉ
Tests for electric cables under fire conditions – Circuit integrity –
Part 2: Test method for fire with shock at a temperature of at least 830 °C for
cables of rated voltage up to and including 0,6/1,0 kV and with an overall
diameter not exceeding 20 mm
Essais pour câbles électriques soumis au feu – Intégrité des circuits –
Partie 2: Méthode d’essai au feu avec chocs pour les câbles de tension assignée
au plus égale à 0,6/1,0 kV et de diamètre externe inférieur ou égal à 20 mm, à une
température d’au moins 830 °C
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form or by

any means, electronic or mechanical, including photocopying and microfilm, without permission in writing from either IEC or

IEC's member National Committee in the country of the requester.
If you have any questions about IEC copyright or have an enquiry about obtaining additional rights to this publication,
please contact the address below or your local IEC member National Committee for further information.

Droits de reproduction réservés. Sauf indication contraire, aucune partie de cette publication ne peut être reproduite
ni utilisée sous quelque forme que ce soit et par aucun procédé, électronique ou mécanique, y compris la photocopie
et les microfilms, sans l'accord écrit de la CEI ou du Comité national de la CEI du pays du demandeur.

Si vous avez des questions sur le copyright de la CEI ou si vous désirez obtenir des droits supplémentaires sur cette

publication, utilisez les coordonnées ci-après ou contactez le Comité national de la CEI de votre pays de résidence.

IEC Central Office
3, rue de Varembé
CH-1211 Geneva 20
Switzerland
Email: inmail@iec.ch
Web: www.iec.ch
About the IEC
The International Electrotechnical Commission (IEC) is the leading global organization that prepares and publishes
International Standards for all electrical, electronic and related technologies.

About IEC publications
The technical content of IEC publications is kept under constant review by the IEC. Please make sure that you have the
latest edition, a corrigenda or an amendment might have been published.
ƒ Catalogue of IEC publications: www.iec.ch/searchpub
The IEC on-line Catalogue enables you to search by a variety of criteria (reference number, text, technical committee,…).
It also gives information on projects, withdrawn and replaced publications.
ƒ IEC Just Published: www.iec.ch/online_news/justpub
Stay up to date on all new IEC publications. Just Published details twice a month all new publications released. Available
on-line and also by email.
ƒ Electropedia: www.electropedia.org
The world's leading online dictionary of electronic and electrical terms containing more than 20 000 terms and definitions
in English and French, with equivalent terms in additional languages. Also known as the International Electrotechnical
Vocabulary online.
ƒ Customer Service Centre: www.iec.ch/webstore/custserv
If you wish to give us your feedback on this publication or need further assistance, please visit the Customer Service
Centre FAQ or contact us:
Email: csc@iec.ch
Tel.: +41 22 919 02 11
Fax: +41 22 919 03 00
A propos de la CEI
La Commission Electrotechnique Internationale (CEI) est la première organisation mondiale qui élabore et publie des
normes internationales pour tout ce qui a trait à l'électricité, à l'électronique et aux technologies apparentées.

A propos des publications CEI
Le contenu technique des publications de la CEI est constamment revu. Veuillez vous assurer que vous possédez
l’édition la plus récente, un corrigendum ou amendement peut avoir été publié.
ƒ Catalogue des publications de la CEI: www.iec.ch/searchpub/cur_fut-f.htm
Le Catalogue en-ligne de la CEI vous permet d’effectuer des recherches en utilisant différents critères (numéro de référence,
texte, comité d’études,…). Il donne aussi des informations sur les projets et les publications retirées ou remplacées.
ƒ Just Published CEI: www.iec.ch/online_news/justpub
Restez informé sur les nouvelles publications de la CEI. Just Published détaille deux fois par mois les nouvelles
publications parues. Disponible en-ligne et aussi par email.
ƒ Electropedia: www.electropedia.org
Le premier dictionnaire en ligne au monde de termes électroniques et électriques. Il contient plus de 20 000 termes et
définitions en anglais et en français, ainsi que les termes équivalents dans les langues additionnelles. Egalement appelé
Vocabulaire Electrotechnique International en ligne.
ƒ Service Clients: www.iec.ch/webstore/custserv/custserv_entry-f.htm
Si vous désirez nous donner des commentaires sur cette publication ou si vous avez des questions, visitez le FAQ du
Service clients ou contactez-nous:
Email: csc@iec.ch
Tél.: +41 22 919 02 11
Fax: +41 22 919 03 00
IEC 60331-2 ®
Edition 1.0 2009-05
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
GROUP SAFETY PUBLICATION
PUBLICATION GROUPÉE DE SÉCURITÉ
Tests for electric cables under fire conditions – Circuit integrity –
Part 2: Test method for fire with shock at a temperature of at least 830 °C for
cables of rated voltage up to and including 0,6/1,0 kV and with an overall
diameter not exceeding 20 mm
Essais pour câbles électriques soumis au feu – Intégrité des circuits –
Partie 2: Méthode d’essai au feu avec chocs pour les câbles de tension
assignée au plus égale à 0,6/1,0 kV et de diamètre externe inférieur ou égal à
20 mm, à une température d’au moins 830 °C

INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
PRICE CODE
INTERNATIONALE
T
CODE PRIX
ICS 13.220.40; 29.020; 29.060.20 ISBN 978-2-88910-125-2
– 2 – 60331-2 © IEC:2009
CONTENTS
FOREWORD.4

INTRODUCTION.6

1 Scope.7

2 Normative references.7

3 Terms and definitions .7

4 Test conditions – Test environment.8

5 Test apparatus .8

5.1 Test equipment.8
5.2 Test wall and mounting .11
5.3 Source of heat .13
5.3.1 Burner .13
5.3.2 Flow meters and flow rates .14
5.3.3 Verification .15
5.4 Shock producing device.15
5.5 Positioning of source of heat.16
5.6 Continuity checking arrangements .16
5.7 Fuses .16
6 Test specimen .16
6.1 Test specimen preparation.16
6.2 Test specimen mounting.17
7 Test procedure .17
7.1 Test equipment and arrangement.17
7.2 Electrical connections .17
7.3 Flame and shock application.19
7.4 Electrification.19
8 Performance requirements.20
8.1 Flame application time.20
8.2 Acceptance criteria .20
9 Retest procedure .20
10 Test report.20
11 Cable marking .20

Annex A (normative) Verification procedure for the source of heat .21
Annex B (informative) Guidance on the choice of recommended test apparatus .23
Bibliography .24

Figure 1 – Schematic diagram of test configuration.9
Figure 2 – Plan view of fire test equipment .10
Figure 3 – End elevation of fire test equipment (not to scale) .11
Figure 4 – Typical rubber bush (hardness: 50-60 shore A) for fastening wall .13
Figure 5 – Burner face .14
Figure 6 – Schematic diagram of an example of a burner control system using
rotameters .15
Figure 7 – Example of method of mounting a sample for test .17

60331-2 © IEC:2009 – 3 –
Figure 8 – Basic circuit diagram – Electric power and control cables with rated voltage

up to 600/1 000 V.19

Figure A.1 – Temperature measuring arrangement .21

– 4 – 60331-2 © IEC:2009
INTERNATIONAL ELECTROTECHNICAL COMMISSION

____________
TESTS FOR ELECTRIC CABLES UNDER FIRE CONDITIONS –

CIRCUIT INTEGRITY –
Part 2: Test method for fire with shock at a temperature of at least 830 °C

for cables of rated voltage up to and including 0,6/1,0 kV and

with an overall diameter not exceeding 20 mm

FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with an IEC Publication.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.

9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 60331-2 has been prepared by IEC technical committee 20: Electric
cables.
The text of this standard is based on the following documents:
FDIS Report on voting
20/1050/FDIS 20/1054/RVD
Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.
This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.

60331-2 © IEC:2009 – 5 –
It has the status of a group safety publication in accordance with IEC Guide 104.

A list of all the parts in the IEC 60331 series, under the general title Tests for electric cables

under fire conditions – circuit integrity, can be found on the IEC website.

The committee has decided that the contents of this publication will remain unchanged until the

maintenance result date indicated on the IEC web site under "http://webstore.iec.ch" in the data

related to the specific publication. At this date, the publication will be

• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
– 6 – 60331-2 © IEC:2009
INTRODUCTION
IEC 60331 consists of the following parts under the general title: Tests for electric cables under

fire conditions – Circuit integrity:

Part 1: Test method for fire with shock at a temperature of at least 830 °C for cables of

rated voltage up to and including 0,6/1,0 kV and with an overall diameter exceeding

20 mm
Part 2: Test method for fire with shock at a temperature of at least 830 °C for cables of

rated voltage up to and including 0,6/1,0 kV and with an overall diameter not

exceeding 20 mm
Part 3: Test method for fire with shock at a temperature of at least 830 °C for cables of
rated voltage up to and including 0,6/1,0 kV tested in a metal enclosure
Part 11: Apparatus – Fire alone at a flame temperature of at least 750 °C
Part 21: Procedures and requirements – Cables of rated voltage up to and including
0,6/1,0 kV
Part 23: Procedures and requirements – Electric data cables
Part 25: Procedures and requirements – Optical fibre cables
NOTE Parts 21, 23 and 25 relate to fire-only conditions at a flame temperature of at least 750 °C.
Since its first edition (1970), IEC 60331 has been extended and has introduced a range of test
apparatus in order that a test may be carried out on large and small power, control, data and
optical fibre cables.
Successful tests carried out in accordance with this standard will enable an identification to be
marked on the product.
60331-2 © IEC:2009 – 7 –
TESTS FOR ELECTRIC CABLES UNDER FIRE CONDITIONS –

CIRCUIT INTEGRITY –
Part 2: Test method for fire with shock at a temperature of at least 830 °C

for cables of rated voltage up to and including 0,6/1,0 kV and

with an overall diameter not exceeding 20 mm

1 Scope
This part of IEC 60331 specifies the test apparatus and procedure and gives the performance
requirements, including recommended flame application times, for low-voltage power cables of
rated voltage up to and including 0,6/1,0 kV and control cables with a rated voltage which are
required to maintain circuit integrity when subject to fire and mechanical shock under specified
conditions. It is intended for use when testing cables not greater than 20 mm overall diameter.
NOTE Cables of larger diameter should be tested using the apparatus, procedure and requirements of
IEC 60331−1.
This standard describes the means of test specimen preparation, the continuity checking
arrangements, the electrical testing procedure, the method of burning the cables and the
method of shock production, and gives requirements for evaluating test results
Annex A provides the method of verification of the burner and control system used for the test.
Requirements are stated for an identification that may optionally be marked on the cable to
signify compliance with this standard.
2 Normative references
The following referenced documents are indispensable for the application of this document.
For dated references, only the edition cited applies. For undated references, the latest edition
of the referenced document (including any amendments) applies.
IEC 60584-1, Thermocouples – Part 1: Reference tables
IEC 60269-3, Low-voltage fuses – Part 3: Supplementary requirements for fuses for use by
unskilled persons (fuses mainly for household and similar applications) – Examples of

standardized systems of fuses A to F
IEC Guide 104, The preparation of safety publications and the use of basic safety publications
and group safety publications
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
3.1
circuit integrity
ability of an electric cable to continue to operate in the designated manner whilst subjected to a
specified flame source for a specified period of time under specified conditions.

– 8 – 60331-2 © IEC:2009
4 Test conditions – Test environment

The test shall be carried out in a suitable chamber, of minimum volume 10 m , with facilities for

disposing of any noxious gases resulting from burning. Sufficient ventilation shall be available

to sustain the flame for the duration of the test.

NOTE 1 Guidance on the choice of suitable chambers is given in Annex B.

The chamber and test apparatus shall be at a temperature of between 10 °C and 40 °C at the

start of each test.
The same ventilation and shielding conditions shall be used in the chamber during both the
verification and cable test procedures.
NOTE 2 The test given in this standard may involve the use of dangerous voltages and temperatures. Suitable
precautions should be taken against the risk of shock, burning, fire and explosion that may be involved, and against
any noxious fumes that may be produced.
5 Test apparatus
5.1 Test equipment
The test equipment shall consist of the following:
a) a test wall on to which the cable is mounted, comprising a board manufactured from heat-
resistant, non-combustible material with steel supports fastened to a rigid support as
described in 5.2;
b) a source of heat comprising a horizontally mounted ribbon burner as described in 5.3;
c) a shock-producing device as described in 5.4;
d) a test wall equipped with thermocouples for verification of the source of heat as described
in Annex A.
e) a continuity checking arrangement as described in 5.6;
f) fuses as described in 5.7
A general arrangement of the test equipment is shown in Figures 1, 2 and 3.

60331-2 © IEC:2009 – 9 –
Dimensions in millimetres
IEC  824/09
Key
1 shock-producing device 4 ribbon gas burner
2 steel support 5 air inlet pipe
3 rubber bush 6 propane inlet pipe
Figure 1 – Schematic diagram of test configuration

– 10 – 60331-2 © IEC:2009
Dimensions in millimetres
IEC  825/09
Key
1 entry for air 4 support framework
2 board 5 horizontal steel support for board
3 rubber bush 6 entry for propane gas

Figure 2 – Plan view of fire test equipment

60331-2 © IEC:2009 – 11 –
Dimensions in millimetres
IEC  826/09
Key
1 shock producing device 4 centre line of burner face
2 board 5 support framework
3 gas burner
Figure 3 – End elevation of fire test equipment (not to scale)
5.2 Test wall and mounting
The test wall shall consist of a board of heat-resistant, non-combustible and non-metallic
material fastened rigidly to two horizontal steel supports, one at the top of the board and the
other at the bottom, as shown in Figure 1. Vertical supports may also be used. The board shall
be (900 ± 100) mm long and (300 ± 50) mm high and (10 ± 2) mm thick and the total mass of
the test wall (i.e. board and steel supports) shall be (10,0 ± 0,5) kg. Ballast, if required, shall be
placed on the steel supports.
NOTE 1 Supports made from square section steel tube approximately 25 mm x 25 mm and approximately 1 m long
have been found to be suitable.

– 12 – 60331-2 © IEC:2009
NOTE 2 The top support should be fastened to the board so that its upper face is slightly above the upper edge of

the board, so that the shock-producing device impacts on the support and not the board.

Each horizontal support shall have a mounting hole at each end, not more than 100 mm from

the edge of the board, the exact position and diameter being determined by the particular

supporting bush and supporting framework used. The test wall shall be fastened to a rigid

support by four bonded rubber bushes of hardness 50–60 Shore A fitted between the horizontal

steel supports of the wall and the support framework, as shown in Figures 1 and 2 so as to

allow movement under impact.
NOTE 3 A typical rubber bush, which has been found to be suitable, is shown in Figure 4.

In order to check the mounting of the wall, the static deflection following application of a mass
to the centre of the upper support of the wall shall periodically be measured.
The values of mass and deflection shall comply with the following:
Mass Deflection
kg mm
25,0 ± 0,2 1,5 ± 0,3
60331-2 © IEC:2009 – 13 –
Dimensions in millimetres
IEC  817/09
Figure 4 – Typical rubber bush (hardness: 50-60 shore A) for fastening wall
5.3 Source of heat
5.3.1 Burner
The source of heat shall be a ribbon type propane gas burner with a nominal burner face length
of 500 mm with a Venturi mixer. A centre-feed burner is recommended. The nominal burner
face width shall be 10 mm. The face of the burner shall have three staggered rows of drilled
holes, nominally 1,32 mm in diameter and drilled at centres 3,2 mm from one another, as shown
in Figure 5. Additionally, a row of small holes milled on each side of the burner plate, to serve
as pilot holes for keeping the flame burning, is permitted.

Guidance on the choice of a recommended burner system is given in Annex B.

– 14 – 60331-2 © IEC:2009
Dimensions in millimetres
IEC  818/09
NOTE Round holes, 1,32 mm in diameter, on centres 3,2 mm from one another, staggered in three rows and
centred on the face of the burner. Nominal burner face length 500 mm.
Figure 5 – Burner face
5.3.2 Flow meters and flow rates
Mass flow meters/controllers should be used as the means of controlling accurately the input
flow rates of fuel and air to the burner.
NOTE 1 Rotameter type flow meters may be used as an alternative, but are not recommended. Guidance on their
use, and the application of appropriate correction factors is given in IEC 60331-11:1999, Annex C.
NOTE 2 Figure 6 shows an example of a rotameter type system.
For the purpose of this test, the air shall have a dew point not higher than 0 °C.
The flow rates used for the test shall be as follows:
– air: (80 ± 4) l/min at reference conditions (1 bar and 20 °C) or (1600 ± 80) mg/s;
– propane: (5,0 ± 0,2) l/min at reference conditions (1 bar and 20 °C) or (160 ± 6) mg/s.
NOTE 3 The purity of the propane is not defined. Industrial grades that contain impurities are allowed provided
that the calibration requirements are achieved.

60331-2 © IEC:2009 – 15 –
IEC  819/09
Key
1 regulator 9 flowmeters
2 piezoelectric igniter 10 Venturi mixer
3 flame failure device 11 burner
4 control thermocouples 12 ball valve
5 propane cylinder 13 air flow
6 screw valve (6A = alternative position) 14 compressed air cylinder
7 pilot feed 15 screw valve on pilot feed
8 gas flow
Figure 6 – Schematic diagram of an example of a burner control system using rotameters
5.3.3 Verification
The burner and control system shall be subject to verification following the procedure given in
Annex A.
5.4 Shock-producing device
The shock producing device shall be a mild steel round bar (25,0 ± 0,1) mm in diameter and
(600 ± 5) mm long. The bar shall be freely pivoted about an axis parallel to the test wall, which
shall be in the same horizontal plane as, and (200 ± 5) mm away from, the upper edge of the
wall. The axis shall divide the bar into two unequal lengths, the longer length being
(400 ± 5) mm which shall impact the wall. The bar shall drop under its own weight from an
+5
angle of (60 ) ° to the horizontal to strike the upper steel support of the wall at its midpoint as
shown in Figures 1 and 3.
– 16 – 60331-2 © IEC:2009
5.5 Positioning of source of heat

The burner face shall be positioned in the test chamber so that it is at least 200 mm above the

floor of the chamber, or any solid mounting block, and at least 500 mm from any chamber wall.

By reference to the centre point of the cable to be tested, the burner shall be positioned

centrally at a horizontal distance of (40 ± 2) mm from the burner face to the test wall and at a

vertical distance of (V ± 2) mm from the burner horizontal central plane to the central horizontal

plane of the test specimen, as shown in Figure 3 and Figure A.1.

The exact burner location to be used during cable testing shall be determined using the

verification procedure given in Annex A, where the value of V to be used shall be determined.
NOTE The burner should be rigidly fixed to the framework during testing so as to prevent movement relative to the
test sample.
5.6 Continuity checking arrangements
During the test, a current for continuity checking shall be passed through all conductors of the
test specimen. This shall be provided by a three-phase star connected or single-phase
transformer(s) of sufficient capacity to maintain the test voltage up to the maximum leakage
current allowable.
NOTE 1 Due note should be taken of the fuse characteristics when determining the power rating of the
transformer.
This current shall be achieved by connecting, at the other end of the test specimen, a suitable
load and an indicating device (e.g. lamp) to each conductor, or group of conductors.
NOTE 2 A current of 0,25 A at the test voltage, through each conductor or group of conductors, has been found to
be suitable.
5.7 Fuses
Fuses used in the test procedure in Clause 7 shall be of type DII, complying with IEC 60269-3.
Alternatively, a circuit-breaker with equivalent characteristics may be used.
Where a circuit-breaker is used, its equivalent characteristics shall be demonstrated by
reference to the characteristic curve shown in IEC 60269-3.
The test method using fuses shall be the reference method in the case of dispute.
6 Test specimen
6.1 Test specimen preparation
A cable sample at least 4,5m long shall be available from the cable length for test. Each
individual test specimen to be tested shall be a piece of cable, taken from the cable sample,
not less than 1 200 mm long with approximately 100 mm of sheath or outer coverings removed
at each end.
At each end of the test specimen each conductor shall be suitably prepared for electrical
connections, and the exposed conductors shall be spread apart to avoid contact with each
other.
60331-2 © IEC:2009 – 17 –
6.2 Test specimen mounting
The test specimen shall be bent to form an approximate “U” shape. The internal radius of each

bend shall be the manufacturer’s declared minimum bending radius and the overall distance

between the vertical portions of the cable shall be (475 ± 10) mm as shown in Figure 7.

The test specimen shall be mounted centrally on the wall using metal clips which shall be

earthed. The lower edge of the cable shall be (200 ± 10) mm below the top of the test wall. P-

clips made of metal strip (10 ± 1) mm wide shall support the test specimen at either end of the

radiused section and in the centre as shown in Figure 7. The P-clips shall be formed so as to

have approximately the same diameter as the cable under test.

Dimensions in millimetres
IEC  827/09
Key
1 metal clips
R minimum bending radius of cables
Figure 7 – Example of method of mounting a sample for test

7 Test procedure
7.1 Test equipment and arrangement
The test procedure shall be carried out using the apparatus detailed in Clause 5.
Mount the test specimen on the test wall and adjust the burner to the correct position relative to
the specimen in accordance with 5.5.
7.2 Electrical connections
At the transformer end of the test specimen, earth the neutral conductor and any protective
conductors. Any metal screens, drain wire or metallic layer shall be interconnected and
earthed. Connect the transformer(s) to the conductors, excluding any conductor which is
specifically identified as intended for use as a neutral or a protective conductor, as shown in
the circuit diagram in Figure 8. Where a metallic sheath, armour or screen acts as a neutral or

– 18 – 60331-2 © IEC:2009
protective conductor, it shall be connected, as shown in the circuit diagram in Figure 8, as for

a neutral or protective conductor.

For single-, twin- or three-phase conductor cables, connect each phase conductor to a

separate phase of the transformer(s) output with a 2 A fuse or circuit-breaker with equivalent

characteristics in each phase.

For multicore cables that have four or more conductors (excluding any neutral or protective

conductors), the conductors shall be divided into three roughly equal groups, ensuring that

adjacent conductors are, as far as possible, in different groups.

For multipair cables, the conductors shall be divided into two equal groups, ensuring that the
a-core of each pair is connected to one phase and the b-core of each pair is connected to
another phase (L1 and L2 in Figure 8). Quads shall be treated as two pairs.
For multi-triple cables, the conductors shall be divided into three equal groups, ensuring that
the a-core of each triple is connected to one phase, the b-core of each triple to another phase
and the c-core of each triple to the third phase of the transformer (L1, L2 and L3 in Figure 8.).
Connect the conductors of each group in series and connect each group to a separate phase of
the transformer output with a 2 A fuse or circuit-breaker with equivalent characteristics in each
phase.
NOTE 1 The above test procedure connects the neutral conductor to earth. This may not be appropriate if the
cable is designed for use on a system where neutral is not earthed. If required by the cable standard it is
permissible for the neutral conductor to be tested as if it were a phase conductor. Where a metallic sheath, armour
or screen acts as a neutral conductor it shall always be connected to earth. Any such variations in methodology
should be included in the test report.
NOTE 2 For cable constructions not specifically identified above, the test voltage should be applied, as far as is
practicable, to ensure that adjacent conductors are connected to different phases.
NOTE 3 In certain cases, for example when testing a control cable using a three-phase transformer, it may not be
possible to apply a test voltage between conductors and from conductor to earth equal to the rated voltage
simultaneously. In such cases, either the test voltage between conductors, or the test voltage from conductor to
earth shall be equal to the rated voltage, such that both the test voltage between conductors and the test voltage
from conductor to earth is equal to or higher than the rated voltage.
At the end of the test specimen remote from the transformer:
– connect each phase conductor, or group of conductors, to one terminal of the load and
indicating device (as described in 5.6), the other terminal being earthed;
– connect the neutral conductor and any protective conductor to one terminal of the load and
indicating device (as described in 5.6), the other terminal being connected to L1 (or L2 or
L3) at the transformer end (see Figure 8).

60331-2 © IEC:2009 – 19 –
IEC  822/09
Key
L1, L2, L3 phase conductors (L2, L3 if present)
N neutral conductor (if present)
PE protective earth (if present)
1 transformer 5 test conductor or group
2 fuse (2 A) 6 load and indicating device (e.g. Lamp)
3 connection to phase L1 (or L2 or L3) 7 test specimen
4 metal clips 8 metal screen (if present)

Figure 8 – Basic circuit diagram – Electric power and control cables
with rated voltage up to 600/1 000 V
7.3 Flame and shock application
Ignite the burner and adjust the propane and air flow rates to those obtained during the
verification procedure (see Annex A).
Immediately after igniting the burner, activate the shock-producing device and start the test
duration timer. The shock-producing device shall impact the wall after 5 min ± 10 s from

activation and subsequently at 5 min ± 10 s intervals. After each impact, the impacting bar shall
be raised from the test wall no more than 20 s after the impact.
7.4 Electrification
Immediately after starting the test duration timer, switch on the electricity supply and adjust the
voltage to the rated voltage of the cable (subject to a minimum voltage of 100 V a.c.), i.e. the
test voltage between conductors shall equal the rated voltage between conductors, and the test
voltage from conductor to earth shall equal the rated voltage from conductor to earth.
The test shall continue for the flame application time given in 8.1, after which the flame shall be
extinguished.
– 20 – 60331-2 © IEC:2009
8 Performance requirements
8.1 Flame application time
The flame application time shall be as specified in the relevant cable standard. In the absence

of such a standard, a flame and impact application of 30 min, 60 min, 90 min or 120 min shall

be chosen.
8.2 Acceptance criteria
With reference to the test procedure given in Clause 7, the cable possesses the characteristics

for providing circuit integrity so long as during the course of the test
– the voltage is maintained, i.e. no fuse fails or circuit-breaker is interrupted,
– a conductor does not rupture, i.e. the lamp is not extinguished.
9 Retest procedure
In the event of a failure, as judged by the requirements of the relevant standard, two further
test specimens, taken from the same cable sample, shall be tested. If both comply, the test
shall be deemed successful.
10 Test report
The test report shall include the following information:
a) the number of this standard;
b) a full description of the cable tested;
c) the manufacturer of the cable tested;
d) the test voltage;
e) the actual cable bending radius used for the test;
f) the actual performance requirement applied (by reference to Clause 8);
g) the flame application time;
h) the chamber volume and temperature at the start of the test.
11 Cable marking
If a cable is required to be marked to signify compliance with this standard, it shall be marked

with the number of this standard and the duration of flame application, as follows: “IEC 60331-2
(XX)” where XX shall be the duration in minutes. The marking shall be in addition to any
requirement of the cable standard.

60331-2 © IEC:2009 – 21 –
Annex A
(normative)
Verification procedure for the source of heat

A.1 Measuring equipment
The flame temperature shall be measured using two 1,5 mm mineral-insulated, stainless steel
sheathed thermocouples, type K (see IEC 60584-1), mounted on the test wall as shown in

Figure A.1. The thermocouple tips shall be (10,0 ± 0,5) mm in front of the test wall. The
horizontal line of the thermocouples shall be (100 ± 10) mm above the bottom of the wall. The
wall shall consist of a board of heat-resistant, non-combustible and non-metallic material
(900 ± 100) mm long, (300 ± 50) mm high and (10 ± 2) mm thick.
Position the burner (40 ± 2) mm horizontally from the wall and (65 ± 10) mm vertically below
the centre line of the thermocouples (V) as shown in Figure A.1.
Dimensions in millimetres
IEC  828/09
Key
1 thermocouple supports 3 burner

2 thermocouple tip 4 1,5 mm type K sheathed thermocouples
Figure A.1 – Temperature measuring arrangement
A.2 Procedure
Ignite the burner and adjust the gas and air supplies to those given in 5.3.
Monitor the temperature as recorded by the thermocouples over a period of 10 min to ensure
conditions are stable.
A.3 Evaluation
The verification procedure shall be considered satisfactory if:

– 22 – 60331-2 © IEC:2009
a) the mean of the averaged readings for each of the two thermocouples over the 10 min falls

+40
within the requirement of (830 )°C; and

b) the difference of the averaged readings for each of the two thermocouples over the 10 min

period does not exceed 40 °C.
At least one measurement shall be made every 30 s in order to obtain the average.

NOTE The actual method of obtaining the average thermocouple reading over the period is not specified, but it is
recommended that a recorder with averaging facilities is used in order to damp the variability caused by point

measurement.
If the verification is not successful, the flow rates shall be altered within the tolerances given in
5.3 and a further verification carried out.
A.4 Further verification
If the verification of Clause A.3 is not successful, the vertical distance (V) between burner and
thermocouples shall be altered (within the tolerance given in Clause A.1) and a further
verification carried out.
If no successful verification can be achieved within the tolerances given, then the burner
system shall be considered as incapable of providing the source of heat required by this
standard.
A.5 Verification report
The position established for successful verification (V) and flow rates used shall be recorded.

60331-2 © IEC:2009 – 23 –
Annex B
(informative)
Guidance on the choice of recommended test apparatus

B.1 Burner and Venturi
A commercially available burner face meeting the recommendations of this standard is the AGF
burner insert 11-55, and a suitable 500 mm burner, including the specified burner face, is the

AGF, reference 1857B . A recommended Venturi mixer is the AGF 14-18 .
Pemfab
30 Indel Avenue
PO Box 227
Rancocas
NJ 08073-0227
USA
www.amgasfur.com or www.pemfab.com
B.2 Test wall material
Examples of materials which have been found to be suitable for the wall are:
i) Tenmat Limited, UK - Sindanyo H61
ii) Frenzelit-Werke, Germany - Isoplan 1100
iii) Skamol, Denmark - Skamolex V-1100 Mk.2
iv) Elit, France - Monolax 500
B.3 Influence of draughts in the test chamber
Experience has shown that the flame geometry is influenced by any draughts in the test
chamber and it is recommended that the burner be shielded from any draughts by the use of
draught shields.
B.4 Guidance on provision of a suitable test chamber

The chamber must have a sufficient volume such that fire effluents released during combustion
do not alter the test conditions. Experience has shown a chamber similar to the “3 m cube”
specified in IEC 61034-1 to be suitable, although other chambers of suitable volume may be
used. Windows may be installed in the walls of the chamber in order to observe the behaviour
of the cable during the test. Fume exhaust should be by means of a chimney located at least
1 m from the burner. A damper may be used for adjustment of ventilation conditions.
Air inlet to the chamber should be made through orifices located near the base of the chamber.
Air inlets and an exhaust chimney should be located in such a way that the burner flame
remains stable during the verification procedure and test.
–––––––––––
This information is given for the convenience of users of this International Standard and does not constitute an
endorsement by IEC of the product named. Equivalent products may be used if they can be shown to lead to the
same results.
– 24 – 60331-2 © IEC:2009
Bibliography
IEC 60331-1, Tests for electric cables under fire conditions – Circuit integrity – Part 1: Test

method for fire with shock at a temperature of at least 830 °C for cables of rated voltage up to

and including 0,6/1,0 kV and wit
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.

Loading comments...